Refrigerant R410A is used in the outdoor units.
* Salt-Air Damage Resistant Specifications.
U-72MF1U9
U-72MF1U9E
U-96MF1U9
U-96MF1U9E
**
Indoor Units
Class912151824193654487
U1
4-Way Cassette
4-Way Cassette 60×60
Y1
D1
1-Way Cassette
Low Silhouette Ducted
F1
Slim Low Static Ducted
M1
High Static Pressure
E1
Ducted
Ceiling
T1
Wall Mounted
K1
Floor Standing
P1
Concealed Floor
R1
Standing
** Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U).
85464849301000
S-07MD1U6
S-07MF1U6
S-07MM1U6
S-07MK1U6
S-07MP1U6
S-07MR1U6
S-09MD1U6
S-09MF1U6
S-09MM1U6
S-09MK1U6
S-09MP1U6
S-09MR1U6
S-12MU1U6
S-12MY1U6
S-12MD1U6
S-12MF1U6
S-12MM1U6
S-12MT1U6
S-12MK1U6
S-12MP1U6
S-12MR1U6
S-15MF1U6
S-15MM1U6
S-15MP1U6
S-15MR1U6
S-18MU1U6
S-18MY1U6
S-18MF1U6
S-18MM1U6
S-18MT1U6
S-18MK1U6
S-18MP1U6
S-18MR1U6
S-19MS1U6**
S-24MU1U6
S-24MF1U6
S-24MT1U6
S-24MK1U6
S-24MP1U6
S-24MR1U6
S-36MU1U6
S-36MF1U6
S-36ME1U6
REFERENCE NO.
S-48MF1U6
S-48ME1U6
S-54MF1U6
SM830201-00
Page 2
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person, it
is an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
Do not supply power to the unit until all wiring and tubing •
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this •
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or death.
•
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause •
overheating at connection points and a possible fire
hazard.
To prevent possible hazards from insulation failure, •
the unit must be grounded.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
thin aluminum fins on the air conditioner can cut your
fingers.
When Installing…
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location
for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
outlet at least 5 feet away from the
unit.
When Connecting Refrigerant Tubing
Ventilate the room well, in the event that is refrigerant •
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
Keep all tubing runs as short as possible.•
Use the flare method for connecting tubing.•
Apply refrigerant lubricant to the matching surfaces of •
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
Check carefully for leaks before starting the test run.•
When performing piping work do •
not mix air except for specified
refrigerant (R410A) in refrigeration
cycle. It causes capacity down,
and risk of explosion and injury
due to high tension inside the
WARNING
Do not leak refrigerant while piping work for an •
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
refrigerant cycle.
Refrigerant gas leakage may •
cause fire.
Do not add or replace refrigerant •
other than specified type. It may
cause product damage, burst and
injury etc.
i
Page 3
When Servicing
Turn the power OFF at the main power box (mains) •
before opening the unit to check or repair electrical
parts and wiring.
Keep your fingers and clothing away from any moving •
parts.
Clean up the site after you finish, remembering to check •
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
WAR NI NG
Do not clean inside the indoor and •
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
In case of malfunction of this •
appliance, do not repair by yourself.
Contact to the sales dealer or service
dealer for a repair.
Others
CAUTION
CAUTION
Do not touch the air inlet or the
•
sharp aluminum fins of the
outdoor unit. You may get injured.
Ventilate any enclosed areas when •
installing or testing the refrigeration
system. Escaped refrigerant gas, on
contact with fire or heat, can produce
dangerously toxic gas.
Confirm after installation that no •
refrigerant gas is leaking. If the gas
comes in contact with a burning stove,
gas water heater, electric room heater
or other heat source, it can cause the
generation of poisonous gas.
Do not touch the air inlet or the
•
sharp aluminum fins of the
outdoor unit. You may get injured.
Do not sit or step on the unit, •
you may fall down accidentally.
Do not stick any object into the •
FAN CASE.
You may be injured and the unit
may be damaged.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws imposed to
protect the ozone layer. However, since it contains more
than air, it poses the risk of suffocation if its density
should rise excessively. Suffocation from leakage of
refrigerant is almost non-existent.
With the recent increase in the number of high density
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks
out, its density does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and define
safeguards related to the use of refrigerants, all of which
define a Refrigerant Concentration Level (RCL) of 25
pounds per 1,000 cubic feet for R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following
documents:
International Mechanical Code 2009 (IMC-2009)
(or more recently revised)
ASHRAE 15
ASHRAE 34
ii
Page 4
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless
Pipes and Tubes.”
For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints
(optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to
prevent dirt, moisture, or other foreign substances from entering. These substances
can result in system malfunction.
Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine
oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1.
Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects
in the unit.
2-2.nce decreases when gas leaks, collect the remaining
Since refrigerant composition changes and performa
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1.
Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
R407C tools
New
Item
Manifold gaugeYesNoTypes of refrigerant, refrigerating machine
Charge hoseYes
Vacuum pumpUse a conventional vacuum pump if it is equipped
Leak detectorLeak detectors for CFC and HCFC that
Flaring oilFor systems that use R22, apply mineral oil (Suniso oil)
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
compatible
tool?
with R410A?
Yes
YesNo
YesNo
No
Yes
oil, and pressure gauge are different.
To resist higher pressure, material must be changed.
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
react to chlorine do not function because
R410A contains no chlorine. Leak detector
for HFC134a can be used for R410A.
to the flare nuts on the tubing to prevent refrigerant
leakage. For machines that use R407C or R410A, apply
synthetic oil (ether oil) to the flare nuts.
Remarks
Manifold gauge
Vacuum pump
Outlet
Inlet
iii
Page 5
3-2. Use R410A exclusive cylinder only.
New refrigerant R410A cannot be used for
earlier models
1. Compressor specifications are different.
If recharging a R22 or R407C compressor with R410A,
durability will significantly decrease since some of the
materials used for compressor parts are different.
2. Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
Val ve
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
Liquid
3. Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it
does not dissolve in R410A. Therefore, refrigerating
machine oil discharged from the compressor can cause
compressor damage.
The 3-WAY VRF is a system that allows multiple outdoor units to be connected. The outdoor units all contain
inverter compressors, and the system does not utilize the sub units that were used in earlier systems.
The outdoor unit where the unit No. is set to “1” includes the CCU (command controller unit) functions that are used
to control the entire system. As a result, the system will not operate if no outdoor unit has been set as unit No. “1.”
Required settings for Test Run
Outdoor unit No. 1Outdoor unit Nos. 2
At time of shipmentOn-site settingAt time of shipmentOn-site setting
System address1System 1 ~ 301Not necessary
No. of indoor units11 ~ 40 units1Not necessary
No. of outdoor units11 ~ 3 units1Not necessary
Unit No.1Unit No. 11Unit Nos. 2
This system can be expanded to connect a maximum of 3 outdoor units. (The system maximum capacity is 24
To n. )
The CCU functions are disabled at all units except the unit that is set as unit No. 1. Therefore no problems will
result even if the system address, No. of indoor units, and No. of outdoor units settings are made at the other units.
However, making these settings may be convenient for manual backup operation, as it eliminates the necessity of
making the settings again if unit No. 1 fails. (If unit No. 1 fails, and the power supply to it is interrupted, it will be necessary to set a different unit as unit No. 1 in order to use manual backup operation.)
Control Functions
1 - 2
Page 11
3-WAY VRF SYSTEM
2. Selecting an Outdoor Unit for Operation
Control Functions
2-1. Outdoor Unit Operating Rules
Because in this system all outdoor units contain an inverter compressor, ordinarily there is no absolute order of
priority for compressor operation. Therefore there is no order of priority for the outdoor units.
However, it is possible to operate the outdoor units in sequence, beginning with unit No. 1, by using the outdoor
unit maintenance remote controller to change the outdoor unit EEPROM settings.
* For information concerning EEPROM settings, refer to the field application functions.
2-2. Delayed Start of Outdoor Units
(1) Delayed start of outdoor units in the same system
If it is necessary to operate the compressors simultaneously at multiple outdoor units, each outdoor unit will
start, beginning with unit No. 1, after a delay of a number of seconds equivalent to the outdoor unit address.
The units do not start simultaneously.
This is in order to reduce the load on the power receiving equipment.
Outdoor unit
address 1
Starts after 1 secondStarts after 2 seconds
(2) Delayed start for each system
At the time of factory shipment, delayed start for each system is not set to occur. Therefore when systems are
linked and multiple systems are selected for start simultaneously by the central control device, all systems will
begin operating simultaneously. For this reason, a function is included to delay the start time for each system
address when systems are linked and multiple systems are selected for start by the central control device.
In order to enable this delay time, it must be set in the EEPROM for each system. Those systems where this
setting has been made will start after a delay according to their system addresses.
* For information concerning EEPROM settings, refer to the field application functions.
Outdoor unit
address 2
1
2-3. Outdoor Unit Stop Rules
(1) Simultaneous stop of multiple outdoor units
When all outdoor units, or multiple outdoor units, must stop, the units stop at the same time. However,
depending on the communications timing, a difference of approximately 10 seconds may occur.
(2) Stopping individual outdoor units
●
The last unit to stop operating is the outdoor unit that contains the inverter compressor with the shortest
amount of operating time.
●
If the indoor load decreases, and it becomes necessary to reduce the number of operating outdoor units, the
compressors are stopped individually, in sequence. When all compressors installed in an outdoor unit have
stopped, that outdoor unit also stops.
1 - 3
Page 12
1
3. Compressor Control
3-1. Compressors Mounted in the Outdoor Units
[U-72MF1U9, U-72MF1U9E, U-96MF1U9, U-96MF1U9E]
Capacity7296
Installed
compressor
Compressor 1RotaryDC InverterDC Inverter
Compressor 2Scroll
–
hp = horsepower
Compressor 2Compressor 1Compressor 1
5 hp
Constant
speed
3-WAY VRF SYSTEM
Control Functions
INVINV
Type 96Type 72
3-2. Compressor Selection Rules
Because all outdoor units in this system contain an inverter compressor, ordinarily there is no absolute order of
priority for compressor operation.
(1) Normal compressor operation sequence (set at time of shipment)
At least one inverter compressor is always operating in order to make fine adjustments to the system
lower-limit capacity. When multiple outdoor units are connected, each unit contains an inverter compressor.
Therefore, the inverter which operates is the inverter with the shortest amount of operating time. After the first
inverter compressor has started, the remaining inverter compressors and constant-speed compressors start
operating in order of the compressors which have the shortest amount of operating time.
* Immediately after installation, all compressors have an operating time of zero. In this case, the compressors
start in the following sequence: Inverter compressor > Constant-speed compressor.
<Details>
The A/C units are selected with consideration for the maximum load. Therefore, in most cases the maximum
capacity is not required. Ordinarily, the operating range of an inverter compressor is approximately 25 Hz – 90
Hz, however operating efficiency declines somewhat in the high-frequency operating range. With consideration
for these characteristics, control of inverter compressors in this system is divided into two ranges, according
to the frequencies. Ordinarily, for reasons of efficiency, the upper limit for operation is approximately 50 Hz. If
greater capacity is required, the next compressor is started. When all compressors are operating and greater
capacity is required, the inverter compressors are operated at frequencies above approximately 50 Hz. This
control may increase the lifetimes of the inverter compressors and refrigerant oil.
* If the number of connected outdoor units is small, the number of inverter compressors is also small. Therefore,
the compressors may operate at a high frequency even when the load is not large.
(2) Sequential operation beginning from unit No. 1
By using the outdoor unit maintenance remote controller to change the outdoor unit EEPROM settings, it is
possible to start the units in sequence, beginning from unit No. 1.
* For information concerning EEPROM settings, refer to the field application functions.
1 - 4
Page 13
3-WAY VRF SYSTEM
3. Compressor Control
Control Functions
3-3. Compressor Capacity Control
The compressor operating conditions vary depending on the indoor unit operating conditions and on the effects
of indoor heat load, outside temperature, and other factors. Unit No. 1 (CCU) calculates the required capacity
according to these operating conditions, and allocates the capacity requirement among the outdoor units,
according to the compressor start/stop rules. Fine adjustments to system capacity control are made by the inverter
compressors. (Depending on the conditions, all inverter compressors may be operating for fine adjustment.)
3-4. Inverter Compressor Capacity Control
(1) The inverter compressor has a center limit value and upper limit value for the operating frequency. These limits
are set for each outdoor unit capacity.
(2) The inverter frequency during operation may be lower than the frequency listed above due to overload current
protection control. In this case, the inverter frequency lower limit is 22 Hz.
* If Quiet mode is selected, the inverter may stabilize at a frequency lower than those stated above.
For information about Quiet mode, refer to the field application functions.
3-5. Forced Compressor Stop
After a compressor stops, it will not start for a period of 3 minutes (3 minutes forced OFF). However, this does not
apply when the compressor was forced to stop as the result of a control operation during the special controls (start
control, defrost control, refrigerant oil recovery control, etc.) which are described later.
1
3-6. Roadmap Control
(1) The below controls are performed according to the pressure sensor on the outdoor unit, and the 2 temperature
sensors attached to the indoor unit heat exchanger.
* With roadmap control, the pressure detected by the pressure sensor is converted to saturation temperature.
A temperature that has been converted to saturation temperature is called the pressure sensor temperature.
(2) These controls are performed every 30 seconds.
(3) The temperatures used to determine the area (A, AB, B, C) for the evaporation temperature control shown in
the figure on the next page, and for condensation temperature control, may vary depending on the relationships
among factors including the difference between the room temperature setting and the indoor unit air intake
temperature (= air intake temperature difference) and the difference between the air discharge temperature
setting and the air discharge temperature (= air discharge temperature difference).
(4) Definitions of evaporation temperature and condensation temperature
Evaporation temperature (Te): Lowest heat exchanger temperature (E1, E3) at any indoor unit
Condensation temperature (Tc): Highest temperature among the outdoor unit pressure sensor temperature and
the heat exchanger temperatures (E1) at all indoor units where the heating
thermostat is ON.
Ordinarily, this is the outdoor unit pressure sensor temperature. (If multiple
outdoor units are connected, this is the highest outdoor unit pressure sensor
temperature.)
* E3 temperature is not used for condensation temperature detection, because it may indicate the temperature
of superheated gas.
1 - 5
Page 14
1
3-WAY VRF SYSTEM
3. Compressor Control
3-6-1. Evaporation Temperature (Te) Control: Control of Indoor Units Operating in Cooling Mode
60.8
˚F
Horsepower increase
permitted
51.9
51.8
Horsepower increase
permitted
41.1
41.0
Horsepower increase
prohibited
35.6
Horsepower decrease
35.4
Depending on the maximum requirement level of the indoor unit, the judgment
*
temperatures for each area may vary as shown in the figure (example).
Area A
Area AB
Area B
Area C
(1) For indoor units that are operating in Cooling mode, if one unit is selected for a test run, then the air
intake temperature difference (difference between the room temperature setting and indoor unit air intake
temperature) is ignored, and areas B and C are considered to be area A for control purposes. (This is used for
additional charging, test run checks, etc.)
For this reason, vapor may be discharged if the test run continues for a long period of time, however this does
not indicate a problem. In addition, the test run is canceled automatically after 1 hour.
(2) Even within the same area, the compressor capacity varies depending on the refrigerant temperature.
(3) For 6 minutes after the compressors start, area C is considered to be area B for control purposes.
(4) During special control, control of the compressor capacity according to Te is not performed.
(5) If the thermostat turns OFF while Te is within area C, the next time the compressor starts it may restart from a
lower capacity.
(6) When the area changes to area C, area C is considered to be area B for control purposes for the first 6
minutes, even if the horsepower is the minimum value within the range where capacity control is possible
(operation with inverter frequency of 25 Hz only). Subsequently if C area continues, the thermostat turns OFF.
53.6
51.8
45.5
0
Maximum requirement level [L]
15
41.0
35.6
30
Control Functions
1 - 6
Page 15
3. Compressor Control
3-6-2. Condensation Temperature (Tc) Control:
Control when there are indoor units operating in Heating mode
3-WAY VRF SYSTEM
Control Functions
PX = 125.6 ˚FPXThermostat OFF
–0.1
Horsepower decrease
118.5
118.4
Horsepower increase
prohibited
116.6
116.4
Horsepower increase
permitted
113.0
112.8
Horsepower increase
permitted
*
Depending on the maximum requirement level
of the indoor unit, the judgment temperatures
for each area may vary as shown in the figure
(example).
Area D
Area C
Area B
Area AB
Area A
109.4
107.6100.4
98.6
0
Maximum requirement level [L]
1530
118.4
116.6
(1) For indoor units which are operating in Heating mode, if one unit is selected for a test run, the air intake
temperature difference is ignored, however Tc control is performed according to the figure above in order to
prevent excessive load. (This is used for test run checks, etc.)
(2) Even within the same area, the compressor capacity varies depending on the refrigerant temperature.
(3) Temperature PX is the coefficient value used to correct for any deviation with the high pressure or condensation
temperature. It may vary. (At the time of shipment it is 125°F.)
(4) If the condensation temperature (Tc) enters area D and the thermostat turns OFF, the next time the compressor
starts it may restart from a lower capacity.
(5) When the area changes to area C, area C is considered to be area B for control purposes for the first 6
minutes, even if the horsepower is the minimum value within the range where capacity control is possible
(operation with inverter frequency of 25 Hz only). Subsequently if C area continues, the thermostat turns OFF.
1
3-6-3. Control of condensation temperature and evaporation temperature during mixed cooling/heating
operation
During mixed cooling/heating operation, the control maintains a heat balance with a target evaporation temperature
(Te) for the Cooling mode indoor units of 35 ~ 42°F and a target condensation temperature (Tc) for the Heating
mode indoor units of 116 ~ 118°F.
Heat balance control is performed by varying the compressor capacity and heat discharge (heat intake) of the heat
exchanger.
(1) Increasing/decreasing the compressor capacity
• When evaporation temperature (Te) is high and condensation temperature (Tc) is low
This occurs when both the cooling capacity (heat intake) and the heating capacity (heat discharge) are low.
The compressor capacity and the circulation flow of refrigerant are increased in order to lower the evaporation
temperature (Te) and raise the condensation temperature (Tc).
• When evaporation temperature (Te) is low and condensation temperature (Tc) is high
This occurs when both the cooling capacity (heat intake) and the heating capacity (heat discharge) are
high. The compressor capacity and the circulation flow of refrigerant are decreased in order to raise the
evaporation temperature (Te) and lower the condensation temperature (Tc).
* Under conditions other than those listed above, the capacity of the outdoor unit heat exchanger is adjusted.
In some cases the heat exchanger capacity may also be adjusted at the same time when the compressor
capacity is varied.
1 - 7
Page 16
3. Compressor Control
Compressor Control Table
Low Condensation Temp. [Tc] High
A
B
CD
3-WAY VRF SYSTEM
Control Functions
1
AUP
High
B
C
Evaporation Temp. [Te]
Low
slow_UPTarget
not_UP
not_UP
STOP
DOWN
Evaporation temperature (Te) and condensation temperature (Tc) areas A, B, C, and D are the same as for
evaporation temperature control and condensation temperature control.
