Paloma PHH-32 User Manual

Page 1
Horizontal Vent Terminal Location
Outside Walls
INSTALLATION INSTRUCTIONS
C
F
B
D E
Fixed
Closed
Operable
L
H
B
Fixed
Closed
K
X
I
MM
Vent Terminal
X
Air Supply Inlet
Area Where Terminal is Not Permitted
Interior Wall
A
X
G
B
Operable
A J
B
Venting
37
Page 2
INSTALLATION INSTRUCTIONS
Venting for Direct-Vent Water Heater (cont.)
The following chart details the minimal dimensional information needed to determine the proper location of the vent terminal for direct vent and outdoor tankless water heaters. See corresponding letter reference in the illustration at left.
Venting
Location
A = Clearance above grade, veranda, porch,
deck, or balcony.
B = Clearance to window or door that may be
opened.
U.S. Installation Requirements
12 in. (30 cm) above anticipated snow level.
6 in. (15 cm) for water heaters less
than or equal to 10,000 Btuh (3 kW).
1
9 in. (23 cm) for water heaters greater
than 10,000 Btuh (3 kW) and less than or equal to 50,000 Btuh (15 kW).
12 in. (30 cm) for water heaters
greater than 50,000 Btuh (15 kW).
C = Clearance to permanently closed window.
D = Vertical clearance to ventilated soffit lo-
cated above the terminal within a horizontal distance of 2 ft. (61 cm) from the centerline of the terminal.
E = Clearance to unventilated soffit.
F = Clearance to outside corner.
G = Clearance to corner.
H = Clearance to each side of centerline ex-
tended above meter/regulator assembly.
I = Clearance to service regulator vent outlet.
J = Clearance to nonmechanical air supply inlet
to the combustion air inlet to any building or other appliance.
6 in. (15 cm) for water heaters less
than or equal to 10,000 Btuh (3 kW).
9 in. (23 cm) for water heaters greater
than 10,000 Btuh (3 kW) and less than or equal to 50,000 Btuh (15 kW).
12 in. (30 cm) for water heaters
greater than 50,000 Btuh (15 kW).
K = Clearance to mechanical air supply inlet. 3 ft. (91 cm) above if within 10 ft. (3 m)
L = Clearance above paved sidewalk or paved
driveway located on public property.
M = Clearance under veranda, porch, deck, or
balcony.
1 In accordance with current ANSI Z223.1/NFPA 54 National Fuel Gas Code. 2 In accordance with current CSA B149.1 Installation Codes.
For clearances not specified in ANSI 223.1/NFPA 54 or CSA B149.1, one of the following shall be indicated:
a) A minimum clearance value determined by testing in accordance with section 2.20, or b) A reference to the following footnote: “Clearance in accordance with local installation codes and the requirements of the
gas supplier.”
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and
serves both dwellings.
horizontally.
Not Allowed Not Allowed
Canadian Installation Requirements
12 in. (30 cm) above anticipated snow level.
2
6 in. (15 cm) for water heaters less
than or equal to 10,000 Btuh (3 kW).
12 in. (30 cm) for water heaters
greater than 10,000 Btuh (3 kW) and less than or equal to 100,000 Btuh (30 kW).
36 in. (91 cm) for water heaters
greater than 100,000 Btuh (30 kW).
3 ft. (91 cm) within a height of 15 ft. (4,57 m) above the meter/regulator assembly.
3 ft. (91 cm)
6 in. (15 cm) for water heaters less
than or equal to 10,000 Btuh (3 kW).
12 in. (30 cm) for water heaters
greater than 10,000 Btuh (3 kW) and less than or equal to 100,000 Btuh (30 kW).
36 in. (91 cm) for water heaters
greater than 100,000 Btuh (30 kW).
6 ft. (1,83 m)
7 ft. (2,13 m)
38
Page 3
Horizontal Vent Considerations
Rising moisture will collect under eaves.
Inside
Corner
Caulk
Caulk
Caulk
Caulk
If soft vent is too close, block off and install new vent at another location.
6' (1.8 m) Caulk zone or to edge of window etc., starting within 6' (1.8 m)
4'
(1.2 m)
Rising moisture will collect under eaves.
Inside
Corner
Caulk
Caulk
Caulk
If soft vent is too close, block off and install new vent at another location.
6' (1.8 m) Caulk zone or to edge of window etc., starting within 6' (1.8 m)
4'
(1.2 m)
12"
(300 mm)
WARNING: Moisture in the flue gas
will condense as it leaves the vent terminal. In cold weather this condensate can freeze on the exterior wall, under the eaves, and on surrounding objects. Some discoloration to the exterior of the building is to be expected. However, improper location or installation can result in severe damage to the structure or exterior finish of the building.
Do not install vent terminals under any patio or
deck.
Do not locate vent terminal on the side of a
building with prevailing winter winds. This will help prevent water lines from freezing and moisture from freezing on walls and under eaves.
Do not locate vent terminal too close to
shrubbery, since flue gases may damage them.
All painted surfaces should be primed to
lessen the chance of physical damage. Painted surfaces will require maintenance.
Guard against accidental contact with people
and pets.
INDOOR TANKLESS WATER HEATERS
WARNING: For multiple-unit
installation, a minimum distance between vent terminations must be maintained to prevent recirculation of vent gases. Maintain a center­to-center distance between each pair of vent terminations of 24 in. (61 cm) for a two-unit installation; 24 in. (61 cm) and 36 in. (91.4 cm) for an installation of three units; and 24 in. (61 cm), 36 in. (91.4 cm), and 24 in. (61 cm) for an installation of four units.
INSTALLATION INSTRUCTIONS
Venting
Do not terminate vent directly on brick or
masonry surfaces. Use rust-resistant, sheet­metal backing plate of 1 sq. ft. (30 sq. cm) behind the vent.
Caulk all cracks, seams, and joints within
6 ft. (1.8 m) of the vent terminal.
Caulk around wall faceplate for weather-tight
seal.
Do not extend exposed vent pipe of indoor
water heaters outside of the building.
This water heater requires its own separate
venting system. Do not connect the exhaust vent to an existing vent pipe or chimney.
OUTDOOR TANKLESS WATER HEATERS
Install outdoor water heater such that air inlet
and flue outlet are above anticipated snow level.
39
Page 4
INSTALLATION INSTRUCTIONS
Exhaust Vent Pipe
Air Intake Pipe
Wall Plate
Inspection
Access Panel
(Optional)
Inspection
Access Panel
(Optional)
Ceiling
Downward Slope
12"
(300 mm)
Venting for Direct-Vent Water Heater (cont.)
Venting
40
Horizontal Vent Installation
injury – Solvent cements and primers are highly flammable. Provide adequate ventilation and do not assemble near heat source or open flame. Do not smoke. Avoid skin or eye contact. Observe all cautions and warnings on material containers.
heater manufacturer-approved Schedule 40 PVC (foam core is not permitted at any time), Schedule 80 PVC, CPVC, ABS polypropylene, or UL 1738-listed Category III Stainless Steel. No other vent material is permitted.
Joining Pipes and Fittings
All pipe, fittings, solvent cement, primers, and procedures, for the U.S., must conform to American National Standards Institute and American Society for Testing and Materials (ANSI/ASTM) standards. For Canada, all pipe, fittings, solvent cement, primers, and procedures must conform to ULC­S636 and vent manufacture specifications.
