Pacific Power Source certifies that this instrument was thoroughly tested and inspected and found to meet or
exceed its published specifications when it was shipped from the factory.
LIMITED WARRANTY
Pacific Power Source (PPS) warrants each unit to be free from defects in material and workmanship. For the
period of two (2) years from the date of shipment to the purchaser, PPS will either repair or replace, at its sole
discretion, any unit returned to its factory in Irvine, California. This warranty does not cover batteries. It does
not cover damage arising from mis-use of the unit or attempted field modifications or repairs. This warranty
specifically excludes damage to other equipment connected to this unit.
Upon notice from the purchaser within (30) days of shipment of units found to be defective in material or
workmanship, PPS will pay all shipping charges for the repair or replacement. If notice is received more than
thirty (30) days from shipment, all shipping charges shall be paid by the purchaser. Units returned on debit
memos will not be accepted and will be returned without repair.
This warranty is exclusive of all other warranties, express or implied.
TABLE OF CONTENTS
PAGE
1.0 GENERAL
1.1 USING THIS MANUAL ..................................................................................................................1
This manual is written to provide the information required to use the AMX-Series AC Power Source. Operation
of the Models 105-AMX, 108-AMX, 112-AMX, 125-AMX, 140-AMX, 160-AMX, 305-AMX, 308-AMX, 312AMX, 320-AMX, 345-AMX, 360-AMX, 390-AMX, and 3120-AMX is described in this document.
This manual is an Operations Manual. Installation, operation, and calibration are the subjects covered by this
manual.
1.1 USING THIS MANUAL
This manual provides instructions for installation and use of the AMX-Series Power Source equipment. For this
reason, it is very important that the user reads sections 1, 3, and 4 prior to using this equipment. A thorough
understanding of these sections is required to properly operate this equipment.
Section 2 states the specifications of the equipment. Knowledge of this information is required to gain
maximum use of this equipment for a given application. The user is encouraged to read this section in order to
gain a deeper understanding of the capabilities of the AMX-Series Power Source.
Sections 5 and 6 list maintenance and calibration requirements of this equipment. Refer to these sections when
either maintenance or calibration is required.
Section 7 describes service methodology and provides system, sub-assembly, and component part numbers to
aid the user in making factory authorized field repairs.
This equipment is configured with a modular controller. This allows for the creation of systems with various
control characteristics and specifications. This manual describes the operation of the basic power source.
Detailed information relative to the UMC-31 Controller is also included is described in Section 8 of this
manual. The UPC controllers are described in a separate manual. Refer to the UPC-Series Operation Manual
for such information.
Section 9 contains product change notices, errata and data relative to customer specified modifications.
Always read this section before operating the equipment. This is especially true when modifications have been
installed, since these can change system operation.
If questions arise while reading this manual, the user is encouraged to call the Pacific Power Source. Pacific
maintains a toll-free number which is 1-800-854-2433.
- 1 -
SECTION 1 GENERAL
MODEL 305−AMX
w/ UMC−31 Controller
MODEL 360−AMX
w/ UPC−32 Controller
4
FIGURE 1.3
SECTION 1 GENERAL
1.3 GENERAL PRODUCT DESCRIPTION
The AMX-Series Power Source is high-performance AC power conversion equipment. This series of
equipment features models with power ratings from 500 VA to 12 kVA. All systems are designed to fit into the
standard 19 inch rack. These systems are suitable for use as frequency changers as well as sophisticated test
power generators.
All systems are configured with an interchangeable controller. Controller options range from the basic manual
type (UMC-Series) to the sophisticated programmable controller (UPC-Series). The manual controller allows
the user to adjust voltage and frequency. The programmable controller, on the other hand, not only allows
control of voltage and frequency, but also allows the user to simulate virtually any transient (including subcycle waveform disturbance) required for testing today's modern electronic equipment.
The standard output voltage range of the AMX-Series is 0-135 VAC
(0-150 VAC
l-n
Additionally, the Models 112-AMX and 312-AMX can be configured for several output voltage ranges
between and including 0-110 VAC
and 0-150 VAC
l-n
. Optional output transformers are available to provide
l-n
higher voltages. Voltage ratios up to 2.5:1 are available.
The AMX-Series consists of the basic models listed below:
1. Model 105-AMX - 500 VA Chassis capable of 1 or 2 Phase operation. Standard
Output voltage range is 0-135 VAC
, 1φ or 0-270 VAC, 2 Phase. Phase separation fixed at 180°
l-n
when operating in 2 Phase Mode.
