1. General information about the measuring equipment .................................................................... 3
2. Technical data ..................................................................................................................................... 4
3. Model variants ..................................................................................................................................... 5
4. Program versions ............................................................................................................................... 6
Connection example M1 ................................................................................................ 10
Connection example M2, M3 ......................................................................................... 11
8. Start up guide ......................................................................................................................................12
9. Operation
Displays, buttons and LEDs ...................................................................................................... 13
1. General information about the measuring equipment
Autodos M is an equipment intended for measurements and dosage of chemicals in swimming pools. The apparatus is equipped
with 1-3 channels (depending on model) to measure levels of chlorine (free chlorine and bound chlorine), redox and pH.
This manual covers all combinations. Please read the whole manual to get a full picture of how the system works and all its
setting possibilities.
Autodos M is delivered in two different parts: one measuring and control unit Autodos and one complete electrode kit.
• Autodos: include a measuring- and control unit, connectors, and this systems manual. The control unit is preprogrammed with factory settings for each respective model, but individual changes are possible to make by the user.
It is also possible to enter different access codes to avoid accidental changes.
• Electrode kit: include electrodes (different electrode types depending on which measurements and results you wish to
present), calibration liquids, connectors for the electrodes, and manual for the electrodes.
Autodos M´s properties
• Measures and controls pH (base or acid dosage) and chlorine in the forms of redox, free chlorine and bound chlorine.
With regards to bound chlorine, the total level of chlorine is measured and the display shows the value for bound chlorine.
This is calculated by Total chlorine – Free chlorine = Bound chlorine.
• Autodos uses two point calibration for each measuring cannel to ensure optimal measurements.
• Has a separate galvanic part for each electrode entry point.
• Warns for uidity errors in the valve, dosage errors and measurement values outside preset boundaries.
• Continuously shows the pool water’s current pH-value, free chlorine, bound cholrine and redox in clear LED-displays.
By pressing different buttons, the displays can also be made to show other values, for example ow and temperature.
pH-regulator
pH adjustment can be used according to:
• Manuel off.
• Automatic regulation against set value as per:
a. On/off control*.
b. Pulse width control
c. Frequency control P, PD, PI or PID regulator 10–180 pulses/min.
d. Current output control P, PD, PI or PID regulator 4–20 or 0–20mA.
• Manuel dosing:
a. On/off control*: dosing relay pH always On.
b. Pulse width control: dosing relay always On.
c. Frequency control: maximum deection (10–180 pulses/min).
d. Current output control: maximum deection (20mA).
(CO2 dosing equipment requires on/off or pulse width control).
Control is programmed in conguration mode.
Acid dosing or alkali dosing On/Off is programmed in conguration mode.
Chlorine regulator
Free and combined chlorine works the same and can be used according to:
• Manuel off.
• Automatic regulation against set value:
a. On/off control*.
b. Pulse width control
c. Frequency control P, PD, PI or PID regulator 10–180 pulses/min.
d. Current output control P, PD, PI or PID regulator 4–20 or 0–20mA.
• Manuel chlorine dosing:
a. On/off control*: dosing relay chlorine always On.
b. Pulse width control: dosing relay always On.
c. Frequency control: maximum deection (10–180 pulses/min).
d. Current output control: maximum deection (20mA).
Control is programmed in conguration mode.
1–3 current outputs (free chlorine, redox, combined chlorine and pH) 0–20 mA or 4–20 mA are programmed in conguration
mode (individually for each channel). Current outputs normally follow the measurement value, but can also be congured so that
the control value is followed thereby allowing current output control.
* default from fabric
MA60-10E
MA60-10E
3
Page 4
ENGLISH
Autodos M
Autodos M
Separate high and low alarms (limits can be set) are indicated via ashing alarm LED(s) and a common alarm relay.
The alarm is shown as “Lo” or “Hi” on display 1–3 while the Reset button [15] is held depressed.
pH value outside of limit values stops chlorine dosing. This is indicated by a ashing AUTO LED on the chlorine channels and
the alarm text “PHF”. Chlorine dosing is stopped until the pH value has returned to a permitted value.
Flow alarm (PNP potential-free connector/turbine sensor that can be deactivated in conguration mode) is indicated via alarm
LED and alarm relay in alarm mode. The registered alarm is also shown as “FLo” on display 1–3 while the Reset button [15] is
held depressed. There is no automatic dosing during stop in ow.
All alarms have a 5-second delay, except for ow alarm, high alarm and low alarm. For the high and low alarms, delay can be
set (in Setup) between 5 and 600 seconds. The ow alarm delay can be set (in Setup) between 0 and 30 minutes.
Alarm for dosing error can be selected in conguration mode (time in minutes > 0).
Dosing error is indicated (if dosing time is selected in conguration mode) via ashing alarm LED(s) and a common alarm relay.
The alarm is shown as “doS” on display 1–3 while the Reset button [15] is held depressed.
Dosing is stopped until the alarm is reset. The dosing time counter is always zeroed with a reset.
A dosing error alarm is generated in the following conditions
• On/Off dosing, Pulse width dosing, Frequency dosing, Control output-controlled dosing :
An alarm is triggered if dosing is continual for a longer time than the specied max. time in minutes (1-60 as specied in conguration mode). An alarm is also triggered if manual dosing is too long.
Electrode connection, total chlorine4–20mA current input
StandbyPNP, approx. 16 VDC, approx. 5 mA
LevelPNP, approx. 16 VDC, approx. 5 mA
Alarm output relayClosing/opening 1 A resistive load
Maximum load, current outputs400 Ohm
Enclosure ratingIP54
Ambient temperature5–40 ºC
Nominal ow (min–max)30 (20–60) l/h
MA60-10E
MA60-10E
4
Page 5
Autodos M
Autodos M
3. Model variants
Also see point 2 page 12.
M1
ENGLISH
ENGLISH
M2
M3
Flow
MA60-10E
MA60-10E
5
Page 6
Autodos M
Autodos M
ENGLISH
ENGLISH
M1M2
Flow
adjustment
Start module
Flow measurement
Flow switch
Water tempera-
ture
Water sample outlet
Electronic
unit
Electrode:
Redox,
Total chlorine,
pH or Free chlorine
Module 2
Water out
Water in
Flow
adjustment
Start module
Flow measurement
Flow switch
Water tempera-
ture
Water sample outlet
Electronic
unit
Free chlorine
electrode
Module 2
pH electrode
Module 3
Water ut
Water in
Elektroder
Redox
CTE 1
Total chlorine
pH
4. Program versions
Ver. 5.3: (2011-04-29)
PB200
Free chlorine
CLE 3
Free chlorine
M3
Flow
adjustment
Start module
Flow measurement
Flow switch
Water tempera-
ture
Water sample outlet
Electronic
unit
Free chlorine
electrode
Module 2
Total chlorine
electrode
Module 3
pH electrode
Module 4
Water out
Water in
5. Reservation
We retain the right to modify the functionality of Autodos M without prior notice. We accept no liability for any errors in this
manual or any consequences stemming from Autodos M malfunction.
We strive to keep the manual as free from errors as possible. We would therefore be grateful to have any errors or ambiguities
pointed out to us so we can correct them.
MA60-10E
MA60-10E
6
Page 7
ENGLISH
Autodos M
Autodos M
ENGLISH
6. Safety
To prevent direct contact between the chemicals, separate the chlorine dosing point and the acid/alkali dosing point with at least
500 mm, always ACID BEFORE CHLORINE, refering to the installation example on pages 8–9.
Lock the dosing pumps to the circulation pump using the motor guard or the ow switch.
For best results, use a photometer during calibration.
Proper installation and care is required to prevent invalidation of the warranty.
“Persons (including children) with limited physical or mental capabilities must not use the device without instructions on how to
use it in a safe manner,” as per IEC 60335-1.
7. Installation
General
The system can be installed at any time point without consideration to the life span of the electrodes as these are delivered
separately and can even be delivered at a later point in time.