Do NOT use solvent cement that has become curdled, lumpy, or thickened.
Do NOT thin solvent cement. Observe shelf precautions printed on the containers.
For applications below 32°F, use only lower temperature-type solvent cement.
Appropriate solvent and cleaner must be used for the type of vent pipe used (PVC, CPVC, or ABS).
WARNING: Danger of fire or bodily
CAUTION: Use tankless water
CAUTIONS:
Cleaner-Primer and Medium-Body Solvent Cement
All joints in vent piping must be properly sealed, and we recommend using the following material:
PVC materials should use ASTM D-2564-grade cement.
CPVC materials should use ASTM F-493-grade cement.
ABS materials should use ASTM D-2235-grade cement (ABS is not allowed in Canada).
Cementing Joints
1. Cut pipe end square; remove jagged edges and
burrs. Chamfer end of pipe; then clean fitting socket and pipe joint area of all dirt, grease, or moisture.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe and insert pipe into fitting with a slight twisting motion until it bottoms out.
4. Hold the pipe fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time will vary according to fit, temperature, and humidity.
NOTICES:
Cement must be fluid; if not, recoat.
Stir the solvent frequently while using. Use a
natural bristle brush or the dauber supplied with the can. The proper brush size is one inch.
Page 5
Horizontal Vent Installation (cont.)
Fasteners will vary depending on the wall type.
For particle board or composite sheathing, use
4 hollow wall anchors. The anchors should be at least 1/8 in. (0.3 cm) in diameter and the appropriate length for the sheathing thickness.
For plywood or solid
wood sheathing or members, use 4 #10 x
1 1/4-in. wood screws.
For masonry walls, use
suitable masonry anchors long enough to pass through the wall.
NOTICES:
The distance between the back edge of the exhaust vent terminal and the exterior wall must
be 12 inches (30.5 cm) more for the exhaust vent terminal than the air intake terminal.
To prevent possibility of condensate freeze-up, do not install vent kits one above the other.
Once the vent terminal location has been determined, make holes through the exterior wall to accommodate the vent pipes. Vent pipes must exit exterior wall horizontally only.
The standard horizontal air intake termination is a 2-inch or 3-inch pipe which terminates at the exterior wall and uses a coupling to prevent the pipe from being pushed back into the structure. The standard horizontal exhaust outlet termination is a 2-inch or 3-inch pipe which terminates 12 inches from the air intake termination. Insert a small length of vent pipe through the wall and connect the coupling. Connect vent cap or terminal to the vent pipe on the exterior of the building.
1. Use the vent plate as a template to locate air
intake holes and four mounting holes. Observe minimum clearances. Vent terminals must be a minimum of 5.5 inches (14 cm) and a maximum of 24 inches (61 cm) apart horizontally.
2. Cut two 2 1/2" (6.4 cm) diameter holes (for a
2" [5.1-cm] diameter pipe) or 3 1/2" (8.9 cm) diameter holes (for a 3" [7.6-cm] diameter pipe) for the exhaust vent and air intake openings.
Reinstall the decorative sheathing around the faceplate. The decorative sheathing may be painted to match the exterior decor.
INSTALLATION INSTRUCTIONS
1
Apply silicone sealant or silicone/latex caulk to seal the vent pipe to the vent cap to permit field disassembly for annual inspection and cleaning. Completely seal where it passes through the wall plate and where it is attached to the structure.
2
Attach the female end of the next vent pipe
section to the male end of the 2-in./3-in. (5.1-cm/7.6-cm) vent pipe. See “Cementing Joints” on page 40.
3
Complete the rest of the vent pipe installation to the water heater’s flue outlet and air intake.
Venting
41
Page 6
INSTALLATION INSTRUCTIONS
Exhaust Vent Pipe
Air Intake Pipe
Inspection
Access Panel
(Optional)
Inspection
Access Panel
(Optional)
Ceiling
Downward Slope
Exhaust Vent Pipe
Air Intake Pipe
Wall Plate
Inspection
Access Panel
(Optional)
Inspection
Access Panel
(Optional)
Ceiling
Downward Slope
Air Inlet
Exhaust Outlet
Pipe Support Strap
24"
Max.
12"
From Wall
For information about termination kits, refer to "If You Need Service" on page 26, "Call for Assistance" for the telephone number to speak to Customer Service Representative.
Venting for Direct-Vent Water Heater (cont.)
Alternative Horizontal Vent Installations
Alternative horizontal vent termination kits are commercially available. Please refer to the instruction sheet packaged with the kit for complete installation instructions.
Venting
Concentric vent termination kit
42
Flat horizontal termination kit
Page 7
INSTALLATION INSTRUCTIONS
Hole
Through Roof
C
L
Hole
Through Ceiling
C
L
A, B, C, D
Vertical Vent Installation
WARNING: Improper vent
installation can result in death, personal injury, product damage, and/or poor performance.
NOTICES:
Only Rheem-approved termination and parts should be used during installation.
Maintain the recommended air space clearance to combustible materials and building insulation.
1
Cut a hole through the roof and interior ceiling to accommodate the vent pipes.
NOTICE: Free-standing vent pipe that
penetrates a roof/ceiling requires another means of support from a second location. Determine the vent terminal height and install
the vent pipe accordingly. Refer to “Vertical Vent Terminal Location” on page 44 for clearance requirements.
Venting
4
Install adequate flashing where the vent pipe
passes through the roof.
2
Complete the vent pipe installation to the water
heater’s vent connector fittings. Use cleaner­primer and PVC cement where the vent pipes join the water heater.
3
Support vertical and horizontal runs as described on page 35. Vertical supports are required every 4 ft. (1.2 m) along a vertical pipe route, after every transition to vertical, and after every offset elbow.
5
Air Intake Condensate Trap
For vertical terminations or where the air intake pipe slops down towards the water heater, it is recommended to install a drain tee assembly. This is to prevent any condensate or liquid water from entering the intake of the water heater. Connect the trap drain line to a suitable drain. Do not connect it directly to the condensate drain line from the water heater.
1
One trap method: Glue a 3” by 4” adapter
coupling to each end of a 4” PVC pipe length. Drill a ½” hole in the side of the larger diameter pipe. Tap and thread for a ½” barbed fitting, install fitting. Install the collector with the fitting facing down. Connect a drain hose to the fitting and clamp, run hose to a suitable drain.
43
Page 8
A, B, C, D
12" Min.
(300 mm)
Vent Pipe
Through Roof
Optional
INSTALLATION INSTRUCTIONS
Venting for Direct-Vent Water Heater (cont.)
Vertical Vent Terminal Location
Venting
The following chart with diagrams details the minimum dimensional information needed to determine the proper location of the vertical vent terminal for direct-vent indoor tankless water heaters:
U.S. Installation
Location
A = Minimum clearance above the roof level. 12 in. (30.5 cm) above roof level. 18 in. (45.7 cm) above roof level.
B = Minimum clearance above anticipated snow
level.
C = Maximum clearance above roof level (without
additional support for vent pipe).
D = Maximum clearance above anticipated snow
level (requires additional vent support).
E = Required vent clearance from any gable,
dormer, or other roof structure with building interior access (i.e., vent, window).
F = Required vent clearance from any forced air
inlet, including dryer and furnace air inlets.