2. Model 108-AMX - Same as 105-AMX, but rated for 750 VA output power.
3. Model 112-AMX - Same as 105-AMX, but rated for 1.2 kVA output power. Standard
Output voltage ranges are 0-110 VAC
through 0-150 VAC
l-n
, 1φ or 0-220 VAC through 0-300 VAC,
l-n
2 Phase.
4. Model 125-AMX - Same as 105-AMX, but rated for 2.5 kVA output power. Standard
Output voltage range is 0-150 VAC
, 1φ or 0-300 VAC, 2 Phase.
l-n
5. Model 140-AMX - Same as 105-AMX, but rated for 4.0 kVA output power.
6. Model 160-AMX - Same as 105-AMX, but rated for 6.0 kVA output power.
7. Model 305-AMX - 500 VA Chassis capable of 1, 2, or 3 Phase operation. Standard
Output voltage range is 0-135 VAC
. Phase separation fixed at 180° when operating in 2 Phase
l-n
Mode. In 3 Phase Mode, phase separation is fixed at 120° or programmable.
8. Model 308-AMX - Same as 305-AMX, but rated for 750 VA output power.
9. Model 312-AMX - Same as 305-AMX, but rated for 1.2 kVA output power. Standard
Output voltage ranges are 0-110 VAC
through 0-150 VAC
l-n
, 1φ or 0-220 VAC through 0-300 VAC,
l-n
2 Phase.
10. Model 320-AMX - Same as 305-AMX, but rated for 2.25 kVA output power.
for the Model 125-AMX).
l-n
5
SECTION 1 GENERAL
1.3 GENERAL PRODUCT DESCRIPTION (cont.)
11. Model 345-AMX - Same as 305-AMX, but rated for 4.5 kVA output power.
12. Model 360-AMX - Same as 305-AMX, but rated for 6.0 kVA output power.
13. Model 390-AMX - Same as 305-AMX, but rated for 9.0 kVA output power.
14. Model 3120-AMX - Same as 305-AMX, but rated for 12.0 kVA output power.
External voltage sense is provided on all systems. Systems configured with the programmable controller also
feature Continuous Self Calibration (CSC).
Output voltage and current metering is provided on all systems. Specifications of the metering functions vary
by controller type. Refer to Section 8 or the UPC-Series Operation Manual, as appropriate, for details relative
to the metering functions.
6
SECTION 2 SPECIFICATIONS
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 125-AMX
INPUT VOLTAGE
The Model 125-AMX accepts one of the following three phase input voltages:
INPUT CURRENT
The input current required by the Model 360-AMX at full rated load is stated below. Recommended input
service is also stated.
INPUT CURRENT
V
1) 208 VAC ∆ 31 A
in
2) 220 VAC ∆ 29 A
3) 240 VAC ∆ 27 A
4) 220/380 VAC 17 A
5) 240/416 VAC 16 A
(cost option) 6) 277/480 VAC 14 A
; 40 A Service Recommended
rms
; 40 A Service Recommended
rms
; 40 A Service Recommended
rms
; 20 A Service Recommended
rms
; 20 A Service Recommended
rms
; 20 A Service Recommended
rms
9A
SECTION 2 SPECIFICATIONS
(THIS PAGE INTENTIONALLY BLANK)
9B
SECTION 2 SPECIFICATIONS
INPUT VOLTAGE
The Model 305-AMX accepts one of the following single phase input voltages:
1) 110 VAC ±10%, 47-63 Hz (360-440 Hz optional)
2) 120 VAC ±10%, 47-63 Hz (360-440 Hz optional)
3) 220 VAC ±10%, 47-63 Hz (360-440 Hz optional)
4) 230 VAC ±10%, 47-63 Hz (360-440 Hz optional)
5) 240 VAC ±10%, 47-63 Hz (360-440 Hz optional)
INPUT CURRENT
The input current required by the Model 305-AMX at full rated load is stated below. Recommended input
service is also stated.