Install Autodos M at a dry and vibration-free location, against rm, at support and accessible for support and reading.
The display must be well visible and the buttons easily accessible.
The ow cell should be positioned as close to the monitoring point as possible to prevent unnecessarily long response times.
Note the direction of ow.
Check that the electrode kit complies to your Autodos M unit, see point 2 page 12.
If the position of the Autodos puts it at risk of freezing, the ow cell modules must be emptied of all water and the electrodes
must be stored frost-free standing in water (save the electrode packaging for this purpose).
Note! When installing Autodos M with free chlorine electrode in pools where organic chlorine was previously used,
all water must be drained and replaced with new water. This because the cyanuric acid content in the pool water from orga-
nic chlorine (Trichlor or Dichlor) produces a signicantly higher chlorine value in a DPD no. 1 test. This makes correct calibration
impossible.
Installation, pipes
The outlet from the ow cell should be kept free from pressure, e.g. by leading outlet water to an equalization tank or a drain.
For installations in which the ow cell outlet cannot be routed without pressure to a drain or equalization tank, the measurement
water should be sampled after the lter and the return of the pump suction line.
Connections only need to be tightened by hand.
Monitoring and dosing points are most easily made with saddle clamps.
In order to prevent air from being mixed in with the measurement water (which could affect the measurement value), the
measurement connection on the pipes should not sit at the highest point.
MA60-10E
MA60-10E
7
Page 8
Autodos M
Autodos M
Installationsexempel
Installation example 1: Autodos M1 - chlorine
ENGLISH
ENGLISH
Prelter
Fresh water
lling
Chlorine dosing
Chlorine
PC
Autologger
Equalization
tank
Jet Swim
Lighting Lighting
Filter
Pump
Overow gutter
Inlet
Electric heater
Drain
Check
valve
Installation example 2: Autodos M1 - acid/alkali
PC
Autologger
Acid/alkali dosing
Alt. A
Acid/alkali
Alt. B CO2 dosing
Prelter
Fresh water
lling
Scale
Equalization
tank
Jet Swim
Lighting Lighting
Filter
Pump
Overow gutter
Inlet
Electric heater
Check
valve
MA60-10E
MA60-10E
Drain
8
Page 9
Autodos M
Autodos M
Installation example 3: Autodos M2
PC
Autologger
Chlorine
dosing
Chlorine
Acid/alkali dosing
Alt. A
Acid/alcali
Alt. B CO2 dosing
Jet Swim
Lighting Lighting
ENGLISH
ENGLISH
Overow gutter
Inlet
Prelter
Fresh water
lling
Scale
Equalization
tank
Installation example 4: Autodos M3
PC
Autologger
Chlorine
dosing
Chlorine
Acid/alcali
Alt. A
dosing
Filter
Pump
Jet Swim
Lighting Lighting
Electric heater
Drain
Overow gutter
Inlet
Check
valve
MA60-10E
MA60-10E
Prelter
Fresh water
lling
Acid/alcali
Alt. B CO2 dosing
Scale
Equalization
tank
Filter
Check
valve
Electric heater
Pump
Avlopp
9
Page 10
~230VACFlow/Temp
CTE
Dosing
Redox
pH
35
Autodos M
Autodos M
Installation, electrics
Electrical installation must only be carried out by an authorized electrical installation technician.
Electrical installation must be performed after pipe installation is complete.
The equipment must be permanently grounded and monitored by a residual current device (RCD) with a maximum leakage
current of 30 mA.
The equipment should be supplied via an additional 2-pin switch.
Inputs/outputs for cables as per gure below.
CLE
PB200
View from below
The following example shows how connections are to be made
ENGLISH
ENGLISH
Connection example
Connection example - Autodos M1
Current input free chlorine (4–20mA)
Flow meter (white cable)/ – GND current outputs
Current output 1 (pH) 4–20mA (0–20mA)
Current output 2 (redox/chlorine) 4–20mA (0–20mA)
Flow meter (green cable)/NPN in ow switch
PNP in, level switch (alarm upon closed input)
Flow meter (brown cable)/16 VDC PNP input
–GND Temperature sensor
Twin-cable communication with PC
GND free chlorine
24 VDC
PNP in STDBY
Temperature sensor
PB200 chlorine electrode
Chlorine electrode
GND
V–
V+
Connection of ProMinent CLE 3-mA 10ppm
CLE2.2
Terminal 1 (+) to terminal 26
Terminal 2 (–) to terminal 27
Accessories
Modelbus RTU
9600 band, Parity None
Example D:
Current output controlled
dosing pump
Example A:
On/Off
controlled
dosing pump
Acid/alkali dosing/chlorine dosing (free)
de-energized state
MA60-10E
MA60-10E
230 VAC L
Alarm (common)
Example C:
Frequency
controlled
dosing pump
10
Page 11
Autodos M
Autodos M
Connection example - Autodos M2
Current input free chlorine (4–20mA)
Flow meter (white cable)/ – GND current outputs
Current output 2 (redox/chlorine) 4–20mA (0–20mA)
Current output 1 (pH) 4–20 mA (0–20 mA)
GND free chlorine
24 VDC
PB200 chlorine electrode
Chlorine electrode
GND
V–
V+
CLE2.2
Connection of ProMinent CLE 3-mA 10ppm
Terminal 1 (+) to terminal 26
Terminal 2 (–) to terminal 27
Accessories
Modelbus RTU
9600 band, Parity None
ENGLISH
ENGLISH
Flow meter (green cable)/NPN in ow switch
PNP in, level switch (alarm upon closed input)
Flow meter (brown cable)/16 VDC PNP input
Twin-cable communication with PC
Chlorine dosing (free)
Connection example - Autodos M3
Current input combined chlorine (4–20mA)
Flow meter (white cable)/ – GND current outputs
Current output 1 (pH) 4–20mA (0–20mA)
Current output 2 (combined chlorine) 4–20mA (0–20mA)
Current output 3 (free chlorine) 4–20mA (0–20mA)
Flow meter (green cable)/NPN in ow switch
PNP in, level switch (alarm upon closed input)
Flow meter (brown cable)/16 VDC PNP input
PNP in STDBY
–GND temperature sensor
Temperature sensor
230 VAC L
Acid/alkali dosing
230 VAC L
Alarm (common)
de-energized state
GND combined chlorine
24 VDC
GND free chlorine
Current input free chlorine (4–20mA)
24 VDC
PNP in STDBY
–GND temperature sensor
Temperature sensor
Twin-cable communication with PC
Example D:
Current
output
controlled
dosing pump
Example A:
On/Off
controlled
dosing pump
Example C:
Frequency
controlled
dosing pump
Connection of ProMinent CTE 1-mA 10ppm
PB200 chlorine
electrode
Chlorine electrode CLE2.2
GND
V–
V+
Terminal 1 (+) to terminal 29
Terminal 2 (–) to terminal 30
Connection of ProMinent CLE 3-mA 10ppm
Terminal 1 (+) to terminal 26
Terminal 2 (–) to terminal 27
Accessories
Modelbus RTU
9600 band, Parity None
Example D:
Current
output
controlled
dosing pump
MA60-10E
MA60-10E
M3 - free chlorine, redox, pHM3 -
230 VAC L
Acid dosing
230 VAC L
Alkali dosing
Chlorine dosing (free)
230 VAC L
Alarm (common)
de-energized state
230 VAC L, Chlorine
dosing (combined)
Chlorine dosing (free)
de-energized state
free chlorine, combined chlorine, pH
230 VAC L
Acid/alkali dosing
230 VAC L
Alarm (common)
11
Example A:
On/Off
controlled
dosing pump
Example C:
Frequency
controlled
dosing pump
230 VAC N
230 VAC L
Page 12
ENGLISH
Autodos M
Autodos M
ENGLISH
8. Startup guide
This is a short check list with the different steps needed to get started with Autodos. References are given to the sections in the
manual relevant for each step. Still, read through the whole manual to have a complete picture of how the system works and all
its setting possibilities.