G = Minimum/maximum horizontal distance
between vent terminals
1 In accordance with current ANSI Z223.1/NFPA 54 National Fuel Gas Code. 2 In accordance with current CSA B149.1 Installation Codes.
The vertical intake air termination requires a
Requirements
12 in. (30.5 cm) above anticipated snow level.
24 in. (61 cm) above roof level. 24 in. (61 cm) above roof level.
24 in. (61 cm) above anticipated snow level.
4 ft. (1.2 m) 4 ft. (1.2 m)
10 ft. (3 m) 6 ft. (1.8 m)
5.5 in. (14 cm)/24 in. (61 cm) 5.5 in. (14 cm)/24 in. (61 cm)
1
Canadian Installation Requirements
12 in. (30.5 cm) above anticipated snow level.
24 in. (61 cm) above anticipated snow level.
2
return bend or two short or long sweep radius 90° elbows to keep the inlet downward and prevent entry of rain. Refer to figure above for the proper location of the air intake with respect to the exhaust outlet termination. The vertical exhaust outlet termination is a 2-inch or 3-inch pipe which terminates at least 12 inches above the air intake termination. The air intake and exhaust outlet terminations must be at least 12 inches above the roof line or anticipated snow levels.
44
Page 9
Adjustable Roof Flashing
Support Clamp
Upward Slope
Support Hanger
Air Intake
Pipe
Exhaust Vent
Pipe
Condensate
Drain
Optional
Standard Vertical Vent Termination
INSTALLATION INSTRUCTIONS
Venting
45
Page 10
Support Hanger
Adjustable Roof Flashing
Support Clamp
Upward Slope
Air Intake
Pipe
Exhaust Vent
Pipe
Minimum Clearance Above Anticipated Snow Level
Condensate
Drain
INSTALLATION INSTRUCTIONS
Venting for Direct-Vent Water Heater (cont.)
Alternative Vertical Vent Termination
Alternative vertical vent termination kits are commercially available. Please refer to the instruction sheet packaged with the kit for complete installation instructions.
Venting
46
Page 11
Water Supply
INSTALLATION INSTRUCTIONS
CAUTION: This water heater
MUST ONLY be used with the following water supply conditions to prevent product damage and operation failure.
Clean, potable water free of corrosive chemicals, sand, dirt, or other contaminates.
Inlet water temperatures above 32°F (0°C), but not exceeding 120°F (49°C).
DO NOT reverse the HOT and COLD water connections.
DO NOT connect this water heater to water lines previously used for space heating. All water piping and components shall be suitable for potable water.
With recommended water quality (see chart).
Chart for Recommended Water Quality Levels
pH
6.5–8.5 Up to 500 mg/L Up to 15 mg/L
TDS (Total
Dissolved Solids)
Free Carbon
Dioxide (CO
)
2
Total
Hardness
Up to
200 mg/L
Aluminum Chlorides Copper Iron Manganese Zinc
0.2 mg/L
Up to
Thermal Expansion
A thermal expansion tank will be required if the water heater is installed in a recirculation system. This prevents damage to the heater, related piping, and the relief valve.
NOTICE: Replacing the relief valve will
not correct the problem!
The expansion tank is designed with a built-in air cushion that compresses as the system pressure increases. This relieves the over-pressure condition and eliminates the repeat operation of the relief valve.
For other approved methods of thermal expansion, contact an installing contractor, water supplier, or plumbing inspector.
Up to
200 mg/L
Up to
1.0 mg/L
Up to
0.3 mg/L
Up to
0.05 mg/L
Up to
1.0 mg/L
Plumbing
Water Supply Connections
CAUTION: IMPORTANT—Do
not apply heat to the HOT or COLD water connections. If sweat connections are used, sweat tubing to the adapter before fitting the adapter to the water connections on the water heater. Any heat applied to the water supply fittings will permanently damage the internal components of the water heater.
NOTICE: In cold environments, ice can
accumulate in the water heater’s connectors. Plug in the water heater power cord for approximately 10 minutes before making these connections. This will melt any ice buildup.
Plumbing should be carried out by a qualified plumbing contractor in accordance with local codes.
Only use approved plumbing materials.
The minimum diameter of all water pipes should be 3/4 in. (1.9 cm).
To conserve energy and to prevent freezing, insulate both COLD and HOT water supply lines. Do not insulate the drain line or pressure-relief valve.
47
Page 12
INSTALLATION INSTRUCTIONS
Water Supply
Water Supply Connections (cont.)
Plumbing
To ensure proper operation of the water heater, follow these water pressure guidelines.
Operation of the water heater requires a
minimum water pressure of 14 psi (97 kPa) and a minimum water flow rate of 0.4 gpm (1.5 lpm).
Water pressure of 40 psi (276 kPa) is required to achieve maximum flow rate.
To maintain proper performance, there must be sufficient water supply pressure.
Required Water Pressure =
Min. Operating Water Pressure
(14 psi [97 kPa])
+ Pipe Pressure Loss
+ Faucet Pressure Loss
+ Safety Margin
(more than 5 psi [34 kPa]).
Water Supply Installation
NOTICES:
Use only Teflon tape on all COLD and HOT water connections.
If the water flow resistance of a showerhead is too high, the burner in the water heater will fail to ignite. Keep all showerheads clean from debris that could cause additional pressure drop.
If using mixing valves on the outlet, choose one that prevents COLD water pressure from overcoming HOT water pressure.
If multiple water heaters are installed in a manifold system, the water piping MUST be in “parallel” and the water pressure at each water heater should be 40 psi (276 kPa).
To supply HOT water to upper floors, additional water pressure will be required (0.44 psi [3 kPa] per foot of height). Calculate the distance between the water inlet of the water heater (ground level) to the HOT water faucet farthest away from the water heater (upper floor level).
Well water systems should be set to ensure a minimum system pressure of 40 psi (276 kPa). The pressure should remain constant and stable during the operation of the water heater.
• Gravity water pressure is not recommended.
When the water is supplied from a water supply tank, the height of the tank, the diameter of the supply pipes, and their relation to water pressure need to be taken into consideration.
2
Before attaching the water line to the water
heater, open the shut-off valve. Run the water until it has purged all contaminants (sand, debris, air, caulking, etc.).
48
1
Install a COLD water shut-off valve near the
inlet line on the water heater. This valve will be used for servicing and draining purposes.
NOTICE: It is not recommended to
use pipes with smaller diameters than the water supply connection of the water heater.
3
Install a service valve on the end of the COLD
water supply line and connect it to the water inlet on the water heater.
Page 13
Pressure
Relief Valve
Pressure
Relief Valve
Cold Water
Service Valve
Cold Water
Service Valve
Water
Inlet
Water
Inlet
Water
Outlet
Water Outlet
Hot Water
Service Valve
Hot Water
Service Valve
Drain
Drain
Water Supply Installation (cont.)
4
Open the shut-off valve in the COLD water Inlet
line to check the water flow through the water heater.
INSTALLATION INSTRUCTIONS
NOTICES:
Be sure to connect the COLD water inlet and the HOT water outlet as shown on the water heater. If reversed, the water heater will not function.
The flow rate of HOT water may vary when more than two faucets (appliances, fixtures, etc.) are being used simultaneously.
The pipes MUST be completely drainable. If the HOT water faucets are located at a point higher than the water heater, place a drain valve at the lowest point.
Plumbing
5
Close the shut-off valve and remove, clean, and
replace the water filter.