(2) Increasing/decreasing the heat exchanger capacity (when the outdoor unit heat exchanger is functioning as a
condenser)
• Primarily when both the evaporation temperature (Te) and condensation temperature (Tc) are high
This occurs when the cooling capacity (heat intake) is low and the heating capacity (heat discharge) is high.
The outdoor heat exchanger capacity is increased, increasing the system condensation capacity and lowering
the condensation temperature (Tc). The amount of heat discharge at the outdoor unit heat exchanger
increases, increasing the heat intake at the Cooling mode indoor units and lowering the evaporation
temperature (Te).
• Primarily when both the evaporation temperature (Te) and condensation temperature (Tc) are low
This occurs when the cooling capacity (heat intake) is high and the heating capacity (heat discharge) is
low. The outdoor heat exchanger capacity is decreased, decreasing the system condensation capacity and
raising the condensation temperature (Tc). The amount of heat discharge at the outdoor unit heat exchanger
decreases, decreasing the heat intake at the Cooling mode indoor units and raising the evaporation
temperature (Te).
Outdoor Unit Heat Exchanger Control Table (when the outdoor unit heat exchanger is functioning as a
condenser)
High
Evaporation Temp. [Te]
Low
Low Condensation Temp. [Tc] High
A
B
C
STAY
DOWN
A
B
Target
CD
UP
STAY
STAY
STAY
Compressor stop
STAY
1 - 8
Page 17
3-WAY VRF SYSTEM
3. Compressor Control
(3) Increasing/decreasing the heat exchanger capacity (when the outdoor unit heat exchanger is functioning as an
evaporator)
• Primarily when both the evaporation temperature (Te) and condensation temperature (Tc) are low
This occurs when the cooling capacity (heat intake) is high and the heating capacity (heat discharge) is low.
The outdoor heat exchanger capacity is increased, increasing the system evaporation capacity and raising
the evaporation temperature (Te). The amount of heat intake at the outdoor unit heat exchanger increases,
increasing the heat discharge at the Heating mode indoor units and raising the condensation temperature (Tc).
• Primarily when both the evaporation temperature (Te) and condensation temperature (Tc) are high
This occurs when the cooling capacity (heat intake) is low and the heating capacity (heat discharge) is high.
The outdoor heat exchanger capacity is decreased, decreasing the system evaporation capacity and lowering
the evaporation temperature (Te). The amount of heat intake at the outdoor unit heat exchanger decreases,
decreasing the heat discharge at the Heating mode indoor units and lowering the condensation temperature (Tc).
Outdoor Heat Exchanger Control Table (when the outdoor heat exchanger is functioning as an evaporator)
Low Condensation Temp. [Tc] High
A
B
CD
Control Functions
1
High
Evaporation Temp. [Te]
Low
STAY
Target
STAY
UP
UP
DOWN
STAY
STAY
STAY
Compressor stop
STAY
3-6-4. Protection control
Protection control consists of 2 types of protection: air discharge temperature protection and current protection. The
limit values from this protection control are incorporated into the output compressor capacity increase/decrease
values that were calculated from control based on the temperature at the indoor unit heat exchanger (roadmap
control).
* In some cases, the control shown below may stop the compressor, issue a warning, or reduce the compressor
capacity.
(1) Air discharge temperature protection
During operation when only a single outdoor unit is installed, the air discharge temperature level is determined
(the highest value is used), and the compressor capacity is limited, by using the air discharge temperature of
the operating compressor (as shown in the tables below).
Air discharge temperature level: Highest level among the air discharge temperature levels of all compressors
Air discharge temp. levelDischarge temp.Horsepower limit
5
4
3
2
1
0
The values shown in the table above are reduced to the values calculated by roadmap control.
212 ~ Less than 217
208 ~ Less than 212
221
219
217
Less than 208
1 - 9
Decrease by 2 horsepower
Decrease by 1 horsepower
Decrease by 0.5 horsepower
Prohibit horsepower increase
Permit horsepower increase
No control
Page 18
3-WAY VRF SYSTEM
4. Special Controls
(2) Current protection
Inverter compressor current control is composed of primary current control and secondary current control.
Current protection control for the inverter compressor is performed by self-protection in the inverter circuit, and
does not increase or decrease the compressor capacity.
Primary currentSecondary current
Control Functions
1
–75 or (302 °F)Thermostat OFF
–48 or aboveThermostat OFF
26.525 ~ 32.5Horsepower decreased
2524 ~ Less than 25Prohibit horsepower increase
24Less than 24Permit horsepower increase
3-6-5. Roadmap control after trip
When restarting after trip stop occurs, the horsepower may increase slowly depending on the trip counter value.
(1) If Trip counter = 1, the horsepower increases at a speed that is 1/2 of ordinary roadmap control.
(2) If Trip counter = 2, the horsepower increases at a speed that is 1/3 of ordinary roadmap control.
The trip counter is cleared if no trip occurs within 10 minutes after operation starts.
Operation stops instantaneously due
to activation of hybrid IC
Thermostat OFF. Operation stops for
100 ms for current protection
1 - 10
Page 19
3-WAY VRF SYSTEM
4. Special Controls
In addition to ordinary heating and cooling operation, this system also includes the following 3 types of special
controls for control of the system as a whole.
1. Tube refrigerant recovery control
2. System refrigerant oil recovery control
3. Defrost control
Control Functions
4-1. Tube Refrigerant Recovery Control
This control recovers refrigerant from the tubing when the microcomputer is initialized immediately after power-ON,
after warning output occurs, and after a set amount of time has elapsed (standard = 60 minutes) when all outdoor
units are stopped.
This control is intended to recover refrigerant if refrigerant has accumulated somewhere in the tubing when the
units have been stopped for long periods, as well as to compensate for tubing thermal loss during heating start,
and is also used for oil recovery.
(1) Control when the outdoor unit heat exchanger is acting as a condenser (when all units are in Cooling mode or
at start of mixed operation when the cooling load is high)
Control time60 seconds
Outdoor unitsAll outdoor units operate at maximum horsepower.
Electronic control valve Valves at all indoor units operate at a fi xed pulse according to the indoor unit capacity.
Indoor
units
* When the above operation is fi nished, normal operation starts at the horsepower determined by the indoor units
where thermostats are ON.
RAP valve kitValve kits at all indoor units operate in Cooling mode (ON status).
Fan
Fan operates at the set fan speed, stops, or operates at L speed, depending on the
indoor unit operation mode.
1
(2) Control when outdoor unit heat exchanger is acting as a condenser (when all units are in Cooling mode or at
start of mixed operation when cooling load is high)
Control timeMinimum 1 min – Maximum 10 min [until max (pressure sensor temp., E1) ≥ 95°F]
Outdoor unitsAll outdoor units operate at maximum horsepower.
Electronic control valve Valves at all indoor units operate at 480 pulses.
Indoor
units
* When the above operation is fi nished, normal operation starts at the horsepower determined by the indoor units
where thermostats are ON.
RAP valve kitValve kits at all indoor units operate in heating mode (ON status).
Fan
Fan operates at the set fan speed, stops, or operates at L speed, depending on the
indoor unit operation mode.
4-2. System Refrigerant Oil Recovery Control
4-2-1. System refrigerant oil recovery cycle
This control is performed using the cooling cycle during cooling operation and using the heating cycle during
heating operation.
4-2-2. Start of system refrigerant oil recovery control
When the oil level in an operating compressor changes to 0, the compressor stops after 120 seconds. If this
compressor repeats this operation 3 times and the oil level does not reach 2, system refrigerant oil recovery control
is started.
* When the compressor has stopped because the oil level is 0, a count is added to the alarm counter. The counter
for this compressor is not cleared unless the oil level for that compressor reaches 2, or else alarm output occurs.
1 - 11
Page 20
1
3-WAY VRF SYSTEM
4. Special Controls
4-2-3. Flow of system refrigerant oil recovery control
(1) Simplified flow of system refrigerant oil recovery control
System refrigerant oil recovery control follows this flow:
Normal operation → 3-minute stop (May stop for 6 minutes.) → System refrigerant oil recovery control (Max. 3
minutes) → 3-minute stop → Normal operation
(2) Cooling cycle
Control timeMaximum 3 minutes (Stops once before and once after control.)
Outdoor unitsAll outdoor units operate at maximum horsepower.
Electronic control valve Valves at all indoor units operate at a fi xed pulse according to the indoor unit capacity.
Indoor
units
(3) Heating cycle
Indoor
units
RAP valve kitValve kits at all indoor units operate in Cooling mode (OFF status.)
Fan
Control timeMaximum 3 minutes (Stops once before and once after control.)
Outdoor unitsAll outdoor units operate at maximum horsepower.
Electronic control valve Valves at all indoor units operate at 480 pulses.
RAP valve kitValve kits at all indoor units operate in Heating mode (ON status).
Fan
Fan operates at the set fan speed, stops, or operates at L speed, depending on the
indoor unit operation mode.
Fan operates at the set fan speed, stops, or operates at L speed, depending on the
indoor unit operation mode.
Control Functions
4-3. Defrost Control
4-3-1. Defrost control method
This system uses the following 2 defrost methods.
(1) If there is 1 outdoor unit in the refrigerant system: Reverse cycle defrost
(2) If there are 2 or more outdoor units in the refrigerant system: Outdoor unit cycle defrost
4-3-2. Constraint conditions
(1) Frost detection does not occur for 5 minutes after operation starts.
(2) Defrost does not begin again for 35 minutes of A/C operation after defrost was once completed.
(3) If all indoor units are stopped while defrost control is in effect, or if the outdoor unit is stopped due to protection
control or another reason, then defrost control will not start for a minimum of 10 minutes after restart occurs.
1 - 12
Page 21
3-WAY VRF SYSTEM
4. Special Controls
4-3-3. Frost detection
(A) Frost detection does not occur for 5 minutes after operation starts.
(B) Frost is detected when either condition 1 or 2 below is met.
Condition 1: L2 line or below is detected twice, each time continuously for 4 minutes, when the compressor is
operating.
Condition 2: L1 line or below is detected for a total of 60 minutes when the compressor is operating.
Heat exchange liquid temperature ˚F
Defrosting operation
42.8
end temperature
(The end temperature is different from
the above detection temperature.)
Control Functions
1
–6.5
17
30
26
14
–9
–13
50
The frost detection area is
located under the thick lines
External temperature ˚F
L1
L2
4-3-4. Outdoor units where defrost occurs
Even if the total time has not reached 35 minutes, if there is 1 or more outdoor units that fulfills the defrost
detection conditions, all operating outdoor units perform defrost control at the same time.
* Defrost control is also performed at outdoor units where the outdoor unit heat exchanger is not functioning as an
evaporator (such as stopped outdoor units).
4-3-5. Reverse cycle defrost
Reverse cycle defrost is performed in systems where only 1 outdoor unit is connected to the refrigerant system.
• Defrost flow E: Evaporator operation
C: Condenser operation
E→C: Switching from evaporator operation to condenser operation
C→E: Switching from condenser operation to evaporator operation
* With type E1, E → C occurs for 3 minutes after defrost ends. Therefore the thermostat remains OFF for 3
minutes.
1 - 13
Page 22
1
3-WAY VRF SYSTEM
4. Special Controls
4-3-6. Outdoor unit cycle defrost
Outdoor unit cycle defrost is performed in systems where 2 outdoor units are connected to the refrigerant system.
(1) Description of outdoor unit cycle defrost
With this defrost method, when 1 outdoor unit operates in defrost mode (heat exchanger operating as a
condenser), another outdoor unit operates as an evaporator in the same way as in ordinary heating mode. In
this way, the other outdoor unit is heating the unit where defrost is occurring. When 1 outdoor unit completes
defrost, the other outdoor unit performs defrost in the same way. Because the amount of time that the unit
operates as an evaporator is very short, there is little danger of frost forming again quickly. Rather, because the
heat source is very powerful, it is possible to shorten the defrost operating time.
(2) Defrost sequence
Outdoor unit cycle defrost is always completed in 2 defrost operations.
(A) When there are 2 outdoor units
Control Functions
Defrost
outdoor unit
First operationSecond operation
Evaporator
outdoor unit
Switch
Evaporator
outdoor unit
Defrost
outdoor unit
• Defrost flow E: Evaporator operation
C: Condenser operation
S: Shut off
E→C: Switching from evaporator operation to condenser operation
C→E: Switching from condenser operation to evaporator operation
Defrost
preparation
Outdoor unit(s) where defrost occurs fi rstE→CCC→EE
* With type E1, E → C occurs for 3 minutes after defrost ends. Therefore the thermostat remains OFF for 3
minutes.
1 - 14
Page 23
3-WAY VRF SYSTEM
4. Special Controls
4-3-7. Defrost end judgment conditions
Defrost ends when either of the below defrost end judgment conditions is met.
Condition 1: The temperatures are 42.8°F or higher at all temperatures sensors installed on the outdoor unit heat
exchangers.
However, if there is any other outdoor unit where the defrost end condition has not been met, defrost
control continues for all outdoor units, and system defrost control is not ended.
Condition 2: The maximum defrost time listed in the table above has elapsed.
4-3-8. System defrost end
When all outdoor units where defrost control is in effect have met the defrost end conditions, defrost control is
ended for the system.
Control Functions
1
1 - 15
Page 24
5. Other Controls
5-1. Oil Control
5-1-1. Oil level
3-WAY VRF SYSTEM
Control Functions
1
Oil level
2Sufficient
1
0
MeaningOil stateAssessment
This is the normal operating state
of the system and not a problem.
Check that oil control recovers oil.
Check that system oil recovery
control restores the oil level.
Slightly
low
Extremely
low
There is more than an adequate amount of oil in the
compressor.
The compressor may contain an adequate amount of oil, but
it may also contain less than an adequate amount of oil.
There is not enough oil in the compressor.
The compressor contains enough oil when the oil level is in the range between level 2 and until it has just become
1. Thus oil level 1 does not mean that the compressor is empty of oil. When the compressor reaches oil level 0
during operation, the system is likely to run out of oil within 5 to 10 minutes. Check for oil leaks and make sure that
refrigerant pipes are intact.
5-1-2. Oil level detection
Excess oil in the compressor is sent by bypass via a capillary tube to the low-pressure circuit. The temperature
detected by a temperature sensor is used to determine whether it is oil (warm) or refrigerant (cold).
5-1-3. Self-separator oil recovery control
* When a low oil level is detected, this control recovers the oil which has accumulated in that oil separator and
sends it to the compressor.
(1) Operation when oil level is 1
30 seconds after the oil level changes from 2 to 1, both the balance valve and recovery valve turn ON for up to
2 minutes.
However, if the oil level becomes 2 during these 2 minutes, this control is stopped.
When this control has been stopped, it will not restart for 3.5 minutes unless the oil level becomes 0.
(2) Operation when oil level is 0
Both the balance valve and recovery valve turn ON and remain ON.
5-1-4. Unit refrigerant oil recovery control – utilizing balance tubes
* If the low oil level continues, that outdoor unit (oil-receiving outdoor unit) receives a supply of oil from operating
outdoor units where the oil level is not low (oil-supply outdoor units).
(1) Control at the oil-supply outdoor unit begins 3 minutes after the oil level at the outdoor unit changes to 0 or 1.
Oil supply is performed for a maximum of 5 minutes from each unit.
(2) When oil supply is ended, oil supply from that outdoor unit will not occur again for a period of [(No. of outdoor
units – 1) x 5 minutes]. In addition, oil supply is ended if the oil-receiving outdoor unit oil level changes to 2, or if
the oil-supply outdoor unit oil level becomes low.
(3) The supply of oil is received from 1 unit at a time, in sequence, according to the order of priority of their inverter
compressors.
(4) Operation during unit refrigerant oil recovery
(A) Oil-receiving outdoor unit
The recovery valve turns ON and remains ON.
* Because self-separator oil recovery may occur simultaneously at the same unit, both the balance valve
and recovery valve turn ON at this time.
(B) Oil-supply outdoor unit
The balance valve turns ON and remains ON.
The bypass valve repeatedly turns ON and OFF according to a fixed cycle.
* When the balance valve is ON, the oil in the oil separator is discharged into the balance tube. The bypass
valve releases high-pressure gas which forces this oil toward the oil-receiving outdoor unit, and flushes out
the balance tubes.
The operation of this bypass valve allows oil to be supplied even when there is a difference in height
between the outdoor units.
5-1-5. Indoor unit refrigerant oil self-recovery control
Refer to the items concerned with indoor unit special control.
1 - 16
Page 25
3-WAY VRF SYSTEM
6. Operation of Solenoid Valves
Control Functions
6-1. Refrigerant Control Valve [RCV]
The main purpose of this valve is to detect the flow of refrigerant (refrigerant volume) on the indoor-unit side when
the outdoor unit heat exchanger is functioning as a condenser. When the valve determines that there are signs of a
low refrigerant level, refrigerant is supplied from the receiver tank to the system.
(1) The OFF conditions take priority over the ON conditions for this valve.
(2) This valve is OFF when the outdoor unit is stopped.
(3) This valve is ON when special control is in progress.
(4) Control during normal operation
(A) Cooling operation
●
This valve turns ON when symptoms of insufficient refrigerant gas occur at an
indoor unit.
●
This valve turns ON when the outdoor air temperature is 59°F or below. (Under
these conditions the high pressure is low and refrigerant flow becomes poor.)
●
This valve turns OFF when symptoms of refrigerant overcharge are detected at
the outdoor unit.
(B) Mixed cooling/heating operation
●
The RCV turns ON at stopped outdoor units when the heat exchanger at
another outdoor unit is functioning as a condenser.
Hp
1
6-2. Refrigerant Balance Valve [RBV] – Gas Purge Valve
The main purpose of this valve is to detect the flow of refrigerant (refrigerant volume) on the indoor-unit side when
the outdoor unit heat exchanger is functioning as an evaporator. When the valve determines that there are signs of
excess refrigerant, refrigerant is recovered at the receiver tank.
This valve is ON during heating operation and when the outdoor unit heat exchanger is functioning as an
evaporator during mixed heating/cooling operation. It also turns ON in order to recover refrigerant at the outdoor
unit after heating operation is stopped.
* This valve is never ON at the same time as the RCV.
(1) The OFF conditions take priority over the ON conditions for this valve.
(2) This valve turns ON for 30 – 50 seconds after the outdoor unit stops, and then turns OFF.
(3) This valve turns ON once after the outdoor unit starts.
(A) Heating operation
●
This valve turns ON when poor refrigerant flow at an indoor unit is detected,
and when symptoms of overcharge are detected.
After the valve turns OFF, it will not turn ON again for 15 minutes.
(B) Mixed heating/cooling operation
●
This valve turns ON when poor refrigerant flow at an indoor unit is detected,
and when symptoms of overcharge are detected, if the heat exchanger at the
outdoor unit is functioning as an evaporator.
(4) This valve turns OFF when an abnormal drop in discharge gas temperature is detected.
(5) This valve turns OFF when a drop in the detected receiver tank temperature
continues for a set length of time, and when liquid back-flow is judged to be occurring.
Lp
1 - 17
Page 26
1
6. Operation of Solenoid Valves
6-3. Balance Valve (BALV)
This valve moves some of the oil from the oil separator to the balance tube.