1. Install the Autodos unit, see section 7 Installation pipes.
2. Check that you have the correct electrode kit for your valve, see below.
3. Install the electrodes and the installation kit with connector details in the corresponding measuring cell in the valve, see
page 6. An instruction showing how the details of the installation kit shall be connected is included in each respective kit.
NOTE! The electrodes can not be dry or be exposed to frost or quick temperature changes. For more information about the
electrodes, please see the instruction “Handling and care of electrodes” which is enclosed with the electrode kit.
4. Connect the electrode connectors for the water ow for measurements and check that water ows through the valve.
5. Open the faucets for the water ow for measurements and check that water ows through the valve.
6. Turn on the voltage to Autodos M. After a startup time of 60 seconds, the values are shown in each respective channel/dis-
play, see section 9: Operation, page 13.
7. Basic settings, electrodes.
Autodos M has preset factory settings for all types of electrodes that normally corresponds to the electrode combination in
the supplied electrode kit. To check/change electrode type, see further under Systems conguration, pages 21-26.
8. Basic settings, dosage type.
Autodos M can control the dosage equipment either via on/off- frequency- , pulse width- or current control. Which to choose
depends on what dosage product that shall be connected. To check or change dosage type, see further for the specic models under Electrode specic conguration, pages 26-29.
9. Adjust the ow of water for measurement to 30-40 liters/hour with the adjustment screw on the start module. Press the
button ↑ Flow [9] and keep pushing and the current ow is shown in the right display.
10. Calibrate electrodes, see section 10: Calibration, pages 30-32.
11. Let Autodos M run without dosage for around one hour with correct ow of water after the calibration have been done. This is
because the electrodes need to adjust to the measuring water in order for the signals to be stable. Read more under section
9: Handling/choice of dosage, page 15. Normal operating mode: diode “Auto” is lit.
12. Dosage times and response times depends solely on pool volume, turnaround ratio, dosage type, and dosage ratio.
Concentrations of chemicals and dosage products also affects. See section 9: Handling/Settings recommended values,
pages 17-18.
13. Alarm; diodes with ashing lights show active or retset alarms. Pushing the button Reset [15] will shows the type of alarm.
Diodes with a steady red light are acknowledged/active alarms, see section 9: Handling/Alarm diodes, page 20.
If diode “Auto” ashes on the chlorine/redox channel, the pH-value is outside the alarm limits and no dosage is done until
the pH-value is restored within given limits.
14. Maintenance and care; see section 11: Care, page 32. All reference measurements of water quality shall be done with a
digital photometric measuring tool. The measuring water shall always be taken from the draining faucet on Autodos M´s
prelter unit.
MA60-10E
MA60-10E
12
Page 13
ENGLISH
Autodos M
Autodos M
ENGLISH
9. Operation
Displays, buttons and LEDS – general
The panel is divided into 4 groups. Group 1 (on the left) handles all activities and the others show values and handle limit and
value settings.
Group 1 Group 2 Group 3 Group 4
Button
no..
0Calibration1
1Function selection2
2Level –2
3Level +2
4Function selection3
5Level –3
6Level +3
7Function selection4
8Level + / Temp4
9Level – / Flow4
10Authorization1
11–14Activity1
15Reset1
FunctionGroup
The picture shows one example of all Autodos variants.
Displays
Depending on the Autodos M model variant, the values of free chlorine, combined chlorine and/or redox and pH are indecated in
one, two or three separate displays (each with three digits).
The displays can also show simple text messages; see the chapter Text display on page 16.
In some displays different values can be shown in the same eld but then requires certain keystrokes, see page 14.
Under he actual display arrows and explanatory text are found. The position of the decimal point in the display conrms which
type of value is indicated.
The display to the far right can also be used to show ow and temperature.
The displays displays parameters within the following limits:
Free chlorine: –.99–9.99 mg/l (ppm)
Combined chlorine: –.99–9.99 mg/l (ppm)
pH: 4.00–11.0
Redox –99.–999. mV
Temperature: 10 – 40°C
Buttons
Each button has a unique number in the top right-hand corner. In this manual, reference is made to this number with [ ] and the
buttons text reference with bold style e.g. Reset [15].
Further on in this chapter we describe how and what buttons to press in which modes.
LEDs
Function activation is indicated with a green LED and all types of alarms are indicated with a red LED.
Read more about each LED indication on page 15.
MA60-10E
MA60-10E
13
Page 14
ENGLISH
Autodos M
Autodos M
ENGLISH
Authorization
To avoid unintentional changes to settings and unauthorized use, two authorization codes can be set, see below.
NOTE! Autodos M has no authorization code set when delivered. When necessary this must be activated.
AuthorizationExplanation
Normal modeNo settings can be altered; only Reset is possible
Authorization code 1Set values, alarm limits and control parameters can be changed. Calibration is also possible.
Authorization code 2All available changes, including system conguration, are possible.
Activate authorization
If no codes are set, authorization level 2 is accessed automatically when the Code button [10] is pressed. The display then
shows “Cd2”.If authorization code is required “Cd–” is showing.
When the Code button [10] is held depressed, the opening code can be entered using the buttons indicated below:
Autodos M3: Buttons 0–9
Autodos M2: Buttons 0 and 4–9
Autodos M1: Buttons 0 and 7–9
If the entered code is the same as opening code 1 you access authorization level 1 and if the entered code is the same as opening code 2 you access authorization level 2 when the Code button [10] is released. This is indicated via the “Code” LED being
illuminated for authorization level 1 and ashing for authorization level 2..
Set/select authorization code
The opening code can only be changed in authorization level 2. If you forgot the code for authorization level 2, it can be displayed by pressing Code [10] during the start-up sequence (after the countdown of seconds has begun).
Enter the opening code (for authorization level 1 or level 2):
2. Enter calibration mode, with the button Cal [0], diode “Active” light steadily.
3. Hold the button Code [10] depressed and enter the opening code with buttons [0] – [9]. Reset [15] is used to clear the display
and enter up to six digits for the code. The display shows “Cd1” when the button Code [10] is pressed the rst time. “Cd2” is
shown the next time the button is pressed. The display then switches back and forth each time the button is pressed. The text
indicates which code (for authorization level 1 or 2) should be entered.
View/change set values
Press and hold the button Set value [13] (or the button Set alk/Cl [13]) to display the set value
- for free chlorine on display 1
M3
M2
M1
- for combined chlorine/redox on display 2
- for pH on display 3
To change the set value, hold the button [13] depressed while pressing ↑ or ↓ under the relevant display.
Press and hold the button Set value [13] to display the set value
- for chlorine/redox on display 1
- for pH on display 2
To change the set value, hold the button depressed while pressing ↑ or ↓ under the relevant display.
Press and hold the button Set value [13] to display the set value.
To change the set value, hold the button depressed while pressing ↑ [9] or ↓ [8].
View/change alarm limits
HIGH
ALARM
LOW
ALARM
Press and hold the button Alarm high [12] to display the high alarm limit value on the relevant display.
To change the limit value, hold the button depressed while pressing ↑ or ↓ under the relevant display.
At least authorization level 1 is required in order to make changes.
Press and hold the button Alarm low [14] to display the low alarm limit value on the relevant display.
To change the limit value, hold the button depressed while pressing ↑ or ↓ under the relevant display.
At least authorization level 1 is required in order to make changes.
MA60-10E
MA60-10E
14
Page 15
Autodos M
Autodos M
Showing other information on the display
ENGLISH
ENGLISH
Show
Uncalibrated
values
Show
Flow
Show
Temperature
Show
Version
Show
Serial number
Press and hold the Set value [13] (or Set Alk/Cl [13]) and Alarm low [14] buttons simultaneously to show
uncalibrated values on the relevant display.