INPUT CURRENT
V
in
1) 110 VAC 9 A
2) 120 VAC 8 A
3) 220 VAC 5 A
4) 230 VAC 4 A
5) 240 VAC 4 A
INPUT VOLTAGE
The Model 308-AMX accepts one of the following single phase input voltages:
1) 110 VAC ±10%, 47-63 Hz (360-440 Hz optional)
2) 120 VAC ±10%, 47-63 Hz (360-440 Hz optional)
3) 220 VAC ±10%, 47-63 Hz (360-440 Hz optional)
4) 230 VAC ±10%, 47-63 Hz (360-440 Hz optional)
5) 240 VAC ±10%, 47-63 Hz (360-440 Hz optional)
INPUT CURRENT
The input current required by the Model 308-AMX at full rated load is stated below. Recommended input
service is also stated.
INPUT CURRENT
V
in
1) 110 VAC 14 A
2) 120 VAC 13 A
3) 220 VAC 7 A
4) 230 VAC 7 A
5) 240 VAC 6 A
MODEL 305-AMX
; 20 A Service Recommended
rms
; 20 A Service Recommended
rms
; 15 A Service Recommended
rms
; 15 A Service Recommended
rms
; 15 A Service Recommended
rms
MODEL 308-AMX
; 20 A Service Recommended
rms
; 20 A Service Recommended
rms
; 15 A Service Recommended
rms
; 15 A Service Recommended
rms
; 15 A Service Recommended
rms
10
SECTION 2 SPECIFICATIONS
2.1.2 OUTPUT POWER
OUTPUT VOLTAGE RANGE
DIRECT-COUPLED
The standard output voltage range of the AMX-Series Power Source is 0-135 VAC
Model 125-AMX) when operated in the direct-coupled mode. Additionally, the Models 112-AMX and 312AMX can be configured for several direct-coupled output voltage ranges between and including 0-110 VAC
and 0-150 VAC
TRANSFORMER-COUPLED
The output voltage range of the AMX-Series Power Source varies when operated in the transformer-coupled
mode. Maximum output voltage is determined by the transformer turns ratio. See list below for maximum
output voltage vs. turns ratio.
TURNS RATIO MAXIMUM OUTPUT VOLTAGE (No Load)
1.5:1 204 VAC
2.0:1 273 VAC
2.5:1 341 VAC
OUTPUT CURRENT
FULL-RATED CURRENT
The full-rated output current the AMX-Series Power Source is listed below by model number. Current stated
for output voltage set to 125 VAC
maximum current at reduced voltage. Output current ratings are scaled appropriately when using transformercoupled outputs.
MODEL I
105-AMX 4 A 40 A 2 A 20 A N/A N/A
108-AMX 6 A 40 A 3 A 20 A N/A N/A
112-AMX 10 A 40 A 5 A 20 A N/A N/A
125-AMX 20 A 90 A 10 A 45 A N/A N/A
140-AMX 32 A 140 A 16 A 70 A N/A N/A
160-AMX 48 A 210 A 16 A 70 A N/A N/A
305-AMX 4 A 45 A 2 A 15 A 1.33 A 15 A
308-AMX 6 A 45 A 2 A 15 A 2 A 15 A
312-AMX 10 A 45 A 3 A 15 A 3 A 15 A
320-AMX 18 A 60 A 6 A 20 A 6 A 20 A
345-AMX 36 A 165 A 12 A 55 A 12 A 55 A
360-AMX 48 A 210 A 16 A 70 A 16 A 70 A
390-AMX 72 A 330 A 24 A 110 A 24 A 110 A
3120-AMX 96 A 410 A 32 A 140 A 32 A 140 A
OVERLOAD OPERATION
The AMX-Series Power Source will deliver up to 150% of rated rms output current into unity power factor
loads at full-rated output voltage. Low output power factor, reduced output voltage, and elevated ambient
temperatures will increase the internal dissipation of the power source and can cause overload shutdown due to
over-temperature conditions. Length of time to reach over-temperature varies with the models and the above
parameters.
. These voltages are stated for full rated load and nominal input voltage applied.
l-n
1φ 2φ 3φ
out, rms
I
I
out, pk
(0-150 VAC
l-n
l-n
l-n
l-n
. Refer to the Power Factor Derating chart of Figure 2.1.2(A-N) for
l-n
out, rms
I
I
out, pk
out, rms
I
out, pk
for the
l-n
l-n
14
SECTION 2 SPECIFICATIONS
FIGURE 2.1.2(E2) MODEL 160-AMX OUTPUT DERATING CURVES
Output power is taken from the AMX-Series Power Source via rear panel mounted terminal blocks.
2.2.4 CHASSIS SLIDE MOUNTS
The chassis of the AMX-Series Power Source is designed to accept slide rails. These are provided as a cost
option. For more information, contact your local sales representative or the Pacific Power Source Sales Office.