It is recommended to use unions and flexible copper connections at the COLD and HOT water lines. They allow the water heater to be disconnected easily for servicing.
Use the following guidelines when connecting the HOT WATER OUTLET:
Connections between the water heater and
point(s) of use should be as short as possible.
Local codes shall govern the piping used for water connections.
To conserve energy and to prevent freezing, insulate both COLD and HOT water supply lines. Do not insulate drain line or pressure-relief valve.
Water Piping Arrangement With Service Valve Kit
Service valve kits are available on all tankless water heater systems. All kits include two full-port isolation valves to be used in the COLD and HOT water lines. When installed, these valves allow one person full diagnostic testing and ease of flushing the system. Contact your distributor or place of purchase for availability and installation information.
49
Page 14
INSTALLATION INSTRUCTIONS
Relief Valve
Union
Union
Cold Water Supply
Shut-Off Valve
Cold Water Supply Inlet
Hot Water
Supply Outlet
Relief Valve
Discharge Line
Water Supply (cont.)
Plumbing
Relief Valve
A new pressure-relief valve, complying with the Standard for Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22/CSA 4.4, must be installed at the HOT water outlet connection of the water heater during installation. Local codes shall govern the installation of any relief valves or place of purchase for availability and installation information.
NOTICES:
The following drawing illustrates a pressure-only relief valve. If local codes require a combination temperature and pressure-relief valve, you may need to install an extension piece to ensure that the valve probe is not directly in the flow path of the water.
If local codes require that a temperature and
pressure-relief valve be installed, the manufacturer recommends a type 40XL Watts temperature and pressure-relief valve or equivalent model be used.
Manual operation of relief valves should be performed at least once a year.
If the relief valve on the system discharges periodically, a problem exists. Turn off the water heater, unplug the unit, and call for service.
For safe operation of the water heater, be sure that:
The pressure rating of the relief valve must not
exceed 150 psi (1,034 kPa) or the maximum working pressure of the water heater. (See the rating plate on the water heater.)
The BTUH rating of the relief valve must equal or exceed the BTUH input of the water heater. (See the rating plate on the water heater.)
No valve of any type should be installed between the relief valve and the water heater.
Discharge from the relief valve should be piped to a suitable drain. Piping used should be of a type approved for the distribution of hot water.
HOT and COLD water lines should be insulated up to the water heater. See page 51.
The discharge line must be NO SMALLER than the outlet of the relief valve. The drain line must pitch downward to allow for complete drainage of the line and the valve.
The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction, or reducer coupling should be installed in the discharge line.
50
One end of the relief valve discharge line connects to the HOT water outlet pipe as shown above. The other end of the pipe should be routed to a suitable drain to eliminate potential water damage.
Page 15
Hot and Cold Pipe Insulation Installation
Cold Water
Service Valve
Hot Water
Service Valve
Pressure
Relief Valve
Pressure
Relief Valve
Water Outlet
Water
Outlet
Water
Inlet
Water
Inlet
Drain
Drain
Condensate Drain
INSTALLATION INSTRUCTIONS
WARNINGS:
When pipe insulation is not rated for the appropriate weather conditions, install electric heat tracing or equivalent to prevent freezing of the pipes.
Do not insulate or block drain valve on the hot outlet fitting.
If pipes are allowed to freeze, the water heater and the pipes may malfunction or leak due to freezing water.
NOTICE: The hot and cold water supply
pipes should be insulated to provide additional freeze protection.
Condensate
Condensate Drainage
Be sure the condensate runs freely to a drain and does not accumulate inside the water heater. In cold climates, precautions may need to be taken to ensure that the condensate drain does not freeze.
All condensation must drain and dispose of per local code.
If the condensate drain gets blocked, an error code will display on the remote control. If this occurs, the condensate drain must be cleared.
Use only PVC or CPVC pipe or flexible tube for the condensate drain line.
For increased energy efficiency, use pipe insulation as shown in the diagram. Insulate the pipes all the way to the top. DO NOT cover any drain or pressure-relief valve(s).
Plumbing
The drain pipe (along its entire length) must be at least the same diameter as the drain line.
The drain line should be as short as possible and have a downward slope toward the end.
The end of the drain pipe should be open to the atmosphere. The end should not be under water or other substances.
Do not connect the drain pipe directly to the drain sewer.
Do not connect the drain pipe with an air­conditioning evaporator coil drain.
51
Page 16
INSTALLATION INSTRUCTIONS
Union
Manual Gas
Supply Line
Shut-Off Valve
Cap
Sediment Trap
Manual Gas
Shut-Off Valve
Gas Supply
Gas Supply
Gas Supply Connections
WARNING: Do not attempt to
convert this water heater for use with a different type of gas other than the type shown on the rating plate. Doing so could result in death, personal injury, explosion or fire, product damage, and/or poor operating conditions or performance.
NOTICES:
Gas piping shall be in accordance with local utility company requirements and/or in the absence of local codes, use the latest edition of National Fuel Gas Code (NFGC), ANSI Z223.1. In Canada, use the latest edition of CSA B149.1, National Gas and Propane installation code.
Apply a thin coat of pipe compound to all threaded male ends. Compound must be of the type resistant to the action of LP gas.
To ensure proper water heater operation, the gas pipe and gas meter must be sized correctly.
If flexible connectors are used, the minimum inside diameter must be 3/4" or greater and the rated capacity of the connector must be equal to or greater than the BTU capacity of the water heater. See manufacturer information for the gas connector. Lengths over 36 inches are not recommended.
Do not use excessive force (over 31.5 ft. lbs. [42,7 Nm]) when tightening the pipe sections. Excessive force can damage the water heater, especially when Teflon pipe compound is used.
52
Page 17
INSTALLATION INSTRUCTIONS
Gas Piping
Pipe-Sizing Procedure – Example
The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas type, the pressure drop in the system, the gas pressure supplied, and gas line type. For gas pipe sizing in the United States, refer to the National Fuel Gas Code, NFPA 54. For Canadian gas pipe sizing, refer to the Natural Gas and Propane Installation Code CAN/CSA B149.1. The information below is provided as an example. The appropriate table from the applicable code must be used.
1. Determine the cubic feet per hour of gas required by dividing the gas input (on the rating plate) by the heating value of the gas (available from the local gas company). The gas input needs to include all gas products at the location and the maximum BTU usage at full load when all gas products are in use.
Gas Input of Cubic Feet Water Heater (BTU/HR) Per Hour (CFH) = Heating Value of Gas (BTU/FT
2. Use the table for your gas type to find the pipe size required for your cubic feet per hour of gas and your pipe length.
Example: The heating value of propane gas for
3
your location is 2500 BTU/FT
. The gas input of the tankless water heater is 199,900 BTU/ HR. Additional appliances at the location require 75,000 BTU/HR. Therefore, the cubic feet per hour = (199,900 + 75,000)/2500 = 109 FT3/HR. If the pipe length is 100 ft., then the 3/4-inch pipe size capable of supplying 197 FT3/HR of propane gas will be adequate.
Gas Supply
3
)
Pipe-Sizing Table – Natural Gas
Schedule 40 Metallic Pipe
Inlet Pressure: Less than 2 psi (55 inches W.C.)
Length
10
20
30
40
50
60
70
80
90
100
125
150
175
200
Refer to current National Fuel Gas Code, NFPA 54.
Pressure Drop: 0.3 inches W.C.