Press and hold the ↑ Flow button [9] to display ow in litres per hour.
Press and hold the ↓ Temp button [8] to display temperature (in °C).
Press and hold the Alarm high [12] and Alarm low [14] buttons simultaneously to display the program
version.
Press and hold the Function [11] (or Set Acid [11]) and Alarm high [12] buttons simultaneously to display
the factory-programmed serial number.
Dosing selection
Press the Select function button [1], [4] or [7] to switch dosing selection between Off and Auto.
Select
Function
Off No dosing
Auto Automatic dosing based on set parameters (normal setting)
Dosing Indicates dosing (including when there is an error; stopped if there is a dosing time error)
Dosing can be deselected in conguration mode.
To access manual dosing: press and hold the Select function button depressed, then press Set value [13]
button also. (The Set value button [13] is called Set alk/Cl [13] on M3 with redox.)
Deactivate manual dosing by pressing the Select function button.
Other buttons
Press and hold the Reset button [15] to display triggered alarms for the respective channel in the form of a
Reset
Cal.
↑ ↓
brief text. If the button is depressed for less than about one second, the alarms are reset and the common
alarm relay is de-energized. The dosing time counter is always zeroed with a reset.
Press the Cal. button [0] to page in calibration mode between Off – Active – Adjust ...
This is indicated via unlit LEDs (Off), illuminated Active LED or illuminated Active and Adjust LEDs.
(Exit calibration mode by pressing and holding Cal. [0] until the LEDs go out.)
Use the arrow buttons to adjust set values, limits and calibration values on the relevant display.
If an arrow button is held in, a “fast forward” function engages after about one second.
LEDs – dosing indicators
Off Dosing of pH-regulating or chlorine-regulating agent is deactivated.
Auto Dosing of pH-regulating or chlorine-regulating agent is regulated automatically.
Dosing Dosing of pH-regulating or chlorine-regulating agent is in progress.
If neither LED “Off” nor “Auto” is illuminated, then manual dosing is selected. If dosing does not occur at this time (the LED
“Dosing” is not lit), then dosing was deselected at setup. It may also be deactivated due to excessively long dosing time if this
function has been selected. If this is the case the “Alarm” LED will ash also (or be illuminated).
If the pH value is outside of alarm limits, there is an alarm on the chlorine channel if chlorine dosing is active.
Chlorine dosing is stopped until the pH values are once again within permitted limits.
The alarm is indicated via a ashing “Auto” LED on the chlorine channel and the alarm test “PHF” at Reset..
LEDs – alarm indicators
Low ow Insufcient ow in the ow cell.
Alarm High alarm, low alarm, dosing error or ow error.
If the “Alarm” LED ashes, there is an error that has not been cleared. If an error has been cleared but remains active, the LED
is illuminated with a steady glow.
MA60-10E
MA60-10E
15
Page 16
ENGLISH
Autodos M
Autodos M
ENGLISH
LEDs – indicators for calibration in progress
ActiveCalibration in progress; calibration of pH7, pH9 and chlorine zero points possible.
AdjustCalibration in progress; calibration of chlorine values possible.
If the “Active” LED ashes, it indicates you are in conguration mode (see the chapter System conguration on page 21).
To exit conguration mode, press and hold the Cal. button [0] until the “Active” LED stops ashing.
dEL SEC # # #restart performed, # # # indicates the time before start delay is nished.
Error codes
See section 12: Troubleshoting, sid 32.
Start-up sequence
When Autodos M is started up, a text (see below) is shown. The three digits in the text indicate how many seconds are left until
the end of the start-up sequence. The waiting time during start-up is intended to avoid problems with alarms being triggered
because the measurement values have not had time to stabilize, etc. (The start delay can be bypassed by pressing and holding
the Reset button [15] for about one second.)
Set value1.000.507.40740
Low alarm0.400.006.80600
High alarm2.001.007.80800
Adjusting set value – General
Set values etc. that have been set are saved in EEPROM approx. 10 seconds after they are entered. The values are saved
alternatingly in two separate memory areas to avoid errors due to loss of power during the saving phase.
Adjusting set value – Chlorine regulation (free chlorine)
Set value adjustment for free chlorine regulation is carried out by pressing and holding the Set value button [13].
The selected chlorine set value is then shown in the display.
To change the set value, press and hold the button while pressing ↑ or ↓ under the display. Pressing and holding an
arrow button for about one second triggers a “fast forward” function until the button is released.
Frequency controlled chlorine regulation (free chlorine)
Chlorine set value
Dosing
range
approx 30 pulses/min
approx 70 pulses/min
Chlorine actual value
Chlorine actual value
Max. chlorine dosing
(approx. 100 pulses/min)*
Dosing range indicates the interval within which dosing is steplessly changed (pband) between 0 pulses/min and max. number
of pulses/min. Adjustment of dosing range size is done in electrode specic conguration mode (see separate chapter).
If the actual value (in gure) is greater than the chlorine set value, there is no chlorine dosing (0 pulses/min).
If actual value = (set value - dosing range) there is full dosing (approx. 100 pulses/min). In the range between the two, dosing is
modied based on the actual value. For example, if the actual value is in the middle of the dosing range, half-dosing is carried
out (approx. 50 pulses/min).
Adjusting set value – Chlorine regulation (combined chlorine)
The procedure is the same as that for free chlorine, except that the arrows [5] and [6] under display 2 are used and regulation is
done against the measurement value for combined chlorine.
* Default value. Adjustable to max. 180 pulses/minute
MA60-10E
MA60-10E
17
Page 18
bas-dosering
ärvärde
syra-dosering
doser-område
max bas-dos (ca 100 pulser/min)
ärvärde
max syra-dos
ca 30 pulser/min
ca 60 pulser/min
ENGLISH
Autodos M
Autodos M
ENGLISH
Adjusting set value – pH regulation
Set value adjustment for pH regulation is carried out by pressing and holding the Set value button [13].
The selected pH set value is then shown in the display. To change the set value, hold the button depressed while pressing
↑ or ↓ under display 3. Pressing and holding an arrow button for about one second triggers a “fast forward” function until the
button is released.
The gures below show dosing with both pH-elevating (alkali) and pH-lowering (acid) agent. The principle is the same, but the
direction is reversed.
On/Off controlled pH regulation
Acid set value
Alkali set value
Frequency controlled pH regulation
Acid set value
Acid dosing
Max. acid dosing
Actual value pH
Alkali dosing
pH actual value
Dosing range
P-band* indicates the range within which dosing is steplessly changed from 0 to maximum dosing. In the example above,
acid is dosed when the actual value (= pH value) is greater than the set value. Acid and alkali are dosed when the actual value
is less than the alkali set value.
At maximum dosing, the dosing pump gives max. frequency* strokes/minute.
Presume there is acid dosing (pH value = 7.54, acid set value = 7.40), P regulation (P-band = 0.20) and frequency dosing
(max. frequency = 50 strokes/minute). Dosing is then calculated as follows:
Does = (pH actual value – acid set value) / P-band x Max. frequency = (7.54–7.40) / 0.20 × 50 = 35 strokes/minute.
If the dose as calculated above is negative, 0 strokes/minute is dosed. If the dose is greater than 50, then 50 strokes/minute
is dosed.
* set in “Electrode specic conguration”.
** Default value. Adjustable to max. 180 pulses/minute
MA60-10E
MA60-10E
Alkali set value
approx. 30 pulses/min
approx. 70 pulses/min
Max. alkali dosing
(approx. 100 pulses/min)**
18
Page 19
börvärde
gränsvärde för höglarm
ärvärde
larmtidpunkt
börvärde
gränsvärde för låglarm
ärvärde
larmtidpunkt
Autodos M
Autodos M
Setting high alarm
ENGLISH
ENGLISH
Actual value
Alarm time point
Set value
High alarm setting is done by pressing and holding the Alarm high button [12]. The high alarm limits for free chlorine, combined
chlorine and pH are then displayed in the measurement value windows.
