Pacific Power Source (PPS) warrants each unit to be free from defects in material and
workmanship. For the period of two (2) years from the date of shipment to the
purchaser, PPS will either repair or replace, at its sole discretion, any unit returned to its
factory in Irvine, California. Excepted from this warranty are fuses and batteries, which
carry the warranty of their original manufacturer if applicable. It does not cover damage
arising from misuse of the unit or attempted field modifications or repairs. This warranty
specifically excludes damage to other equipment connected to this unit.
Upon notice from the purchaser within thirty (30) days of shipment of units found to be
defective in material or workmanship, PPS will pay all shipping charges for the repair or
replacement. If notice is received more than thirty (30) days from shipment, all shipping
charges shall be paid by the purchaser. Units returned on debit memo will not be
accepted and will be returned without repair.
This warranty is exclusive of all other warranties, expressed or implied.
Service & Spare Parts Limited Warranty:
Pacific Power Source (PPS) warrants repair work to be free from defects in material and
workmanship for the period of ninety (90) days from the invoice date. This warranty
applies to replaced parts or subassemblies only. This warranty does not include
batteries. All shipping and packaging charges are the sole responsibility of the buyer.
Pacific Power Source will not accept debit memos for returned power sources or
subassemblies. Debit memos will cause return of power sources or assemblies without
repair.
This warranty is exclusive of all other warranties, expressed or implied.
Page 3
3060-MS
SOLID-STATE
AC POWER SOURCE/FREQUENCY CONVERTER
INSTALLATION AND OPERATION MANUAL
THE INFORMATION CONTAINED IN THIS MANUAL
IS PROPRIETARY TO PACIFIC POWER SOURCE, INC.
THIS MANUAL MAY NOT BE COPIED OR REPRINTED
WITHOUT THE EXPRESSED WRITTEN CONSENT
OF PACIFIC POWER SOURCE, INC..
PACIFIC POWER SOURCE, INC.
17692 FITCH
IRVINE, CA., U.S.A. 92614
PHONE: (949) 251-1800
FAX: (949) 756-0756
February 2013
MANUAL PART NO. 126050
Revision E
DWG NO. 126050-10e
Page 4
THIS PAGE INTENTIONALLY BLANK
Page 5
TABLE OF CONTENTS
Section Description Page
1.0 GENERAL DESCRIPTION................................................................................ 1-1
1.1 MANUAL DESCRIPTION
This manual is written to provide the information required to use the MS-Series
AC Power Source effectively. This Operations Manual describes proper
installation, operation and maintenance of the MS series power source units.
1.2 USING THIS MANUAL
This manual primarily covers installation and operation. It is very important that
the user reads Section 3, INSTALLATION and Section 4, OPERATION, prior to
installing this equipment. A thorough understanding of these two sections is
required to operate this equipment properly.
If questions arise while reading this manual, the user is encouraged to call Pacific
Power Source Inc. Pacific maintains a toll-free number which is 1-800-854-2433
(949-251-1800 Outside the USA), Fax 949-756-0756 or contact us through our
website: www.pacificpopwer.com
Section 5 discusses maintenance, Section 6 is for service. These sections need
to be read only when such activities are required to be performed.
1.3 SAFETY NOTICES
MS-Series equipment is capable of transferring very large amounts of electrical
energy very quickly. This basic quality is fundamental to any high-performance
power source. The warnings and cautions listed below should be observed at all
times.
Warnings indicate potentially hazardous situations which, if not avoided, could
result in death or serious injury. All warnings throughout this manual will appear
as shown below.
THIS EQUIPMENT CONTAINS HIGH ENERGY, LOW IMPEDANCE CIRCUITS!! LETHAL POTENTIALS
ARE CONTAINED WITHIN THE CABINET.
CARE MUST BE EXERCISED WHEN SERVICING THIS EQUIPMENT IN ORDER TO PREVENT
SERIOUS OPERATOR INJURY OR EQUIPMENT DAMAGE.
OBSERVE THE FOLLOWING WHEN SERVICE AND MAINTENANCE ARE REQUIRED:
1) REMOVE ALL JEWELRY FROM ARMS AND NECK WHEN SERVICING THIS EQUIPMENT.
THIS PREVENTS THE POSSIBILITY OF SHORTING THROUGH THE JEWELRY AND
CAUSING BURNS TO THE OPERATOR.
2) WEAR SAFETY GLASSES WHEN SERVICING THIS EQUIPMENT TO PREVENT EYE INJURY
DUE TO FLYING PARTICLES CAUSED BY ACCIDENTAL SHORT CIRCUIT CONDITIONS.
3) DO NOT REMOVE ANY PANEL OR COVER WITHOUT FIRST REMOVING THE INPUT
SERVICE BY OPENING ALL CIRCUIT BREAKERS.
4) SERVICE OTHER THAN EXTERNAL CLEANING SHOULD BE REFERRED TO PERSONNEL
AUTHORIZED BY THE FACTORY TO SERVICE THIS EQUIPMENT.
CAUTION -
Read Section 3, INSTALLATION, and Section 4, OPERATION,
of this manual before installing or operating this equipment.
CAUTION
USING IMPROPER GAUGE OF INPUT CABLE MAY OVERHEAT AND DAMAGE THE
EQUIPMENT. SEE SECTION 2.0 SPECIFICATIONS FOR THE PROPER SIZING OF
INPUT CABLE.
!
!
Cautions indicate a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury. A caution also may be used to alert against
unsafe practices. Cautions will appear as shown below. All cautions should be
rigorously observed.
To protect equipment from damage a caution will be used as follows:
Page 12
SECTION 1 GENERAL
WARNING
IF THIS EQUIPMENT IS NOT USED IN A MANNER SPECIFIED BY THE
MANUFACTURER, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE
IMPAIRED
1.4 GENERAL PRODUCT DESCRIPTION
The intended use of the Pacific Power Source MS-Series equipment is basic
frequency or voltage conversion with manually adjustable settings. With the
optional external programmable controller (UPC) it is suitable for testing
applications such as sag, surge, etc. The MS-Series power sources are a family
of Line-Conditioners/Frequency-Changers covering the power range from 62.5 to
750 kVA (50 - 600 kW), at output frequencies of 50 - 400 Hz. The basic 62.5 kVA
/ 50 kW unit is designated as the model 3060-MS. Up to 12 units can be
paralleled to provide 750 kVA / 600 kW.
The 3060-MS functions as a double conversion power source. Input AC power is
rectified to DC by a special power supply that provides both isolation and low
input current distortion. The DC power is then converted back to AC by a high
frequency pulse-width modulated inverter stage, under the control of a highly
stable digital oscillator.
The 3060-MS unit is designed to provide high quality output power. Output
regulation and total harmonic distortion are of the order of 1% at 50 or 60Hz and
2% at 400Hz. Response time to a 100% step load change is 300 microseconds.
The machine is therefore capable of delivering very high pulse current loads.
The fast response time and excellent regulation of the MS-Series are extremely
important in applications where mixed or switched loads may cause power
interference and load "Cross-talk".
MS Series equipment is designed for long term, continuous operation in a
sheltered (no rain) environment. Because there are no batteries, it will accept a
wide ambient temperature range. The equipment is efficient (about 90%),
circulates little cooling air and is relatively tolerant of dusty environments.
The MTBF of a single cabinet 3060-MS is high (approx. 5 years).
System operation is controlled by simple, high reliability digital logic. A
microprocessor provides internal diagnostics and communicates with the
operator via a 160 character digital display.
All components functioning together which convert input AC
power to isolated, conditioned, variable frequency and variable
voltage output AC power to the load.
Cabinet
One enclosure that contains a Power Source.
System
One or more enclosures which make up a paralleled cabinet
power source.
Rectifier
The circuit component that contains the equipment and controls
necessary to convert the input AC power to DC power.
Inverter
The circuit component that contains the equipment and controls
necessary to convert DC power from the rectifier to AC power
required by the load. A high frequency pulse-width modulated
switcher.
Internal
Control
System
The signal processing circuits that regulate the power
conversion processes, detect fault conditions, and control the
sequence of operation of the Power Source. This term may be
shortened to "Control System."
Operator
Controls
The controls which are used by the operator to monitor and
operate the Power Source. They are located on the front of the
cabinet exterior.
Input Power
Power provided by the electrical utility company, or auxiliary
generator, connected to the input of the Power Source.
Output Power
Power provided by the Power Source to the load, connected to
the output of the Power Source.
1.5 DEFINITIONS
Common terms and component names, as used throughout this MS-Series
1.6 DETAILED DESCRIPTION
This paragraph provides a detailed description of each major sub-assembly, its
purpose, and its general operation.
1.6.1 3060-MS CABINET
The cabinet consists of a rectifier, three-phase inverter, protective devices, and
accessories as required for proper operation.
1.6.2 RECTIFIER CIRCUIT
The rectifier circuit is a solid-state assembly designed to provide direct current to
the inverter unit.
A 12 pulse input rectifier is used, reducing current harmonic feedback into the
input AC line to a nominal 12%rms. The rectifier also controls the input power
factor so that it remains above 0.85 lagging at full load.
