Panasonic 3309 User Manual

Fire alarm systems
Enclosed analog
3309
Different modes for compatibility with other EBL systems / detectors
Algorithms for class A1, A2 S or B S
Waterproof (IP67)
ATEX compliance
General
The analog heat detector 3309 measures the temperature through a thermistor. The temperature range is 0°C to 100°C in steps of 0.5°C. The detector has an LED that will light up when the detector goes into alarm. The detector also has an output for an external LED, e.g. 2218.
Programming/Compatibility
The address setting tool 3314 is used to set the detector's COM loop address. The detector has an address label inside, where the address is to be written. 3314 is also used to set the detector mode.
NORMAL mode (analog): Used in the
system EBL512 (SW version > EBL128. The detector works as a temperature sensor where the analog readings (0°C to 100°C) are converted to digital "sensor values" that are read and evaluated by the c.i.e. Algorithms for class A1, A2 S or B S (set in Win512). When the class A1 or A2 S algorithm is used, 3309 is a spare part for detector 2340 and when the class B S algorithm is used, 3309 is a spare part for 2341.
2330 mode (conventional): Used in the
systems EBL512 / 1000 / 2000 as an equivalent to the enclosed addressable fixed temperature heat detector 2340 (60°C), i.e. as a class A2 S heat detector (static response temperature 57°C).
2312 mode: Not used for 3309.
Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
2.0) and
Algorithms
EBL512 / EBL128 use algorithms for class A1, A2 S and B S, according to EN54­5:2000, for fire alarm detection. Via Win512 / Win128 is an algorithm selected for each 3309 in NORMAL mode.
ATEX classification
3309 complies with the ATEX classification Ex II 3GD EEx nA II T5.
Waterproof
The thermistor, the LED, all electronics, etc. is mounted in a waterproof detector housing, mounted on a connection box.
Label holder
A label holder, intended for a label showing "zone-address" or "technical number", can be mounted in the connection box.
Miscellaneous
The COM loop is connected to the detector, which is provided with three pairs of flying leads with female push-on connectors.
Product applications
Used in the systems EBL512 / 128 / 1000 /
2000. Heat detectors are normally used where
smoke detectors can not be used or in rooms where the temperature can be expected to rise rapidly in case of a fire.
The detector is intended for outdoor use (must not be exposed to heavy sunlight) or in high humidity indoor premises.
Type numbers
3309 Enclosed analog heat detector (incl. conn. box, 3 compr. glands and gasket) 3390 Label holder (100 holders per packet, excl. labels) 3391 Labels for 3390 (10 sheets à 132 labels)
Connection box mounting holes (2 x 5 mm) c/c = 108 mm. The connection box is prepared for required number of compression glands, two (in / out) or three (in / out / ext. LED). A gland is approx. 30 mm high.
Detector
mounting holes, (2 x 4 x 7 mm) c/c = 70 mm. SA / SB (Red/White) = COM loop in
and out respectively. One SA and one SB connector is provided with a short "wire" to be used to connect the Address setting tool 3314 during mode and address setting. The "wires" are to be pulled out before the COM loop wires are connected. E+ / E- = Ext. LED (cable length max. 30 m). Connectors for wire diameter 0.6 – 1.2 mm (0.3 – 1.13 mm
2
approx.).
Technical data
Voltage (V DC) rated allowed normal (on the COM loop)
Current consumption at norm. volt. (mA) quiescent active (incl. internal LED) ext. LED
Internal capacitance (nF) Internal inductance
Ambient temperature (°C) operating (Min. / Typical / Max.) (Min. / Typical / Max.) storage
Ingress Protection rating IP67 (attached connection box, silicon gasket and compression glands
Sensitivity (°C) Static response temperature (range)
Size x H (mm) Weight (g) Detector: 112 Connection box (incl. 3 glands): 134 Construction / Colour Modified Polycarbonate / Grey (N8, Munsell colour code) Approvals 05 EC Certificate no. 0845-CPD-232.1190
ATEX classification
28 12-30 24
0.185
1.650 2
< 0
0 Depending on the mode.
NORMAL mode Class A1: -20 /+25 /+50, A2 S: -20 /+25 /+50 or B S: -20 /+40 /+65 2330 mode
-45 to +70
are required) NORMAL mode
Class A1: 54-65, A2 S: 54-70 & B S: 69-85 2330 mode: Class A2 S: 57
100 x 78
NORMAL mode 2330 mode
II 3GD EEx nA II T5 (T70°C), -20°C ≤ T
(Class is depending on the algorithm)
: -20 /+25 /+50
: Depending on the algorithm.
: EN54-5:2000: Class P (depending on algorithm).
: EN54-5:2000: Class A2 S.
65°C
a
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00133 2001-10-19 8 / 2008-10-10