Specific Gravity: 0.60
(Capacity in cubic feet per hour)
Pipe Size (inches)
3/4 1 1 1/4 1 1/2
273 514 1060 1580
188 353 726 1090
151 284 583 873
129 243 499 747
114 215 442 662
104 195 400 600
95 179 368 552
89 167 343 514
83 157 322 482
79 148 304 455
70 131 269 403
63 119 244 366
58 109 224 336
54 102 209 313
Pipe-Sizing Table – Propane Gas
Schedule 40 Metallic Pipe
Inlet Pressure: 11.0 inches W.C.
Pressure Drop: 0.5 inches W.C.
Specific Gravity: 1.50
(Capacity in cubic feet per hour)
Length
10
20
30
40
50
60
80
100
125
150
175
200
1/2 3/4 1 1 1/4
291 608 1150 2350
200 418 787 1620
160 336 632 1300
137 287 541 1110
122 255 480 985
110 231 434 892
101 212 400 821
94 197 372 763
89 185 349 716
84 175 330 677
74 155 292 600
67 140 265 543
Pipe Size (inches)
53
Page 18
INSTALLATION INSTRUCTIONS
Gas Supply (cont.)
Gas Supply Installation
4
Gas Supply
1
Install the manual gas appliance shut-off valve
to the gas connection at the water heater. The shut-off is supplied with the water heater.
2
Install a ground joint union or ANSI design-
certified semi-rigid or flexible gas appliance connector to the open end of the manual gas appliance shut-off valve. The (NFGC) ANSI Z223.1 and CSA B149.1 codes mandate the use of manual gas shut-off valves.
Using the proper-size piping, fittings, and
components, build the gas supply line to the water heater.
NOTICE: The gas supply line should
be a minimum of 3/4-in. (1.9-cm) black steel pipe or other approved gas piping material.
5
Install a sediment trap at the lowest portion of the gas line.
The inlet gas pressure to the water heater must NOT exceed 10.5 in. w.c. (2.6 kPa) for natural gas and 14 in. w.c. (3.5 kPa) for LP gas. For purposes of input adjustment, the minimum inlet gas pressure (with main burner on) is shown on the water heater rating plate. If high or low gas pressures are present, contact your gas supplier for correction.
54
3
Install a manual gas supply line shut-off valve
to the end of the gas supply line.
NOTICE: Lever-type gas shut-offs
should all be T-handle type.
Page 19
Leak Testing
WARNING: Never use an open
flame to test for gas leaks, because death, personal injury, and/or property damage can result.
The water heater and its gas connections MUST be leak-tested at normal operating pressures before the unit is placed in operation. These tests should also include all factory connections.
INSTALLATION INSTRUCTIONS
Turn on the gas shut-off valve(s) to the water heater.
Use a soapy water solution to test for leaks at all the connections and fittings. If bubbles are seen, it indicates a gas leak that must be corrected.
Contact a qualified service technician.
Pressure Testing the Gas Supply System
CAUTION: Install a gas pressure
regulator in the gas supply line. This regulator should not exceed the maximum supply pressure. DO NOT use an industrial-type gas regulator.
Gas Supply
The water heater and its manual gas shut-off valve must be disconnected from the gas supply piping system whenever the pressure testing will exceed 1/2 psi (14 in. w.c. [3.5 kPa]).
The water heater must be isolated from the gas piping system whenever the pressure testing will be less than and/or up to 1/2 psi (14 in. w.c. [3.5 kPa]). Closing the manual gas shut-off valve will isolate the water heater from the gas piping system.
55
Page 20
INSTALLATION INSTRUCTIONS
Gas Supply (cont.)
Gas Supply
Electrical
56
High-Altitude Installation
The water heater is certified for installations up to 3,280 ft. (1,000 m) above sea level. The input rating of this water heater is based on sea level operation. At higher elevations, the actual input rate may be lower than the value listed on the rating label.
Electrical Wiring
DANGER: Shock Hazard – Before
servicing the water heater, turn off the electrical power to the water heater at the main disconnect or circuit breaker. Failure to do so will result in death or serious personal injury.
WARNING: Field wiring connections
and electrical grounding must comply with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/ NFPA 70, in the U.S., or Canadian Electrical Code, CSA C22.1, Part 1, in Canada.
CAUTION:
disconnecting. Wiring errors can cause personal injury, product damage, and/or dangerous operating conditions. Verify correct operation after servicing.
Label all wires prior to
NOTICES:
Do not connect power until venting installation is complete (see Venting Installation pages 34–46).
Wait ninety (90) seconds after power is connected for the first time to initiate operation of the water heater.
Power Cord
The electric power supply requirement for this water heater is 120 VAC/60 Hz, 2 amps.
A dedicated circuit is recommended for the water heater. Do not connect to a GFCI or AFCI circuit. Multiple units may be connected to a single circuit up to the circuit rating.
Do not use 3-prong to 2-prong adapters. Do not use power strips or multiple outlet adapters.
NOTICES:
For installations above 3,280 ft. (1,000 m) elevation, contact a qualified service technician to make the proper altitude adjustments. See pages 67 and 68 for additional information.
Do not install this water heater at elevations above 3,280 ft. (1,000 m) without the proper adjustments. Please contact your installer, local gas supplier, place of purchase, or the Rheem Customer Service phone number listed on page 26 in the “Call for Assistance” section.
All direct-vent gas models come with a three­prong power cord. Only use this power cord and a matching grounded electrical outlet.
All outdoor gas models do not come with a power cord. Only hard-wire to an appropriate power outlet with a ground terminal.
Keep any excess length of the power supply cord on the outside of the water heater.
If local codes require hard-wiring, see instructions for “Hard-Wiring the Electrical Connections” below.
Hard-Wiring the Electrical Connections
Wiring should be performed by a qualified electrician in accordance with local codes.
The water heater requires a properly grounded 120 VAC/60 Hz dedicated power supply. Multiple water heaters may be connected to a single circuit up to that circuit’s rating.
DO NOT connect grounding wire to water pipes, gas pipes, telephone cables, lighting conductor circuits, or to any other grounding circuits that require a GFCI or AFCI (arc fault circuit interrupter).
An ON/OFF switch must be provided and installed for the incoming 120 VAC power supply.
Wire the water heater exactly as shown in the wiring diagram. This wiring diagram can also be found inside the water heater cover panel.
The green screw is provided in the enclosure for a grounding connection.
Connect the live wire to the black wire and neutral wire to the white neutral wire.