For input isolation and adapting to a variety of available input voltages, a dry type
power transformer is used before the rectifier unit. The transformer's winding
temperature is monitored by Internal Control System diagnostics to ensure that
the transformer temperature does not exceed design limits.
The rectifier circuit provides a soft start-up feature whereby when the AC power
is first applied, the total initial power drawn at the input terminals will not exceed
100% of rated input power.
DC overvoltage protection is provided so that if the DC Bus voltage rises above
the pre-set limit, the Power Source will shut down automatically.
DC undervoltage protection is provided so that if the DC Bus voltage drops below
the pre-set limit, the Power Source will shut down automatically.
AC overvoltage protection on the AC input circuit shuts down the power source
when the input voltage rises above a preset percent of input voltage.
The Low Voltage Power Supply has its own undervoltage protection to shut down
the power source should the power supply voltage to the control circuits fall
below an acceptable level.
1.6.3 INVERTER MODULE
The inverter module is a solid-state device that converts power from the rectifier
circuit to provide the rated AC system output within specified limits.
The output frequency of the inverter is controlled by a digital oscillator.
The oscillator is adjustable over the range of 47 to 500Hz in the variable position.
In the fixed frequency positions, the oscillator is designed to control the inverter
output frequency within ±0.01%. Drift will not exceed ±0.01% during a 24-hour
period. Total frequency deviation, including short time fluctuations and drift, is
typically within ±0.01% from the specified frequency.
The inverter is capable of supporting transient overloads up to 150%, or any
continuous load within its rating, without reducing the output voltage. Loads
greater than 150% may cause a reduction of the output voltage.
The inverter will current limit at 150% of rated current. The inverter is capable of
supplying at least 200% of rated RMS current for short circuit conditions. If the
short circuit is sustained, the inverter will shut down and disconnect automatically
from the output.
Each inverter output phase voltage is independently regulated to ±0.5%, with
AGC enabled, such that unbalanced loading will not cause the output voltage to
exceed the specified voltage unbalance.
An output power filter is incorporated in the inverter unit. The filter reduces the
inverter output sine wave voltage harmonics to 1% RMS total and single
harmonics to 0.5% RMS maximum for linear loads at 50-60Hz.
Power semiconductors in the inverter unit are fused with fast acting fuses, so that
loss of any one power semiconductor will not cause cascading failures.
1.6.4 MULTI-CABINET PARALLELED SYSTEM
Up to twelve cabinets may be paralleled together for higher power systems.
Each 3060-MS is capable of operating as either a SLAVE or MASTER in multicabinet parallel operation but only one Master may be active at a time.
Parallel system architecture is such that any failed slave unit automatically drops
off-line.
A failed MASTER turns the entire system off. In this event an operator can select
any other paralleled unit as the MASTER from a front panel control and restore
system operation.
Voltage: 120/208 3Φ WYE. May be loaded WYE or DELTA.
0-132 VAC
Adjustment Range, with nominal input,
L-N
adjustable by front panel controls
Other voltages available as options..
Volt Regulation 0-100% Load Step: ±1% of output voltage regardless of load
unbalance, with AGC enabled.
Transient Voltage Regulation and Recovery: Output voltage recovers from a
50% load step to within 1% of nominal in less than 150
microseconds.
Harmonic Voltage Content for Linear Loads: Maximum 1% RMS total,
maximum 0.5% any single harmonic for linear loads 5060Hz, 2% RMS total for 400Hz. Paralleled Systems maybe
higher.
Current: 175 amps per phase.
Inverter Fault Clearing Current: Greater than 200% of full load.
Pulse Current: Greater than 200% per phase of pulse current for driving
non-linear loads.
Inverter Overload: - 150% of full load for 30 seconds
- 125% of full load for 10 minutes
- 110% of full load for 1 hour
Frequency Range Selectable, fixed frequencies at 50, 60, 400 Hz.
Variable frequency range 47-500 Hz.
External Oscillator input available.
Frequency Accuracy and Stability: ±0.01% typically for fixed frequencies.
Frequency Drift: ±0.01% for fixed frequencies. (24hr period)
Load Power Factor: No Restrictions
FIGURE 2.1.3 OUTPUT RATINGS
For a paralleled cabinet system multiply the above ratings by the number of
cabinets in the system.
THE PROPER INSTALLATION OF AN MS-SERIES AC POWER SOURCE REQUIRES
A THOROUGH UNDERSTANDING OF THE INFORMATION PRESENTED IN THIS
SECTION OF THE MANUAL.
IF THIS EQUIPMENT IS NOT INSTALLED AND USED IN A MANNER SPECIFIED BY
THE MANUFACTURER, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY
BE IMPAIRED
1.
Planning the job. (Refer to paragraph 3.1)
2.
Uncrating and Moving the system. (Refer to paragraph 3.2)
3.
Changing Input Voltage, if required. (Refer to paragraph 3.3)
4.
Setting the cabinet into place. (Refer to paragraph 3.4)
5.
Making Input Connections. (Refer to paragraph 3.6)
6.
Making Output Connections. (Refer to paragraph 3.7)
7.
Multiple Cabinet Paralleled Systems. (Refer to paragraph 3.8)
8.
Inspecting the Installation. (Refer to paragraph 3.9)
3.0 INSTALLATION
Should any question arise regarding the installation of this equipment, the user is
encouraged to call Pacific Power Source, toll free in the USA at 1-800-854-2433 or 949251-1800 internationally.
Installation of an MS Power Source consists of the following steps:
3.1 PLANNING THE JOB
The main objective in planning the job is to determine the hardware required to
install the MS-Series Power Source. Proper consideration of the items below will
allow the installation to proceed in an orderly manner.
The first step in planning the job is to determine the size of power source
required to service the load. In normal situations the load should not exceed
80% of the power source's full load ratings. This margin allows the user to add
future loads to the Power Source without sacrificing surge and overload
capabilities.
After a particular model has been selected, location of the Power Source, input
and output wiring and environmental conditions must be considered. Table 3.1,
Environmental Survey Checklist, is provided to verify environmental conditions.
Be sure to refer to the clearances required for ventilation in Figure 3.1 for
planning the mechanical installation.
The cabinet should be placed as close as possible to the load to minimize output
wiring lengths. This is done to reduce distribution losses between the load and
power source. Shorter output wiring will provide higher quality power to the load.
If there is a choice between shorter power source input or output wiring, choose
shorter output wiring. Final equipment location must maintain the minimum
physical clearances as shown in Figure 3.1 Installation Detail.
Ambient temperature between 0-40 degrees Centigrade.
2.
Cooling and air exchange rates in the room adequate to
support the heat load.
3.
A minimum of 12" above the Cabinet for exhaust.
4.
Unrestricted air intake at the lower front and rear of the
cabinet. (Exception: Forced air intake from raised floor
installations requires sealing off of the lower front and rear
areas. Consult factory.)
5.
A minimum of 24" in front of the Cabinet for service.
6.
Altitude of installation does not exceed 6500 feet. Altitudes in
excess of 6500 feet require the derating of maximum operating
levels.
7.
Relative humidity does not exceed 80% (95% with conformal
coat PCB option) non-condensing. It is suggested that
equipment not be located directly under cooling equipment due
to the danger of condensing vapor.
TO AVOID DAMAGE TO THE EQUIPMENT, LIFTING FORKS MUST EXTEND
COMPLETELY THROUGH THE LIFTING CHANNEL UNDER THE CABINET AS
SHOWN IN FIGURE 3.2, CRATING AND MOVING OUTLINE DRAWING.
WARNING
TIP OVER HAZARD.
USE CAUTION WHEN MOVING UNITS
EQUIPPED WITH THE CASTER
OPTION. THE CENTER OF GRAVITY IS
RAISED BY 3” AND THE BASE IS
SMALLER.
3.2 MOVING, UNCRATING, AND INSPECTION
Unless specified otherwise, all Pacific MS-Series cabinets will be shipped in one
wooden crate, with a crated weight between 1,700-1,800 lbs depending upon the
model and options selected. Dimensions and center of gravity can be seen in
figure 3.2, Crating and Moving Outline drawing. The weight will be marked on all
sides for safe handling. The crate is constructed of wood and designed to be
moved with a forklift or hand truck of adequate capacity.
Upon receiving the equipment, remove the packing list. Separate and remove
the top then the sides of the crate setting these aside for the moment. Inspect all
equipment for signs of damage in shipping. If any damage has occurred, contact
the shipper and the Pacific factory for instructions. If the cabinet is to be
returned, it must be shipped back in the original crate.
If no signs of damage are evident, the equipment may be removed from the
pallet. A forklift is required to lift the cabinets off the pallets. Do not attempt to
"rock" or slide them off as damage may occur to the equipment or injury may
occur to personnel.
INPUT TRANSFORMER. FOR SAFETY,
OPEN THE INPUT CIRCUIT BREAKER.
CAUTION
DAMAGE TO THE EQUIPMENT MAY RESULT IF INCORRECTLY WIRED. VERIFY
CONNECTIONS ARE MADE TO PROPER TAPS.
