Panasonic 3378 User Manual

High or low sound output
Three different tones and priority levels
Connected directly on the COM loop
Fire alarm systems
Addressable
3378
General
3378 consists of an analog base (a modified
3312) mounted together with a sounder, which gives an ultra slim profile. Two flying leads from the sounder are plugged into two flying leads from the base. The base is thereafter mounted on the sounder in the ceiling, so that the detector can be plugged in the base. The base is connected directly to the COM loop like the base 3312.
High or low sound output
The volume is selected via a jumper in the sounder (high or low sound output).
Tones
Three tones are available:
Continuous 510 Hz
Pulsed (Intermittent) 510 Hz,
0.5s / 0.5s
Two-tone (Alternating) 510/610 Hz,
0.25s / 0.25s
Priority levels
Three priority levels are available in system EBL512 and two in system EBL128. For each level an output control expression and a tone is programmed (via Win512 / Win
128). The sounder can, for example, be used for pre-warning, fire alarm and general fire alarm with a different tone for each type of alarm.
Address & Mode setting
For COM loop address setting, the address setting tool 3314 is used. The sounder one address and the detector plugged in the base has one address. There are two address labels where the address respectively can be written. 3314 is also used to set the mode:
NORMAL mode: 3378 (3378 in
Win512 / Win128).
2330 mode: Can not be used.
2312 mode: Can not be used.
has
Miscellaneous
The address setting tool 3314 is connected to the COM loop terminals (SA / SB) to set the sounder's COM loop address. The detector's COM loop address is set in the detector.
3378 is power supplied via the COM loop, i.e. the number of sounder bases is depending on the other units connected to the same COM loop.
Two 8 mm spacers are supplied for easier access of surface mounted cables to the unit.
Product applications
Used in the systems EBL512 (SW version >
2.2) and EBL128 when a sounder is required in the same room as a detector (e.g. a hotel room). The sounder base is intended for indoor use and in dry premises.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Type number
3378 Addressable sounder base (sounder & a special version of analog base 3312)
Sounder
Base
The sounder: A = Mounting hole (5 x 9.5) for the sounder. Between the sounder and the ceiling can an 8 mm spacer (Ø B = Mounting hole (M4) for the base. C = Must not
= 13) be mounted for easier access of surface mounted cables.
o
be used. D = Connector for the base
connector. JP1 = Jumper (in position = high output; removed = low output). Analog detector types 33xx and 430x can be plugged in the base.
NOTE! The COM loop address for 3378 is to be set before the COM loop is connected. Another COM loop address has to be set in the detector.
Technical data
Voltage (V DC) rated
allowed normal
Current consumption from COM loop at norm. volt. (mA)
quiescent
active (low / high)
Ambient temperature (°C) operating
storage Ambient humidity (% RH) Max. 95, non condensing Ingress Protection rating (estimated) IP 42
Sound output (dB (A) @ 1 m) 95 ±2 (high output)
Frequency stability (%) ±0.5 Weight (g)
sounder + base Construction / Colour sounder + base Approvals CE
24 12-30 24
2 <
6 / <12
-10 to +50
-20 to +70
86 ±2 (low output)
160 + 55 = 215
ABS plastic / Gray (N8, Munsell colour code)
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00129 2003-07-02 4 / 2008-09-24