Fire alarm systems
• Common base for the different analog detectors
• Fast connectors
• Label holder recess
Analog base
3312F / FL
Common base
The analog base 3312F / FL is connected to
a COM loop. Analog heat, smoke and multi
detector types 33xx / 43xx can be plugged in
the base. (See Product Leaflet for the
detector type respectively, for type of base.)
Fast connectors
3312F has fast connectors (blue) for the
COM loop (in/out). 3312FL also has fast
connectors (grey) for an external indicator
(LED), e.g. 2218.
Label holder
A label holder could be mounted in the base
(in the label holder recess). The label holder
is intended for a label showing "zoneaddress" or "technical number" information,
which can be read also when the detector is
plugged in the base.
Miscellaneous
The base has an address label (Al) where the
detector's COM loop address is to be
written.
Individual fault signal is obtained if wrong
type of detector (compared with the
programming) is plugged in the base or if
the detector is unplugged.
When a detector with a locking screw is
plugged in the base, the detector can be
locked in its base to prevent theft.
The position of the detector's built-in LED is
marked in the base for correct mounting
position of the base.
For more information regarding detector
types, connections, etc. see Planning
Instructions and connection diagrams for the
system respectively.
Product applications
Used for analog detectors in the systems
EBL512 / 128 / 1000 / 2000.
The base is intended for indoor use and in
dry premises.
Panasonic Electric Works Fire & Security Technology Europe AB
Jungmansgatan 12, SE-211 19 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Type number
3312F Analog base with fast connectors (blue) for the COM loop.
3312FL Analog base with fast connectors (blue) for the COM loop and fast
connectors (grey) for one ext. LED (e.g. 2218).
3390 Label holder (100 holders per packet, excl. labels)
3391 Labels for 3390 (10 sheets à 132 labels)
Ext
LED
E
+
Al
IN OUT
A
S
Connectors
E+ and Enot on 3312F
E
-
Lss (33xx)
SA Fast connector for COM loop (in/out)
Lss (430x)
S
SB Fast connector for COM loop (in/out)
B
Al Address Label
50 mm
73 mm
Lss Locking screw stopper (for detector
type 33xx and 430x respectively)
E- Fast connector for external LED
15
6.2
102 mm
E+ Fast connector for external LED
NOTE! E- and E+ on 3312FL only.
The base is prepared for mechanical locking of the detector, when a detector with a locking
screw is plugged into the base. Connector wire ∅ 0.6 – 1.2 mm (approx. 0.28 – 1.13 mm
2
). If
wire ∅ 0.6 mm is used the release button may be pushed as the wire is pressed into the
connector. Analog detector types 33xx and 43xx can be plugged in the base 3312F / FL.
Technical data
Voltage (V DC)
Rated
allowed
normal
Current consumption at nom. volt.
from COM loop (mA)
quiescent (base only)
active (base only)
Ext. LED connectors (3312FL only)
voltage (V)
max. current output (mA)
Ambient temperature (°C)
Operating
storage
Ambient humidity (% RH) max. 95, non condensing
Ingress Protection rating (estimated) IP51
Size ∅ x H (mm)
Weight 3312F / 3312FL (g) 41 / 47
Construction / Colour ABS / Grey (N8, Munsell colour code)
Approvals CE; Conforms with EN54-5 and -7 (when applicable)
28
12-30
24 (COM loop voltage)
Depending on the type of detector that is plugged into the base.
0
0
Depending on the detector plugged in the base. Normally:
5
2
-10 to +50
-20 to +70
102 x 15
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW01119 2008-09-19