3.3 CHANGING INPUT VOLTAGE
Configure the system for the correct input voltage prior to installing. All voltages
listed in this procedure are line to line.
When changing the input voltage, the input circuit breaker and fuses must also
be changed to accommodate the different current required. The input
transformer, T1, and LVPS transformer, T2, must be reconnected to the correct
taps. See figure 3.3.1 through figure 3.3.4.
Each mainframe, dependent upon model number, will require the following Input
Circuit Breaker and Fuses:
Verify no input power is connected.
Open Input Circuit Breaker.
2:
Remove front covers and sub-panels.
Remove rear panel.
3:
Remove input circuit breaker CB1.
Install new CB1 with correct amperage for new input voltage.
NOTE: Wires between CB1 and the terminal block on the Input
Power Panel must be sized appropriately for the new input power
form, see Table 3.6.1 for wire size reference.
4:
Remove input fuses F1, F2 and F3.
Install new fuses with correct amperage for new input voltage.
5:
Rewire T1 and T2 per fig 3.3.1, 3.3.2, 3.3.3 or 3.3.4 as required
6:
Reinstall rear panel.
Reinstall front covers and sub-panels.
7:
Go to section 4.3.1 for first time operation.
INPUT VOLTAGE
Fig.
INPUT
CONNECT
Actual
Nominal
TAPS
TAPS
480
480
3.3.1
1,8
4-5
448
480-7%, 416+8%
3.3.1
1,8
3-5
430
480-10%, 416+3%, 400+8%
3.3.1
2,8
4-5
416
416, 400+4%, 380+10%
3.3.1
1,7
3-5
398
400, 416-4%, 380+5%
3.3.1
1,8
3-6
380
380 416-9%, 400-4%
3.3.2
2,8
4-6
366
400-9%, 380-4%
3.3.2
2,7
3-5
348
380-8%
3.3.2
2,8
3-6
240
240, 208+15%
3.3.3
1,8
1-5,4-8
208
208, 240-13%
3.3.4
1,7
1-5,3-7
190
208-9%
3.3.4
2,8
2-6,4-8
The system may be configured for any of the following input voltages:
3.4 SETTING THE CABINET INTO PLACE
Depending on the site, it may be advisable to rough-in the input and output wiring
prior to moving the cabinet into place. This is best evaluated by the installation
team and they should proceed appropriately. Observe clearances as shown in
Figure 3.1.
3.5 SAFETY GROUNDING / EARTHING
Prior to any input power connections the safety ground or earth ground must be
connected. Observe minimum wire sizes as stated in TABLE 3.6.1
3.6 CONNECTING THE INPUT SERVICE
NOTE
IT IS THE USER'S RESPONSIBILITY TO MEET ALL APPLICABLE LOCAL AND
NATIONAL CODE REQUIREMENTS WHEN INSTALLING THIS EQUIPMENT.
When connecting the input service, certain requirements relating to safety are stated in
these instructions and should be followed rigorously.
Input connections to the MS-Series AC Power Source are made at the Circuit Breaker
labeled "INPUT POWER." Refer to figure 3.6 AND 3.6.1 for location and orientation of
terminals.
The input terminals are compression type. It is very important that the connections are
clean and properly tightened. Torque input connector set screws to 55 lb-in [120 lb-in
for the CE option].
The MS-Series is not sensitive to input phase sequence.
3.7 CONNECTING THE OUTPUT SERVICE
When connecting the output service, certain requirements relating to safety are
stated in the following procedure and should be followed rigorously.
The standard output form of the MS-Series is 120/208Y, 50, 60, 400 Hz or
Variable frequency. Phase sequence of the output is ABC. Maximum output
current for each 3060-MS in a system is:
The CE option incorporates output fuses F12-F14 in the mainframe cabinet. (No
output fuses are provided within the Cabinet in the standard configuration.)
Output connections in the standard MS-Series AC Power Source are made at the
output contactor terminals. Refer to figures 3.7, 3.7.1, 3.7.2 for location and
orientation of terminals.
The output terminals are compression type. It is very important that the
connections are clean and properly tightened. Torque output connector set
screws to 150 in-lbs (17 N-m).
If the optional output circuit breaker is installed, connect the output wiring to the
output breaker.
WHEN THREE OR MORE CABINETS ARE CONNECTED IN PARALLEL, A
PARALLELING / OUTPUT LOAD CENTER WITH INDIVIDUAL CIRCUIT BREAKERS
FOR EACH CABINET MUST BE INSTALLED TO PROTECT OUTPUT WIRING AND
CABINETS.
3.8 MULTIPLE CABINET SYSTEM
When connecting the two or more cabinets in parallel to make a Multiple Cabinet
System, follow the procedure as described below.
Install each cabinet as a single cabinet power source with each cabinet next to
each other. No side clearance is necessary. Connect the input wiring to each
cabinet. See figure 3.8.1 for a Multiple Cabinet System Outline.
Connect a paralleling cable PN (126088) between each cabinet of the paralleled
system. Connect one cable from Cabinet #1-P2 to Cabinet #2-P1. Connect
another cable from Cabinet #2-P2 to Cabinet #3-P1, etc. Connect as many
paralleling cables (up to eleven for a twelve cabinet system) as needed. This
paralleling cable contains all of the control signals necessary to operate the
Multiple Cabinet System.
All five output wires (Chassis, Neutral, Phase A, Phase B and Phase C) from
each cabinet need to be paralleled. Each individual output wire from each
Cabinet to the output load connection MUST BE THE SAME LENGTH AND
WIRE SIZE. Refer to figure 3.8.2 for Multiple Cabinet System Wiring.
For three or more cabinets in parallel an Output Load Center is REQUIRED. The
Output Load Center must contain INDIVIDUAL CIRCUIT BREAKERS, one for
each 3060-MS unit. The circuit breaker must be sized for the individual cabinet's
output voltage and frequency. Pacific Power's Part Number 716048, a 175 Amp
Circuit Breaker may be used for standard 120/208 volt direct coupled output.
Refer to modification or option documentation for other output voltage forms and
frequencies.
Check input service, voltage and frequency, with the service
listed on the Cabinet Identification Plate on the upper rear of the
cabinet.
2.
Check input service ratings. Circuit breakers and wiring to be
sized in accordance with currents listed in Section 3.0. Circuit
breaker time-overload curves should be compatible with
published curves on the Cabinet.
3.
Safety wiring should be sized in accordance with currents listed
in Section 3.6. Ground for the Cabinet shall be connected to the
Cabinet from the building ground.
4.
All power input and output wiring shall be run in individual
conduits. All control wiring shall be contained in separate conduit
runs.
5.
Only one neutral point is to be used by the cabinet. Input neutral
is not connected and is not required. Output neutral shall be
connected at the output neutral terminal. Refer to Figure 3.5.
6.
Verify that all pressure terminations are tightened per
specifications listed in Section 3.6 and 3.7.
3.9 ELECTRICAL SURVEY CHECKLIST
This paragraph provides a comprehensive checklist to be performed prior to first
time power-up of the MS-Series Power Source.
All work must be performed in accordance with applicable local, state, and
national electrical codes. In the event of conflict between this document and the
aforementioned codes, the codes shall be observed. It is requested that in the
event of conflict, the factory be notified.
4.1 INSPECTION OF INSTALLATION
Inspection of the installation is a very important step prior to operation of the MS-
Series AC Power Source. This is done as a safety measure to prevent injury to
personnel or damage to equipment. Before the cabinet is first turned on, the
wiring and distribution system should be checked. Input and output wiring should
be examined carefully.
Solid-state power sources are capable of delivering large amounts of energy.
This is by design and the primary mission of the power source. Make sure that
the loads attached match the output voltage and frequency of the Power Source.
First time operation requires a more in depth inspection than would otherwise be
indicated. Specific items to check on first time turn on are:
1. Proper input voltage brought into the Power Source.
2. Input connections properly tightened. No nicked or damaged wires,
etc.
3. Output connections made properly. Also, are loads attached of the
proper voltage and frequency rating.
The operator should refer to Section 3.0, Installation, if there is any doubt
regarding the above conditions.
4.2 INSTALLATION RECORD
During first time operation, the Power Source Installation Record, Table 4.2,
should be completed. This information will record initial operating parameters as
well as providing the beginning of the maintenance and service record.
After installation of the power source, if commissioning service has been
contracted, contact the Pacific Power Source factory for check-out and initial
turn-on. Two weeks should be allowed in scheduling personnel, with a maximum
of two days normally required on site. The first half of the Installation Record
should be completed prior to the arrival of factory personnel. The second half will
be recorded by factory personnel during the commissioning field service.
If a factory visit has not been contracted, the following record should be
completed by properly trained personnel only.