(1) When unit is stopped
This valve is always OFF.
(2) When unit is operating
(A) This valve is ON when separator oil self-recovery control is in progress.
(B) This valve is ON when unit refrigerant oil recovery control is in progress (oil-supply unit).
(C) This valve turns ON for 30 seconds each time a constant-speed compressor starts.
(D) This valve turns ON for 60 seconds after defrost control ends.
6-4. Recovery Valve (ORVR)
This valve recovers refrigerant oil from the balance tube to the compressor.
(1) When unit is stopped
This valve is always OFF.
(2) When unit is operating
(A) This valve is ON when separator oil self-recovery control is in progress.
(B) This valve is ON when unit refrigerant oil recovery control is in progress (oil-receiving unit).
(C) This valve is ON when control for insufficient gas is in progress.
(D) This valve turns ON for 60 seconds after a constant-speed compressor starts.
(E) This valve turns ON for 120 seconds after defrost control ends.
(F) This valve turns ON for 10 seconds after the outdoor unit stops.
(G) This valve remains OFF at all times other than (A) – (F) above.
3-WAY VRF SYSTEM
Control Functions
6-5. Bypass Valve (BPV)
This valve flushes the oil from the balance tubes. In addition, it is used for recovering refrigerant from stopped
outdoor units during cooling operation.
(1) When unit is stopped
This valve is always OFF.
(2) When unit is operating
This valve is ON at the oil-supply outdoor unit when unit refrigerant oil recovery control is in progress.
* This valve repeatedly turns ON/OFF at regular intervals during unit refrigerant oil recovery control. (It is not
constantly ON.)
1 - 18
Page 27
3-WAY VRF SYSTEM
7. Outdoor Unit Electronic Control Valves [MOV1, MOV2, MOV4]
Control Functions
7-1. Types of Electronic Control Valves
[U-72MF1U9, U-72MF1U9E, U-96MF1U9, U-96MF1U9E]
Capacity7296
Electronic
control valve
Electronic control valve 1
Electronic control valve 2
Electronic control valve 4
Heat exchanger 1 valve
Heat exchanger 2 valve
For SC circuit
Heat exchanger 1 valve
Heat exchanger 2 valve
For SC circuit
7-2. Power Initialization
If no indoor units have started (even once) after the power was turned ON, the outdoor unit electronic control valve
operates at 480 pulses.
7-3. Heat Exchanger Controlled by Each Electronic Control Valve
The configuration of the heat exchangers is different depending on the capacity of the outdoor unit.
1
Heat
exchanger 1
Heat exchanger 2
Front
Type 72, 96
Operation of electronic control valves during normal unit operation
Heat exchanger
status
All indoor units in Cooling mode
All indoor units in Heating mode
Mixed
heating/
cooling
operation
●
When all indoor units are operating in Cooling mode or Heating mode, all outdoor unit heat exchangers are used
Outdoor heat
exchanger condenser
Outdoor heat
exchanger evaporator
Condensor480480Maximum fl ow control
Stopped00Refrigerant shut-off
Evaporator45~48015~480SH control
Stopped00Refrigerant shut-off
Condensor50~48050~480Heat exchanger capacity control
Stopped00Refrigerant shut-off
Evaporator45~48015~480SH control
Stopped00Refrigerant shut-off
MOV1MOV2Remarks
if even one of the compressors in that outdoor unit is operating.
●
During mixed heating/cooling operation, the number of heat exchangers used varies according the conditions of
the indoor units. However, heat exchanger 1 at the outdoor unit which contains the inverter compressor with the
lowest amount of operating time is always used.
●
SH control controls the difference between the liquid temperature and gas temperature to 2 ~ 10°F.
●
During heating mode SH operation, refrigerant may not flow to the heat exchanger.
1 - 19
Page 28
1
3-WAY VRF SYSTEM
7. Outdoor Unit Electronic Control Valves [MOV1, MOV2, MOV4]
Control Functions
7-4. SC Circuit Electronic Control Valve [MOV4]
(1) Operation to increase SC
During cooling operation, or mixed heating/cooling operation when the outdoor unit heat exchanger is
functioning as a condenser, the liquid refrigerant which condenses at the outdoor unit heat exchanger flows into
the receiver tank, and SC (sub-cool = supercooling) approaches 0°F. When SC is small and the length of the
tubing connecting the indoor and outdoor units is long, the pressure loss increases, possibly resulting in lower
capacities. Therefore, MOV4 operates at the double tube near the discharge port of the outdoor unit in order to
increase SC.
MOV4 uses the receiver tank detection sensor and low-pressure sensor located near the accumulator to
perform control in order to prevent liquid back-up.
Liquid refrigerant (SC = 0˚F)
Gas refrigerant returns
to the accumulator.
Refrigerant on the outer side evaporates,
cooling the liquid refrigerant on the inner side.
Liquid refrigerant
(large SC)
Electronic control valve 4
(expansion valve) controls the flow.
(2) Operation when discharge temperature is high
When the discharge temperature increases, the SC circuit electronic control valve opens to 480 pulses. This
intentionally causes a mild liquid back-up, cooling the compressor. This operation takes priority over operation
intended to increase SC. It is performed at top priority in all operating modes.
Liquid refrigerant returns
to the accumulator.
Liquid refrigerant
Does not fully evaporate,
resulting in liquid back-up.
Electronic control valve
4 opens to 480 pulses.
Liquid refrigerant
1 - 20
Page 29
3-WAY VRF SYSTEM
8. Outdoor Fan Control
Control Functions
8-1. Fan mode
These outdoor units utilize a DC fan motor that can be controlled in a maximum of 16 steps (16 modes).
However, fan modes 15 and 16 can only be used if high static-pressure mode has been set.
* For information concerning EEPROM settings, refer to the field application functions.
8-2. Outdoor Fan Min. Fan Mode and Max. Fan Mode
Min. fan modeMax. fan mode
Cooling operation
Heating operation114
* Even if the fan mode is 0 during cooling operation, the fan mode may change to 1 at regular intervals for
temperature protection of the inverter hybrid IC.
Outdoor air temp. > 59°F: 1
Outdoor air temp. ≤ 59°F: 0
14
8-3. Fixed Initial Fan Mode
For the first 30 seconds after operation starts, the mode is fixed at the initial mode which was calculated from the
relationship between the outdoor air temperature and the outdoor unit horsepower.
If the outdoor unit horsepower changes dramatically, the initial mode may be recalculated and may be again fixed
for 30 seconds.
8-4. Operation after Fixed Initial Fan Mode
After the fixed initial fan mode, the fan mode is increased or decreased according to the operating conditions.
(1) Cooling mode at all indoor units, or else mixed heating/cooling operation when the outdoor unit is functioning
as a condenser
(A) Fan mode is increased when the pressure sensor temperature is high, and is decreased when the pressure
sensor temperature is low.
* The fan mode is always increased when the pressure sensor temperature is 122°F or higher.
(B) The fan mode may be decreased when symptoms of insufficient gas are detected at an indoor unit.
1
(2) Heating mode at all indoor units, or else mixed heating/cooling operation when the outdoor unit is functioning
as an evaporator
(A) If the condensation temperature is low, the fan mode is increased at regular intervals.
(B) If the condensation temperature is high, the fan mode is decreased in order to prevent excessive loads.
(C) The fan mode may be increased when the outdoor liquid temperature drops to 44°F or below.
8-5. Snow Removal Control
(1) When the outdoor air temperature is 50°F or below, the fan operates for 30 seconds every 2 hours in fan mode
8, even when the outdoor unit is stopped or the heat exchanger is not in use. This control is intended to prevent
snow from accumulating on stopped fans. (Because the outdoor air temperature cannot be accurately detected
when the unit is stopped, a higher outdoor air temperature is used for the control condition, in order to ensure
correct operation.)
(2) If the fan mode becomes 0 during cooling operation, the fan mode is changed to 1.
* This control is predictive control. Use a snowfall sensor as necessary according to the installation conditions.
8-6. When the Compressor Magnet Switch Seizing Alarm Occurs
Because there is the possibility that the high pressure has increased, the fan operates in Max. fan mode.
8-7. Other
This unit includes settings for high static-pressure and for Quiet mode.
For information about these settings, refer to the field application functions.
1 - 21
Page 30
3-WAY VRF SYSTEM
9. Demand Control
Serial-parallel I/O must be connected in order to perform demand control. The below input is received by
serial-parallel I/O, and demand control is performed.
The demand values can be set as needed with this device. For more information, refer to the field application
functions.
Control Functions
1
Demand setting
Contact 1Contact 2
¯¯
{¯
¯{
{{
: Input present
{
No controlOperates to maximum capacity.
Rated current—
Operates at up to 70% of rated current—
Shutdown state—
: Input not present
¯
ControlDemand meaning
* The rated current indicates the current value that is listed in the catalog or similar material. If the capacity of this
device is insufficient, the inverter compressor raises its operating frequency in order to maintain capacity. For
this reason, it is capable of operating at a current which exceeds the rated current (up to approximately 130%).
1 - 22
Page 31
3-WAY VRF SYSTEM
10. Indoor Unit Control of the Electronic Control Valve
Control Functions
10-1. Normal Control
(1) Cooling operation
Position of electronic control valve
Outdoor unit operating
Stopped2020
Fan2020
Thermostat
Cooling
*
The SH target value is controlled so that the difference [E3 – E1] is 4 – 12°F, depending on the operating conditions.
OFF
Thermostat ONPerforms SH control in the range of 55 – 480
pulses.
2020
However, a decline in the required level may cause the SH target value to increase. Be aware that in this case, the
electronic control valve closes slightly. This can be easily identified incorrectly as insufficient gas.
(2) Heating operation
(A) Except Type E1
Position of electronic control valve
Outdoor unit operating
StoppedShuts off refrigerant at 20 pulses.85
FanShuts off refrigerant at 20 pulses.85
Heating
Thermostat
OFF
Thermostat ONPerforms SC distribution control within the range of 55 –
Shuts off refrigerant at 20 pulses.85
480 pulses.
Outdoor unit
stopped
–
Outdoor unit
stopped
–
1
* The SC target value is controlled so that the difference [Pressure temp. sensor – E1] is 10 – 40°F, depending
on the operating conditions.
(B) Type E1
Position of electronic control valve
Outdoor unit
stopped
–
Heating
Outdoor unit operating
Stopped2020
Fan2020
Thermostat
OFF
Thermostat ONPerforms SC distribution control within the range of 55 –
480 pulses.
2020
* The SC target value is controlled so that the difference [Pressure temp. sensor – E1] is 10 – 40°F, depending
on the operating conditions.
However, if installation is combined with except type E1, the value is controlled so that the difference
[Pressure temp. sensor – E1] is 10 – 80°F.
1 - 23
Page 32
1
10. Indoor Unit Control of the Electronic Control Valve
10-2. Special Control
Control
Tube refrigerant oil
recovery control
Reverse cycle
defrost control
Outdoor cycle
defrost control
System refrigerant
oil recovery control
Operating
mode
CoolingAll indoor units
HeatingAll indoor units480
Heating
Cooling/
heating
CoolingAll indoor units
HeatingAll indoor units250
Subject indoor unitsPosition of electronic control valve
StoppedCooling control, according to indoor unit capacity
FanCooling control, according to indoor unit capacity
Thermostat
ON
Thermostat
Cooling
Heating
Cooling
Heating
OFF
Thermostat ONFixed pulse for heating, according to indoor unit
Thermostat
OFF
Stopped20
Fan20
Thermostat
ON
Thermostat
OFF
Thermostat
ON
Thermostat
OFF
Fixed pulse for cooling, according to indoor unit
capacity
Cooling control, according to indoor unit capacity
Cooling control, according to indoor unit capacity
However, position is 20 pulses for type E1.
capacity
Heating control, according to indoor unit capacity
However, position is 20 pulses for type E1.
Cooling control, according to indoor unit capacity
20
Heating control, according to indoor unit capacity
20
Fixed pulse for cooling, according to indoor unit
capacity
3-WAY VRF SYSTEM
Control Functions
1 - 24
Page 33
3-WAY VRF SYSTEM
11. Solenoid Valve Kit Control
This device connects the solenoid valve kit which is used to switch between indoor unit cooling/heating for 3-WAY
types.
Operation of the except type E1 solenoid valve kit
Discharge
valve
StoppedOFFOFFONOFF
FanOFFOFFONOFF
Thermostat
Thermostat
Cooling
Thermostat
Thermostat
Heating
OFF
ON
OFF
ON
OFFONONON
OFFONONON
ONOFFOFFOFF
ONOFFOFFOFF
Operation of the type E1 solenoid valve kit
Discharge
valve
StoppedOFFOFFONOFF
FanOFFOFFONOFF
Thermostat
Thermostat
Cooling
Thermostat
Thermostat
Heating
OFF
ON
OFF
ON
OFFONONON
OFFONONON
OFFOFFOFFOFF
ONOFFOFFOFF
Intake
valve
Intake
valve
Balance
valve
Balance
valve
EP valve (evaporation
temp. control valve)
EP valve (evaporation
temp. control valve)
Control Functions
1
1 - 25
Page 34
3-WAY VRF SYSTEM
12. Indoor Special Control
Control Functions
12-1. Switching Control (EC control)
If the settings indicate that an RAP valve kit is present (for type E1, the setting on initial shipment from the factory
is “present”), then the thermostat does not turn ON for 3 minutes after the indoor unit operating mode is changed
from any mode other than heating (including stopped) to heating with thermostat ON. This is done in order to balance the pressure within the heat exchanger.
* With type E1, this control is activated after defrost control is completed, turning the thermostat OFF for 3 minutes.
1
12-2. Indoor Unit Thermostat ON/OFF Delay Timer
(1) After the thermostat turns ON at an indoor unit, the thermostat will not be turned OFF by the room temperature
thermostat or discharge temperature thermostat for a period of 3 minutes.
However, if the condensation temperature reaches or exceeds the PX temperature, the thermostat turns off in
order to prevent overload.
(2) After the thermostat turns OFF at an indoor unit, the thermostat will not turn ON again for a minimum of 3 minutes.
12-3. Indoor Unit Refrigerant Oil Self-Recovery Control
This control is performed periodically only during cooling operation.
(1) At indoor units which are stopped, operating in fan mode, or where the thermostat is OFF, the electronic control
valve is opened for 1 – 2 minutes.
(2) At indoor units where the thermostat is ON, the electronic control valve position is opened by 10 pulses from
the current position.
1 - 26
Page 35
3-WAY VRF SYSTEM
13. Discharge Temperature
Control Functions
<Alarm Information>
(1) Discharge temperature protection alarm
This device sets an upper limit discharge temperature of 222°F for all compressors. When the discharge tem-
perature reaches 222°F, that compressor is stopped and restarted. If the same high discharge condition occurs
4 times, then an alarm occurs.
After a compressor has stopped, that compressor will not operate until the temperature has dropped to or below
the start-prohibit temperature.
Discharge temperature protection list
Compressor No.Compressor 1Compressor 2
TypeInverterConstant-speed
Stop temp.222222
Start-prohibit temp.194194
Alarm displayP03P17
(2) Discharge sensor trouble detection control
An alarm occurs if the discharge temperature remains abnormally high when the system has been stopped for
60 minutes.
* In this case, possible causes include sensor failure and compressor overheating caused by an insufficient
level of refrigerant.
The alarm also occurs if the sensor temperature is at or above the abnormal temperature (176°F) when 20 min-
utes have passed after the compressor stopped.
* In this case, it is possible that the discharge temperature from a different outdoor unit is being detected, due to
an error in the installation of the discharge thermistor.
Discharge sensor failure list
Compressor No.Compressor 1Compressor 2
TypeInverterConstant-speed
Stop temp.F04F05
1
1 - 27
Page 36
1
3-WAY VRF SYSTEM
14. Current Protection
(1) Fan motor
AlarmDescription
P22Occurs when the fan motor detects overcurrent, or when the motor is locked and does
not turn.
(2) Inverter compressor
AlarmDescription
P16Occurs during ordinary operation when overcurrent (27 A) is detected.
P26Occurs under the same conditions as P16 when the inverter compressor is operating
at or above 80 Hz.
P29Occurs when missing phase or overcurrent (48 A) is detected at inverter compressor
start. (The alarm at frequencies below 25 Hz)
H31Occurs when HIC detects overcurrent (75 A), or when an abnormal high temperature
(302 °F) is reached.
The inverter current includes a primary current and secondary current. The alarm judgment utilizes both
currents. Generally, the secondary current is larger that the primary current.
(3) Constant-speed compressor
An alarm occurs when overcurrent or lock current is detected.
List of overcurrent and lock currents
Control Functions
Outdoor unit
type
96Compressor 223.127.3
Constant-speed
compressor
Overload
current [A]
Lock current
[A]
List of Alarms
Compressor
No.
Detected
current
Alarm displayH11H12
Compressor 2
Overcurrent
Lock
current
(4) CT circuit detection trouble
AlarmDescription
Compressor 1 (inverter
compressor)
Compressor 2 (constantspeed compressor)
H03Occurs when an open CT circuit is detected in the inverter
compressor.
H13Occurs when a current value of 1.5 A or less is detected
when the constant-speed compressor is operating.
If the inverter compressor operating frequency is low, the current value is also low. Therefore this alarm is
detected only when the compressor is stopped.
The operating current of the constant-speed compressors is always higher than 1.5 A. Therefore, this alarm
occurs as the result of an open circuit or failure.
1 - 28
Page 37
3-WAY VRF SYSTEM
15. Low Oil Alarm
Ordinary operation is resumed after system oil recovery control is completed. If a stop occurs again as a result
of a low oil level, this alarm occurs. This alarm will not occur if system oil recovery control has not already been
performed.
However, the alarm may not occur if the outdoor unit where the system oil recovery conditions were met is not
the same as the outdoor unit which stopped due to low oil level. In this case, system oil recovery control may be
performed again.
Low oil alarm
Alarm displayH07
Control Functions
1
1 - 29
Page 38
1
3-WAY VRF SYSTEM
16. Pressure Sensor Failure
This system contains 2 types of pressure sensors: a high-pressure sensor and a low-pressure sensor.
(1) High-pressure sensor failure
Identification of a failure caused by a loose or displaced connector is based on the relationship between the pres-
sure detected by the high-pressure sensor and the operation of the high-pressure switch, and on the relationship
between the temperature detected by the high-pressure sensor and the various temperature thermistors.
However, when the pressure increases suddenly, the judgment for the high-pressure sensor failure alarm may
occur before operation of the high-pressure switch. Therefore, before concluding that there is a failure in the
pressure sensor, first verify that the service valve was not accidentally left closed, that there are no blocked circuits, and that there is no leakage of refrigerant into stopped outdoor units. Also check for a difference between
the high pressure measured by the manifold gauge and the pressure detected by the pressure sensor.
(2) Low-pressure sensor failure
Identification of a failure caused by a loose or displaced connector is based on the relationship between the
temperature detected by the low-pressure sensor and the various temperature thermistors.
Before concluding that a failure has occurred, check for a difference between the low pressure measured by the
manifold gauge and the pressure detected by the low-pressure sensor.