Page 21
Wiring Diagram
W: WHITE, BLANC
BK: BLACK, NOIR
BR: BROWN, BRUN
BL: BLUE, BLEU
FOR INDOOR, DIRECT-VENT
GY: GRAY, GRIS
CODE DE COULEUR
COLOR CODE
R: RED, ROUGE
AMBIENT AIR
THERMISTOR
THERMISTOR
VERT/JAUNE
Y: YELLOW, JAUNE
G/Y: GREEN/ YELLOW,
O: ORANGE, ORANGE
G: GREEN, VERT
R4
FLAME ROD 1
ÉLECTRODE DE
DÉTECTION
DE FLAMME 1
MODEL ONLY
POUR MODÈLE INTÉRIEUR À
ÉVENT DIRECT SEULEMENT
HEAT EXCHANGER
THERMISTOR
D’ADMISSION D'EAU
WATER INLET
THERMISTOR
D’AIR AMBIANT
R3
BK
FLAME ROD 2
ÉLECTRODE DE
DÉTECTION
DE FLAMME 2
R2
BK
GAS TYPE
INSTALLATION INSTRUCTIONS
THERMISTOR
DE SORTIE D’EAU CHAUDE
HOT WATER OUTLET
THERMISTOR
THERMISTOR
D’ECHANGEUR DE CHALEUR
THERMISTOR
P.G.F.R VALVE
WATER VOLUME CONTROL MOTORWATER BY-PASS CONTROL MOTOR
MOTEUR DE CONTRÔLE DU VOLUME D’EAU
PSV
+
ÉLECTROVALVE DE DÉRIVATION D’EAU
CIRCUIT BOARD
PLAQUE DE CIRCUIT
R1
BK
IMPRIMÉ DE TYPE Â GAZ
MOTOR
MOTEUR
LIMITER
LIMITEUR
MOTOR
MOTEUR
LIMITER
LIMITEUR
GG BL BL BK R Y O WBR
R Y O WBR BK
CONTROL 2
BATH REMOTE
TÉLÉCOMMANDE 2
« BATH »
BATH REMOTE
CONTROL 1
TÉLÉCOMMANDE 1
« BATH »
MAIN REMOTE
CONTROL
TÉLÉCOMMANDE
« MAIN »
(USC2-117)
31-98419 2
(USC1-117)
(UMC-117)
8
8
NEUTRALIZER WATER
ON
MARCHE
LEVEL ELECTRODE
ÉLECTRODE DE NIVEAU
CONTACTEUR DIP 1
DIP SWITCH 1
ON
OFF
ARRÊT
4 3 2 1
R
R
D’EAU DE NEUTRALISANT
5
FAN MOTOR
DIP SWITCH 2
CONTACTEUR DIP 2
MARCHE
OFF
ARRÊT 4
3
2 1
YWR BK BL
FM
MOTEUR DU
VENTILATEUR
FOR DIRECT-VENT MODEL ONLY
BL
BOUTON DE RÉGLAGE
BOUTON MAX.
BOUTON MIN.
CIRCUIT BOARD
T
W
M
LED
PLAQUE DE CIRCUIT
SW3SW2SW1
MAX BUTTON ADJUSTER BUTTON
MIN BUTTON
1
2
P
G
123456
W BL R O Y
GND
BK
SV4
SV3
`
POUR MODELE À ÉVENT DIRECT SEULEMENT
SOLENOID VALVE 4
ÉLECTROVALVE 4
SOLENOID VALVE 3
ÉLECTROVALVE 3
SV2
SOLENOID VALVE 2
ÉLECTROVALVE 2
BK
A
4 3 2 1
F
G/Y
SV1
SOLENOID VALVE 1
2
345
USUALLY
DISCONNECTED
NORMALEMENT
K
R
5678
BK
W BK
BK
BK
SV0
ÉLECTROVALVE 1
ÉLECTROVALVE DANS
SOLENOID VALVE 0
1
DÉCONNECTÉ
G
W
BL
B
R
R
BK
BK
( )
123
4
567
YW
1 23
GY
4
BL
W
RÉSISTANCE
RESISTOR
ADMISSION DE GAZ
IG
BK
ELECTRODE
GY GY
ALLUMEUR
IGNITER
ELECTRODE
Y
R
G
BL
BK
45678
R
Y
G
BK
8C9
BL
456
7
1
2
U
R
H
3
1
WW
2
4
W
W
ANTI-FROST HEATER
CHAUFFAGE ANTI-GIVRE
W
BL
O
W
BR
1
2
3
O
W
BR
1
2
3 3
2
1
BL
1
2
3
V
WATER FLOW SENSOR
CAPTEUR DE DÉBIT D’EAU
S
W
BR
W
BK
R
Electrical
IJ
W
W
W
W
BK
W
BK
W
BK
G/Y or G
AC
120V
FUSIBLE (3A)
FUSE (3A)
OVER HEAT LIMITER
GND
FOR INDOOR, DIRECT-VENT
LIMITEUR DE SURCHAUFFE
`
MODEL ONLY
POUR MODELE INTERIÉUR À
ÉVENT DIRECT SEULEMENT
57
Page 22
INSTALLATION INSTRUCTIONS
Electrical Wiring (cont.)
Remote Control Selection and Location
WARNING: Field wiring connections
and electrical grounding must comply with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/ NFPA 70, in the U.S., or Canadian Electrical Code,
CSA C22.1, Part 1, in Canada.
NOTICES:
The provided remote control will allow maximum temperature settings of 120°F (49°C). Temperatures up to 140°F (60°C) for residential applications and up to 185°F (85°C) for commercial applications* can be achieved with the MAIN (UMC-117) remote control. Only qualified service personnel should perform this adjustment.
An optional cable (EZ Link CableTM) can be purchased separately to manifold two water heaters together.
• Do not attempt to disassemble a remote control. All controls are sealed and calibrated for accurate water heater control and operation.
Review the following considerations before determining the location of the remote control(s):
• Do not install any remote control
outdoors or where it can come in contact with water.
Avoid installing the remote control in
the following areas and/or conditions: – area exposed to heat. – area exposed to steam. – area exposed to oil. – area exposed to direct sunlight. – areas near stored or used
flammable products.
Place remote control out of children’s reach.
The remote control should be installed in a
convenient location (e.g., kitchen, laundry room, utility room, or directly next to the water heater).
The maximum distance between the water heater and the remote control installation location is limited to 195 ft. (59 m) of wire.
Electrical
58
One remote control is provided with the water heater. Additional remote controls may be purchased separately. The available remote controls are listed in the following chart. Up to three remote controls can be used with the water heater. No other manufacturer’s controls are
suitable for use with this water heater.
Remote Control
Model Number
UMC-117 MAIN
USC1-117
USC2-117 BATH 2
MIC-6 or MIC-185**
Manifold System
*A commercial conversion kit can be purchased to achieve temperatures up to 185°F (85°C). **When a manifold system is installed, the main remote control connected to the manifold controller (MIC-6 or MIC-185) has priority over the remote controls connected to the water heater.
Remote Control
Description
BATH 1
Manifold System Optional (Sold Separately)
Temperature
Set Point Range Availability
100°F–120°F (38°C–49°C) Factory Default
85°F (29°C)
125°F–140°F (52°C–60°C)
85°F (29°C)
125°F–185°F (52°C–85°C)
100°F–120°F (38°C–49°C) Optional (Sold Separately)
85°F (29°C) Qualified Technician Adjustment
100°F–120°F (38°C–49°C) Optional (Sold Separately)
85°F (29°C) Qualified Technician Adjustment
Adjustment for Residential Products
Adjustment for Commercial Products*
Qualified Technician
Qualified Technician
Page 23
Remote Control Installation
WARNING: Field wiring connections
and electrical grounding must comply with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/ NFPA 70, in the U.S., or Canadian Electrical Code,
CSA C22.1, Part 1, in Canada.
INSTALLATION INSTRUCTIONS
4
NOTICES:
Remote control cable can be any Type–T 18 AWG wire similar to a thermostat wire and need not be polarity-sensitive.
It is not recommended to have wiring exposed.
• Do not apply sealant to remote control cable.
• Do not use network cable, telephone wire, or
any twisted-pair cable.