I1: INPUT V XXX/XXX XXX/XXX XXX/XXX
(AB)NORMAL A XXX XXX XXX
kW XX.X XX.X XX.X
FREQ=XXX.X kVA XX.X XX.X XX.X
O1: CABINET V XXX/XXX XXX/XXX XXX/XXX
OUTPUT A XXX XXX XXX
EFF=XX% kW XX.X XX.X XX.X
FREQ=XXX.X kVA XX.X XX.X XX.X
4.3.1.1 INPUT KEY
The INPUT Key is used to display the current status of all power source input
power parameters. It may be pressed any time while power is applied to the unit.
I1 displayed when the INPUT key is pressed.
NORMAL input power is acceptable.
ABNORMAL input power is not acceptable.
FREQ input frequency.
V input volts, phase to neutral / phase to phase.
A input amps for each phase.
kW input kilowatts for each phase
kVA input kilo-Volt-Amps for each phase.
4.3.1.2 OUTPUT KEY
The OUTPUT Key is used to display the current status of all power source output
power parameters. It may be pressed any time power is applied to the unit. Any
one of several OUTPUT displays can be seen by pressing OUTPUT and one of
the function keys (f1-f4) as follows:
O1 displayed when the OUTPUT then f1 keys are pressed, showing basic
output parameters for that cabinet.
V output volts, phase to neutral / phase to phase
A output amps for each phase.
EFF single cabinet operating efficiency
kW single cabinet output kilowatts for each phase
FREQ output frequency
kVA single cabinet output kilo-Volt-Amps for each phase.
O3: SYSTEM V XXX/XXX XXX/XXX XXX/XXX
SUMMARY A XXXX XXXX XXXX
OUTPUT kW XXX XXX XXX
FREQ=XXX.X kVA XXX XXX XXX
O4: REMOTE V XXX/XXX XXX/XXX XXX/XXX
OUTPUT A XXXX XXXX XXXX
KW XXX XXX XXX
FREQ=XXX.X kVA XXX XXX XXX
O2 displayed when the OUTPUT then f2 keys are pressed, showing output
usage for that cabinet.
V output volts, phase to neutral / phase to phase
%I-PEAK percent of maximum peak amps for each phase.
%kVA percent of maximum kVA for each phase
FREQ output frequency
%kW percent of maximum kilowatts for each phase
O3 displayed when the OUTPUT then f3 keys are depressed, showing system
basic output parameters for multiple cabinet systems.
V output volts, phase to neutral / phase to phase
A total system output amps for each phase.
kW total system output kilowatts for each phase
FREQ output frequency
kVA total system output kilo-Volt-Amps for each phase.
O4 displayed when the OUTPUT then f4 keys are depressed, showing remote
sense metering parameters.
V remote sense output volts, phase to neutral / phase to phase
A total system output amps for each phase.
kW total system output kilowatts for each phase
FREQ output frequency
kVA total system output kilo-Volt-Amps for each phase.
If any OUTPUT display is already active, it is not necessary to press the
OUTPUT key each time to view another message. Simply pressing another f1-f4
key will display the corresponding message.
S4: CAB IS ON - OPERATION NORMAL
V XXX/XXX XXX/XXX XXX/XXX
A XXX XXX XXX
FREQ=XXX.X %LOAD XXX
S5: CAB IS ON - WARNING - OVERLOAD
V XXX/XXX XXX/XXX XXX/XXX
A XXX XXX XXX
FREQ=XXX.X %LOAD XXX
4.3.1.3 STATUS KEY
The STATUS key is used to display the operating status of the Power Source.
This key may be pressed at any time power is applied to the cabinet. Based on
internal sense circuits one of the following messages may be displayed.
S1Displayed when the Power Source is in an Emergency Off state. The
EMER OFF lamp shall be lit.
S2Displayed when the Power Source is in the Normal Off state. The OFF
lamp shall be lit.
S3Displayed when the Power Source is in the Standby state. The STANDBY
lamp shall be lit.
S4Displayed when the Power Source is in the Normal ON state. The ON
lamp shall be lit. Output Frequency and %LOAD (the highest percent load
shown in the Output O2 message) is displayed. Single Cabinet output
volts and amps information are displayed for each phase.
S5Displayed when the Power Source is OVERLOADED. The Power Source
is overloaded when %LOAD is greater than 100%. The ON lamp shall be
lit. Output Frequency and %LOAD (the highest percent load as shown in
the Output O2 message) is displayed. Single Cabinet output volts and
amps information are displayed for each phase.
4.3.1.4 DIAGNOSTIC KEY
The Diagnostic (DIAG) key is dual purpose. First, by saving the cause of the
Emergency Off state, an audit trail is provided for trouble shooting purposes.
Second, technical operating parameters are displayed and recorded for
determining Power Source operational status.
When the DIAG then f1 keys are depressed the cause of the Emergency Off
state is displayed.
OR
When the DIAG then f2 keys are pressed the input transformer temperature in
degrees C and inverter temperature status (OK/Not OK) are displayed.
When the DIAG then f3 keys are pressed the internal High and Low Voltage are
displayed.
When the DIAG then f4 keys are pressed the digital inputs to the Display PCB
are displayed.
D4: PORT # 2 PORT # 3 PORT # 4 PORT # 5
PWR XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX
EMER XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX
NOW XXXXXXXX XXXXXXXX XXXXXXXX XXXXXXXX
BIT
PORT # 2
PORT # 3
7
KYBD f3
ML
6
KYBD f4
INV OVERTEMP
5
MASTER EMER OFF
EMER OFF SW
4
XFMR OVERTEMP
SUSTAINED O/L
3
LVPS FAULT
INPUT LINE FAULT
2
LS
Q6 1 C0
VDC > 240
0
LM
EXT EMER OFF
BIT
PORT # 4
PORT # 5
7
VDC > 160
SPARE
6
INV FAULT
MOD ENABLE
5
S3 CLOSE COMM
SPARE
4
SPARE
SPARE
3
S5 CLOSE COMM
INV TEST OK
2
S7 CLOSE COMM
SPARE
1
C2
INV O/L
0
POLARITY
SPARE
H1: INPUT SERVICE IS NOT CORRECT.
CHECK ALL THREE INPUT PHASES
FOR PROPER VOLTAGE.
This display shows the status of all of the 32 digital inputs to the Display PCB at
the last PWR down (when the + 18 VDC fell below 12.3VDC,) the last EMER off
(when Q6 went hi) and NOW (present real time.)
If a DIAGNOSTIC display is already active, it is not necessary to press the DIAG
key each time to view another message. Simply pressing another f1-f4 key shall
display the corresponding message.
4.3.1.5 HELP KEY
The HELP key is provided to direct the operator with the proper course of action
to turn on and operate the machine. Six different help messages are available
for display. If the HELP key is pressed the first applicable message, H1 through
H6, is displayed.
H1Displayed when the Input Voltage is not within acceptable range.
H2: CABINET IS IN EMERGENCY OFF STATE.
PRESS DIAG KEY TO DETERMINE FAULT.
TO CLEAR FAULT PRESS START/RESET.
IF FAULT REMAINS, SERVICE IS REQUIRED.
H3: SYSTEM IS IN NORMAL OFF STATE.
TO PLACE IN STANDBY, ROTATE THE
MODE SELECT SWITCH TO STANDBY AND
PRESS START/RESET.
H4: SYSTEM IS IN STANDBY STATE.
TO TURN ON THE OUTPUT, ROTATE
THE MODE SELECT SWITCH TO ON.
H5: SYSTEM IS IN ON STATE.
TO READ METERING INFORMATION
PRESS THE ASSOCIATED BUTTON.
H2Displayed when the cabinet is in an Emergency Off State, instructs the
user to press the DIAG then f1 keys to determine the cause of the FAULT.
Instructs the user to press the START/RESET to clear the FAULT.
Instructs the user that service is required if the fault cannot be cleared.
H3Displayed when the cabinet is in a Normal Off State. Instructs the user
how to place the cabinet in the Standby state by rotating the MODE
SELECT switch to the STANDBY position and pressing the
START/RESET button. This will charge up the internal high voltage dc
power supplies and start the inverter operating.
H4Displayed when the cabinet is in the Standby State. The cabinet is ready
to deliver output power but the output contactor is open. Instructs the user
to rotate the MODE SELECT switch to the ON position to turn on the
output contactor.
H5Displayed when the cabinet is in the On State. The cabinet's output
terminals are energized. The output contactor is closed. Instructs the user
to press a button to read metering information.
H6: SYSTEM IS IN ALARM STATE.
PRESS STATUS TO DETERMINE CAUSE
OF ALARM. PRESS ALARM TO SILENCE.
A1: ALARM DISABLED- PRESS f1> OV XXX
AND HOLD ALARM TO ENABLE. f2> UV XXX
USE f1 f2 f3 f4 BUTTONS f3> OF XXX
TO CHANGE LIMITS f4> UF XXX
H6Displayed when the cabinet is in the Alarm State. Instructs the user to
press the STATUS button to determine the cause of the alarm. Instructs
the user to press the ALARM button to silence the audible alarm.
4.3.1.6 ALARM KEY
Whenever ALARM is pressed message A1 appears. It remains displayed until
some other button is pressed. Pressing ALARM momentarily there after has no
effect. Pressing and holding ALARM for 2+ seconds shall cause the ALARM
buzzer to change state between ENABLED and DISABLED (display text changes
accordingly).