To change the limit, press and hold the button while pressing ↑ or ↓ for the relevant channel.
Pressing and holding an arrow button for about one second triggers a “fast forward” function until the button is released.
High alarm limits can be adjusted within the intervals:
free chlorine -.99 – 9.99 ppm
combined chlorine -.99 – 9.99 ppm
pH -.99 – 9.99
High alarm limit value
Setting low alarm
Actual value
Set value
Alarm time point
Low alarm setting is done by pressing and holding the Alarm low button [14]. The low alarm limits for free chlorine, combined
chlorine and pH are then displayed in the measurement value windows.
To change the limit, press and hold the button while pressing ↑ or ↓ for the relevant channel.
Pressing and holding an arrow button for about one second triggers a “fast forward” function until the button is released.
Low alarm limits can be adjusted within the intervals:
free chlorine -.99 – 9.99 ppm
combined chlorine -.99 – 9.99 ppm
pH -.99 – 9.99
Low alarm limit value
MA60-10E
MA60-10E
19
Page 20
ENGLISH
Autodos M
Autodos M
ENGLISH
Alarm diodes
The alarm diodes indicate an alert with a ashing light. The alarm relay is an alternating contact free from electric potential.
It alternates when the diode is ashing (this means that a shut off unit indicates an alarm). Upon reset/acknowledgement of
alarm, the alarm relay alternates back but the alarm diode continues to be lit if the alarm is still active or is shut off if no alarm is
active. Indications are made for low alarms, high alarms, dosage errors and ow errors.
Dosing is affected by alarm as follows:
Flow error stops all dosing (starts when ow is correct)
Low alarm pHstops chlorine dosing (starts when value is within limits)
High alarm pHstops chlorine dosing (starts when value is within limits)
Low alarm redox / chlorineno effect on dosing
High alarm redox / chlorineno effect on dosing
Low alarm free/combined chlorineno effect on dosing
High alarm free/combined chlorineno effect on dosing
Dosing error pHstops all dosing (starts after Reset)
Dosing error free/combined chlorinestops chlorine dosing (starts after Reset)
Alarm level switchno effect on dosing
All alarms have a 5-second delay
Alarm delay
The high and low alarms have a delay of 5–600 seconds (set in electrode-specic conguration).
The ow switch alarm has a delay of 0–30 minutes (set in system conguration).
This is how the alarm delay works
• Delay time is counted up when an “alarm condition” applies.
• Delay time is counted down when an “alarm condition” does not apply.
• “Alarm” is activated (LED ashes) when delay time has reached the set delay time limit.
• “Alarm” is deactivated when the alarm is reset with the Reset button [15] and when delay time has been counted down to zero.
Alarm relay delay
The alarm relay has a delay of 0–30 minutes (set in system conguration). Function as follows:
• The delay time is counted up when there is an alarm that has not been reset and when the alarm delay time has not been
zeroed.
• The delay time is reset when it is not counted up (as per condition above).
• The alarm relay is activated when the delay time has reached the set delay time limit.
• Reset [15] deactivates the alarm relay and resets the delay time.
Alarm reset
Alarm reset is carried out by pressing and holding the Reset button [15] for about one second until the LEDs stop ashing (and
the alarm relay is de-energized).
While the Reset button [15] is held depressed, the display(s) show text indicating which alarms were active when the button was
pressed (see chapter Troubleshoting on page 32, there you nd all alarm codes and what they mean).
If several alarms are active, these are displayed at a 1-second interval.
The acknowledged, non-active alarms disappear when the button is released. Pressing the button again will display the
remaining active alarms.
Reset is not possible while Autodos M is in calibration mode.
The dosing time counter is always zeroed with a reset.
Showing uncalibrated values
Display of the factory-calibrated values (as if no calibration was carried out since delivery from the factory) can be carried out by
pressing the Function [11] and Alarm low [14] buttons simultaneously (also works during calibration).
NOTE: On Autodos M3 with acid/alkali dosing, these buttons are called Set acid [11] and Alarm low [14].
The function is a good troubleshooting aid if the electrodes are not functioning normally.
This function helps troubleshooting if the electrodes do not work as intended.
MA60-10E
MA60-10E
20
Page 21
ENGLISH
Autodos M
Autodos M
ENGLISH
Systems conguration
General
In the cases where another setting than the pre-programmed factory settings is desired, conguration mode needs to be
entered. To enter conguration mode, authorisation level 2 must be activated with a code and calibration mode shall be activated.
(No access code is programmed in factory settings.)
The systems conguration consists of two parts: Basic functions with shared settings and Electrode specic conguration
for the respective channel settings.
Enter conguration mode
Press the button Code [10], enter the opening code. Release the button. The diode “Code” ashes as conrmation.
Press the button Cal. [0] to enter conguration mode. The diode “Active” illuminates as conrmation.
There are different conguration modes depending on the Autodos model used, but all have a common mode where entered
settings affect the basic functions and one mode with specic settings for the respective electrodes.
Conguration of basic functions
Proceed as follows to congure all channels:
Model Autodos M3 - free chlorine, redox, pH: press the buttons Set acid [11] + Reset [15].
On all other models: press the buttons Function [11] + Reset [15].This is indicated via the text “SEt UP” and the “Off” and “Auto” LEDs being unlit.
To exit conguration, press the Cal. button [0] or scroll past the last line.
The following can be changed in the common conguration; see relevant model pages 22–26.
Autodos M1
Select the line for which you want to change the setting on by pressing Alarm high [12] or Alarm low [14] button.
When the button Alarm high [12] or Alarm low [14] is held depressed, the display shows the actual line number.
When the buttons are released, the display shows either a text indicating which setting can be changed or a numeric value.
To change a text or value, press ↑ or ↓ .
The selected conguration type is indicated via one of the following texts: ”SEt”, ”FCL”, ”ACi” or ”bAS” depending on variant.
Autodos M2 and M3
Select the line for which you want to change the setting on by pressing ↑ or ↓ under display 2.
When the arrow button is held depressed, display 3 shows the actual line number and display 2 shows the selected congu-
ration type (e.g. “SET” “-01”).
When the buttons are released, display 2 shows a text indicating which setting can be changed and display 3 shows a text or
a numeric value.
To change a text or value, press ↑ or ↓ under the relevant display.
-08SbyThe Sby input blocks all dosing plus the alarm relay.
rEL*Activates the alarm.
nonDoes not activate the alarm.
ENGLISH
ENGLISH
* Factory default!
Electrode-specic conguration – general
To access conguration mode, see page 19.
NOTE! Before starting up check the setting for electrode-specic conguration; row -01 for each channel (redox / chlorine / pH):
This must correspond to the electrical connection of the dosing equipment (On/Off or Frequency dosing) for each connection
example. If that does not conform it will cause damage to the circuit board.
NOTE! Dosing should not be charged with 230VAC when selecting the type of dosing Frequency control.
The following button combinations are used to enter the different conguration modes:
All M1, M2 and M3 models - Free chlorine, combined chlorine, pH
Basic functions:Function [11] + Reset [15]
Conguration for electrode 1: Set value [13] + Select function [1]
Conguration for electrode 2:Set value [13] + Select function [4]
Conguration for electrode 3:Set value [13] + Select function [7]
M3 - Free chlorine, redox, pH
Basic functions:Set acid [11] + Reset [15]
Conguration for electrode 1: Set alk/Chl [13] + Select function [1]
Conguration for electrode 3 (acid):Set acid [11] + Select function [7]
Conguration for electrode 3 (alkali): Set alk/Chl [13] + Select function [7]
Flashing LEDs conrm which conguration mode you accessed when the buttons are released: Active conguration is indicated
by the “Active” LED ashing. If any of the electrode-specic conguration modes are active, the LEDs “Off” and “Auto” ash for
the relevant electrode.