2.3 ENVIRONMENTAL SPECIFICATIONS
This paragraph lists the environmental requirements of the AMX-Series Power Source.
2.3.1 TEMPERATURE RANGE
The AMX-Series Power Source is rated for full operation in ambient temperatures of 0 - 55°C and where the
relative humidity is in the range of 0 - 95%, non-condensing.
2.3.2 COOLING
The AMX-Series Power Source utilizes thermally regulated forced-air cooling to maintain proper temperatures
throughout. The maximum airflow of the Models 105-AMX, 108-AMX, 305-AMX, and 308-AMX is 100
CFM. The maximum airflow of the Models 112-AMX and 312-AMX is 200 CFM. The maximum airflow of
the Models 125-AMX and 320-AMX is 300 CFM. The maximum airflow of the Models 140-AMX, 160-AMX,
345-AMX, and 360-AMX is 600 CFM. The maximum airflow of the Models 390-AMX and 3120-AMX is
1200 CFM.
2.3.3 THERMAL PROTECTION
The input power transformer is configured with a thermocouple which senses its temperature. Additionally, the
power amplifier PCB assemblies are also configured with temperature sensors. When the transformer or any
power amplifier PCB exceeds maximum safe operating temperature, the output relays are opened and the
Shutdown Lamp, located on the front panel, is lighted.
The shutdown fault is implemented such that it must be manually reset. The fault can be reset after the overtemperature condition has ceased to exist and the Output Power Switch is placed in the "OFF" position.
Sending an Output Off command via the remote interface (applies to programmable systems only) also resets
the shutdown fault, provided that the condition which originally caused the shutdown has been cleared. If the
Output On/Off command is sent via the remote interface and the shutdown condition has not been cleared, the
power source will remain in the shutdown state until the offending condition has cleared.
38
SECTION 3
INSTALLATION
3.0 INSTALLATION
This section describes the installation of the AMX-Series AC Power Source.
3.1 CHASSIS PLACEMENT
The AMX-Series Power Source is designed to fit into the standard 19 inch rack. Provisions for mounting slide
rails are included in the chassis. The chassis can also be used as a bench-top unit, if desired.
* * * W A R N I N G * * *
• THE AMX-SERIES CHASSIS IS HEAVY !
(VARIOUS MODELS WEIGH APPROX 50-180 lbs PER ASSY)
USE EXTREME CARE WHEN MOVING THE UNIT.
• THE MAGNETICS MODULE, MODELS 125-AMX, 140-AMX, 160-AMX,
AND 320-AMX THROUGH 3120-AMX ARE NOT
UNIT MUST BE LIFTED BY TWO OR MORE INDIVIDUALS
IN ORDER TO REDUCE CHANCE OF PHYSICAL INJURY.
* * * W A R N I N G * * *
- - - - - - - - P A C K I N G N O T I C E - - - - - -
IT IS THE CUSTOMER'S RESPONSIBILITY TO ENSURE THAT UNITS ARE
ADEQUATELY PACKAGED WHEN THEY ARE MOVED TO A DIFFERENT
LOCATION. THE UNITS SHOULD ALWAYS BE PACKAGED IN THE
ORIGINAL SHIPPING CONTAINER WHEN MOVED OR RETURNED TO THE
FACTORY FOR SERVICE. INADEQUATE PACKAGING WILL RESULT IN
CHASSIS DAMAGE--INCURRING NON-WARRANTY SERVICE COSTS.
- - - - - - - - P A C K I N G N O T I C E - - - - - -
A ONE-PERSON LIFT.
39
SECTION 3 INSTALLATION
3.1 CHASSIS PLACEMENT
The first step in setting the chassis into place is to remove it from its shipping container. The next step is to
select an appropriate location for the unit. Key points to consider when locating the chassis are:
1. PROXIMITY TO THE LOAD - The power source should be located as close to the load as
possible. This helps to reduce distribution losses. These losses become more critical as the output
frequency increases.
2. VENTILATION - The chassis requires good ventilation to adequately cool the internal components.
Airflow ranges from 200 to 1200 CFM. A minimum of 12 inches front and back clearance is
recommended for proper operation of the Models 125-AMX, 140-AMX, 160-AMX, 320-AMX, 345AMX, 360-AMX, 390-AMX, and 3120-AMX. The air intake for the Models 105-AMX, 108-AMX,
112-AMX, 305-AMX, 308-AMX, 312-AMX, and 320-AMX is located on both sides near the front. A
minimum clearance of two inches on each side and 12 inches to the rear is required for proper
operation of these models.