Whenever message A1 is displayed, limits are subject to change by use of f1
through f4 buttons.
First press and hold of f1 causes OV to increase at about 5 volts per second.
Second press and hold causes OV to decrease at about 5 volts per second.
Similarly for f2, f3 and f4.
If ALARM is ENABLED and any parameter exceeds its limit the ALARM BUZZER
shall sound. When parameter returns to limits buzzer shall extinguish.
When RAM is cleared, ALARM system shall be DISABLED and default limits
shall be:
OV 132
UV 108
OF 440
UF 47
This feature monitors CABINET PARAMETERS ONLY. No system or remote
parameters are monitored. The alarm shall NOT sound if enabled and the output
contactor is open.
Pressed simultaneously shall cause a software
reset of the display CPU.
OUTPUT/
DIAG/
ALARM:
Pressed simultaneously shall clear the RAM.
OFF
The cabinet is shut off. No power is supplied to the load. A red
LED next to the OFF position is lighted when there is no power
applied to the output and diagnostic checks are OK.
STANDBY
The cabinet is in the Standby State. The internal high voltage
power supplies are energized. The inverter is operating. The
cabinet is ready to deliver output power but the output contactor
is open. A red LED next to the STANDBY position is lighted.
ON
The output terminals are energized. The output contactor is
closed and supplying power to the load. A red LED next to the
ON position is lighted.
4.3.1.7 SPECIAL KEY COMBINATIONS
4.3.2 MODE SELECT, EMERGENCY OFF, AND ON-RESET SWITCHES
As the name implies, these switches control the operational mode of the Power
Source. The operator must be fully familiar with these switches and their function
prior to operating the Power Source.
4.3.2.1 MODE SELECT SWITCH
During normal operation of the MS, control of the cabinet is through the MODE
SELECT switch. The design of the switch is such that only one Mode Position
can occur at any time. The three available switch positions are defined as
follows:
FIGURE 4.3.2 MODE SELECT, EMER OFF, AND START/RESET
4.3.2.2 EMERGENCY OFF AND START/RESET SWITCHES
During normal operation of the Power Source, return to the OFF state is
accomplished through the use of the Mode Select Switch. In the event of an
emergency, the EMER OFF button may be used to cause an immediate
shutdown of the cabinet. Manual reset of the Mode Select switch to the OFF
position, and pushing the START/RESET switch is then required before the
cabinet can be brought back on line.
Two off lamps are used to indicate the Off states. The Emergency Off state is
indicated by a lamp that illuminates the EMER OFF push button. A lamp next to
the OFF text on the Mode Select switch indicates that the cabinet is in the
Normal Off State. The Normal Off state lamp is inhibited from being ON when an
EMERGENCY OFF condition exists.
When power is first applied during turn-on, the cabinet is automatically set to the
Off state. If the cabinet is in the Emergency Off state the operator must switch
the MODE SELECT switch to OFF and press START/RESET to reset the
cabinet. The operator may then proceed to Power Source operation.
These are fixed, crystal controlled frequencies for the
internal oscillator.
VAR
This is a 47 to 500 Hz variable frequency control for the
internal oscillator.
EXT
This selects an external oscillator input for the Power
Source.
SLAVE
In this position this cabinet is a SLAVE to another master in
a Multiple Cabinet System. One and only one cabinet may
be MASTER in a Multiple Cabinet System. The MASTER
Frequency shall control the entire Multiple Cabinet System.
4.3.3 FREQUENCY SELECT SWITCH AND VOLTS ADJUST
These switches also control the operation of the Power Source. The operator
must be fully familiar with these switches and their function prior to operating the
Power Source.
4.3.3.1 FREQUENCY SELECT SWITCH
The primary of the Frequency Select Switch is to control the internal Oscillator. It
also is used to determine whether the cabinet is a MASTER or SLAVE.
4.3.3.2 VOLTAGE ADJUST CONTROLS
The Voltage Adjust Controls control the internal Oscillator output voltage. The
center control is for all three output phases. ØB and ØC are for Phase B and
Phase C trim adjustments only. These controls only work if the cabinet is a
master and the internal oscillator is selected.
BEFORE APPLYING POWER OF ANY KIND TO THE POWER SOURCE, READ
SECTION 4.0 OF THIS MANUAL ENTIRELY AND DO NOT PROCEED UNTIL ITS
CONTENTS ARE FULLY UNDERSTOOD.
!
4.4 OPERATING PROCEDURES
This paragraph describes Power Source modes of operation and the various
operating procedures to be used in operating the MS-Series Power Source.
This section is divided into four sub-paragraphs:
1. Power Source Modes of Operation
Provides definition of Power Source operational states.
2. First Time Turn-On Procedure
To be performed at initial turn-on or when service has been performed.
3. Normal Shut-Down Procedure
To be performed when Power Source power is secured for load maintenance.
4. Emergency Shutdown Procedure
Action taken to secure Power Source output power in emergency situations.
Operation of the MS-Series Power Source has been designed to be simple and
straightforward. This is done for several reasons the primary reason being safety.
The addition of an Emergency Off Switch allows for quick action in the case of an
emergency.
It cannot be stressed too many times that Solid-State Power Sources are
capable of delivering tremendous amounts of energy. Things happen quickly
when something goes wrong. However, good habits and a methodical approach,
when operating this equipment will, avoid most hazards.
The OFF state is achieved by rotating the Mode Select Switch to Off. If the
EMER OFF switch is illuminated, pressing START/RESET is also required to
change the state from EMER OFF to normal OFF.
OFF causes the machine to be dead except for the low voltage power supply.
OFF shall be achieved if the following are true:
A) The EMER OFF lamp is off.
B) The OFF lamp is on.
C) The STANDBY lamp is off.
D) The ON lamp is off.
STANDBY STATE
STANDBY is when the input contactor is closed and the machine is ready to
deliver power to a load but the output contactor is open. The STANDBY lamp is
on. Observe the following start sequence to achieve STANDBY:
A) The EMER OFF lamp is off.
B) The OFF lamp is on.
C) The MODE SELECT switch is rotated to STANDBY.
D) The START/RESET button is pushed.
E) The slow turn on contactor is closed and the modulator is enabled.
F) The main input contactor closes.
G) The slow input contactor opens. The machine is now in STANDBY
ON is when the output contactor is closed and the machine is ready to deliver
power to a load. The ON lamp is on. Observe the following sequence to achieve
ON:
A) The STANDBY lamp is on.
B) The MODE SELECT switch is rotated to ON. The machine is now
in ON mode.
OR
A) The EMER OFF lamp is off.
B) The MODE SELECT switch is in the ON position and the
START/RESET switch is pressed. The machine shall go to
STANDBY mode and then to ON mode.
EMER OFF STATE
EMER OFF causes the machine to be dead except for the low voltage power
supply. The EMER OFF push button shall be lit. The following shall cause an
EMER OFF:
A) EMER OFF BUTTON, the EMER OFF push button has been
pressed.
B) MASTER EMERGENCY OFF, The Master Cabinet is in an
EMERGENCY OFF STATE and this machine is a SLAVE.
C) INPUT LINE FAULT, the input power is not within limits.
D) LVPS FAULT, one of the low voltage power supplies has failed.
E) BUS VOLTAGE > 240 VDC, one of the high voltage power supplies
has exceeded 240 VDC.
F) INVERTER FAULT, one of the inverters has failed.
G) INVERTER OVERTEMP, one of the inverters is too hot.
H) TRANSFORMER OVERTEMP, the large input transformer has
overheated.
I) SUSTAINED OVERLOAD, the power source has been in current
limit for a long time.
J) EXTERNAL EMERGENCY OFF, an external signal has caused an
IF AUTO RE-START IS ENABLED, THE OUTPUT TERMINALS OF POWER SOURCE
MAY BE ENEGRIZED AUTOMATICALLY WHEN INPUT POWER IS APPLIED
SLAVE STATE
SLAVE causes the machine to act as a slave in a multi cabinet system. The
machine is a SLAVE if the FREQUENCY SELECT switch is rotated to SLAVE,
and a MASTER if in any other position. The SLAVE lamp and either EMER OFF,
OFF, STANDBY or ON lamps shall be lit. The control mode shall be determined
by the following table:
FIGURE 4.4.1 SLAVE CONTROL MODE
AUTO RE-START
If AUTO RE-START is enabled, the Power Source shall start AUTOMATICALLY
when input power is applied. The Power Source shall attain the mode as
selected by the MODE SELECT switch if all internal diagnostics check out ok.
Verify the AUTO RE-START option has been disabled by switching S14-1 OFF
(refer to Section 4.5.2, Figure 4.5.2.)
STEP 2:
Inspect the installation. Verify that the wiring is correct (refer to Section 3.0, figure
3.6, and figure 3.7.) If this is first time turn-up operation, complete Table 4.2,
(Installation Record) as operation proceeds.
STEP 3:
Open main breakers of output distribution system. No load should be connected to
cabinet at this point.