Autodos M3 model - Free chlorine, redox, pH: press the buttons Set alk/Cl [13] + Select function [1].
For all other models: press the buttons Set value [13] + Select function.
This is indicated via the text “SEt FCL” and ashing of the “Off” and “Auto” LEDs.
To exit conguration, press the Cal. button [0] or scroll past the last line.
Autodos M2 and M3
Select the desired line with the ↑ or ↓ button under the relevant display.
While the ↑ or ↓ button is depressed, display 2 shows the selected conguration type (e.g. “FCL” “-01”) and display 3 shows
the actual line number.
When the button is released, display 2 shows a text indicating which setting can be changed and display 3 shows a text or a
numeric value.
To change a text or value, press ↑ or ↓ under the relevant display.
The selected conguration is indicated via one of the following texts: “SEt”, “FCL”, “CCL”, “ACi” or “bAS”.
Autodos M1
Select the line for which you want to change the setting by pressing the Alarm high [12] or Alarm low [14] button.
When the Alarm high [12] or Alarm low [14] button is held depressed, the display shows the actual line number.
When the button is released, the display shows either a text or a numeric value. To change a text or value, press ↓ or ↑ .
The selected conguration is indicated via one of the following texts:: “SEt”, ”FCL”, ”ACi” or ”bAS” depending on type.
The following can be modied in the channel-specic conguration – Free chlorine:
LineTextSettingExplanation
-01doSSelection of dosing outlet and function.
oFFNo dosing.
ono*On-/Off-dosing.
PdoPulse width dosing..
FrEFrequency dosing..
CurDosing via current output..
-02P0.10–2.00 (0,20*)ppmP-band. (Pdo, FrE, Cur)
-03I000–100 (000*)minutesI-time, 000 = no I-regulation. (Pdo, FrE, Cur)
-04d000–100 (000*)secondsD-tid, 000 = no D-regulation. (Pdo, FrE, Cur)
-05dF010–180 (100*)strokes/minuteMax. frequency dosing. (FrE)
-06Pdo005–015 (010*)minutesPulse width during pulse width dosing. (Pdo)
-07Ldt000–060 (000*)minutesLong dosing time alarm, 0 = no function.
-08oFt000–600 secondsMin. time OFF for relay, 0 = no function. (ono)
-09ont000-600secondsMin. time ON for relay, 0 = no function. (ono)
-10Cur - - 0 / - - 4 (- - 4*)Current output, selection of range 0–20mA / 4–20mA.
-11C-L0.00–9.99 (0.00*) ppmCurrent output, value for 0/4mA.
-12C-H 0.00–9.99 (5.00*) ppmCurrent output, value for 20mA.
-13AHd005–600 (005*)secondsDelay time for high alarm.
-14ALd005–600 (005*)secondsDelay time for low alarm.
For conguration of total chlorine electrodes, press the buttons Set value [13] + Select function. This is indicated via the text
“SEt CCL” and ashing of the “Off” and “Auto” LEDs.
To exit conguration, press the Cal. button [0] or scroll past the last line.
The following can be modied in the channel-specic conguration – Combined chlorine:
LineTextSettingExplanation
-01
-02P0.10–2.00 (0.20*)ppmP-band. (Pdo, FrE, Cur)
-03I000–100 (000*)minutesI-time, 000 = no I-regulation. (Pdo, FrE, Cur)
-04d000–100 (000*)secondsD-time, 000 = no D-regulation. (Pdo, FrE, Cur)
-05dF010–180 (100*)strokes/minuteMax. frequency dosing. (FrE)
-06Pdo005–015 (010*)minutesPulse width during pulse width dosing. (Pdo)
-07Ldt000–060 (000*)minutesLong dosing time alarm, 0 = no function.
-08oFt000–600 (000*)secondsMin. time OFF for relay, 0 = no function. (ono)
-09ont000–600 (000*)secondsMin. time ON for relay, 0 = no function. (ono)
-10Cur - - 0 / - - 4 (- - 4*)Current output, selection of range 0–20mA / 4–20mA.
-11C-L0.00–9.99 (0.00*) ppmCurrent output, value for 0/4mA.
-12C-H 0.00–9.99 (5.00*) ppmCurrent output, value for 20mA.
-13AHd005–600 (005*)secondsDelay time for high alarm.
-14ALd005–600 (005*)secondsDelay time for low alarm.
doSSelection of dosing outlet and function.
oFFNo dosing.
ono*On/Off dosing.
PdoPulse width dosing.
FrEFrequency dosing.
CurDosing via current output.
* Factory default
MA60-10E
MA60-10E
28
Page 29
ENGLISH
Autodos M
Autodos M
ENGLISH
Electrode-specic conguration – pH
For conguration of pH electrodes.
Autodos M1-3 with acid or alkali dosing: press the buttons Set value [13] + Function [11].
Autodos M3 with acid dosing: press the buttons Set acid [11] + Select function [7].
Autodos M3 with alkali dosing: press the buttons Set alk/chlor [13] + Select function [7].
This is indicated via the text “SEt ACi” or “SEt bAS” (depending on whether acid or alkali dosing is selected) and ashing of the
“Off” and “Auto” LEDs.
To exit conguration, press the Cal. button [0] or scroll past the last line.
The following can be modied in the channel-specic conguration – pH:
LineTextSettingExplanation
-01
-02P0.10–2.00 (0.20*)pHP-band. (Pdo, FrE, Cur)
-03I000–100 (000*)minutesI-time, 000 = no I-regutlation. (Pdo, FrE, Cur)
-04d000–100 (000*)secondesD-time, 000 = no D-regulation. (Pdo, FrE, Cur)
-05dF010–180 (100*)strokes/minuteMax. frequency dosing. (FrE)
-06Pdo005–015 (010*)minutesPulse width during pulse width dosing. (Pdo)
-07Ldt000–060 (000*)minutesLong dosing time alarm, 0 = no function.
-08oFt000–600 (000*)secondsMin. time OFF for relay, 0 = no function. (ono)
-09ont000–600 (000*)secondsMin. time ON for relay, 0 = no function. (ono)
-10Cur - - 0 / - - 4 (- - 4*)Current output, selection of range 0–20 mA/4–20 mA.
-11C-L0.00–9.99 (6.00*)pHCurrent output, value for 0/4 mA
-12C-H 0.00–9.99 (8.50*)pHCurrent output, value for 20 mA.
-13AHd005–600 (005*)secondsDelay time for high alarm.
-14ALd005–600 (005*)secondsDelay time for low alarm
doSSelection of dosing outlet and function.
oFFNo dosing.
ono*On-/Off-dosing.
PdoPulse width dosing.
FrEFrequency dosing.
CurDosing via current output.
* Factory default!
MA60-10E
MA60-10E
29
Page 30
ENGLISH
Autodos M
Autodos M
ENGLISH
10. Calibration
To access calibration mode, authorization level 1 is required at a minimum, i.e. the “Code” LED must be illuminated or ash.
During calibration, no settings can be made and high alarm, low alarm and ow alarm are not activated. Automatic dosing is
stopped during calibration.
Calibration mode “Active” is accessed by pressing and holding the Cal. button [0] until the “Active” LED illuminates. Dosing
stops automatically during calibration and output signals on the current outputs are frozen at the last measured value before
calibration.
In calibration mode “Active” calibration of pH7, pH9 and chlorine zero points is possible.
Calibration mode “Adjust” is accessed by pressing and holding the Cal. button [0] until the “Adjust” LED illuminates (presuming
the “Active” is already lit). If combination with pH exists, no pH value is displayed. “- - -” is instead displayed to indicate that pH
calibration is not possible.
Calibration mode “Off” is accessed by pressing and holding the Cal. button [0] until the “Adjust” and “Active” LEDs go out.
To exit code mode, press the Code button [10]. The LED goes out as conrmation.
Calibration - pH
Calibration is done at two points – normally pH7 and pH9.