Connecting the MAIN (UMC-117) Remote Control to a Wall:
1
Drill a 1- to 1 1/2-in. (2.5/3.8-cm) hole at the
proposed control location. Install the remote control cable between the location of the remote control and the water heater.
Install the base plate to the wall using suitable
screws and wall anchors.
NOTICE: The tabs on the base plate
should always point out.
5
Connect the remote control to the remote
control cable.
Electrical
6
Position the remote control on the base plate.
2
Remove the remote control from the base plate.
3
Feed the remote control cable through the large
center hole in the base plate.
NOTICE: The tabs on the base plate
should line up with the slots on the back of the control panel.
Secure the control panel to the base plate with
one screw into the bottom tab.
NOTICE: Do not attempt to connect the
remote control or control wire to the water heater while the water heater has power applied to it. Damage to the water heater will occur. Do not cut or strip the wiring while it is connected to the water heater or while the water heater has power applied to it.
59
Page 24
INSTALLATION INSTRUCTIONS
Remote Control
Connection Cover
Remote Control
Connection Cover
Electrical Wiring (cont.)
Connecting the Remote Control to the Water Heater:
1
Ensure that the power to the water heater has
been disconnected.
4
Firmly tighten the terminal screws by hand. Secure the remote control extension cable on
5
Electrical
2
Loosen the one screw located on the remote
control connection cover. The connection cover is made of white plastic.
NOTICE: DO NOT REMOVE FRONT
PANEL. Remote control wires are connected on
the bottom of the unit.
There are no accessible remote control
terminals inside the water heater.
3
Connect the remote control extension cables
from the remote control to the remote control connection terminals.
the hook located on the side of the remote control connection base.
Reinstall the remote control connection cover
6
and secure with the one screw.
NOTICE: Do not connect power until
venting installation is complete.
Switch on the power supply to the water heater.
60
NOTICE: The remote control wire
connection terminals are not polarity-sensitive.
7
Check for proper operation of the remote control and the water heater.
Page 25
Insulation Blankets
INSTALLATION INSTRUCTIONS
In general, insulation blankets for external use on gas water heaters are not necessary. The purpose of an insulation blanket is to reduce the standby heat loss from the water heater’s storage tank. Since these water heaters do not store water, they eliminate the need for the insulation blanket.
WARNINGS:
If local codes require the application of external insulation blanket kits, carefully follow the manufacturer’s installation instructions included with the kit. Only use blanket kits that are approved for use with your water heater.
NEVER cover the air inlet, flue outlet, or operating and warning labels attached to the water heater. Operating and warning labels should not be relocated to the exterior of an insulation blanket. Covering these components will cause dangerous operating conditions that can lead to death, personal injury, property damage, and/or product damage.
The manufacturer’s warranty does not cover any damage or defect caused by insulation, insulation attachment, or use of any type of energy-saving or other unapproved devices (unless authorized by the manufacturer). The use of unauthorized energy-saving devices can result in death, personal injury, and/or property damage. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices.
Installation Precautions
Follow all installation instructions covered in this manual.
Check the inlet gas pressure to make sure it is within the range specified on the rating plate.
Make sure there is adequate air for combustion and ventilation as described on pages 37–38 or page 44 in this manual.
Maintain proper clearances to combustibles and noncombustibles as specified on the rating plate.
Make sure the venting system complies with local codes, National Fuel Gas Codes (ANSI Z223.1/NFPA 54) or CSA B149.1, and the guidelines found on pages 34 through 46 in this manual.
Electrical
Contact the local gas company to make sure the gas meter and gas piping are adequately sized.
Use only Teflon tape on all male water line connections and fittings.
• Do not block or restrict any air intake openings.
• Do not remove the front cover unless absolutely
necessary. This should only be done by a qualified service technician.
• Do not install this product where standing water may occur.
• Do not use pipe dope on water line connections and fittings.
61
Page 26
INSTALLATION INSTRUCTIONS
Installation Checklist
A. Water Heater Location
Indoor water heaters must be installed indoors.
Outdoor water heaters must be installed outdoors.
Close to area of ventilation termination (indoor models).
Protected from freezing temperatures.
Proper clearance from combustible material observed.
Sufficient fresh air supply for proper operation of water heater.
Air supply free of corrosive elements and flammable vapors.
Provisions made to protect area from water damage.
Sufficient room to service heater.
C. Water Supply/Relief Valve
Water supply has sufficient pressure.
Air has been purged from the water heater and the piping.
Water connections tight and free from leaks.
Water filter is clean and in place.
All piping has been assembled as described on pages 48 and 49.
Water pipes are insulated and protected from freezing, if necessary.
Pressure-relief valve properly installed with discharge line running to open drain.
Discharge line protected from freezing, if necessary.
D. Gas Supply
Gas type matches listing on rating plate.
Checklist
Combustible materials, such as clothing, cleaning materials, and rags, clear of the heater and vent piping.
Water heater is properly attached to the wall.
B. Vent (Indoor Models)
Vent pipe material is PVC and is manufacturer-approved.
Horizontal air intake and exhaust pipes have a 1/4" per foot DOWNWARD slope toward the vent terminal.
Vertical venting is installed as described on pages 43 and 44.
Connection(s) securely fastened together with cement and airtight.
All vent runs are properly installed.
Vent terminal is properly installed.
Maximum vent length is observed.
Gas supply pressure is sufficient for the water heater.
Gas line equipped with shut-off valve, union and sediment trap as described on page 54.
Approved pipe-joint compound has been used on all gas pipe connections.
All connections and fittings have been checked for leaks with a soapy water solution.
Gas company inspected installation (if required).
E. Electrical Wiring
Supply cord and/or wiring meets all local codes, National Electrical Code, ANSI/NFPA 70, in the U.S., or Canadian Electrical Code, CSA C22.1, Part 1, in Canada.
Voltage matches listing on rating plate.
Water heater is properly grounded.
62
F. Condensate
Condensate drain is properly installed.
Page 27
Lighting the Water Heater
INSTALLATION INSTRUCTIONS
WARNING: Before operating
this water heater, be sure to read and follow the instructions on the following label, all labels on the water heater, and the “Important Safety Information” section in this manual. Failure to do so can result in unsafe operating conditions that can result in death, personal injury, property damage, and/or product damage.
NOTICE: If you have any problems
reading or following the instructions in this manual, STOP and call a qualified service technician or contractor.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING : If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
OPERATING INSTRUCTIONS
1.STOP! Read the safety information above on this label.
2.Turn off all electric power to the appliance.
3.Do not attempt to light the burner by hand.
4.Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the "OFF" position.
5.Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.
6.Turn the Gas Shutoff Valve located on the outside of the unit counterclockwise to the "ON" position.
7.Turn on all electric power to the appliance.
8.If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
GAS SHUTOFF
VALVE
OPEN CLOSE
TO TURN OFF GAS TO APPLIANCE
1.Turn off all electric power to the appliance if service is to be performed.
2.Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the "OFF" position.
Start/Adjust
63
Page 28
INSTALLATION INSTRUCTIONS
Lighting the Water Heater
Operating Instructions
Read, understand, and follow the safety information listed on the operating label on page 63 and in the “Important Safety Information” section in this manual.
4
Turn on all electric power to the water heater.
The water heater burner will automatically light when there is a demand for hot water.
1
Disconnect all electric power to the water heater.