STEP 4:
Close input power circuit breaker. The OFF lamp on the Power Source Mode
Select switch should illuminate.
If this lamp does not light the EMER OFF lamp should be on. Press the DIAG then
f1 keys to determine the cause of the EMERGENCY OFF. If the EMERGENCY
OFF is caused by INPUT LINE FAULT, check the input power by pressing the
INPUT key on the front panel. ABNORMAL will be indicate if the input power is not
within limits and NORMAL if input power is within limits. Correct the fault, if any,
and proceed.
Rotate the Mode Select Switch to OFF and press START/RESET. The EMER OFF
indicator will go out.
STEP 5:
Place the cabinet in the STANDBY state by rotating the Mode Select Switch to
STANDBY and pressing the START/RESET button. The STANDBY lamp will
illuminate. The high voltage power supplies are now energized and the inverters
are producing voltage. The output contactor is open. Cabinet output voltages and
frequency may be checked by pressing the OUTPUT then f1 keys on the front
panel.
STEP 6:
If inverter voltage is not at desired levels, it may be changed by adjusting the
VOLTS ADJUST controls on the front panel. The center VOLTS ADJUST control
adjusts all three outputs simultaneously. ØB and ØC are trim adjustments.
Frequency may be changed by using the FREQUENCY SELECT switch. 50, 60,
and 400Hz are fixed crystal stabilized frequencies. The VAR position is variable
from 47 to 500Hz. The EXT position allows external oscillator input on connector
J6. The SLAVE position makes this cabinet a slave.
STEP 7:
Place the cabinet in the ON State by rotating the Mode Select Switch to ON. The
internal output contactor is now closed, and the cabinet is ready to deliver load
power. Cabinet output voltages may be checked by pressing the OUTPUT then f2
keys on the front panel.
STEP 8:
Close main breakers of the output distribution system. Monitor output voltages.
The output voltage should not change as load is applied.
4.4.2 FIRST TIME OPERATION
This procedure is to be used to turn on a one Cabinet Power Source for the first
time, or when service has been performed. Proceed as follows:
Inspect the installation. Verify that the wiring is correct (refer to Section
3.8, figure 3.8.2). Open all Circuit Breakers in the Output Load Center.
STEP 2:
Rotate the MODE SELECT switch to the OFF position for each Cabinet in
the System. Rotate the FREQUENCY SELECT switch to the SLAVE
position for each Cabinet in the system. This should cause an EMER OFF
in ALL Cabinets.
STEP 3:
Select ONE Cabinet to be MASTER. Operate the ONE MASTER Cabinet
as a Single Cabinet Power Source as described in section 4.4.2.
STEP 4:
Verify operation of each Cabinet individually as described in steps 2 and 3
above.
STEP 5:
Rotate the MODE SELECT switch to OFF for all Cabinets. Select ONE
Cabinet, in the middle of the System, to be MASTER. Select all other
Cabinets to be slaves. Disconnect any load from the output of the system.
Close all of the Circuit Breakers at the Output Load Center. Press
OUTPUT then f1 keys on all Cabinets in the system to monitor each
Cabinet's output voltages and currents.
STEP 6:
On the MASTER, turn the Volts Adjust down to 0 VAC. Rotate the MODE
SELECT to ON and press START/RESET. Select one and only one
SLAVE. Rotate its MODE SELECT to ON, and press START/RESET.
Verify the MASTER and SLAVE output currents are less than 10 amps.
STEP 7:
On the MASTER, turn the Volts Adjust up to 120 VAC. Verify the MASTER
and SLAVE output currents are less than 10 amps. If output currents are
large, check for miswires.
STEP 8:
Verify operation of each SLAVE individually as described in steps 6 and 7
above.
STEP 9:
Turn ON all Cabinets in the system. On the MASTER, rotate the MODE
SELECT switch to standby and verify all cabinets go to STANDBY. On
the MASTER, press EMER OFF and observe all Cabinet go to EMER
OFF.
STEP 10:
Connect the load. Bring up the MASTER, then all Cabinets to the
STANDBY state. Leave the MASTER in the STANDBY state. Rotate the
MODE SELECT switch to ON for all the SLAVES. Rotate the MASTER
MODE SELECT to ON. Verify all Cabinet output currents are ±10% of
each other. The system is now fully operational.
4.4.3 PARALLEL CABINET OPERATION
This procedure is to be used to turn on the Paralleled Cabinet System for the first
time, or when service has been performed on a cabinet. Proceed as follows:
To secure power from the Power Source proceed as follows:
STEP 1:
Turn off all loads and open output circuit breaker if provided.
STEP 2:
Rotate the Mode Select Switch to the OFF position. Verify that the
OFF lamp is lit. Verify that the STANDBY and ON lamps are
extinguished.
To secure all power to and from the Power Source proceed as follows:
STEP 1:
Turn off all loads and open output circuit breaker if provided.
STEP 2:
Rotate the Mode Select Switch to the OFF position.
STEP 3:
Open the input power circuit breaker. This removes all power to and
from the cabinet.
4.4.4 NORMAL SHUTDOWN PROCEDURE
This procedure describes how to place the Power Source into the normal Off
state. One of two conditions may be desired when turning off the Power Source:
1. Secure power from the Power Source. Turn off high voltage power
supplies, inverters and output to the load. Control circuits remain active.
2. Secure all power; no power applied to either the Power Source or the
Load.
4.4.5 EMERGENCY SHUTDOWN PROCEDURE
Emergency shutdown is accomplished by depressing the EMER OFF Switch at
any time.
The principle function of the Emergency Off state is to open the input and output
contactors in the event of internal Power Source failure.
A secondary purpose is to protect against overheating of the inverter or input
transformer in the event of excessive load current for extended time (an unlikely
occurrence due to conservative thermal design.)
A third function is to give the operator a quick "Turn Off" means in the event of an
emergency - since pressing EMER OFF is slightly faster than rotating the Mode
Select Switch to Off.
The Emergency Off state can only be removed by rotating the Mode Select
Switch to Off and pressing START/RESET. The EMER OFF lamp will extinguish
and the cabinet will be in a normal Off state.
CHANGING ANY SWITCH POSITION, WITHOUT PROPERLY IDENTIFYING ITS
LOCATION AND PURPOSE, MAY CAUSE SERIOUS EQUIPMENT DAMAGE.
WARNING
IF AUTO RE-START IS ENABLED, THE OUTPUT TERMINALS OF POWER SOURCE
MAY BE ENEGRIZED AUTOMATICALLY WHEN INPUT POWER IS APPLIED
4.5 SETUP SWITCHES
This paragraph describes the PC mounted dip switches contained within the MS-
Series AC Power Source, their purpose and location.
Every effort has been made to simplify the Power Source design and its
maintenance. To this end, many common components are used throughout the
product family. To maintain commonality within the product family, logic switches
are used to convey certain operating characteristics to the cabinet. These
switches are summarized as follows:
Refer to Figure 4.5, Cabinet Assembly Drawing, for PC Board location.
4.6 FEATURE CONNECTORS
This paragraph describes the Feature Connectors contained within the MS-
Series AC Power Source, their purpose, location, and pin numbers. The use of
these connectors is optional. Refer to figure 4.6 for location of these connectors.
4.6.1 P1, P2 PARALLELING
These are used for Paralleling cabinets in multiple cabinet systems. They are
4.6.2 J3 AND J4 SERIAL I/O
This paragraph describes the Serial Ports available on the MS-Series Power
Source.
The MS Series Power Source is provided with Dual Serial Communication Ports
designated COM A and COM B. These output are RS-232-C Ports with bidirectional logic. Power Source status is stored in an internal register and
transmitted through these ports when interrogated.
PHYSICAL CONFIGURATION
Refer to Figure 4.6. J3, or COM A, is a female, DB-25 socket. This socket is a
Data Communications Equipment (DCE) Port configured to be interfaced with a
Data Terminal Equipment (DTE) device such as a "dumb" terminal, or PC set up
as a DTE.
J4, or COM B, is a DTE port configured to be interfaced with a DCE device such
as a modem. A female, DB-25 socket is also provided for this port.
BAUD RATE
The Baud Rates for data transmission are 300, 1200, 2400 or 9600 as selected
by switch S41 on the Display PCB Assembly. (Refer to Figure 4.5.1.)
COMMUNICATION DATA FORMAT
Data is transferred as an 8 bit word with 1 Start,
1 Stop, and no Parity bit.
DATA TRANSMISSION
Serial Port design is such that no "Handshaking" is required in hardware or
software. Due to this fact, data transmitted to the MS must be limited to 5
characters per second. Data bursts are sent from the MS in approximately
200ms increments.
Refer to Table 4.6.2. Hardware handshaking signals, (i.e. TXDA, CTSA, DCDA,
etc) are provided for operator convenience. The MS requires only 3 lines:
Receive, Transmit and Ground.
With the serial port, it is possible to obtain all Front Panel Display information
described in section 4.3.1.