This system includes a function for automatic backup operation. An alarm is also displayed to inform the operator
that a failure has occurred.
(1) Alarms that result in automatic backup operation
When compressor trouble or fan motor trouble makes emergency continued operation impossible, automatic
backup operation mode is engaged. Automatic backup mode is not engaged in cases of communications
alarms, automatic reset alarms, and other instances when emergency operation is possible by pressing the
remote controller buttons or changing other conditions.
The alarms that result in automatic backup mode are P16, P22, P26, P29, H11, H12, and H31.
(2) Start of automatic backup operation
If the above alarms occur, the alarm is displayed on the control device. Pressing the control device button again
starts automatic backup mode.
(3) Operation
[1] When 1 outdoor unit is installed
When 1 compressor has failed, backup operation is possible using the other compressors. However, operation
does not occur when the outdoor fan is unable to operate as a result of alarm P22.
[2] When multiple outdoor units are installed
When automatic backup mode is engaged, the outdoor unit where the above alarm occurred stops operating.
However, if one or more of the compressors is able to operate, then this outdoor unit operates only when the
operation of all outdoor units is required for special control or other system purposes.
(4) Alarm display
If a wired remote controller is present, the
(5) Canceling automatic backup operation
Repair the outdoor unit where the failure occurred. When repairs are completed, reset the power on outdoor
unit No.1.
<Caution>
After automatic backup mode has been engaged, it will not be canceled automatically when the repair of the
failed outdoor unit is completed. Automatic backup mode will be canceled only when the power on outdoor
unit No.1 is reset. Therefore, after repair work is completed, be sure to check whether or not automatic backup
mode has been canceled.
How to check: [1] Use test run or other means to verify that all outdoor units operate continuously.
[2] If a wired remote controller is present, check that the display has disappeared.
display blinks during operation.
1
1 - 31
Page 40
1
3-WAY VRF SYSTEM
17. Backup Operation
Control Functions
17-2. Manual Backup
If an alarm that does not result in automatic backup occurs frequently, possible causes include failure (such as
refrigerant leakage) of a functional part at an outdoor unit other than the unit where the alarm occurs.
In this case, because the outdoor unit service valve must be closed, backup operation must be performed manually.
(1) Backup operation procedure
[1] Disconnecting the failed outdoor unit
(A) Reduce the number of outdoor units set at outdoor unit No.1 by the number of failed outdoor units. Then
turn OFF the power or disconnect the inter-unit communications line at the failed outdoor units.
(B) Close all service valves at the failed outdoor units.
(C) Reset the power at outdoor unit No.1.
[2] Disabling operation of 1 compressor
At the S010 switch on the PCB of the failed outdoor unit, turn ON the switch for the compressor to disable, and
turn ON the “backup” switch.
<S010 switch>
INVAC2AC1Backup
ON
OFF
(A) Compressor 1 backup
(B) Compressor 2 backup
• In order to perform simultaneous backup operation for 2 or more compressors, use a combination of the switch
settings shown above.
1 - 32
Page 41
3-WAY VRF SYSTEM
18. Service Maintenance Functions
The outdoor unit EEPROM settings can be used for the following functions.
Control Functions
18-1. Outdoor Unit Noise Countermeasure: EEPROM 05 (set at each outdoor unit)
This unit includes 3 types of Quiet modes. (However, when they are engaged, operation is in Quiet mode 24 hours
a day.) Selecting a Quiet mode results in operation that gives priority to reducing noise. Because these modes
involve restrictions on outdoor unit fan modes and the operation frequency, the capacity will be somewhat reduced.
SettingMax. fan modeEffectAmount of capacity reduction
014
112
211
310
Normal operation (setting at time of
factory shipment)
Noise reduced by approx. 1 – 2 dB from
the catalog value.
Noise reduced by approx. 2 – 3 dB from
the catalog value.
Noise reduced by approx. 5 dB from the
catalog value.
0
Approx. 0.5 hp
Approx. 1.2 hp
Approx. 1.8 hp
* If Quiet mode is set, the capacity will begin to decrease during heating operation at low outdoor temperatures,
when the outdoor air temperature is below standard conditions.
* It is possible to set Quiet mode only for nighttime by using the snowfall sensor input terminal and a timer for quiet
operation. In this case, operation is the Quiet mode determined by the above setting.
18-2. Slime Countermeasure: EEPROM 0C (set only on the main unit)
This setting controls the operation of the drain pump.
SettingDescription
0Normal control (setting at time of factory shipment)
1The drain pump operates for 20 minutes at 2-hour intervals.
2The drain pump operates for 20 minutes at 20-minute intervals.
3The drain pump operates constantly.
1
18-3. Delayed Start for Each System: Outdoor EEPROM 3E (set only on outdoor unit No. 1)
The operation start time can be delayed according to the set system addresses.
This setting reduces the voltage drop by preventing multiple systems from starting at the same time when operation
is restarted after multiple operating systems were stopped due to a power outage or other cause.
SettingEffect
0No delayed start (setting at time of factory shipment)
1Start begins after [1 second × System address]
2Start begins after [2 seconds × System address]
3Start begins after [3 seconds × System address]
18-4. Automatic Backup: Outdoor EEPROM 48 (set only on outdoor unit No. 1)
Automatic backup is set to occur at the time the unit is shipped from the factory. However, the automatic backup
function can be disabled by changing this setting to 1.
1 - 33
Page 42
1
3-WAY VRF SYSTEM
18. Service Maintenance Functions
Control Functions
18-5. Automatic Backup Mode: Outdoor EEPROM 49 (set only on outdoor unit No. 1)
Two types of automatic backup modes (when multiple outdoor units are installed) can be selected.
SettingOperationCondition
0Backup outdoor units operate only during special control.Setting at time of factory
shipment
1Only the backup compressors remain stopped. Other OK
compressors installed in the same outdoor unit operate as
normal.
* Even when “1” is set, the outdoor unit will remain stopped if all of the compressors in the outdoor unit have failed.
* If only 1 outdoor unit is installed, the operation is according to setting “1” even if “0” is set.
18-6. Snowfall Input Switching: Outdoor EEPROM 4A (set at each outdoor unit)
The snowfall sensor input terminal on the outdoor unit PCB is used for input from the snowfall sensor. It is also
possible to connect an external timer and use it to enable nighttime Quiet mode operation.
SettingOperation
0Used for snowfall sensor input (setting at
time of factory shipment).
1Used for Quiet mode input.
18-7. Optional Solenoid Valve Control Operation Setting:
Outdoor EEPROM C0 (set at each outdoor unit)
SettingOperation
0No output (setting at time of factory shipment)
1Refrigerant shut-off valve control (for cooling when the outdoor air temperature is
below standard conditions)
2—
3
External liquid valve control (used in special cases when the discharge gas
temperature is likely to especially rise)
18-8. High Static Pressure Mode: Outdoor EEPROM 8F (set at each outdoor unit)
This product can be made compatible with high static pressure by changing the settings.
By changing the setting item 8F to “6,” this product can be made compatible with outdoor unit static pressure of
(set at outdoor units which include CCU functions)
When this setting is set to “1,” the compressors start in sequence beginning from the No. 1 outdoor unit.
(The setting is “0” at the time of shipment. With this setting, compressors with lower operating time are started
first in order to balance the compressor operating times.)
18-10. Demand value setting: Outdoor EEPROM 1A, 1B
A unit identified as having a snowfall sensor attached will periodically send a signal indicating the snowfall sensor
input status to all outdoor units in the same system (or all wired outdoor units in the case of linked systems). It is
therefore unnecessary to install and wire multiple snowfall sensors.
(1) Snowfall sensor settings
* If the snowfall sensor is used, then depending on the circumstances it is necessary to make the correct setting at
* If “control is not performed” is set, control by the above signal is ignored. This setting is used in order to conserve
(2) Control operation
[1] Outdoor units where “sensor input present” is set send the snowfall sensor input information every 10
[2] At systems where “control is performed” is set, the above information is used to control operation of the
[3] At systems where “control is not performed” is set, the snowfall sensor input and above information ignored,
[4] In the case of a W-Multi system, control can be performed when snowfall sensor input is connected to any
<Caution>
Snowfall sensor input information is detected once every 10 minutes. Therefore, the outdoor fan may continue
In addition, the outdoor fan may remain stopped for up to 10 minutes when snowfall sensor input is present.
SettingOperation
0
1
2
3
all outdoor units in the system.
energy at outdoor units that include a snowfall-protection hood.
Recommended: If a low-speed fan mode is required (for all-year cooling or other reasons), install a snowfall-
minutes to all linked systems if the system wiring is linked.
outdoor fan.
and the outdoor fan does not operate.
outdoor unit.
operating for up to 10 minutes even when there is no snowfall sensor input.
Sensor input not present. Control is performed. (Setting at time of factory shipment)
Sensor input present. Control is performed.
Sensor input not present. Control is not performed.
Sensor input present. Control is not performed.
protection hood and set this setting to ON.
19-2. Function for Automatic Judgment of Insufficient Refrigerant Gas and Overcharge
This system includes a simple function for judging the level of refrigerant. However, be aware that false judgments
may occur if the control elements of the outdoor unit or indoor unit fail.
(1) Starting refrigerant level judgment mode
Short-circuit the CHECK pin on the No. 1 outdoor for 4 seconds or longer to engage this mode. (The LED on
the outdoor unit PCB begins blinking.)
(2) Conditions for refrigerant level judgment
After judgment mode starts, judgment occurs when all outdoor units in the system have been operating
continuously for 30 minutes or longer.
* Refrigerant level judgment requires that all outdoor units operate continuously for 30 minutes or longer. This is
in order to prevent incorrect adjustment of the refrigerant level based on false detection caused by refrigerant
accumulation or recovery at stopped outdoor units (stopped due to failures of functional elements). After
the judgment is displayed, repeated judgment will occur under new operating conditions if all outdoor units
continue operating. Therefore, the judgment display may change when later judgments occur.
* Judgment mode is automatically canceled after 4 hours.
1 - 36
Page 45
19. Other Functions
(3) Outdoor unit PCB LED indications in judgment mode
LED1LED2Recommended response
Judgment modeBlinkingBlinking
NormalONON
Insuffi cient gasBlinkingOFFCharge with refrigerant a little at a time.
3-WAY VRF SYSTEM
Control Functions
OverchargeOFFBlinkingRecover refrigerant a little at a time.
Judgment not
possible
Blinking
alternately
When judgment mode is not engaged, the LED indicates the normal display (OFF), or else indicates alarms or
other information.
If the insufficient gas or overcharge judgment is not stable, then recover refrigerant a little at a time when the
overcharge display appears. End refrigerant adjustment when the normal or insufficient gas display appears.
(4) Canceling judgment mode
When judgment mode is cancelled, the LED returns to the standard status display (OFF unless an alarm or
other event has occurred).
[1] Automatic cancel
Judgment mode is canceled automatically when 4 hours have passed after it was started.
[2] Forced cancel
Short-circuit the CHECK pin while the judgment mode display is active in order to cancel judgment mode.
<Reference> General Guidelines for Insufficient Gas and Overcharge
Judgment in automatic judgment mode can be problematic in some cases. Therefore, the following guidelines
are provided for general judgment of the refrigerant amount.
• Symptoms of insufficient gas
Cooling
operation
There is an indoor unit where the position of the electronic control valve is much higher (open by
300 pulses or more) than it was at start, and the difference [E3 – E1] at that indoor unit is large
(30°F or more).
1
Heating
operation
There is an outdoor unit where the position of the electronic control valve is much higher (open by
300 pulses or more) than it was at start, and the difference [Liquid temp. – Gas temp.] at that
outdoor unit is large (30°F or more).
• Symptoms of overcharge
Cooling
operation
Heating
operation
The high-pressure sensor temperature is 134°F or higher, and the difference [Pressure sensor
temp. – Liquid temp.] at that outdoor unit is large (30°F or more).
There is an indoor unit where the position of the electronic control valve is much higher (open by
300 pulses or more) than it was at start, and the difference [Pressure sensor temp. – E3] at that
indoor unit is large (50°F or more).
These are only guidelines, therefore the judgment may vary depending on the installation conditions, load
9. Pumping Out Refrigerant from Outdoor Unit (when repairing parts other than compressor)
10. Compressor
11. High and Low Pressure Sensors
12. Replacing 4-way valve
(1) Front panel removal (Fig. 2-1)
• Remove the front panel (remove 11 screws).
(2) Power outlet panel & valve cover removal (Fig. 2-2)
• Remove the power outlet panel (remove 2 screws).
• Remove the valve cover (remove 2 screws).
Front panel
Fig. 2-1
Power outlet panel
2 - 2
Valve cover
Fig. 2-2
Page 49
3-WAY VRF SYSTEM
2. Removing Electrical Component Box and Duct
Be sure to turn off the power before removing the electrical component box. Then check that the power LED (D53)
on the control PCB of the outdoor unit is not lit.
(1) Remove the electrical component box cover
(remove 6 screws). (Fig. 2-3)
Outdoor Unit Repair Procedures
(2) Remove power and control wires from terminals.
(3) Remove internal wires with extended connectors
on the outdoor control PCB.
(Solenoid valves, thermistors, crankcase heaters
and others)
(4) Disconnect power lines connected to the
secondary terminals of the magnetic contactor for
the compressor.
Electrical component
box cove
r
2
Fig. 2-3
(5) Remove the electrical component box (remove 2
screws). (Fig. 2-4)
CAUTION
Be sure to release the locking mechanism
before disconnecting each connector.
(6) Remove the center duct. (Fig. 2-5)
The center duct is fitted into the upper and
Ú
lower ducts and held in place by the electrical
component box, an arrangement that makes
possible independent removal of the center
duct.
Discharged oil can be used for checking the condition of the system. Based on the appearance and color of the
discharged oil, a judgment can be made on whether the system is operating normally or not.
Outdoor Unit Repair Procedures
3-1. Discharging Oil from Oil Separator
Recover the refrigerant from the outdoor unit following the procedure given in “5. Recovering Refrigerant.” Install
hoses as indicated on the equipment and feed nitrogen gas gradually to provide pressure to the system from the
low-pressure outlet and collect oil in a pan or container. (Fig. 2-8)
• The low-pressure outlet port is at the Lo side of the right side.
CAUTION
Packless valve or the like
• A faulty outdoor unit may remain pressurized. The oil delivery port employs a
Schrader-type push-to-release valve. Be careful to avoid accidental oil release
when using the port.
Container
Oil delivery port
(For 1/4" (6.35mm)-dia.
connector)
2
Manifold gauge
LoHi
Nitrogen gas
Low-pressure outlet port
(For 5/16" (7.94mm)-dia.
Fig. 2-8
connector)
3-2. Discharging Oil in Compressor
Recover the refrigerant in the outdoor unit following the procedures in “5. Recovering Refrigerant.” Remove the
compressor and discharge the oil in it. Refer to “10. Compressor” for detailed procedures.
3-3. Checking the Oil
Acceptance/rejection criteria for the oil
Condition of
refrigeration cycle
NormalYellowishNone0.02 or less3.5 or less
Abnormal
overheat operation
Motor burnout
Brownish
Brownish /
blackish
Condition of oilJudgment criteria for changing oil*
ColorOdorTotal acid valueHue
Smells somewhat
(not as strong as below)
Pungent / burnt odor
0.06 or over4.0 or over
Changing the oil and system cleaning
with dry-cores are necessary.
Changing the oil and system cleaning
with dry-cores are necessary.
* It is difficult to measure the total acid value in the field, therefore oil hue and odor are the rule of thumb. Checking
for carbon deposits and abrasive metal powder can additionally be used to assess the system condition.
2 - 5
Page 52
3-WAY VRF SYSTEM
4. Backup Operation
This system includes an emergency automatic backup function that allows the A/C to operate during the period
after trouble occurs until repairs are made. However, during repair and at other times, use manual backup
operation.
Outdoor Unit Repair Procedures
4-1. Automatic Backup
For details, refer to the control functions section.
After the alarm details are sent to the control device, control for automatic backup operation begins when the
ON/OFF button of the wired remote controller is pressed again (operation is started after the alarm is cleared).
During this operating mode, “CHECK” flashes on the wired remote controller only to inform the user that operation
is in backup mode. However this is not displayed on any other control devices.
• In order to cancel automatic backup mode, it is necessary to reset the power on the control PCB of the outdoor
unit where the outdoor unit No. setting (S007) on the control PCB is set to No. 1 (main unit).
2
CAUTION
Backup operation is intended as emergency operation until repairs are made. Have repairs made as soon as
possible.
If the power is not reset on the control PCB of the No. 1 outdoor unit (main unit),
backup mode operation will continue after the repairs are completed.
4-2. Manual Backup
This backup operation is the conventional method of backup operation. It involves disconnecting the failed outdoor
unit from the system, and operating only the normal outdoor units.
4-2-1. Backup operation by disconnecting the outdoor unit
(1) Changing the outdoor unit control PCB settings
< If the failed outdoor unit is not the No. 1 unit>
• Settings at No. 1 unit (main unit)
Switch on outdoor unit control PCBAction
System address (S003, S002)No change
No. of indoor units (S005, S004)No change
No. of outdoor units (S006)Subtract the number of failed units from the current setting.
Outdoor unit No. (S007)No change
• Settings at normal outdoor units other than the No. 1 unit
No particular changes
• Settings at the failed outdoor unit
No particular changes
However, close all service valves (suction tube, discharge tube, liquid tube, balance tube) at the failed outdoor
unit, and disconnect the wiring between the outdoor units.
2 - 6
Page 53
3-WAY VRF SYSTEM
4. Backup Operation
<If the failed unit is the No. 1 outdoor unit (main unit)>
If the No. 1 unit (main unit) has failed, a different outdoor unit must be set as the No. 1 unit (main unit).
• Settings at the failed No. 1 outdoor unit
– No particular changes
–
• Settings at No. 1 unit (main unit)
However, close all service valves (suction tube, discharge tube, liquid tube, balance tube) at the failed outdoor
unit, and disconnect the wiring between the outdoor units (main-sub unit wiring).
Switch on outdoor unit control PCBAction
System address (S003, S002)Make the same settings as on the failed No. 1 unit.
No. of indoor units (S005, S004)Make the same settings as on the failed No. 1 unit.
No. of outdoor units (S006)Subtract the number of failed units from the current setting.
Outdoor Unit Repair Procedures
Outdoor unit No. (S007)Change to “1.”
To this outdoor unit, connect the inter-unit communication line which was previously connected to the
No. 1 unit (main unit).
After recovery work is completed, return the outdoor unit No. setting (now =
1) to the value it was before the failure and repair. If this is not done, there will
CAUTION
• Settings at other outdoor units
No particular changes.
(2) Adjusting the refrigerant for backup operation
During backup operation, all of the service valves on the failed unit are closed. However, if a check of the
backup operating conditions shows that the level of gas is low, recover the refrigerant from the failed outdoor
unit. If the level of gas is too high, collect refrigerant at the failed outdoor unit.
Recovering refrigerant
●
With the normal outdoor units operating, monitor the operating condition and open/close the suction tube
service valve on the failed outdoor unit where all the service valves were closed. In this way, recover
refrigerant from the failed outdoor unit in order to adjust the amount of refrigerant in the system.