1. Activate calibration mode “Active”.
2. Take the cleaned and rinsed pH electrode and place it in the pH7 calibration solution (not in the buffer bottle).
Move the electrode up and down for a good reading. Give the measurement value time to stabilize (5-30 seconds).
Then press the calibration button pH7 [8] until the display shows “- - -”.
3. Rinse the electrode and then place it in the pH9 calibration solution (not in the buffer bottle). Move the electrode up and down
a little for a good reading. Give the measurement value time to stabilize (5-30 seconds). Then press the calibration button
pH9 [9] until the display shows “- - -”.
4. pH calibration is complete. Exit calibration mode by pressing the Cal. button [0] twice until the “Adjust” and “Active” LEDs
go out.
5. Discard used buffer solution after calibration.
NOTE: If the signal during two points calibration deviates too greatly from the expected values, electrode error is
indicated with the text “EL1”, “EL2”, “EL3” or “EL4” while the calibration button is held depressed.
When the button is released, Autodos M uses the calibration values that applied before the failed calibration attempt.
Text meaning:
EL1active electrode error 1 (low calibration point < min)
EL2 active electrode error 2 (low calibration point > max)
EL3 active electrode error 3 (high calibration point < min)
EL4 active electrode error 4 (high calibration point > max)
Calibration - redox
The redox value is only calibrated at one measuring point. No reinforcement calibration is necessary for redox electrodes.
The calibration can be done at any known redox value. The calibration value is adjustable +/- 50mV relative to the uncalibrated
redox value.
1. Activate calibration mode by pressing the button Cal. [0] until the diode ”Active” is lit.
2. Put the cleaned and rinsed redox electrode in a reference liquid with known redox value. Let the measured value stabilise.
3. Press the button Cal. [0] until the diode ”Adjust” is lit. The equipment then stores the latest measured electrode signal.
4. Adjust the redox value with the buttons ↑ and ↓ under display 2 according to the current reference liquid.
5. Exit calibration mode by pressing the button Cal. [0] until the diode ”Adjust” is shut off.
6. Reinstall the electrode into the valve. Let the measured value stabilise for around one hour.
7. Activate dosage mode.
MA60-10E
MA60-10E
30
Page 31
ENGLISH
Autodos M
Autodos M
Some buffer solutions for redox and approximate readings:
MixtureRedox potential
at 20°Cat 25°Cat 30°C
Buffer pH 2 + quinhydrone385 mV381 mV377 mV
Buffer pH 4 + quinhydrone268 mV263 mV258 mV
Buffer pH 7 + quinhydrone92 mV86 mV79 mV
Buffer pH 8 + quinhydrone33 mV27 mV19 mV
Mix one dose of quinhydrone powder in 20 ml buffer uid. Stir it weill untill the solution is saturated.
Note: Quinhydrone solution is unstable and must be discarded after use. The time required for stabilization of the new measurement value is an indication of electrode condition as age and contamination increase stabilization time.
ENGLISH
Calibration Chlorine
Calibration of chlorine electrodes shall be done with a measured value of the water in direct connection to Autodos and with a
digital photometric instrument. If the pool water is dosed or has been dosed with organic chlorine containing isocyanuric acid,
the pool water shall be controlled. The level of cyanuric acid can not exceed 5mg/l (ppm). An increased level will give lowered
free chlorine signals which affects calibration, measuring and control of relevant cannel.
Chlorine electrodes are ow dependent and the ow through the valve shall be adjusted to 30-40 liters/minute.
Zero point calibration
Zero point calibration should be done, see 2 under Calibration/Chlorine. An inaccurate zero point will give errors in calibrations
and display of chlorine values.
Lift the electrode (with the electrode cabel connected) from the valve, wait for one minute.
If the chlorine display shows other than 0,00: Activate calibration mode by pressing and holding the Cal. button [0] until the “Ac-tive” LED illuminates.
Press the button ↓ for 4 seconds until the display shows: -, -, -, - - -, after that the calibration is done. To reset the zero point
calibration to factory mode, press the button ↑ for 4 seconds until the display shows: F, F, F, FFF, after that the reset is done.
NOTE! If the signal at zero point calibration deviates too much from the expected value, electrode error will be indicated with the
text ”EL1”, ”EL2” during the time the calibration button is pushed.
When the button is released, Autodos M uses the calibration values that applied before the failed calibration attempt.
Meaning of the texts:
EL1 active electrode error 1 (low calibration point < min)
EL2 active electrode error 2 (low calibration point > max)
(Gain calibration)
The reinforcement mode is limited both upwards and downwards by levels of reasonable electrode signal.
1. Activate calibration mode by pressing and holding the Cal. button [0] until the “Active” LED illuminates.
2. Zero point calibration is carried out by lifting the electrode out of the ow cell, waiting about 1 minute and then pressing the ↓
button under display 1. Before calibration to the laboratory-measured value is possible, the electrode must be 3. retted in the
ow cell and allowed to measure in the cell for about 2 minutes to obtain a correct value.
3. Access calibration mode by pressing and holding the Cal. button [0] until the “Adjust” LED illuminates. The meter stores the
last measured electrode signal.
4. Take a water sample and determine the correct chlorine value with DPD1.
5. Set the correct chlorine value with the ↑ and ↓ buttons under display 1..
6. Exit calibration mode by pressing and holding the Cal. button [0] until the “Adjust” and “Active” LEDs go out.
1. Activate calibration mode by pressing and holding the Cal. button [0] until the “Active” LED illuminates.
2. Zero point calibration is carried out by placing the electrode in chlorine-free water or in the air. Wait about 1 hour and then
press the ↓ button under display 1. Before calibration can continue, the electrode must be allowed to measure in the ow
cell for about 5 minutes to obtain a correct value.
3. Access calibration mode by pressing and holding the Cal. button [0] until the “Adjust” LED illuminates.
The meter stores the last measured electrode signal.
4. Take a water sample and determine the correct chlorine value with DPD1.
5. Set the correct chlorine value with the ↑ and ↓ buttons under display 1.
6. Exit calibration mode by pressing and holding the Cal. button [0] until the “Adjust” and “Active” LEDs go out.
Calibration – combined chlorine
Combined chlorine is a calculated value (total chlorine – free chlorine).
In calibration mode, TOTAL chlorine (i.e. free + combined chlorine) is shown on display 2 and calibration is done on TOTAL
chlorine (DPD1 + DPD3).
1. Activate calibration mode by pressing and holding the Cal. button [0] until the “Active” LED illuminates.
2. Zero point calibration is carried out by placing the electrode in chlorine-free water or in the air. Wait about 1 hour and then
press the ↓ button under display 2. Before calibration can continue, the electrode must be allowed to measure in the ow
cell for about 5 minutes to obtain a correct value.
3. Access calibration mode by pressing and holding the Cal. button [0] until the “Adjust” LED illuminates.
The meter stores the last measured electrode signal.
4. Take a water sample and determine the correct chlorine value with DPD 1 and then DPD 3.
5. Set the correct chlorine value with the ↑ and ↓ buttons under display 2.
6. Exit calibration mode by pressing and holding the Cal. button [0] until the “Adjust” and “Active” LEDs go out.
11. Maintenance
Flow cell
On a daily basis, check that the water ows as it should. Flow should be approx. 30 litres per hour.
Clean the water lter before the ow cell as necessary.
Electrodes
Refer to the electrode manual.
Water quality
As water quality varies and electrodes wear over time, measurement values should be checked regularly.
Water samples should be made with photometric equipment to ensure that the pool water is within recommended limits.
If the electrode value deviates from the pool water value, a recalibration must be done.
Two-point calibration (i.e. both zero point and amplication calibration) is carried out upon initial start-up and when electrodes
are replaced.