This paragraph provides the syntax and a brief description of all MS recognized
commands. Section 4.3.1 should be reviewed for detailed descriptions of
returned messages.
4.6.5 J8 REMOTE METERING INPUTS
J8 is a Remote Metering Input signal connector. Remote Volts are divided down
by 100 to 1 and sent to this connector. Remote Amps are divided down by 400
to 1 and sent to this connector. This connector is a DA15S type.
Example: 120 VAC, 60 Hz at the remote location = 1.20 VAC, 60 Hz at J8.
Example: 400 AAC, 60 Hz at the remote location = 1.00 VAC, 60 Hz at J8.
Pin Numbers are as follows:
1 Phase A Remote Volts Input
2 Phase B Remote Volts Input
3 Phase C Remote Volts Input
4 Phase A Remote Amps Input
5 Phase B Remote Amps Input
6 Phase C Remote Amps Input
7 Neut Remote Amps Input
8 Gnd
4.6.6 J9 AUXILIARY ALARM OUTPUTS
This connector alerts the user to conditions that cause alarm status in the
cabinet. These are digital 0 to +5 VDC outputs designed to operate small relays
which the user may utilize to operate remote lights and buzzers. This connector
is a DA15S type.
Pin Numbers are as follows:
1 Overload
2 Over/Under Voltage
3 Audible Alarm at Cabinet
4 Undefined
5 No connection
6 No connection
7 -18 VDC
8 Gnd
9 Overtemp
10 Over/Under Frequency
11 Undefined
12 Undefined
13 No connection
14 No connection
15 +18 VDC
Refer to section 4.3.1.6 for information on setting ALARM parameter limits.
Disabling ALARM at the cabinet will be reflected here as no output on pin 3
during an ALARM condition.
Record cabinet input data by pressing the INPUT key on the front
panel display.
STEP 2:
Record cabinet output data by pressing the OUTPUT then f1 and f2
keys on the front panel display.
STEP 3:
Record the current Status message by pressing the STATUS key
on the front panel display.
STEP 4:
Record Diagnostic messages by pressing the DIAGNOSTIC then f1
then f2 then f3 and f4 keys on the front panel display.
STEP 5:
Inspect the cabinet carefully. Listen for noisy fan bearings, etc.
STEP 6:
Turn the unit off and inspect the inside of the cabinet
STEP 7:
Clean the Inverter Air Filters by, first, removing the back panel of
the power source (FIGURE 5.1.1). Use a vacuum cleaner and a
soft brush on the underside of each inverter (FIGURE 5.1.2) to
clean each of the two filters per inverter. If rear access is not
available then remove the inverters per section 6.5.1. Clean and
replace.
STEP 8:
Clean the outside of the machine. Make comments as appropriate
in the maintenance log.
STEP 9:
Turn the unit back on.
5.0 MAINTENANCE
The MS-Series equipment has been designed so that maintenance is kept to an
absolute minimum. This section describes the maintenance requirements of this
equipment. Paragraph 5.1 describes the maintenance required by the Power
Source. If there are any questions please call Pacific Power Source, Inc. at 800854-2433 in the United States. For international support dial 1-949-251-1800.
5.1 MAINTENANCE SCHEDULE
Routine maintenance of the MS equipment consists of the steps below. Pacific
recommends the use of a maintenance checklist of the form shown in FIGURE
5.1.3. to help guarantee regular performance of maintenance. Additionally,
equipment history is then created. This is sometimes helpful when servicing the
equipment, particularly when attempting to solve an application type problem.
MAINTENANCE PROCEDURES (Refer to FIGURE 5.1.3)
The following procedure is recommended to be performed at 3 month intervals.
MS-Series equipment has been designed using a subassembly concept. This
design feature allows for service by replacing a faulty assembly. The service
procedures described in this section will isolate a problem to the replaceable
assembly or component level as appropriate. Printed circuit board assemblies
are considered to be replacement items. Mainframe components such as
contactors, diode bridges, filter capacitors, etc. are considered replaceable
components.
For factory assistance call Pacific Power Source, Inc. at 800-854-2433 (in the
United States. For international support dial 1-949-251-1800)
This section is organized as follows:
Paragraph 6.1 Provides a brief description of each assembly.
Paragraph 6.2 Provides the theory of operation required to
troubleshoot the system.
Paragraph 6.3 Provides step-by-step troubleshooting procedures.
Paragraph 6.4 This section contains schematic diagrams for the
LVPS, Input Power, DC Power Supply and Inverter
assemblies.
Paragraph 6.5 Provides procedures for replacing defective
assemblies.
Paragraph 6.6 Provides procedures for replacing defective
components.
Paragraph 6.7 Provides instructions for returning assemblies for
repair.
6.1 DESCRIPTION
6.1.1 MAINFRAME DESCRIPTION
This paragraph describes the various assemblies and components of the
Mainframe. The function of each assembly and component is described below.
The part numbers listed are to be used when ordering spare assemblies and
components. Refer to Figure 6.1.1 for the location of the assemblies and
components.
The 3060-MS unit. The mainframe assembly contains the main cabinet
components, input transformer and input and output power contactors.
2.
POWER SUPPLY PANEL ASSEMBLY (P/N 126100)
A ±200 VDC power supply for the inverter assemblies. This assembly is not
a replaceable piece, but individual components such as fuses, filter
capacitors and rectifier diodes are field replaceable.
3.
DISCHARGE PCB ASSEMBLY (P/N 126075)
This PCB assembly contains a soldi-state switch which is active during
shutdown sequences to load the high voltage DC supply so that the DC
voltages are discharged to safe levels, less than 48 VDC. This board also
contains signal conditioning circuits that scale down high voltages to low
voltages which are required for the control and display PCB's.
[With the CE Option. a High Voltage DC blocking PCB Assembly (P/N
126370) is mounted with the Discharge PCB Assembly.]
A circuit assembly which contains logic, comparator and oscillator
circuits. This board determines the state of the system and controls the
system function. It also contains a crystal-referenced local oscillator
which develops the output waveform. The oscillator output is a digitally
synthesized sine wave.
2.
MODULATOR PCB ASSEMBLY (P/N 126071)
This circuit assembly receives the output of the oscillator and produces
the pulse-width-modulated signals required to drive the inverter
assemblies.
3.
DISPLAY PCB ASSEMBLY (P/N 126072 or 126172)
This circuit assembly is mounted to the front panel and contains a CPU
which drives an LCD for metering, status, diagnostics and alarms. Two
RS232 serial ports are also available for a remote terminal or modem.
4.
LVPS PCB ASSEMBLY (P/N 126074)
This is a smaller circuit assembly which is used to develop regulated ±18
VDC. This DC voltage is distributed throughout the mainframe and is
used to create low voltage DC for the control circuits on each PCB.
5.
COMPONENTS
C21 and C22, LVPS caps (P/N 720449-95)
S12 and S13, Push button switches (P/N 710023)
EMER OFF lamp (P/N 701024)
B1, fan (P/N 703104)
6.1.2 CONTROL MODULE DESCRIPTION
The function of the various assemblies and components of the Control Module is
described below. The numbers listed are to be used when ordering spare
assemblies and components. Refer to Figure 6.1.2 for the location of the
assemblies and components listed below.
A 21kVA inverter assembly which contains the power circuits that convert DC to
AC and drives the output. The inverter assembly is housed in a metal case.
This inverter assembly has been designed to reduce RFI/EMI.
2.
DRIVER PCB ASSEMBLY (P/N 126270)
This PCB assembly receives control signals from the modulator, provides
isolation and then drives the power transistors. This PCB is a subassembly of
the inverter assembly.
3.
SNUBBER PCB ASSEMBLY (P/N 126272)
This PCB assembly is used to snub voltage spikes on the power transistors.
This PCB is a subassembly of the inverter assembly.
4.
COMPONENTS
C11-13, Feed through cap (P/N 720545-30)
C1-8, Filter cap (P/N 720096-10)
CT1, Current sensor (P/N 703130)
B1 and B2, Fan (P/N 703106)
R1-8, Snubber resistor (P/N 760180-10)
TAS1-4, Temp sensor (P/N 710039)
L1-12, Filter inductor (P/N 530014)
6.1.3 INVERTER DESCRIPTION
The function of the various assemblies and components of the Inverter module is
described below. The part numbers listed are to be used when ordering spare
assemblies and components. Refer to Figure 6.1.3 for the location of the
assemblies and components listed below. Refer to Section 6.5.1 for removal and
replacement procedures.
Improves steady state regulation of the output
voltage.
AUTO RESTART PULSE
Same as POWER ON RESET if selected.
C0
Control mode 0.
C2
Control mode 2.
DISCHARGE
True if S3 CLOSE and S7 CLOSE COMM are false.
EMER OFF SW
True when switch is pressed. Momentary contact
panel switch with integral lamp.
EMER OFF LAMP
Is lit whenever Q6 is true.
ERROR IN
Error signal to the modulator.
ERROR OUT
Error signal from the modulator.
ERROR
System Error signal from the master modulator.
EXT EMER OFF
(External Emergency Off)
External contacts have shorted connector P1-18 to
P1-19 causing an emergency off.