After adjusting the amount of refrigerant, close the suction tube valve at the failed outdoor unit.
Collecting refrigerant in the failed outdoor unit
●
• Short-circuit the vacuum application pin (CN102) on the control PCB of the failed outdoor unit where the
service valves are closed, then turn the power ON. Also disconnect the wiring between the outdoor units.
• With the normal outdoor units operating, monitor the operating condition and open/close the liquid tube
service valve on the failed outdoor unit where all the service valves were closed. In this way, collect
refrigerant in the failed outdoor unit in order to adjust the amount of refrigerant in the system.
be duplicated outdoor unit No. settings. In this case an alarm does not occur
immediately, however operation may be unstable.
Reconnect the inter-unit communications line to the No. 1 unit.
2
2 - 7
Page 54
2
3-WAY VRF SYSTEM
4. Backup Operation
• After adjusting the amount of refrigerant, turn OFF the power at the failed outdoor unit, release the
short-circuit at the vacuum application pin, and close the liquid tube valve at the failed outdoor unit.
* Refrigerant recovery is not affected by the power status of the failed outdoor unit. However, collecting
refrigerant in the failed outdoor unit is affected by whether the power at that outdoor unit can be turned
ON. If the power cannot be turned ON, use a refrigerant recovery device and recover the refrigerant into a
recovery cylinder in order to adjust the amount of refrigerant in the system.
4-2-2. Backup operation by setting the failed compressor not to operate
Backup operation settings for each compressor
INV compressorAC1 compressorSetting for backup operation
OKFailedDIP switch S010:
Turn BACK UP and AC1 ON.
FailedOKDIP switch S010:
Turn BACK UP and INV ON.
Outdoor Unit Repair Procedures
2 - 8
Page 55
3-WAY VRF SYSTEM
5. Recovering Refrigerant
Outdoor Unit Repair Procedures
The following equipment and tools are required:
Jumper wire with clips, adjustable wrench, set of manifold gauge valves specially designed for refrigerant R410A
only, vacuum pump, refrigerant recovery unit, pre-purged refrigerant cylinder for recovery, flathead screwdriver, and
outdoor unit maintenance remote controller.
(1) Turn off the power of the outdoor unit beforehand (at power mains).
(2) Fully close each service valve on the suction tube, discharge tube, liquid tube, and the balance tube of the
outdoor unit.
(3) Connect the outdoor unit’s high-pressure and low-pressure outlet ports with the Hi and Lo sides of the manifold
gauge valves using hoses. (Fig. 2-9)
The remaining refrigerant in the faulty outdoor unit may create internal
CAUTION
(4) Connect the manifold gauge valves, refrigerant recovery unit, and recovery cylinder using hoses. To avoid the
entry of air into the refrigerant tubing, carry out this connection work carefully. (Fig. 2-9)
pressure. Before connecting hoses, be sure to confirm that each of the manifold
gauge valves is tightly closed. Note that the connection ports employ Schradertype push-to-release valves.
2
For detailed procedures such as connecting the refrigerant recovery unit
CAUTION
with the recovery cylinder and methods used for recovery, follow the specific
instructions that came with the refrigerant recovery unit.
(5) Locate the AP (Air Purge) pins on the control PCB in the faulty outdoor unit and short them using the clips of
the jumper wire. Then restore electrical power to the outdoor unit.
By short-circuiting the AP pins, each solenoid valve in the outdoor unit is
CAUTION
forcibly opened as soon as power comes on, which releases all remaining
refrigerant into the recovery cylinder. Since neglecting this procedure may leave
some refrigerant in the system, it is important that you carry out this step.
(6) Carry out refrigerant recovery.
CAUTION
To determine the completion of refrigerant recovery, follow the instructions that
came with the refrigerant recovery unit.
Manifold
gauge
Lo
Hi
Refrigerant
recovery unit
Refrigerant recovery cylinder
High-pressure outlet port
(For 5/16" (7.94mm)-dia.
connector)
Fig. 2-9
2 - 9
Low-pressure outlet port
(For 5/16" (7.94mm)-dia.
connector)
The flowchart below shows the refrigerant recovery procedures you must follow when replacing or repairing the
indoor unit due to trouble in the refrigerant circuit.
START
5-2-1. Cooling operation (for all units)
2
Ball valve is provided in the indoor unit
YES
5-2-2.
Refrigerant recovery
procedures (1)
Turn off all equipment in system
When replacing or repairing a faulty
unit, let other normal indoor units run
(excluding indoor unit where refrigerant
Power can independently be turned
off for indoor unit where refrigerant is
Change controllable number of indoor
units (including changes in group
control and integrated-control settings)
Other indoor units can operate normally
Check for leakage in repaired unit
Evacuate air from repaired unit
Charge refrigerant in repaired unit
(Amount of charge should equal that
recovered by refrigerant recovery unit)
is recovered)
YES
recovered
YES
Replace or repair faulty unit
Refrigerant recovery
NO
NO
NO
5-2-3.
procedures (2)
Modify power to permit turning off
power to refrigerant-recovered
indoor units independently
Turn off all equipment in system
Replace or repair faulty unit
Check for leakage in repaired unit
Evacuate air from repaired unit
Charge refrigerant in repaired unit
(Amount of charge should equal that
recovered by refrigerant recovery unit)
Ready for operation
END
Replace or repair faulty unit
Check for leakage in repaired unit
Evacuate air in repaired unit
Change controllable number of indoor
units (including changes in group
control and integrated-control settings)
Open ball valve
Ready for normal operation
END
Service work performed on indoor units is done simultaneously using the service ports at the liquid (narrow tube) side
★
and the gas (wide tube) side ball valves. Refer to each section in the “Installation Instructions” on refrigerant charging,
Charge refrigerant in repaired unit
(Amount of charge should equal that
recovered by refrigerant recovery unit)
Open the ball valve
Ready for normal operation
END
leak checking, and evacuation procedures.
2 - 10
Page 57
3-WAY VRF SYSTEM
5. Recovering Refrigerant
Outdoor Unit Repair Procedures
5-2-1. Cooling operation (for all units)
(1) If the remote controller (CZ-RTC2) is used for maintenance of the outdoor unit
Connect the outdoor unit maintenance remote controller to the RC connector (CN006) (3P) (BLU) on any
➀
one of the outdoor unit control PCBs. Then start a test run of all units. (Press and hold the
button for 4 seconds.)
Press the
➁
CAUTION
Use the remote controller (CZ-RTC2) to check the operating status of the indoor units. Check that all units
➂
are operating in Cooling mode.
(MODE) button and change to cooling operation.
Even if the mode that is originally displayed is “Cool,” be sure to press the
(MODE) button once or more to change to cooling operation. (Pressing the
(MODE) button ensures that heating/cooling operation is not mixed and that all units
are operating in either Heating or Cooling mode.)
(CHECK)
CAUTION
(2) If the remote controller (CZ-RTC2) is not available for maintenance of the outdoor unit
Determine the outdoor unit where the unit No. setting (S007) (3P DIP switch) (BLU) on the outdoor unit
➀
control PCB is set to No. 1.
Short-circuit the mode-change pin (CN101) on the outdoor unit control PCB of the No. 1 unit. Then
➁
short-circuit the test-run pin (CN023) to start operation. (Short-circuiting the mode-change pin ensures that
heating/cooling operation is not mixed and that all units are operating in either Heating or Cooling mode.)
Check the displays of the indoor unit remote controllers. Check that all units are operating in Cooling mode.
➂
If all units are operating in Heating mode, perform the steps listed below.
CAUTION
Release the short-circuit at the test-run pin (CN023) on the outdoor unit control PCB of the No. 1 unit. Then
➃
short-circuit the stop pin (CN104) to stop operation.
Short-circuit the mode-change pin (CN101) on the outdoor unit control PCB of the No. 1 unit.
➄
* Switching of the 4-way valve occurs immediately before operation starts. Therefore it does not change at
this time. (Mode change cannot be judged from the sound.)
Short-circuit the test-run pin (CN023) on the outdoor unit control PCB of the No. 1 unit. Then check the
➅
displays of the indoor unit remote controllers. Check that all units are operating in Cooling mode.
With the 3-way valve, it is difficult to determine whether operation is heating or
cooling by touching the tubing.
With the 3-way valve, it is difficult to determine whether operation is heating or
cooling by touching the tubing.
5-2-2. Refrigerant recovery procedures (1) (using indoor unit ball valve)
(1) If a ball valve with a service port has been provided in the indoor unit as shown in Fig. 2-10, follow the
instructions given in (2) through (6) below. If the service port is instead located in the outdoor side, follow the
instructions in “5-2-3. Refrigerant recovery procedures (2).”
(2) After running the unit in Cooling mode for about 5 minutes as described in “5-2-1. Cooling operation (for all
units),” fully close the discharge line, the liquid line ball valve, and indoor unit ball valve.
(3) Run the unit in Cooling mode for 10 to 20 minutes more.
(4) Fully close the suction line ball valve, and stop the operation of all units.
(5) Use hoses to connect the manifold gauge valves, refrigerant recovery unit, and refrigerant recovery cylinder
with each other. (Fig. 2-10) Do each connection quickly to prevent air from entering the tubing.
2
CAUTION
Remaining refrigerant may create internal pressure, therefore care should be taken
when connecting the hoses.
2 - 11
Page 58
5. Recovering Refrigerant
Outdoor Unit Repair Procedures
(6) Recover the remaining refrigerant from the indoor unit using the refrigerant recovery unit.
3-WAY VRF SYSTEM
2
NOTE
To determine completion of refrigerant
recovery, follow the instructions that
came with the refrigerant recovery unit.
Ball valve (separately purchased)Service port
Outdoor
unit
side
Refrigerant
recovery
Refrigerant recovery cylinder
Discharge tube
unit
Suction tube
Liquid tube
Manifold
gauge
Solenoid
valve kit
Fig. 2-10
Solenoid
valve kit
Indoor unit
5-2-3. Refrigerant recovery procedures (2): for indoor unit with no ball valve
Refrigerant in all indoor units and the refrigerant tubing circuit must be pumped into the outdoor unit. The maximum
refrigerant storage capacity per a single outdoor unit is approx. 529 oz. Thus, in order to collect all refrigerant from
the system, a separate refrigerant recovery unit is necessary. Follow these procedures to correctly perform pump
down.
Perform work correctly, according to the work procedures given below.
Connect the manifold gauge to the high- and low-pressure outlet ports on the outdoor unit where pump down
➀
will be performed. Be sure that no air enters the tubing at this time.
Fully close the discharge tube valve on the outdoor unit where pump down will be performed.
➁
Follow the instructions in “5-2-1. Cooling operation (for all units)” and operate all units in Cooling mode for
➂
approximately 5 minutes. Then fully close the liquid tube valve on the outdoor unit where pump down will be
performed.
When the high-pressure gauge reaches 406.1 psi or higher, or the low-pressure gauge reaches 72.5 psi or
➃
below, at the outdoor unit where pump down is being performed, press the ON/OFF button on the outdoor unit
maintenance remote controller to stop operation at all units. Then immediately fully close the suction tube valve
on the outdoor unit where pump down is being performed.
* If the outdoor unit maintenance remote controller is unavailable, follow the procedure below to stop all of the
units.
Pull out the SCT connector (2P) (YEL) (CN231) on the outdoor unit control PCB of the unit where pump
down is being performed. When the SCT connector is pulled out, immediately alarm F12 (sensor trouble)
occurs and all outdoor units stop operating. Be sure that you do NOT grasp the lead wire when pulling out the
connector. Removing any other connector may not cause the units to stop. Therefore be sure to pull out the
SCT connector only.
CAUTION
Turn off power to all equipment in the system. Then pull out the RC1 connector (4P) (BLU) (CN106) on the
➄
It is not necessary to recover the refrigerant from the balance tube. Therefore do
not operate the balance tube valve.
outdoor control PCB in the outdoor unit for which pump down has been completed.
* By pulling out the RC1 connector, communication between the main and the sub outdoor units will be isolated.
Change the setting of controllable outdoor unit numbers (reduce by 1 unit).
➅
* If the setting is incorrect, the E30 alarm (outdoor unit serial communication signal error) occurs and the unit
will not operate.
Turn on power for all equipment in the system and let the remaining outdoor units run in Cooling mode.
➆
Repeat steps (1) through (7) and complete pump down for all outdoor units.
➇
2 - 12
Page 59
3-WAY VRF SYSTEM
5. Recovering Refrigerant
Using hoses with Schrader-type push-to-release valves, connect the manifold gauge valves to the suction line
➈
service port, the discharge line service port and the liquid line service port in the next outdoor unit to undergo
pump down. (Fig. 2-11)
Remaining refrigerant in the system may cause internal pressure. Check that each
CAUTION
Use hoses to connect the manifold gauge valves, refrigerant recovery unit, and refrigerant recovery cylinder.
➉
Quickly connect each part to prevent air from entering the tubing.
11
Recover remaining refrigerant from the inter-unit tubing and indoor units using the refrigerant recovery unit.
NOTE
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery unit.
valve on the manifold gauge is tightly closed. A Schrader-type
push-to-release valve is provided for each connection port.
Discharge tube service port
(For 5/16" (7.94mm)-dia. connector)
Liquid tube service port
(For 5/16" (7.94mm)-dia.
connector)
Outdoor Unit Repair Procedures
2
Manifold gauge
LoHi
Refrigerant
recover unit
Refrigerant
recovery cylinder
Suction tube service port
(For 5/16" (7.94mm)-dia. connector)
Fig. 2-11
5-3. Recovery of Refrigerant from Entire System
(1) Turn off power to the entire outdoor system.
(2) Short-circuit the AP (Air Purge) pins (CN102) on the outdoor control PCB of all outdoor units, then supply power
to the outdoor units.
* By short-circuiting the AP pins and supplying power to the outdoor units, the solenoid valve in each unit is
forcibly opened and all remaining refrigerant can be recovered.
(3) If any unit has encountered a power failure, follow the instructions in “5-1. Refrigerant Recovery Procedures
(from Outdoor Units)” and perform refrigerant recovery for the faulty outdoor unit.
(4) Connect the manifold gauge to the high- and low-pressure outlet ports (Schrader-type valves) on any outdoor
unit. (Fig. 2-11)
CAUTION
(5) Connect the manifold gauge valves, refrigerant recovery unit, and refrigerant recovery cylinder. Quickly connect
each part to prevent air from entering the tubing.
(6) Check that each service valve of the suction line, discharge line, liquid line, and the balance tube for the outdoor
unit has opened, then perform refrigerant recovery.
* If only a single outdoor unit is installed, the balance tube is not used. Therefore, leave this valve closed.
Remaining refrigerant may cause internal pressure. Check that each valve on the
manifold gauge valves is tightly closed. The connection port uses a Schrader-type
push-to-release valve.
NOTE
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery unit.
2 - 13
Page 60
2
3-WAY VRF SYSTEM
6. Checking for Leakage After Repair
Outdoor Unit Repair Procedures
6-1. Pressure Check for Leakage of Outdoor Unit
After completing repair of the outdoor unit, carry out the following leakage check.
(1) Check that all service valves for suction tube, discharge tube, liquid tube, and balance tube in the repaired
outdoor unit are fully closed.
(2) Connect the manifold gauge valves to the high- and low-pressure outlet ports of the outdoor unit.
(3) Feed nitrogen gas into the circuit until 522.1 psi pressure is reached. If it is apparent that the nitrogen gas is not
entering the repaired section, interrupt the feeding. Short-circuit the AP pins (CN102) on the outdoor unit control
PCB, turn on power to run the outdoor unit, then resume feeding nitrogen.
(4) Apply soapy water to the repaired part (such as a newly welded part), and briefly inspect for any leakage. If
there are any leaks, bubbles will show on the tubing surface.
* To continue the air-tight check after the brief leak inspection, turn on power while short-circuiting the AP pins.
Again feed nitrogen gas to obtain a system pressure of 522.1 psi. Then measure both the outdoor ambient
temperature and the pressure in the system. Leave the system in this state for 1 full day and night, and again
measure the outdoor ambient temperature and pressure (to determine any reduced values). During the
inspection, it is recommended that an awning or cover be used to shield the unit in case of rain. If no problem
is found, purge all nitrogen from the system.
Manifold gauge
LoHi
Nitrogen gas
High-pressure outlet port
(For 5/16" (7.94mm)dia. connector)
Low-pressure outlet port
(For 5/16" (7.94mm)-dia. connector)
Fig. 2-12
6-2. Checking for Leakage in Refrigerant Tubing Between Indoor and Outdoor Units
Refer to the “Installation Instructions” that came with the outdoor unit.
2 - 14
Page 61
3-WAY VRF SYSTEM
7. Evacuating System
This procedure is carried out to ensure there is no remaining refrigerant or other gases (nitrogen, etc.) in the
repaired outdoor unit and tubing.
Outdoor Unit Repair Procedures
7-1. Evacuating Repaired Outdoor Unit
(1) Check that each service valve of the suction tube, discharge tube, liquid tube, and balance tube in the outdoor
unit are fully closed.
(2) Connect the manifold gauge valves to the high-pressure and low-pressure sensor outlets of the outdoor unit.
(Fig. 2-13)
(3) Connect the manifold gauge valves to the vacuum pump.
* If the AP pins (CN102) on the outdoor control PCB have already been short-circuited, step (4) is not
necessary.
(4) Turn off power to the repaired outdoor unit and short-circuit the AP (Air Purge) pins on the outdoor control PCB.
CAUTION
By short-circuiting the AP pins and turning on power to the outdoor unit, all
electronic valves in the outdoor unit are forcibly opened and any remaining nitrogen
gas can be recovered. Failure to perform this procedure may result in nitrogen gas
remaining in the refrigerant circuit and causing operating problems. Therefore,
never skip this step.
(5) Turn the power ON at the outdoor unit where vacuum will be applied. Then run the vacuum pump and continue
evacuation until the vacuum condition falls to less than –14.7 psig (5 Torr).
CAUTION
Vacuum pump
To ensure proper evacuation, refer to the operating instructions that came with the
vacuum pump.
Manifold gauge
LoHi
High-pressure outlet port
(For 5/16" (7.94mm)
-dia. connector)
2
Low-pressure outlet port
Fig. 2-13
(For 5/16" (7.94mm)-dia. connector)
7-2. Evacuating Refrigerant Tubing Between Indoor and Outdoor Units
Refer to the “Installation Instructions” that came with the outdoor unit.
2 - 15
Page 62
3-WAY VRF SYSTEM
8. Charging Compressor Oil
Outdoor Unit Repair Procedures
8-1. If Refrigerant Has Already Been Charged to Outdoor Unit
Be sure to use an exclusive oil-charging tank for charging compressor oil. Prior to charging, carry out vacuum
drying inside the tank and take care that no air (in the form of bubbles) is permitted to enter the tank.
The oil charging procedures are given below.
* The receiver tank used for maintenance may be used as an exclusive oil-charging tank.
2
When installing the oil-charging
(DPR : CV6230817937)
tank to the refrigerant system to
serve as a safety bypass circuit
for refrigerant, connect it to the
Nipple
suction line service port carefully
to avoid releasing refrigerant into
the atmosphere.
