Panasonic 4300 User Manual

Fire alarm systems
Analog
multi detector
Constant sensitivity / Service signal at a fixed level of contamination
New advanced algorithms and functions and yet compatible with older EBL systems
General
The multi detector contains one photo­electric (optical) smoke detector and one heat detector within the low profile housing. The latest IC technology will secure the highest reliability possible. It has unleaded
soldering. In the smoke detection chamber
is a high-efficient optical system consisting of an LED and a photodiode with two lenses. Scattered light (i.e. reflection of infrared light) is used to detect smoke. The smoke enters the detection chamber through an insect filter and an optical labyrinth. This construction not only improves the smoke inflow, it also causes steam, fog, etc. to condense into moisture on its surfaces, to prevent false (nuisance) alarms. The heat sensing element is a thermistor. The detector is supplied with two LEDs that will light when the detector goes into alarm. The detector is plugged in the analog base 3312x / 4313. The COM loop is connected to the base, which also has terminals for an external LED, e.g. 2218. The detector is intended for indoor use in dry premises and in the systems EBL512 / 128 / 1000 / 2000 depending on the detector mode.
Constant sensitivity
The detector maintains a constant sensitivity regardless of its contamination. A service signal will be given when the detector has reached a service level.
Address / Detector mode
The address setting tool 3314 is used to set the detector's COM loop address and the detector mode NORMAL, 2330 or 2312. See Planning Instructions for the system respectively for more information about the modes and functions.
NORMAL mode (analog): Detector
4300 is used in the systems EBL512 (SW version > a spare part for the detector 3316 in NORMAL mode.
2330 mode (conventional): Detector
4300 is used in the systems EBL512 / 1000 / 2000 as the best substitute for the detectors 2316 & 2317 + base 2330
2312 mode (analog): Not used for 4300. The different modes have different functions
and features, e.g. in the 2330 mode, the detector does the fire judgement but in the NORMAL mode this is done in the c.i.e. The detector is prepared for an "Advanced mode" to be used in conjunction with future EBLxxx SW versions.
2.0) and EBL128, also as
.
AI function
In the 2330 mode is the AI function used, i.e.:
Combined heat and smoke sensing will
guarantee reliable and accurate fire alarm detection.
Variable delay function, i.e. the delay
time before an alarm is influenced by temporary temperature and/or smoke obscuration changes.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
p
Type number
4300 Analog multi detector
The detector is plugged in the analog base 3312x / 4313.
Lsh
E­Ls
E+ SA
Tl
The COM loo
SB
Al
COM loop input
C.i.e. EBL512 / EBL128
/ Ext. LED are connected to the analog base.
3312 4313 3312FL/F
SA (L)
SB (C)
SA (L)
SB (C)
Mark Mark
Ext. LED
SA SA
SB SB
E- E-
+
E+ E+
COM loop Mark
SB
SAo
SAi
E-
E+
In the detector: See also "Engineering Instructions for detectors Type 430x".
SA/SB Contact pins for COM loop / address setting tool 3314 E+/E- Contact pins for External LED Tl Type number label; Detector type Al Address label; For the programmed COM loop address to be written. Lsh Locking screw hole (prepared for drilling through detector body) Ls Locking screw
Prepared for mechanical locking with analog base 3312x / 4313. One hexagon socket screw (Ls) is attached (1.5 mm Hex key to be used). The 2.5-2.7 mm hole (Lsh) has to be drilled.
Technical data
Voltage (V DC) rated
allowed normal (on COM loop)
Current consumption at nom. volt. from COM loop (mA)
quiescent active (incl. internal LED) ext. LED (connected via base 3312)
Ambient temperature (°C) operating
storage Ambient humidity (% RH) max. 95, non condensing Ingress Protection rating (estimated) IP 51 Sensitivity (obscuration; %/m)
NORMAL mode 2330 mode
Sensitivity (T=°C; deltaT=°C/min.)
NORMAL mode 2330 mode
Size x h (mm) Weight (g) 70 Construction / Colour Modified polycarbonate / Grey (N8, Munsell colour code) Approvals 05 EC Certificate no. 0786-CPD-20145; EN54-7 (smoke)
28 12-30 24
0.3
2.3 max. 2
-10 to +50
-25 to +75
Depending on mode.
3.6 / 3.0 / 2.4 (Low / Normal / High) 5 >2.5 in combination with temp. rate-of-rise (depending on algorithm)
Depending on mode.
56 / 46 / 60 / 74 (A1; < 4 / A1; > 4 / A2 (S) / B (S)) 57; 6.43 57; >1.07 in combination with smoke obscur. (depending on algorithm)
102 x 44
05 EC Certificate no. 0786-CPD-20146; EN54-5 Class P (heat)
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00307 2003-04-24 6 / 2008-09-15