6.2 THEORY OF OPERATION
The basic theory of operation for the MS-Series Power Source is defined in the
information which follows and is provided as technical reference to aid any
troubleshooting of the equipment.
The MS-Series Power Source consists of five basic subsystems which are as
follows:
1. Power Conversion Circuits (Paragraph 6.2.1)
2. System Control Circuits (Paragraph 6.2.2)
3. DC Power Supply Circuits (Paragraph 6.2.3)
4. Metering and Display Circuits (Paragraph 6.2.4)
5. Paralleling Circuits (Paragraph 6.2.5)
Each of the circuits is discussed in detail in each of the above referenced
paragraphs.
When the DIAG then f4 keys are pressed the status inputs to the Display PCB
are displayed (Reference section 4.3.1.4). This display may be used to
determine the state of control terms in the system.
True when Input voltage is less than 80 % of
nominal or greater than 120 % of nominal or 3
PHASE PRESENT is false.
INPUT AMPS
Input amps from current transformers.
INV OVERTEMP
One of the inverters has overheated.
INV HOLD COMM
Inverter Hold Command.
INV FAULT
Is true when INVERTER HOLD COMM and MXEN
are true and INV TST OK is false. Possible shorted
transistor.
INV TST OK
Inverter test OK indicates that the Inverters, 2 per
phase, are switching at approximately 30 kHz and
no fuses are blown. Does not test the quality of the
sine wave being produced and does not care if
inverter is in current limit.
INV VOLTS
Inverter output voltage. Inverter side of the output
contactor.
INV AMPS
Inverter output amps.
INV O/L
Inverter is in current limit.
LM
Local Master, the FREQUENCY SELECT switch is
not in the SLAVE position.
LS
Local Slave, the FREQUENCY SELECT switch is in
the SLAVE position.
LVPS FAULT
Checks ± 12 VDC on PCB's.
MASTER LAMP
Is lit whenever the FREQUENCY SELECT switch is
not in the SLAVE position.
MASTER EMER OFF
The master cabinet is in an EMER OFF state.
ML
Master on line, at least one Cabinet is a Master.
MOD ENABLE
Modulator enable.
OAC
Output AC Normal.
OFF LAMP
Is lit if Q6, S3 CLOSE COMM and S7 CLOSE
COMM are false.
UV Condition exists if output voltage is less than
preset limit. Limit is set by the ALARM KEY.
VDC > 160
Term goes true when both BUSES are greater than
180 VDC. Term goes false when either Bus goes
below 160 VDC.
VDC > 240
True when either Bus voltage exceeds 240 VDC.
XFMR OVERTEMP
Input Transformer has overheated.
XFMR TEMP
Analog signal from embedded thermocouple in input
transformer.
6.2.1 THEORY OF OPERATION - POWER CONVERSION CIRCUITS
The power conversion circuits of the MS-Series power source consist of the
following assemblies:
1. Control PCB which contains the Oscillator
2. Modulator PCB
3. Inverter Assemblies (3 each)
Figure 6.2.1 is a block diagram of the inverter assembly.
The oscillator generates three low level sine waves which are at the fundamental
output frequency. The amplitude of these signals is 4.8 VAC
is set to 120 VAC
. Potentiometers R261, R262 and R263 supply DC voltage
l-n
when the output
rms
levels which control the amplitude of the appropriate oscillator outputs.
Automatic Gain Control (AGC) can be enabled to improve output voltage
regulation. S14 enables or disables and selects local or remote operation of
AGC. When the Frequency Select Switch is in the EXT or SLAVE positions, all
outputs of the oscillator are disabled and will be 0 VAC.
The oscillator output is fed to the modulator PCB which creates a pulse width
modulated digital signal, as required by the inverter assemblies. The modulator
also receives six current signals, two from each inverter assembly, which are
representative of individual inverter assemblies’ output current. These signals
are used to guarantee current sharing between assemblies on the same phase.
The modulator develops the INV AMPS term which is used to drive the system
output ammeter. The output voltage of each phase is fed back to the modulator
PCB. This is done to achieve high waveform quality.
The inverter assembly uses large transistors which switch between the +/- 200
VDC power supplies as controlled by the modulator. The output of this switch is
filtered to create the output sine wave.
6.2.2 THEORY OF OPERATION - CONTROL CIRCUITS
The Control PCB is mounted to the rear of the keyboard sub-panel and performs
the central system control of an MS-Series mainframe. This PCB monitors key
system parameters and either allows or prohibits operation accordingly. Figure
6.2.2 is a block diagram of the system control circuits within the mainframe.
When input power is applied and the input circuit breaker is closed the LVPS is
on. At this point, the Control PCB is performing preliminary diagnostics and will
light the red System Off LED on the front panel when all diagnostic tests have
been passed. The INPUT LINE FAULT signal will be at -12 VDC when all input
diagnostic tests have been passed.
If the machine has an internal fault the EMER OFF push button will light. After
the fault has been cleared, pressing the START/RESET push button will allow
normal operation.
Rotating the MODE SELECT switch to STANDBY and then pressing
START/RESET will turn on S7, the Slow-Turn-On Contactor. Resistors R1, R2
and R3 limit the inrush current during transformer turn on and charging of the
power supply capacitors. At this point the MODULATOR ENABLE signal is high
allowing the inverter to create sine waves at the output. When the power
supplies have charged S3, the input power contactor, will close. Rotating the
MODE SELECT switch to ON will close the output contactor, S5.
Rotating the MODE SELECT switch to OFF will open all input and output
contactors and cause the Discharge PCB to become active. The Discharge PCB
switches in a pair of resistors, R4 and R5, whose sole purpose is to discharge
the DC supplies.
Pressing the red EMER OFF switch will open all input and output contactors and
cause the Discharge PCB to become active. The emergency off flip-flop, Q6, is
also set.
Figure 6.2.2 shows the various control signals used in the system. These signals
are named appropriately to aid understanding.
6.2.3 THEORY OF OPERATION - DC POWER SUPPLY
The low voltage power supply transformer, T2, generates 3 phase 16/28 VAC for
the low voltage DC power supplies and 3 phase 115 VAC for fans and contactor
coils. The LVPS PCB generates a regulated ±18 VDC from the 16/28 VAC. The
Control PCB continuously monitors the ±18 VDC Low Voltage DC supplies. If
any of these become abnormal, logic circuits on the Control PCB will initiate
system shutdown. Refer to Figure 6.2.3 for the block diagram of this circuit.
The main input power transformer, T1, and power supply panel assembly, which
contains the rectifiers, capacitors and DC fuses, make up the main DC Power
Supply Circuits. The main DC Power Supply is a bipolar supply which produces
±200 VDC. This supply is an unregulated supply. It is actually two independent
200 VDC supplies which are stacked on top of each other. The rectifiers are
configured as two, full-wave three-phase bridges. These two bridges are
connected as shown and feed the capacitor assembly. The capacitors filter the
bridge outputs and DC is produced. The common point of this supply is Output
Neutral and is connected to the chassis. Two red LEDs, one for positive and one
for negative, on the Discharge PCB indicate BUS voltages are present.
The Control PCB continuously monitors the ±200 VDC and will shut down the
system if the DC is higher than 240 VDC or lower than 160 VDC.
6.2.4 THEORY OF OPERATION - DISPLAY CIRCUITS
The Display PCB is mounted to the rear of the keyboard sub-panel. The
metering circuits are contained on the Display PCB assembly. A CPU is used to
meter and display system information on an LCD. The Discharge PCB assembly
contains the resistor voltage dividers to scale down system voltages to a low
level. These system voltages are sent to the Control PCB. The Control PCB
provides all input signals (analog and digital), except input amps, to the Display
PCB. CT11-CT13 provide the input current terms required by the Display PCB.
Figure 6.2.4 is the block diagram for the meter and display portion of the MSSeries power source.
The Control PCB drives the EMER OFF, OFF, STANDBY, ON, MASTER and
SLAVE lamps.
6.2.5 THEORY OF OPERATION - PARALLELING CIRCUITS
The paralleling circuits are located on the Control PCB. The Control PCB is
mounted to the rear of the keyboard sub-panel. The Master Cabinet's Control
PCB assembly is central to the system control of a Multi-Cabinet paralleled
system. This PCB monitors key system parameters and either allows or prohibits
operation accordingly. Figure 6.2.5 is a block diagram of the paralleling circuits
within all cabinets of the paralleled system.
P1 and P2 are the paralleling connectors. Tying pin 18 and pin 19 together with
isolated external contacts shall cause an external emergency off of the system.
If a cabinet is a Master and in an EMER OFF state, it will cause all paralleled
cabinets to be in an EMER OFF state. The master EMER OFF must be cleared
first; then any slave EMER OFF may be cleared.
When all slave cabinets have no EMER OFF and the mode select switch is in the
ON position, the MASTER controls total system operation.
Each cabinet in a paralleled system generates its own inverter amps signal. This
signal is summed together to create the system amps signal. System amps is
total amps of the system and may be displayed at any cabinet.