CAUTION
Perform oil charging
work carefully so that no
Packless valve
(Receiver-tank:
CV6380152988)
liquid refrigerant enters
the charging tank.
Fig. 2-14
(1) Evacuation drying in oil-charging tank
With the lower side valve fully closed, open the upper side valve and connect it to the vacuum pump via the
manifold gauge valves as shown below. Run the vacuum pump and evacuate the tank until the pressure falls to
below –14.7 psig (5 Torr) for the evacuation drying. After the evacuation drying is finished, fully close the upper
valve. Next, fully close the manifold gauge valves and stop the vacuum pump.
CAUTION
To ensure proper evacuation, refer to the operating instructions that came with the
vacuum pump.
Vacuum pump
Manifold gauge
LoHi
Open to run,
then close to stop
Upper side
valve
Close to stop
Lower side
valve
Fig. 2-15
2 - 16
Page 63
3-WAY VRF SYSTEM
8. Charging Compressor Oil
(2) Charging compressor oil into oil-charging tank
Connect a piece of pipe to the lower valve and then insert the other end deeply into the bottom of the oil
container. Make sure you avoid letting any air be sucked into the tube. Next, run the vacuum pump and open the
manifold gauge valves, then open the upper and lower valves to begin charging oil into the charging tank.
First close the lower and then,
this one before stopping.
Manifold gauge
LoHi
Upper valve
Close this valve before stopping.
Outdoor Unit Repair Procedures
Lower valve
Vacuum pump
Oil
Fig. 2-16
When the predetermined amount of oil has been charged into the oil-charging tank, immediately close the lower
valve and start the vacuum pump to reduce the pressure below –14.7 psig (5 Torr). Then close the upper valve and
stop the vacuum pump.
CAUTION
Do this operation quickly because compressor oil easily absorbs moisture
from the air.
(3) Charging compressor oil into outdoor unit
Connect the lower valve to the low-pressure sensor outlet (with Schrader-type push-to-release valve) in the
outdoor unit to be oil-charged, and then connect the high-pressure sensor outlet (with push-to-release valve) to
the upper valve via the manifold gauge valves (at Hi-pressure gauge side). In addition, connect the suction line
service port (with push-to-release valve) to the DPR (Discharge Pressure Regulator). Carry out the connection
work quickly to avoid letting air enter.
• The hoses may be subject to internal pressure from the refrigerant inside the
CAUTION
outdoor unit. A Schrader-type push-to-release valve is provided at each connection
port.
• Since the DPR valve opens at pressures of 362.6 psi and above, be sure to
connect the DPR to the suction line service port (low-pressure side).
2
High-pressure outlet port
(For 5/16" (7.94mm)-dia.
connector)
Low-pressure
outlet port
(For 5/16"
(7.94mm)-dia.
connector)
Suction tube service port
(For 5/16" (7.94mm)-dia. connector)
DPR
Upper valve
Manifold gauge
LoHi
Close to stop
Lower valve
Close to stop
Fig. 2-17
2 - 17
Page 64
2
3-WAY VRF SYSTEM
8. Charging Compressor Oil
Next follow the instructions in “5-2-1. Cooling operation (for all units)” at the outdoor unit where oil will be charged,
and start cooling operation at all units. When the operating conditions have stabilized, perform steps 1, 2, and 3
in sequence and open the valves. When this is done, the refrigerant pressure from operation forces the oil out of
the oil charge tank, and oil is charged into the outdoor unit from the low-pressure outlet port. From time to time
close the upper valve on the top of the oil charge tank (only this valve) and shake the tank to check the amount of
remaining oil.
High-pressure outlet port
(For 5/16" (7.94mm)-dia.
connector)
Upper valve
Low-pressure
outlet port
5/16"
(For
(7.94mm)-dia.
connector)
Manifold gauge
HiLo
Procedure 1:
Open the Hi-side
manifold gauge valve
Lower valve
Outdoor Unit Repair Procedures
DPR
Procedure 2: Open
the upper valve
Suction tube service port
(For 5/16"
(7.94mm)
-dia. connector)
Connect from here to
refrigerant recovery unit
Procedure 3: Open
the lower valve
Fig. 2-18
To terminate the oil charging work, do as follows:
To end the charge process, first close the valve on the high-pressure side of the manifold gauge. Then wait
several tens of seconds after the pressure display on the manifold gauge low-pressure gauge stabilizes (in order
to equalize the pressure with the low-pressure outlet port and to vaporize the refrigerant in the charge tank).
Then perform steps 1 and 3 in sequence and fully close the valves. Finally, connect the refrigerant recovery unit
to the Lo-gauge side, shut down all indoor and outdoor units, and then recover the remaining refrigerant in the
oil-charging tank, manifold gauge valves, and connecting hoses. Perform these procedures quickly and securely
so that no air can enter. After, charge the necessary amount of new refrigerant by referring to the “Installation
Instructions” that came with the outdoor unit.
NOTE
To determine the completion of refrigerant recovery, follow the instructions that came with the refrigerant recovery
unit.
8-2. If Outdoor Unit Has Not Been Charged with Refrigerant
When a compressor has been replaced or in any other case where the outdoor unit has not been charged with
refrigerant, first charge with refrigerant then follow the instructions in “8-1. If Refrigerant Has Already Been Charged
to Outdoor Unit” and charge with oil.
Or, alternatively, follow the procedure below.
(1) Connect a tube to the oil outlet port on the outdoor unit to be charged with oil. Insert the other end of the tube
into the oil container.
(2) Follow the instructions in “7. Evacuating System,” and apply vacuum to the outdoor unit to be charged with oil.
When this is done, oil is charged into the outdoor unit through the oil outlet port.
(3) When the unit has been charged with the designated amount of oil, stop the vacuum pump.
CAUTION
Because oil absorbs moisture readily, this work must be completed quickly.
2 - 18
Page 65
8. Charging Compressor Oil
3-WAY VRF SYSTEM
Outdoor Unit Repair Procedures
High-pressure outlet port
(For 5/16" (7.94mm)-dia. connector)
Vacuum pump
Manifold gauge
HiLo
Oil tube service port
(For 1/4" (6.35mm)-dia.
connector)
When replacing a faulty compressor, be sure to first measure the amount of remaining oil in the compressor.
Charge additional new oil equal to the difference in the remaining oil and the rated amount as listed above.
For example: Type of replaced compressor: JT160G-KTTJ
Remaining oil in the removed compressor: 0.58 gal
Additional oil to be charged: 0.58 gal (remaining oil in the removed compressor) – 0.55 gal (rated oil amount) =
0.026 gal
* If the result is a negative amount (remaining oil in the removed compressor is less than the rated amount), it is
not necessary to discharge the extra oil from the system.
For the method used for additional oil charging after compressor replacement, refer to “8-1. If Refrigerant Has
Already Been Charged to Outdoor Unit.”
Required equipment and tools: Jumper wire with clips, adjustable wrench, set of manifold gauge valves, refrigerant
recovery unit, pre-purged refrigerant cylinder for recovery, flat-head screwdriver,
and outdoor unit maintenance remote controller.
This work is performed in order to collect the refrigerant from an outdoor unit where repairs (other than compressor
replacement) will be performed into other outdoor units and indoor units, and the refrigerant tubing.
2 - 19
Page 66
2
3-WAY VRF SYSTEM
9. Pumping Out Refrigerant from Outdoor Unit
Outdoor Unit Repair Procedures
9-1. If Remote Controller (CZ-RTC2) is Used for Maintenance of Outdoor Unit
(1) Refer to “4. Backup Operation” and perform backup operation.
(2) Connect the manifold gauge valves at the Lo side to the low-pressure outlet port of the outdoor unit to be
repaired. Also connect the refrigerant recovery cylinder to any one of the normal outdoor units at the liquid
line service port (Schrader-type push-to-release valve). Perform the connection work quickly so that no air is
allowed to enter. (Fig. 2-20)
* Connecting the refrigerant recovery cylinder is done to prevent pressure from rising excessively during
backup operation by recovering the refrigerant from the outdoor unit to be repaired.
(Measure the weight of the refrigerant and cylinder itself beforehand and provide sufficient safety measures,
such as installing a high-pressure cutout in the circuit.)
CAUTION
(3) Connect the outdoor unit maintenance remote controller to the RC connector (CN006) (3P) (BLU) on the
outdoor unit control PCB of the outdoor unit to be repaired. Then start a test run of all units. (Press and hold the
(CHECK) button for 4 seconds.)
(4) Press the
CAUTION
(5) Use the outdoor unit maintenance remote controller to check the operating status of the indoor units. Check
that all units are operating in Heating mode. For details concerning operation of the outdoor unit maintenance
remote controller, refer to the “Outdoor unit maintenance remote controller” item.
The hoses may be subject to internal pressure from the refrigerant inside the
outdoor unit. Check that the manifold gauge valves are fully closed beforehand.
A Schrader-type push-to-release valve is provided at each connection port.
(MODE) button and change to heating operation.
Even if the mode that is originally displayed is “Heat,” be sure to press the
(MODE) button once or more to change to heating operation. (Pressing the
(MODE) button ensures that heating/cooling operation is not mixed and that all
units are operating in either Heating or Cooling mode.)
CAUTION
With the 3-way valve, it is difficult to determine whether operation is heating or
cooling by touching the tubing.
(6) Close the suction tube and balance tube on the outdoor unit to be repaired. Then slowly close the liquid tube
service valve.
(7) When the low pressure at the outdoor unit to be repaired reaches 72.5 psi or below, press the ON/OFF button
on the outdoor unit maintenance remote controller to stop all the units. Then immediately fully close the
discharge tube valve on that outdoor unit.
While closing the valves, the rise in discharge temperature or another factor may
CAUTION
cause a protective device to activate, stopping the operation of the outdoor unit. If
this occurs, immediately fully close the discharge tube valve on the outdoor unit to be
repaired.
(8) Connect the high-pressure gauge side of the manifold gauge to the high-pressure outlet port on the outdoor
unit to be repaired, and connect the manifold gauge to the refrigerant recovery device. Be sure that no air
enters the tubing at this time.
(9) Short-circuit the vacuum application pin on the outdoor unit control PCB of the unit to be repaired. Then turn ON
the outdoor unit power.
CAUTION
When the vacuum application pin is short-circuited and the power is turned ON, all
solenoid valves in the outdoor unit are forced open, allowing the refrigerant to be
recovered from all tubes which are separated by solenoid valves. If this work is not
performed, it will not be possible to recover all of the refrigerant at the refrigerant
recovery device. Be sure to perform this step.
(10) Open both Hi- and Lo-side valves on the manifold gauge valves, and recover the refrigerant remaining in the
outdoor unit. After that, measure the amount of recovered refrigerant.
NOTE
To determine the completion of refrigerant recovery, follow the instructions that came with the
refrigerant recovery unit.
2 - 20
Page 67
3-WAY VRF SYSTEM
9. Pumping Out Refrigerant from Outdoor Unit
Outdoor Unit Repair Procedures
9-2. If Remote Controller (CZ-RTC2) is Not Available for Maintenance of the Outdoor Unit
(1) Refer to “4. Backup Operation” and perform backup operation.
(2) Connect the manifold gauge valves at the Lo side to the low-pressure outlet port of the outdoor unit to be
repaired. Also connect the refrigerant recovery cylinder to any one of the normal outdoor units at the liquid
line service port (Schrader-type push-to-release valve). Perform the connection work quickly so that no air is
allowed to enter. (Fig. 2-20)
* Connecting the refrigerant recovery cylinder is done to prevent pressure from rising excessively during the
backup operation by recovering the refrigerant from the outdoor unit to be repaired.
(Measure the weight of the refrigerant and cylinder itself beforehand and provide sufficient safety measures,
such as installing a high-pressure cutout in the circuit.)
CAUTION
(3) Determine the outdoor unit where the unit No. setting (S007) (3P DIP switch) (BLU) on the outdoor unit control
PCB is set to No. 1.
(4) Short-circuit the mode-change pin (CN101) on the outdoor unit control PCB of the No. 1 unit. Then short-circuit
the test-run pin (CN023) to start operation. (Short-circuiting the mode change pin ensures that heating/cooling
operation is not mixed and that all units are operating in either Heating or Cooling mode.)
(5) Check the displays of the indoor unit remote controllers. Check that all units are operating in Heating mode. If all
units are operating in Cooling mode, perform the steps listed below.
CAUTION
The hoses may be subject to internal pressure from the refrigerant inside the
outdoor unit. Check that the manifold gauge valves are fully closed beforehand.
A Schrader-type push-to-release valve is provided at each connection port.
With the 3-way valve, it is difficult to determine whether operation is heating or
cooling by touching the tubing.
2
(6) Release the short-circuit at the test-run pin on the outdoor unit control PCB of the No. 1 unit. Then short-circuit
the stop pin (CN104) to stop operation.
(7) Short-circuit the mode-change pin (CN101) on the outdoor unit control PCB of the No. 1 unit.
* Switching of the 4-way valve occurs immediately before operation starts. Therefore it does not change at this
time. (Mode change cannot be judged from the sound.)
(8) Short-circuit the test-run pin (CN023) on the outdoor unit control PCB of the No. 1 unit. Then check the displays
of the indoor unit remote controllers. Check that all units are operating in Cooling mode.
(9) Close the suction tube and balance tube on the outdoor unit to be repaired. Then slowly close the liquid tube
service valve.
(10) When the low pressure at the outdoor unit to be repaired reaches 72.5 psi or below, pull out the SCT
connector (2P) (YEL) (CN231) from the outdoor unit control PCB of that outdoor unit. Then immediately fully
close the discharge tube valve on that outdoor unit.
* Pulling out the SCT connector immediately stops all of the outdoor units.
While closing the valves, the rise in discharge temperature or another factor may cause
CAUTION
(11) Connect the high-pressure gauge side of the manifold gauge to the high-pressure outlet port on the outdoor
unit to be repaired, and connect the manifold gauge to the refrigerant recovery device. Be sure that no air
enters the tubing at this time.
(12) Open both Hi- and Lo-side valves on the manifold gauge valves, and recover the refrigerant remaining in the
outdoor unit. After that, measure the amount of recovered refrigerant.
NOTE
To determine the completion of refrigerant recovery, follow the instructions that came with the
refrigerant recovery unit.
a protective device to activate, stopping the operation of the outdoor unit. If this occurs,
immediately fully close the discharge tube valve on the outdoor unit to be repaired.
2 - 21
Page 68
9. Pumping Out Refrigerant from Outdoor Unit
Faulty outdoor unitOther outdoor unit
Manifold gauge
LoHi
High-pressure outlet port
(For 5/16" (7.94mm-dia.
connector)
Low-pressure outlet port
(For 5/16" (7.94mm-dia.
connector)
3-WAY VRF SYSTEM
Outdoor Unit Repair Procedures
Liquid tube service port
(For 5/16" (7.94mm-dia.
connector)
Refrigerant
recovery
cylinder
2
Measuring scale
Connect from here to
refrigerant recovery unit
Fig. 2-20
2 - 22
Page 69
3-WAY VRF SYSTEM
10. Compressor
Outdoor Unit Repair Procedures
10-1. Compressor Trouble Diagnosis and Check Methods
Generally, compressor failures can be classified into the following categories.
(1) Mechanical trouble → (A) Locking (intrusion of foreign objects, galling, etc.)
(B) Pressure rise failure (damaged valve, seal, bearing, or other component)
(C) Noise (damaged stator rotor, valve, or other component)
(2) Electrical trouble
(A) Coil burning
→
(B) Open circuit
(C) Insulation failure
(D) Short circuit
Trouble diagnosis is based on the following remote controller displays: [H03] (Compressor 1: INV compressor,
center), [H11] [H12] [H13] (Compressor 2: constant-speed compressor 1, left side when viewed from front).
A judgment is made based on factors that include the following: coil resistance (varies depending on the
compressor), insulation resistance, current, leakage breaker operation, oil and refrigerant fouling, odor, pressure,
and noise.
Reference: Insulation resistance (Use a DC 500 V insulation resistance meter and measure the insulation
resistance between the electrified and non-electrified parts.)
(a) Motor
Min. 300 M
→
Ω
(b) Compressor → Min. 100 MΩ (servicing part)
(c) Unit
Min. 10 MΩ (This is due to the presence of refrigerant, which decreases the
→
insulation resistance.)
* Minimum insulation resistance as required by generally accepted requirements is 1 MΩ.
JUDGMENT START
Is there
Is there burning of the failed
compressor motor?
YES
YES
Follow the instructions in
“3. Discharging Compressor Oil” and
drain the oil from all compressors in the
same system. Then inspect.
NO
NO
Follow the instructions in
“3. Discharging Compressor Oil”
and drain the oil from the failed
compressor. Then inspect.
Is the color phase 4.0 or above, or is a
YES
YES
sharp odor present?
NO
NO
2
Are there 2 or more outdoor units where
the compressor oil color phase is 4.0 or
higher or where a sharp odor is present?
YES
YES
Go to “10-2-3. Replacing all
compressors in a system.”
Follow the instructions in “10-2-4. Dry
core cleaning” and perform dry core
cleaning of all outdoor units.
NO
NO
Go to “10-2-2. Replacing all
compressors in a failed unit.”
Follow the instructions in
“10-2-4. Dry core cleaning” and
perform dry core cleaning of the
failed outdoor unit.
Reference: Symptoms of motor burning
1. Ground fault results in breaker operation.
2. Short circuit results in different coil resistance at different phases.
3. Open circuit
2 - 23
Go to “10-2-1. Replacing only the
failed compressor.”
Page 70
2
3-WAY VRF SYSTEM
10. Compressor
Outdoor Unit Repair Procedures
10-2. Replacing the Compressor(s)
10-2-1. Replacing only the failed compressor
(1) If backup operation is required, follow the instructions in “4. Backup Operation” and engage backup operation.
(2) Follow the instructions in “10-3. Removing and Installing Compressors” and replace the failed compressor.
(3) Fully close the high- and low-pressure gauge valves on the manifold gauge, then stop the vacuum pump.
(4) Disconnect the manifold gauge from vacuum pump. Connect the manifold gauge to the cylinder where the
refrigerant was recovered. At this time, be careful that air does not enter the tubing.
(5) Open the valve on the refrigerant recovery cylinder and the high-pressure gauge valve on the manifold gauge
to charge with refrigerant. At this time, the low-pressure gauge valve on the manifold gauge remains fully
closed.
If the recovered refrigerant becomes mixed with another refrigerant or another gas
CAUTION
(6) When charging has been completed with an amount of new refrigerant equal to the amount of recovered
refrigerant, or when charging with the same amount of new refrigerant has not been completed but no more
refrigerant will enter the unit, fully close the high-pressure gauge valve on the manifold gauge. Next, turn the
power OFF at the repaired outdoor unit, then remove the short circuit at the AP pin (CN102). Finally, fully
open all valves on the suction tube, discharge tube, liquid tube, and balance tube.
(7) If backup operation was engaged, follow the instructions in “4. Backup Operation” and perform backup
operation recovery.