12. Troubleshooting
Error codes
CodeCause
EL1 active electrode error 1 (low calibration point < min)
EL2 active electrode error 2 (low calibration point > max)
EL3 active electrode error 3 (high calibration point < min)
EL4 active electrode error 4 (high calibration point > max)
noCchlorine value too low; calibration not possible
MA60-10E
MA60-10E
32
Page 33
Autodos M
Autodos M
ErrorProbable causeAction
Meter completely deadNo power supply.Check the electrical connection.
Measurement value
uctuates greatly
up and down..
Incorrect measurement
values
(pH or chlorine).
Calibration cannot be carriedDefective electrodeReplace the electrode.
Electrodes give sluggish
but correct value in buffer
solution but incorrect during
measurement
Measurement value stuck at
pH = 7 and 0 mV or 0 mg/l
Meter is not dosing, dosing
lamp is not illuminated or
AUTO is ashing.
The meter is not dosing, the
dosing lamp is illuminated.
Incorrect chlorine measurement values
(Prominent measuring cell).
Chlorine value too low to be
adjusted to measured value
(Prominent measuring cell).
Incorrect chlorine measurement values
(PB-200 measuring cell).
Chlorine value shows zero all
the time
(PB-200 measuring cell).
No “click” during dosing;
dosing lamp is illuminated.
(Frequency controlled dosing).
Electrode not connected.Check the connection.
Cable fault.Check the cable.
Electrode without measurement water.Check the ow cell
Dirty electrode. Clean the electrode.
Incorrectly calibrated meter. Carry out calibration with fresh buffer solution.
Defective electrode. Try shaking the electrode (if there is an air bubble
in the glass ball); otherwise replace the electrode.
Poor contact with the meter.Check the cables, including the cables on the
inside connecting the BNC connectors on the out-
side with the circuit board.
Defect buffer solution. Check the buffer solution.
Dirty electrode.Clean the electrode.
Electrode used up.Replace the electrode.
Short-circuit of measurement signal.Check electrode, cables and connections.
Meter in “manual” mode.Put the meter in “auto” mode.
“PHF” error.Determine the cause and reset the alarm; chlorine
dosing starts when the pH value is correct.
Dosing equipment is not connected cor-
rectly.
Dosing relay defectiveReturn the meter for repair.
Air bubbles in the membrane.Carefully tap on the outside of the electrode’s glass
Dirty membrane.Clean the membrane and ll with fresh electrolyte.
Pressure changes.Depressurize the outlet from the ow cell.
Unstable pH value.The pH value must be stable during chlorine mea-
Incorrectly calibrated meter.Calibrate chlorine.
Poor electrolyte.Replace the electrolyte or wipe off the gold tip of
Oxides on the gold tip of the
measuring cell.
Test water ow too low.Ensure that the ow through the measuring cell is
Unstable pH value.The pH value must be stable during chlorine
Incorrectly calibrated meter.Calibrate chlorine.
Water sample contains high content of
isocyanuric acid.
Cable connection to metal cylinder loose. Fasten the cable connection.
Dosing relay defective.Return the meter for repair.
Check connection
casing or temporarily increase ow past the cell.
surement; adjust pH to 7.4
the measuring cell with a napkin.
Carefully polish with wet grinding paper.
correct.
measurement; adjust pH to 7.4
Dilute or replace the pool water with fresh water.
ENGLISH
ENGLISH
Alarm codes
The following error codes can occur when the Reset button [15] is held depressed:
MA60-10E
MA60-10E
FLo active ow error
Lo active low alarm
Hi active high alarm
doSincorrect dosing
PHFstopped chlorine dosing because pH value outside permitted limits
SbYstandby
LoLactive level switch alarm
- - - everything OK
33
Page 34
ENGLISH
Autodos M
Autodos M
ENGLISH
13. Jesco free chlorine electrode (option)
Jesco free chlorine electrode is not marketed by Pahlén AB, but connection is possible if desired.
Note that Jesco uses a separate measuring cell and the corresponding electrode/cell on the Autodos unit must then be plugged.
Maintenance
Refer to the Jesco manual regarding service and maintenance.
Calibration of free chlorine (Jesco chlorine electrode)
NOTE: In order to obtain the correct chlorine value, the measuring cell must rst have correct ow for 3 hours so that the glass
balls have time to clean the electrodes. This is vital in order to prevent a zero point error.
1. Activate calibration mode by pressing and holding the Cal. button [0] until the “Active” LED illuminates.
2. Fill the measuring cell with chlorine-free water and then wait about 10 seconds.
3. Activate zero point calibration by pressing the ↓ button under display 1. Before calibration can continue, the electrode must
be allowed to measure in the ow cell for about 2 minutes to obtain a correct value.
4. Access calibration mode Adjust by pressing and holding the Cal. button [0] until the “Adjust” LED illuminates.
The meter stores the last measured electrode signal.
5. Take a water sample and determine the correct chlorine value with DPD1.
6. Set the correct chlorine value with the ↑ and ↓ buttons under display 1.
7. Exit calibration mode Adjust by pressing and holding the Cal. button [0] until the “Adjust” LED goes out.
Flow
Flow must be large enough that the glass balls rotate so forcefully that they reach the top of the measuring cell (but not too
violently). If necessary, the copper plate can be replaced.
14. Autodos PC connection (expansion)
Simply installing an extra circuit board makes it possible to connect Autodos M to a PC.
The PC connection kit includes the following parts: Datalogger with real-time clock and communication module.
The circuit board is connected to the bottom card in Autodos M with a connector and plastic clips.
Externally, the circuit board is connected either to a communication module via a twin-cable connector or via an RJ45 connector to the serial port of a PC or modem. Program version 1.0 has no support for modem connection. Such support is planned for
later versions.
Identication of a single Autodos M in the twin-cable loop is done through a unique, factory-programmed serial number for each
delivered unit.
The communication program “Autodos Monitor” is used to monitor Autodos M and modify parameters.
The program is described in a separate document.
Datalogger32kB EEPROM
Real-time clock
24kB (3 days) with minute average values for 4 channels
8kB events (255 events); an event can be e.g. an alarm or a calibration
Communication
module
RS232 PC communication, cables included
Twin-cable connection with Autodos
With recommended cable FKAR-PG 0.5 mm2, up to 200 m and 5 units can be connected to the twincable loop.
External 9 VAC transformer included
MA60-10E
MA60-10E
34
Page 35
ENGLISH
Autodos M
Autodos M
ENGLISH
15. Autodos PLC connection (expansion)
Simply installing an extra circuit board makes it possible to connect Autodos M to a PLC.
The PLC connection kit includes the following parts: Datalogger with real-time clock and Modbus RTU.
The circuit board is connected to the bottom card in Autodos with a connector and plastic clips. Externally, the circuit board is
connected to the RS422 interface via a 5-pin screw terminal.
Datalogger32kB EEPROM
Real-time clock
24kB (3 days) with minute average values for 4 channels
8kB events (255 events); an event can be e.g. an alarm or a calibration
Modbus RTU-interface i Autodos M3, ver. 5.3
Baudrate 9600 baud
Parity None.
Modbus RTU communication in Autodos M3. Autodos only responds via a message:
Slave address As per Autodos “common setup”
Function 03H, Read holding registers
Starting Address Hi 00H
Starting Address Lo 01H
No. of Points Hi 00H
No. of Points Lo 0BH
CRC 55H
CRC CDH
With slave address 1, the message is: 01 03 00 01 00 0B 55 CD
bit 0: Standby mode
bit 1: Flow
bit 2: High alarm pH
bit 3: High alarm Combined chlorine
bit 4: High alarm Free chlorine
bit 5: Low alarm pH
bit 6: Low alarm Combined chlorine
bit 7: Low alarm Free chlorine
Alarm Reset (16 bit)
bit 0: Standby mode
bit 1: Flow
bit 2: High alarm pH
bit 3: High alarm Combined chlorine
bit 4: High alarm Free chlorine
bit 5: Low alarm pH
bit 6: Low alarm Combined chlorine
bit 7: Low alarm Free chlorine
MA60-10E
MA60-10E
35