2
Turn the gas shut-off valve clockwise to the OFF
position. This valve is located on the outside of the water heater. Wait 5 minutes to clear any gas. If you don’t smell gas, proceed to Step 3.
NOTICE: If you smell gas, STOP and
follow the safety instructions listed under B on the operating label or on the front cover of this manual.
WARNING: Do not attempt to light
the burner by hand. Lighting the burner by hand is an unsafe operating condition that can result in death, personal injury, property damage, and/or product damage.
If the water heater burner will not light, turn off
the water heater as described below and call your service technician or gas supplier.
Shutting Off the Water Heater
1
Disconnect all electric power to the water heater.
Start/Adjust
64
3
Turn the gas shut-off valve counterclockwise to
the ON position.
2
Turn the gas shut-off valve clockwise to the
OFF position.
Page 29
INSTALLATION INSTRUCTIONS
The contents on pages 65 through 68 should only be performed by qualified service personnel.
Setting the Water Temperature
WARNING: Improper adjustment,
alteration, service, or maintenance can result in death, personal injury, property damage, and/or product damage.
Maximum Temperature Adjustment by the Main Remote Control (UMC–117)
DANGER: Water temperatures above
125°F (52°C) will result in death and/or severe burns from scalding.
WARNING: Refer to chart below
and the scald potential warnings on page 4 on this manual before making an adjustment. Changing this setting is done at your own risk.
Time/Temperature Relationship in Scalds
Water Time to Produce Temperature a Serious Burn
Priority
Indicator
In-Use
Indicator
(Lit during
operation)
Temperature
Adjustment
LED Display
(Displays
water
temperature
and error
codes)
To change the temperature settings up to 140°F (60°C):
Buttons
ON/OFF
Button and
Indicator
1
T
urn on the remote control.
120°F (49°C) More than 5 minutes 125°F (52°C) 1 1/2 to 2 minutes 130°F (54°C) About 30 seconds 135°F (57°C) About 10 seconds 140°F (60°C) Less than 5 seconds 145°F (63°C) Less than 3 seconds 150°F (66°C) About 1 1/2 seconds 155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
Residential water heater temperatures can be adjusted up to 140°F (60°C). Do not perform the
following adjustment if a setting of up to 140°F (60°C) is not required.
2
Turn off the gas and water to the water heater by closing the shut-off valves.
Start/Adjust
3
Press the UP adjustment button repeatedly until 120°F (49°C) shows in the LED display. Hold the UP button until the “120” on the display starts to blink.
NOTICE: LED display only shows °F.
65
Page 30
INSTALLATION INSTRUCTIONS
Setting the Water Temperature (cont.)
4
While “120” is blinking, press the UP and DOWN adjustment buttons at the same time. “120” will stop blinking.
5
Press the UP or DOWN adjustment button to set the desired temperature.
6
Turn on the gas and water to the water heater by opening the shut-off valves.
To limit maximum water temperature setting to 120°F (49°C):
3
Press the DOWN adjustment button repeatedly until 100°F (38°C) or 85°F (29°C) shows in the LED display. Hold the DOWN button until the number on the display starts to blink.
4
While the number is blinking, press the UP and DOWN adjustment buttons at the same time. The number will stop blinking.
5
Press the UP or DOWN adjustment button to set the desired temperature.
Start/Adjust
66
1
Turn on the remote control.
2
Turn off the gas and water to the water heater by closing the shut-off valves.
6
Turn on the gas and water to the water heater by opening the shut-off valves.
Page 31
Minimum Temperature Adjustment by the Main Remote Control (UMC–117, USC1–117, and USC2–117)
INSTALLATION INSTRUCTIONS
Residential water heater temperatures can be adjusted down to 85°F (29°C), when required.
To change the temperature settings down to 85°F (29°C):
1
Turn on the remote control.
2
Turn off the gas and water to the water heater by closing the shut-off valves.
3
Press the DOWN adjustment button repeatedly until 100°F (38°C) shows in the LED display.
NOTICE: LED display only shows °F.
4
Press the DOWN adjustment button 3 times within 5 seconds. The display will show “85.”
5
Turn on the gas and water to the water heater by opening the shut-off valves.
NOTICE: The maximum flow rate at 85°F
(29°C) is 1.3 gpm (5.0 L/m).
High-Altitude DIP Switch Adjustments
When the water heater is installed above 3,280 ft. (1,000 m), the settings on the DIP switch located on the printed circuit board (PCB) need to be changed. If these settings are not changed, the water heater may not function properly.
NOTICE: If the water heater is installed
under 3,280 ft. (1,000 m) altitude, no action is required.
Verify the altitude that the water heater is installed.
1
Start/Adjust
Turn off the gas and water to the water heater
by closing the shut-off valves. The OFF position is DOWN.
67
Page 32
INSTALLATION INSTRUCTIONS
High-Altitude DIP Switch Adjustments (cont.)
2
Remove the front cover panel on the water
heater.
Dip switch adjustment
3,280 feet (1,000 m)
thru 6,560 feet
5
(2,000 m)
If altitude is above 3,280 ft. (1,000 m) and
below 6,560 ft. (2,000 m), change the third
switch on “DIP 2” to the ON position (UP).
Dip switch adjustment
6,560 feet (2,000 m)
thru 9,840 feet
5
If altitude is above 6,560 ft. (2,000 m) and
below 9,840 ft. (3,000 m), change the fourth
switch to the ON position (UP).
(3,000 m)
Start/Adjust
Dip Switches
Printed Circuit
3
Find DIP Switch 2 located in the top-right
Board (PCB)
portion of the PCB. The switch labeled “DIP 2” is the bottom switch.
As set from factory
4
The factory settings for this switch should all be
in the OFF position (DOWN).
NOTICE: Do not alter any other DIP
switch settings. The manifold pressure will be reduced accordingly.
6
Replace the front cover panel.
7
68
Turn on the gas and water to the water heater
by opening the shut-off valves.
Page 33
Parts Ordering
PARTS REPLACEMENT
WARNING: For your safety, do not
attempt to disassemble, repair, or replace any portion of this unit. Refer all repairs, service, and/ or adjustments to qualified service personnel.
Address all parts orders to the distributor or store where the water heater was purchased. All parts orders should include:
Direct-Vent Gas Components
1. The model and serial number of the water
heater from the rating plate.
2. Specify the gas type (natural or LP) as marked
on the rating plate.
3. Parts description (as shown below) and number
of parts desired.
Ref # Description
1 Control Board
2 Gas Valve
3 Burner Assembly
4 Blower Motor
5 Burner Manifold
6 Gas Inlet Connector
7 Water Control Body
8 Water Inlet Connector 3/4"
9 Drain Relief Valve
10 Hot Outlet Connector
11 Remote Control Terminal Block
12 Neutralization kit
13 Air Intake Connector
14 Flue Connector
15 Front Cover
Parts
69
Page 34
PARTS REPLACEMENT
Parts Ordering (cont.)
Outdoor Gas Components
Parts
Ref # Description
1 Control Board
2 Gas Valve
3 Burner Assembly
4 Blower Motor
5 Burner Manifold
6 Gas Inlet Connector
7 Water Control Body
8 Water Inlet Connector 3/4"
9 Drain Relief Valve
10 Hot Outlet Connector
11 Remote Control Terminal Block
12 Neutralization kit
13 Front Cover
70
Page 35
NOTES
71
Page 36
NOTES
72
Loading...