(8) If charging with an amount of new refrigerant equal to the amount of recovered refrigerant was not possible,
fully close the high-pressure gauge valve on the manifold gauge. Then, while the unit is operating in “5-2-1.
Cooling operation (for all units)”, open the low-pressure gauge valve on the manifold gauge and charge with
the designated amount of refrigerant.
When charging with liquid refrigerant, add refrigerant a little at a time in order to
CAUTION
(such as nitrogen or air), do not use the recovered refrigerant for charging. Charge
with the designated amount of new refrigerant.
prevent liquid back-flow.
(9) Fully close the low-pressure gauge valves on the manifold gauge, follow the instructions in “8. Charging
Compressor Oil,” and charge with oil if necessary.
(10) Remove the manifold gauge.
CAUTION
The connecting port employs a Schrader-type push-to-release valve. When
disconnecting the hose, pressure will be applied from the refrigerant in the
outdoor unit.
2 - 24
Page 71
3-WAY VRF SYSTEM
10. Compressor
Outdoor Unit Repair Procedures
10-2-2. Replacing all compressors in a failed unit
(1) Follow the instructions in “3. Discharging Compressor Oil” and drain the oil from the oil separator in the failed
unit. Measure the amount of drained oil.
(2) If backup operation is required, follow the instructions in “4. Backup Operation” and engage backup operation.
(3) Follow the instructions in “10-3. Removing and Installing Compressors” and replace all compressors in the
failed unit.
(4) Fully close the high- and low-pressure gauge valves on the manifold gauge, then stop the vacuum pump.
(5) Disconnect the manifold gauge from the vacuum pump. Connect the manifold gauge to the refrigerant
cylinder. At this time, be careful that air does not enter the tubing.
CAUTION
(6) Open the valve on the refrigerant cylinder, and open the high-pressure gauge valve on the manifold gauge
(with the low-pressure gauge valve closed). When charging has been completed with an amount of new
refrigerant equal to the amount of recovered refrigerant, or when charging with the same amount of new
refrigerant has not been completed but no more refrigerant will enter the unit, fully close the high-pressure
gauge valve on the manifold gauge. Next, turn the power OFF at the repaired outdoor unit, then remove the
short circuit at the AP pin (CN102). Finally, fully open all valves on the suction tube, discharge tube, liquid
tube, and balance tube.
However, leave the balance tube fully closed if only a single outdoor unit is installed.
(7) If backup operation was engaged, follow the instructions in “4. Backup Operation” and perform backup
operation recovery.
(8) If charging with an amount of new refrigerant equal to the amount of recovered refrigerant was not possible,
fully close the high-pressure gauge valve on the manifold gauge. Then, while the unit is operating according
to “5-2-1. Cooling operation (for all units),” open the low-pressure gauge valve on the manifold gauge and
charge with the designated amount of refrigerant.
CAUTION
(9) Fully close the low-pressure gauge valves on the manifold gauge, follow the instructions in “8. Charging
Compressor Oil,” and charge with the necessary amount of oil. Also add an amount of oil that is equivalent to
the amount that was drained from the oil separator.
(10) Remove the manifold gauge.
Do not reuse the recovered refrigerant. Use a refrigerant cylinder that contains new
refrigerant.
When charging with liquid refrigerant, add refrigerant a little at a time in order to
prevent liquid back-flow.
2
CAUTION
(11) Follow the instructions in “10-2-4. Dry core cleaning” and perform dry core cleaning of the outdoor unit that
failed.
The connecting port employs a Schrader-type push-to-release valve. When
disconnecting the hose, pressure will be applied from the refrigerant in the
outdoor unit.
2 - 25
Page 72
2
3-WAY VRF SYSTEM
10. Compressor
Outdoor Unit Repair Procedures
10-2-3. Replacing all compressors in a system
(1) Follow the instructions in “3. Discharging Compressor Oil” and drain the oil from the oil separators in all
outdoor units. Measure the amount of drained oil.
(2) Follow the instructions in “10-3. Removing and Installing Compressors” and replace all compressors in the
system.
(3) Follow the instructions in “6. Checking for Leakage After Repair” and check for leaks at all outdoor units and
in the tubing.
(4) Follow the instructions in “7. Evacuating System” and apply vacuum to all outdoor units and tubing.
(5) Fully close the high- and low-pressure gauge valves on the manifold gauge, then stop the vacuum pump.
(6) Disconnect the manifold gauge from vacuum pump. Connect the manifold gauge to the refrigerant cylinder.
Be especially careful that air does not enter the tubing.
CAUTION
(7) Open the valve on the refrigerant cylinder, and open the high-pressure gauge valve on the manifold gauge.
When charging has been completed with an amount of new refrigerant equal to the amount of recovered
refrigerant, or when charging with the same amount of new refrigerant has not been completed but no more
refrigerant will enter the unit, first turn the power OFF at the repaired outdoor unit, then remove the short circuit
at the AP pin (CN102). Then fully open all valves on the suction tube, discharge tube, liquid tube, and balance
tube. However, leave the balance tube fully closed if only a single outdoor unit is installed.
(8) If backup operation was engaged, follow the instructions in “4. Backup Operation” and perform backup
operation recovery.
(9) If charging with an amount of new refrigerant equal to the amount of recovered refrigerant was not possible,
fully close the high-pressure gauge valve on the manifold gauge. Then, while the unit is operating in Cooling
mode, open the low-pressure gauge valve on the manifold gauge and charge with the designated amount of
refrigerant.
CAUTION
Do not reuse the recovered refrigerant. Use a refrigerant cylinder that contains unused
refrigerant.
When charging with liquid refrigerant, add refrigerant a little at a time in order to
prevent liquid back-flow.
(10) Fully close the low-pressure gauge valves on the manifold gauge, follow the instructions in “8. Charging
Compressor Oil,” and charge with the necessary amount of oil. Also add an amount of oil that is equivalent to
the amount that was drained from the oil separators.
(11) Remove the manifold gauge.
CAUTION
(12) Follow the instructions in “10-2-4. Dry core cleaning” and perform dry core cleaning of all outdoor units.
The connecting port employs a Schrader-type valve. When disconnecting the hose,
pressure will be applied from the refrigerant in the outdoor unit.
2 - 26
Page 73
3-WAY VRF SYSTEM
10. Compressor
Outdoor Unit Repair Procedures
10-2-4. Dry core cleaning
If burning or other failures occur repeatedly at compressors within the same system, in many cases the cause is
acid, sludge, carbon, or other substances that remain in the refrigeration cycle as the result of insufficient cleaning.
If, when the oil is inspected, there is an outdoor unit where the oil color phase is 4.0 or higher, or where a sharp
odor is present, carry out all steps below to perform dry core cleaning.
(A) If a ball valve is installed on the outdoor unit
(1) Refer to “5-2-1. Cooling operation (for all units)” and operate all outdoor units in either Heating or Cooling mode.
(2) If all units are operated in Cooling mode, close first the liquid tube service valve then the ball valve on all
outdoor units where dry cores will be attached.
If all units are operated in Heating mode, close first the ball valve then the liquid tube service valve on all
outdoor units where dry cores will be attached.
* This step is performed in order to expel refrigerant from the tubing between the liquid tube service valve and
the ball valve. Approximately 4 – 5 seconds is a sufficient interval between closing each of the 2 valves.
(3) Press the ON/OFF button on the outdoor unit maintenance remote controller to stop the operation of all units.
* If the outdoor unit maintenance remote controller is not available, use the following method to stop the
operation of all units:
Pull out the SCT connector (2P) (YEL) (CN231) from the outdoor unit control PCB of the unit where
pump-down is being performed. When the SCT connector is pulled out, alarm F12 (sensor trouble)
immediately occurs and all outdoor units stop operating. Be sure that you do NOT grasp the lead wire when
pulling out the connector. Removing any other connector may not cause the units to stop. Therefore be sure
to pull out only the SCT connector.
(4) Connect a refrigerant recovery device to the liquid tube service port (Schrader-type valve) of all outdoor units
where dry cores will be attached, then recover the refrigerant from the tubing. Be sure that no air enters the
tubing at this time.
CAUTION
When the hose is connected, internal pressure is applied by the remaining
refrigerant in the inter-unit tubing. The connection port employs a Schrader-type
valve. To determine when refrigerant recovery is compete, follow the instructions
in the instruction manual of the refrigerant recovery device.
2
(5) As shown in Fig. 2-21, disconnect the tube that runs from the liquid tube valve to the ball valve on all outdoor
units where dry cores will be attached. Then attach the dry cores.
(6) At all outdoor units where dry cores are attached, pressurize with 522.1 psi of nitrogen from the liquid tube
service port and check for leaks.
(7) After evacuating all nitrogen gas from the tubing, apply vacuum from the liquid tube service port to all outdoor
units where dry cores are attached until the pressure is –14.7 psig (5 Torr) or less.
(8) Fully open the liquid tube valve and ball valve on all outdoor units where dry cores are attached.
(9) Operate all outdoor units for approximately 3 hours (in either Heating or Cooling mode or mixed Cooling and
Heating mode).
(10) Follow the above procedure, and replace all dry cores with new dry cores.
(11) Operate all outdoor units for approximately 20 minutes (in either Heating or Cooling mode or mixed Cooling
and Heating mode).
(12) Follow the instructions in “3. Discharging Compressor Oil” and drain a small amount of the oil from the
oil separators of all outdoor units where dry cores are attached. Check the color phase, odor, and other
characteristics.
(13) If the results show that dry core cleaning is still necessary (for example, a color phase of 4.0 or higher), return
to Step 11 and repeat until the results are normal (including a color phase of 3.5 or less).
(14) Perform steps (1) – (4), and remove all dry cores. Then connect the tubing between the liquid (narrow) tube
valves and the ball valves.
CAUTION
Perform another dry core replacement after approximately 30 hours of system
operation.
2 - 27
Page 74
2
3-WAY VRF SYSTEM
10. Compressor
(15) At all outdoor units where dry cores were removed, pressurize with 522.1 psi of nitrogen from the liquid tube
service port and check for leaks.
(16) After evacuating all nitrogen gas from the tubing, apply vacuum to all outdoor units where dry cores were
removed until the pressure is –14.7 psig (5 Torr) or less.
(17) INSTALLATION: Refer to the “Information for the Person in Charge of Installation” items. Charge with an
amount of refrigerant equal to the amount that was recovered.
Outdoor Unit Repair Procedures
(B) If a ball valve is not installed on the outdoor unit
(1) Refer to “Refrigerant recovery procedures (2) for indoor unit with no ball valve” under “5-2. Refrigerant
Recovery Procedures (Indoor Unit).” Perform pump down of the refrigerant from all indoor units and inter-unit
tubing to the outdoor unit side.
(2) Cut the liquid (narrow) tube at all outdoor units where dry cores will be attached, then attach the dry cores
and ball valves as shown in Fig. 2-21.
(3) For the next steps, refer to (6) – (17) in (A) on the previous page.
Cleaning dry core
Liquid tube service valve
Normal unitOutdoor unit
(Bidirectional type for R410A)
Dry core
Ball valve
Balance tube
Liquid tube
Discharge tube
Suction tube
Fig. 2-21
2 - 28
Page 75
3-WAY VRF SYSTEM
10. Compressor
Outdoor Unit Repair Procedures
10-3. Removing and Installing Compressors
When removing and installing compressors, use sufficient caution to ensure that moisture or other substances do
not enter the refrigerant tubing system.
10-3-1. Replacing compressors
* For all types 72 and 96, follow the replacement procedure below.
(A) Replacing the inverter compressor (Compressor 1 on remote controller alarm display)
Removal
■
1) Connect a manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the
compressor will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas
replacement in the outdoor unit tubings.
(2) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct” and
remove the corresponding parts from the outdoor unit where the compressor will be replaced.
(3) Remove the cap at the compressor terminal plate. Disconnect the power terminal.
(4) Remove the crankcase heater.
(5) Remove the 3 bolts, and remove the washers and rubber washers (quantities indicated in the figure below).
(6) Disconnect the tube-with-flare-nut using two adjustable wrenches. At this time, cover the tube in place with
waste cloth while watching out for oil leaks. Then cap the disconnected tube and mount the flare nut on the
compressor. Tighten the flare nut with a seal bonnet (1/4") in it.
2
NOTE
If oil remaining in the compressor reaches the equalized oil level, oil will come pouring out when the
tube-with-flare-nut is removed.
(7) Prepare to disconnect the 2 brazed locations shown in the figure.
CAUTION
Protect the sensors and the surrounding plates, rubber, lead wires, clamps, and
other items. Remove the discharge sensor shown in the figure 2-22.
(8) Disconnect the 2 brazed locations shown in the figure below.
(9) Pull the compressor toward you.
CAUTION
Brazed locations (2)
Tube-with-flare-nut
Washer (1)
Rubber washer (1)
When pulling the compressor toward you, be careful not to cause any abnormal
deformation of the tube-with-flare-nut.
Bolt
Remove the
discharge sensor
Inverter compressor
Bolt
Washer (1)
Rubber washer (1)
Crankcase heater
Bolt
Washer (1)
Rubber washer (1)
Front view
Fig. 2-22
2 - 29
Page 76
10. Compressor
Installation
■
Outdoor Unit Repair Procedures
(1) Remove the rubber stopper and tube cap (brazed) from the new compressor.
(2) Install the crankcase heater onto the new compressor.
(3) Place the 2 pieces of cushioning rubber in the designated positions on the compressor.
(4) Place the 2 pieces of cushioning rubber onto the legs of the new compressor.
3-WAY VRF SYSTEM
2
CAUTION
When setting the compressor into the unit, be careful not to cause any abnormal
deformation of the tube-with-flare-nut.
(5) Place the remaining cushioning rubber onto the new compressor, at the position shown in the figure below.
(6) Remove the bolts that are temporarily fastening the pieces of cushioning rubber (inner 2 legs), and anchor
the 3 compressor legs using the bolts, washers, and rubber washers.
(7) Remove the flare nut from the new compressor, and connect the tube-with-flare-nut.
(8) Shape the tubes and insert them at the 2 welding locations.
(9) Connect a manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the
compressor was replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas
replacement.
(10) Perform copper brazing at the 2 welding locations.
(11) Follow the instructions in “6. Checking for Leakage After Repair” and check for leaks at the outdoor unit where
the compressor was replaced.
CAUTION
At this time, also check for leaks at the flare nut connection on the tube-with-flare-nut.
(12) Re-install all components that were removed. Re-install the electrical component box in the same position as
it was before.
Be sure to check for looseness of the power terminal connections at the compressor
CAUTION
terminal plate, and to check by pulling vertically on the connections. If the terminals
become disconnected easily, replace the wiring Assy.
(13) Follow the instructions in “7. Evacuating System” and apply vacuum to the outdoor unit where the compressor
(1) Connect the manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the compres-
sor will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replacement.
(2) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct” and
remove the corresponding parts from the outdoor unit where the compressor will be replaced.
(3) Remove the cap at the compressor terminal plate. Disconnect the power terminal.
(4) Remove the crankcase heater.
(5) Remove the bolts(3 locations), washers, and spacers (1 each at the 3 locations shown in the figure).
* The compressor rear leg is not anchored.
(6) Prepare to disconnect the 3 brazed locations shown in the figure.
2
Constant-speed
compressor
(left side)
discharge sensor
Bolt
Washer: 1
Rubber washer: 1
(1 each at the 3 locations)
Crankcase heater
CAUTION
Remove
• Protect the sensors and surrounding plates, rubber, lead wires, clamps, and
Brazed locations (3)
Protect the oil
equalizer tube
connectors
Front view
Fig. 2-25
other items.
Pay particular attention to protection of the oil equalizer tube connector parts,
and removal of the discharge sensor.
An O-ring is mounted inside the oil equalizer tube connector parts. It must be
protected and do not lose it.
(7) Disconnect the 3 brazed locations shown in the figure 2-25.
* First disconnect the ø1/4" (ø6.35 mm) tube, then disconnect the ø1/2" (ø12.7 mm) and ø7/8" (ø22.22 mm)
tubes.
(8) Pull the compressor toward you.
2 - 31
Page 78
2
3-WAY VRF SYSTEM
10. Compressor
Installation
■
(1) Remove the 2 brazed tube caps (2 pieces) from the compressor.
(2) Remove hexagonal caps from the compressor.
* When removing the hexagonal caps, hold the fixing nut at the main unit side so as not to loose it with a
wrench or spanner. And then, loosen and remove the hexagonal cap.
Hexagonal cap
Outdoor Unit Repair Procedures
Oil equalizer tube
connector parts
Fixing nut
at the main unit side
O-ring
Fig. 2-26
(3) Remove the oil equalizer tube connector parts along with the O-ring from the removed compressor and
mount them on the replaced new compressor.
(4) Install the crankcase heater onto the new compressor.
(5) Temporary mount 2 cushion rubbers with bolts at the position as shown in the figure 2-27.
Set up the leg of the new compressor onto the 2 cushion rubbers.
Cushion rubbers
Bolts
(Temporary mounting: 2 locations
at back side, each 1 piece)
Front view
Fig. 2-27
2 - 32
Page 79
3-WAY VRF SYSTEM
10. Compressor
Front view
Fig. 2-28
(6) Set the remaining cushioning rubber beneath the new compressor leg at the locations shown in the figure 2-28.
(7) Remove the bolts which are temporarily fastening the 2 pieces of cushioning rubber, and anchor the 3
compressor legs using the bolts, washers, and rubber washers.
(8) Insert the pre-shaped tube assembly at the 3 brazing locations indicated.
(9) Connect the manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the
compressor was replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas
replacement.
(10) Perform copper brazing at the 3 brazing locations.
CAUTION
In the same way as during removal, pay particular attention to protection of the oil
equalizing tube connector parts shown in the figure 2-28.
An O-ring is mounted inside the oil equalizer tube connector parts. It must be
protected and do not lose it.
Outdoor Unit Repair Procedures
Brazing
locations (3)
Bolt
Washer: 1
Rubber washer: 1
(1 each at the 3 locations)
Protect the oil
equalizer tube
connectors
Cushioning
rubber guide
2
(11) Follow the instructions in “6. Checking for Leakage After Repair” and check for leaks at the outdoor unit where
the compressor was replaced.
(12) Re-install all components that were removed. Re-install the electrical component box in the same position as it
was before.
CAUTION
Be sure to check for looseness of the power terminal connection at the compress
or terminal plate, and to check by pulling vertically on the connections. If the
terminals become disconnected easily, replace the wiring Assy.
(13) Follow the instructions in “7. Evacuating System” and apply vacuum to the outdoor unit where the compressor
was replaced.
2 - 33
Page 80
2
3-WAY VRF SYSTEM
10. Compressor
(C) Replacing multiple compressors
Removal
■
(1) Follow the instructions in “(A) Replacing the inverter compressor,” “(B) Replacing the constant-speed
compressor,” and remove the compressors.
* There is no predetermined sequence for removal; any compressor may be removed first.
Installation
■
(1) Follow the instructions in “(A) Replacing the inverter compressor,” “(B) Replacing the constant-speed
compressor,” and remove the compressors.
* There is no predetermined sequence for installation; any compressor may be installed first.
