Fire alarm systems
Enclosed
call point
Attractive design compliant with EN54-11. IP rating IP67
Test key for routine testing without breaking the glass element
Protection against accidental operation
General
The call point has an attractive design compliant with EN54-11, and is surface mounted in the supplied red backbox. It has a clip retained front cover that makes it easy to replace the glass element and adds security since the clips are concealed. The frangible element is a glass element with a protective plastic film. To operate the call point, the glass element is pressed until it is broken. This will activate the built-in microswitch, which will generate a fire alarm in the c.i.e.
Test key
Routine testing is made with a supplied test key, without breaking the glass element. Inserting the test key simulates the breaking of the glass element. The call point is automatically reset when the test key is removed. The test key is also used to release the security clips for the front cover.
Protective cover
To protect the call point against accidental operation, a transparent polycarbonate cover has to be lifted to get access to the glass element.
Encapsulated circuit
All electronics are encapsulated. Only the terminal block is accessible from the rear. Mounted in the supplied red backbox and the tightening gasket on place (see the opposite page), the IP rating is IP67.
LED indicator
An LED on the front cover indicates fire alarm generated by the call point. Flashing LED: The LED will flash each time the c.i.e. communicates with the call point, until the call point is operated and the LED is switched on. Non-flashing LED: The LED is switched off until the call point is operated and the LED is switched on.
Connections / Settings
The COM loop is connected directly to the call point via a 4-way terminal block. For COM loop address setting is the address setting tool 3314 used. 3314 is also used to set the call point type and the LED mode:
NORMAL mode: (EBL512 SW
version >
3339. (Flashing or non-flashing LED is set via Win512 / Win128.)
2330 mode: M.c.p. type 2339
LED.
2312 mode: M.c.p. type 2339
flashing LED. Two flying leads (wires) are connected to the terminal block, for connection of the 3314 address setting tool's connection cable. The wires are to be disconnected before the COM loop wires are connected.
Product applications
Used in the systems EBL512 / 128 / 1000 / 2000 and is intended for indoor use in premises where IP67 rating is required.
3339
2.0 / EBL128). M.c.p. type
, flashing
, non-
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Type numbers
3339 Enclosed addressable manual call point 2347 Replacement glass (10 pcs.) 2348 Replacement polycarbonate cover (10 pcs.)
Left
: The supplied backbox backside view: Mounting holes and dimensions. Right: The call
point backside view (note the black tightening gasket and the 4-way terminal block).
Technical data
Voltage (V DC) allowed nominal
Current consumption at nom. volt. from COM loop (mA)
quiescent / active Ambient temperature (°C)
operating / storage Ingress Protection rating IP67 Weight (g) 217 (m.c.p.), 105 (red backbox incl. four screws) Construction / Colour ABS / Red (ISO 3864) Approvals CE, EN54-11
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00098 2005-04-14 2 / 2008-09-24
12-30 24
2 / 5
-10 to +55 / -40 to +85