Outdoor Unit Repair Procedures
2 - 34
Page 81
3-WAY VRF SYSTEM
11. High and Low Pressure Sensors
The outdoor unit connection ports for the high and low pressure sensors employ Schrader-type push-to-release
valves. Therefore it is not necessary to recover refrigerant when removing and installing them.
Outdoor Unit Repair Procedures
11-1. Removing the High Pressure Sensor
(1) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct”
and remove the corresponding components from the outdoor unit where the high pressure sensor will be
removed.
(2) Disconnect the high pressure sensor connector (3P) (BLK) from terminal CN009 on the outdoor unit control
PCB of the outdoor unit where the high pressure sensor will be removed.
(3) Use 2 adjustable wrenches in combination to remove the high pressure sensor.
CAUTION
When removing the high pressure sensor, internal pressure will be applied by the
refrigerant in the outdoor unit. The high pressure sensor connection port on the
outdoor unit employs a Schrader-type valve.
11-2. Removing the Low Pressure Sensor
(1) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct ” and
remove the corresponding components from the outdoor unit where the low pressure sensor will be removed.
* If there is sufficient space to allow removal of the left-side panel, then it is possible to remove the low
pressure sensor without removing the electrical component box and duct.
(2) Disconnect the low pressure sensor connector (3P) (WHT) from terminal CN024 on the outdoor unit control
PCB of the outdoor unit where the low pressure sensor will be removed.
(3) Use 2 adjustable wrenches in combination to remove the low pressure sensor.
CAUTION
When removing the low pressure sensor, internal pressure will be applied by the
refrigerant in the outdoor unit. The low pressure sensor connection port on the
outdoor unit employs a Schrader-type valve.
2
11-3. Installing the High and Low Pressure Sensors
(1) Use 2 adjustable wrenches in combination to install the high and low pressure sensors.
Low pressure
sensor
Fig. 2-29
High pressure
sensor
2 - 35
Page 82
3-WAY VRF SYSTEM
12. Replacing 4-way valve
When replacing 4-way valve of type 72 (for type with the inverter compressor), be sure to protect check valves,
which are located adjacent to the 4-way valve, while performing replacement work. Type 96 (for type with 1 or 2
compressor) is not located near to the check valves, therefore no protection is necessary.
Outdoor Unit Repair Procedures
12-1. When the replacement is available from the right side of the unit
(1) Remove the front panel of the outdoor unit, then remove the right side panel of the unit.
(2) Follow the instructions in “9. Pumping Out Refrigerant from Outdoor Unit”, recover the refrigerant of the
outdoor unit where the 4-way valve is located.
(3) Connect the manifold gauge to the high and low-pressure outlet ports at the outdoor unit where the
4-way valve will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas
replacement.
(4) Prepare the brazing kit to disconnect the brazed parts (4 locations).
2
CAUTION
(5) After replacing the 4-way valve, follow the instructions in “6. Checking for Leakage After Repair”, and “7.
Evacuating System”. The outdoor unit after replaced 4-way valve shall be checked for gas leakage and
perform system evacuation.
(6) Fully open service valves on the outdoor unit.
However, if only one outdoor unit is installed, leave the balance tube kept closed.
(7) Charge the recovered refrigerant with the Refrigerant Recovery Unit by referring to the Installation
Instructions that came with the outdoor unit and the refrigerant recovery unit.
Protect the check valves as shown in the figure 2-30.
Fig. 2-30
Check valve
4-way valve
Brazed parts
(4 locations)
2 - 36
Page 83
3-WAY VRF SYSTEM
12. Replacing 4-way valve
Outdoor Unit Repair Procedures
12-2. When the replacement is not available from the right side of the unit
(1) Follow the instructions of “10. Compressor” and remove the constant-speed compressor.
(2) Connect the manifold gauge to the high and low-pressure outlet ports at the outdoor unit where the
4-way valve will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas
replacement.
(3) Prepare the brazing kit to disconnect the brazed parts (4 locations).
CAUTION
Protect the check valves as shown in the figure 2-31.
Check valve
2
4-way valve
Brazed parts (4 locations)
Fig. 2-31
(4) After replacing the 4-way valve, follow the instructions in “10. Compressor”, and reinstall the removed
OUTDOOR UNIT MAINTENANCE REMOTE
CONTROLLER (CZ-RTC2) for 3-WAY VRF
About the outdoor unit maintenance remote controller
■
The outdoor unit utilizes nonvolatile memory (EEPROM) on
its PCB. This allows EEPROM data to replace the setting
switches that were present on previous PCBs. The outdoor
unit maintenance remote controller is used to set and change
these EEPROM data.
In addition to setting and checking the outdoor unit EEPROM
data, this remote controller can also be used to monitor the
outdoor unit alarm history, monitor the various indoor and
outdoor temperatures, and check the indoor unit connection
status (number of units, operating mode, etc.).
NOTE
Outdoor unit maintenance remote controller does not function as an
ordinary remote controller. It is therefore only used for test runs and
during servicing.
System diagram
Outdoor unit maintenance
remote controller
Special service checker wiring
(Servicing No.: CV6231785082)
Outdoor unit
[Service Checker Section]
CZ-RTC2
Inter-unit control wiring
Outdoor unit
control PCB
Remote controller Ass’y
Operation manual included in package.
●
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller
Indoor
unit
Remote
controller
Indoor
unit
Remote
controller
to the outdoor unit PCB.
●
Ordinary remote controllers or other controller are still required for the indoor units, even when the outdoor unit
maintenance remote controller is connected.
3 - 2
Page 87
3-WAY VRF SYSTEM
2. Functions
Functions on the ordinary display
■
(1) Functions: Button operations can be used to perform the following functions.
• Start/stop of all indoor units
• Switching between cooling and heating
• Test run of all indoor units
• Double-speed operation of indoor units (Do not use for actual operation. Doing so may damage the devices.)
(2) Display: The following can be displayed.
• Alarm details display
• No. of indoor/outdoor units
• Unit Nos. of connected indoor/outdoor units
• Indoor/outdoor unit operating status (blinks when an alarm occurs)
• Indoor unit thermostat ON
• Display of individual outdoor unit alarms
• Total operating time of outdoor unit compressors
• Oil level of the outdoor unit oil sensor
• Total outdoor unit power ON time
• Outdoor unit microcomputer version, other information
Outdoor Unit Maintenance Remote Controller
Temperature monitor
■
• Displays the indoor/outdoor unit sensor temperatures.
Outdoor unit alarm history monitor
■
• Displays the outdoor unit alarm history.
Mode settings
■
• Setting mode 1 and setting mode 2 are used to make the outdoor EEPROM setting.
3
3 - 3
Page 88
3. Ordinary Display Controls and Functions
Functions on the ordinary display
■
•
Connect the special service checker wiring to the outdoor unit PCB.
The connection is shown in the figure below.
PCB connector (3P, BLU)
Special service checker wiring
Relay connector (2P, WHT)
Remote controller Ass’y
3-WAY VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
Outdoor unit PCB
RC (3P, BLU)
3
●
If the communications line in the inter-unit control wiring is connected, it can be left as-is.
●
In case of an independent outdoor unit (1 maintenance remote controller connected to 1 outdoor unit, automatic
address setting for indoor units not completed), both setting mode 1 and setting mode 2 can be used.
●
The overall system status for that refrigerant system is displayed.
3 - 4
Page 89
3. Ordinary Display Controls and Functions
●
All units start/stop (Fig. 3-1)
<Operation>
The (ON/OFF operation) button can be used to
start and stop all the indoor units.
• The LED turns ON when 1 or more indoor units is
operating.
• The LED blinks when an alarm has occurred at 1 or
more indoor units during operation.
●
Switching between cooling/heating (Fig. 3-1)
<Operation>
The (MODE) button switches between heating and
cooling modes.
• The specifications are equivalent to the heating/cooling
inputs on the previous outdoor unit PCBs.
• The display shows the operating mode of the indoor unit
with the lowest unit No.
3-WAY VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
LED
Fig. 3-1
●
All units test run (Fig. 3-2)
<Operation>
The (CHECK) button switches test run ON/OFF for
all indoor units.
• Press and hold for 4 seconds to turn ON.
“TEST” is displayed while the test run is in progress.
• The status of test runs that are started from the indoor
unit remote controller are not displayed on the outdoor
unit maintenance remote controller.
●
Double-speed
• Do not use for actual operation.
(Doing so may damage the devices.)
<Operation>
The timer button is used to switch between double-
speed and normal operation.
3
Fig. 3-2
• During double-speed operation, the SLEEPING MODE
mark is displayed.
3 - 5
Page 90
3. Ordinary Display Controls and Functions
Display (functions)
■
•
Use the temperature setting and buttons to change the item code.
Item codeItemRemarks
Outdoor unit alarm
➀
No. of connected indoor unitsQuantity
Unit Nos. of connected indoor unit7-segment display
Operating status of indoor unit7-segment display
Thermostat ON status of indoor unit7-segment display
No. of connected outdoor units1 – 2
Unit Nos. of connected outdoor units7-segment display
Operating status of outdoor unit compressor7-segment display
Display only. Alarm code and unit No. of unit
where alarm occurred are displayed alternately.
0 = CCU
1 – 2 = Outdoor unit
Alarm history 8 (oldest)
Firmware versionDisplay the version No. × 100.
Program versionDisplay the version No. × 100.
3 - 6
Page 91
3. Ordinary Display Controls and Functions
3-WAY VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
(3) XX-YY R.C.
Displays the outdoor unit sub-bus address which is
currently selected.
XX = Outdoor system address on main bus line (1 – 30)
YY = Outdoor unit sub-bus address (1 – 8).
“1” appears when there is only 1 outdoor unit.
Locations where ➀, ➁, and ➂ are displayed
as shown in Fig. 3-3.
2
3
Fig. 3-3
1
LED
3
<Sample displays>
01: <No. of connected indoor units>
4 units connected
Fig. 3-4Fig. 3-5
02: <Unit Nos. 1, 2, 3, and 4 are
connected>
3 - 7
Page 92
3. Ordinary Display Controls and Functions
Concerning the 7-segment, 4-digit display remote controller timer display
■
Outdoor Unit Maintenance Remote Controller
The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit (
the colon.
●
Display for unit Nos. 1 − 20
OFFOFF
1
313188
21217
ONON
61116
414199
7
5101520
ONON
OFFOFF
Meaning of display colon
1 ~ 2021 ~ 40
is not displayed.
●
Display for unit Nos. 21 − 40
OFFOFFOFFOFF
21
23333828
22273237
263136
24343929
25303540
Meaning of display colon
1 ~ 20
21 ~ 40
ONONONON
3-WAY VRF SYSTEM
) display and
61 ~ 8041 ~ 60
61 ~ 8041 ~ 60
3
●
The meaning of the colon display changes in the same way, allowing unit Nos. up to 80 to be displayed.
●
Sample displays of the unit Nos. of connected indoor units
•
Display of unit No. 1
•
Display of unit Nos. 1 and 2
•
Display of unit Nos. 1, 2, and 3
•
Display of unit Nos. 1, 2, 3, and 4
NOTE
The colon display (Unit Nos. 1 – 20, 21 – 40) changes automatically every 10 seconds.
(The display does not change if higher unit numbers do not exist.)
Pressing the
button switches the display immediately to the next higher level, even if 10 seconds have
not passed.
The total compressor operating time is displayed
■
(in 1-hour units) using 8 digits.
• When the fi rst 4 digits are displayed, the bottom dot
of the colon is lit. (Figure (A))
• When the last 4 digits are displayed, the colon
points are not lit. (Figure (B))
• The display of the fi rst 4 and last 4 digits
changes automatically every 10 seconds. It can
also be changed by pressing the button.
(B)(A)
10: <Total compressor operating time>
NOTE
(A) and (B) are displayed alternately.
(The example here (0000, 0062) indicates 62 hours.)
With the outdoor unit maintenance remote controller (when connected to the outdoor unit), the unit remote
controller check functions will not operate.
3 - 8
Page 93
4. Monitoring Operations
Display the indoor unit and outdoor unit sensor
temperatures.
<Operating procedure>
Press and hold the (CHECK) button and
➀
buttons simultaneously for 4 seconds or longer to
switch to temperature monitor mode.
During temperature monitoring, is lit.
(The display and operations are the same as
when monitor mode is started from the unit remote
controller.)
Press the button and select the indoor unit
➁
to monitor.
Use the temperature setting and
➂
buttons to select the item code of the temperature to
monitor.
The selected indoor unit No. and the temperature
data are displayed.
3-WAY VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
4
3
1
2
To end monitoring, press the (CHECK) button.
➃
The display returns to the normal display.
NOTE
The display does not blink.
3
3 - 9
Page 94
3
4. Monitoring Operations
Display of unit No. 1 (main unit)
■
DNDescriptionRemarks
Intake temp.°F
E1°F
E2°F
E3°F Indoor unit
Discharge temp.°F
Discharge temp. setting°F
Indoor unit electronic control valve positionSTEP
Discharge temp. 1°F
Discharge temp. 2°F
High-pressure sensor temp.°F
Heat exchanger gas 1°F
Heat exchanger liquid 1°F
Heat exchanger gas 2°F
Heat exchanger liquid 2°F
Outdoor air temp.°F
Not used
Inverter primary currentA
CT2A Outdoor unit
MOV1 pulseSTEP
MOV2 pulseSTEP
Discharge temp. 3°F
CT3A
MOV3 pulseSTEP
MOV4 pulseSTEP
Heat exchanger gas 3°F
Heat exchanger liquid 3°F
Low-pressure sensor temp.°F
Receiver temp.°F
Oil 1°F
Oil 2°F
Oil 3°F
Actual operating frequencyHz
Outdoor Unit Maintenance Remote Controller
3-WAY VRF SYSTEM
NOTE
0A and subsequent items are outdoor unit data. 0A – 22 are for unit No. 1.
2A – 42 are for unit No. 2.
3 - 10
Page 95
5. Outdoor Unit Alarm History Monitor
•
Displays outdoor unit alarms only. Does not display indoor
unit alarms.
•
Check the indoor unit alarm histories separately using the
indoor unit remote controllers or other control device.
<Operating procedure>
Press and hold the (CHECK) button and button
➀
simultaneously for 4 seconds or longer to change to
outdoor unit alarm history mode.
During temperature monitoring, displays.
The display and operations are the same as the
monitoring of the alarm device history that is performed
using the unit remote controller. However, the outdoor
unit address appears instead of the unit No.
Press the button and select the outdoor unit for
➁
alarm history monitoring.
Use the temperature setting and buttons
➂
to select the item code for the alarm history.
3-WAY VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
3
5
1
24
The display shows the address of the selected outdoor
unit, the item code, and the alarm history (alarm data).
The outdoor unit address is displayed as R.C. XX-YY.
System XX = Outdoor unit system address
R.C. XX = Outdoor unit system address
YY = Outdoor unit sub-bus address (always “1” for
3-WAY VRF units)
Unit code is displayed as 01 – 08. 01 indicates the most
recent alarm.
The alarm history is indicated by the alarm code. (If there
have been no alarm codes, “-- --” is displayed.)
To clear the alarm history, press the button. (The
➃
outdoor unit alarm history will be cleared.)
To exit, press the (CHECK) button. The display
➄
returns to the normal remote controller display.
3
3 - 11
Page 96
3
6. Mode Settings
Setting mode 1
■
<Operating procedure>
Press and hold the (CHECK) button and
➀
(VENTILATION) button simultaneously for 4
seconds or longer.
Use the temperature setting and
➁
buttons to change the item code. The item codes
and setting data are shown in the table below.
Use the timer time and buttons to change
➂
the setting data.
To confirm the changed setting data, press the
button.
(At this time, “
lit.)
During this mode, “
➃
The outdoor unit address display section displays
“ALL,” the item code number (DN value in the
table), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The
display changes between the first 4 digits (Fig. A )
and the last 4 digits (Fig. B ). When the first 4
digits are displayed, the bottom dot of the colon is
lit.)
” stops blinking and remains
” is displayed, blinking.
3-WAY VRF SYSTEM
Outdoor Unit Maintenance Remote Controller
A
Display of first 4 digits
5
1
B
Display of last 4 digits
3
2
To exit the setting mode, press the (CHECK)
➄
button.
5
A and B are displayed alternately.
(Example shows display of 0000 0001.)
DNParameterDescription
0 = Sensor input not present. Control is performed.
Snowfall sensor usage
Outdoor unit fan Quiet
mode
Energy saving mode
Energy saving operation
plug
Demand 1 current
Demand 2 current
1 = Sensor input present. Control is performed.
2 = Sensor input not present. Control is not performed.
3 = Sensor input present. Control is not performed.
Press and hold the (CHECK) button, button, and button
➀
simultaneously for 4 seconds or longer.
Use the temperature setting and buttons to change the item
➁
code. The item codes and setting data are shown in the table below.
Use the timer time and buttons to change the setting data.
➂
To confirm the changed setting data, press the button.
(At this time, “
During this mode, “
➃
outdoor unit address “System XX-YY” (System XX = System address, YY =
Address at outdoor unit sub-bus), item code number (DN value in the table
below), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The display changes between the first 4 digits (Fig. A ) and the last 4
digits (Fig. B ). When the first 4 digits are displayed, the bottom dot of the colon is lit.)
To end the setting mode, press the (CHECK) button. The display returns to the normal display mode.
➄
” stops blinking and remains lit.)
” is displayed, blinking. The display shows the set
Outdoor Unit Maintenance Remote Controller
5
3
1
Fig. 3-6
2
A
Display of first 4 digitsDisplay of last 4 digits
5
2
1
3
<Refrigerant type>
A and B are displayed alternately.
(Example shows 0000 0410 (R410A).)
B
List of Item Codes
DNParameterDescription
81Outdoor unit capacity0 = Disabled 224 = 72 Type 280 = 96 Type
This allows the filter lifetime, operating mode
priority change, central control address, and other
settings to be made for an individual or groupcontrol indoor unit to which the remote controller
used for simple settings is connected.
When simple settings mode is engaged, operation
stops at the individual or group-control indoor unit
to which the remote controller for simple settings is
connected.
<Procedure>
Press and hold the
➀
simultaneously for 4 seconds or longer.
“ ,” unit No. “ ” (or “ ” in the case of
➁
group control), item code “ ,” and settings data
“ ” are displayed blinking on the remote
controller LCD display (Fig. 4-1). At this time, the
indoor unit fan (or all indoor unit fans in the case of
group control) begins operating.
If group control is in effect, press the
➂
button and select the address (unit No.) of the
indoor unit to set. At this time, the fan at the indoor
unit begins operating.
and buttons
[Remote Controller Functions Section]
2
Fig. 7-1
7
1
6
5
Fig. 4-1
CZ-RTC2
3
4
4
* If unit No. “ ” is displayed, the same setting
will be made for all indoor units.
Press the temperature setting /
➃
buttons to select the item code to change.
Press the timer time / buttons to select the
➄
desired setting data.
* For item codes and setting data, refer to the
following page.
Press the button. (The display stops blinking
➅
and remains lit, and setting is completed.)
Press the button to return to normal remote
➆
controller display.
4 - 2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.