When the chassis is placed in a 19 inch rack, it must be supported by either chassis slides or full depth angle
brackets. The front panel alone will not support the weight of the chassis. Chassis slides are available from
Pacific Power Source as a cost option. Call factory service for details.
After the location for the chassis is selected, verify that the input voltage of the power source is correct (Input
voltage is stated on the system ID label). If it requires changing, refer to Paragraph 3.3 for instructions.
Also check that the output voltage range is that which is desired. If not, reconfigure to the desired form as
directed by Paragraph 3.2.
After the input voltage form and output voltage range have been verified as correct, slide the chassis into the
rack or set it into its final position. Make input and output connections as stated in paragraphs 3.3 and 3.4,
respectively.
If either the Remote Interface (GPIB or RS-232) or External Sense feature is to be used, refer to paragraphs 3.5
and 3.7 for connection.
(cont.)
40
3.2 OUTPUT VOLTAGE RANGE CONFIGURATION
This paragraph describes the configuration of the Output Voltage Range for the AMX-Series Power Source.
The AMX-Series Power Source can be configured for several different Output Voltage Ranges. The standard
output configurations are:
1) - 0-110 VAC
0-125 VAC
0-135 VAC
0-150 VAC
2) VR1.5 0-204 VAC
3) VR2.0 0-273 VAC
4) VR2.5 0-341 VAC
The 0-110 through 0-150VAC output ranges are direct-coupled outputs and are always available. The
remaining output forms are transformer-coupled. Only one is available when output transformers are installed.
However, systems can be reconfigured for a different range, if required.
Configuration of the output voltage range is set at the time of order. Systems are configured at the factory as
ordered. The System ID label or Magnetics Module ID label will state the factory configured Voltage Range if
transformer-coupled outputs are present. If the output voltage range specified on the System ID label or
Magnetics Module ID label is that which is desired, no further action is required. Otherwise, reconfiguration is
required.
Also described in the following paragraphs are model specific controller details (Transformer Ratio and Amps
to Volts Ratio settings) that, although factory preset, must be set as described if inadvertantly changed or
otherwise modified.
Configuration of the Output voltage consists of
1) Verifying that the appropriate output transformer taps have been selected.
2) Verifying the proper setting of the Transformer Ratio Switch within the UPC.
3) Verifying the proper setting of the Amps to Volts Ratio Switch within the UPC
4) Calibration of the system.
Configuration varies from model to model. The following paragraphs describe the configuration settings of the
available standard output ranges. Refer to the appropriate paragraph for details. When custom output
transformers have been installed, refer to Section 9, Modifications. The instructions stated in Section 9 take
precedence over those listed in the following paragraphs.
3.2.7 OUTPUT VOLTAGE RANGE CONFIGURATION, MODELS 140-AMX, 160-AMX,
345-AMX, 360-AMX, 390-AMX, and 3120-AMX
This paragraph describes the configuration of the Output Voltage Range for the Models 140, 160, 345, 360,
390, and 3120-AMX Power Sources. These models can be configured for either 0-135 VAC
273 VAC
, or 0-341 VAC
l-n
. The 0-204 VAC range is designated as the VR1.5 output form. The 0-273 VAC
l-n
, 0-204 VAC
l-n
range is defined to be the VR2.0 output form, and, finally, the 0-341 VAC range is defined to be the VR2.5
output form. A Magnetics Module (Assembly No. 134310) is required for the 204, 273 and 341 VAC output
forms.
Refer to Figure 3.2.7 for location of components referenced below and range tap selection information.
Conversion to the 204 VAC Output Range (VR1.5) is as follows:
1) Remove the top cover of the Magnetics Module.
2) Wire for 1.5:1 ratio as per wire table of Figure 3.2.7.
3) Replace top cover of Magnetics Module.
4) Connect Magnetics Module to the power source. The Magnetics Module is connected to the power
source by attaching P20 of the Magnetics Module to J20 of the power source. Also be sure to connect
the Chassis GND wire of the Magnetics Module to the CHS GND stud on the rear panel of the power
source.
5) Set the Transformer Ratio Switch of the UPC to 1.5. (Refer to the UPC-Series Operation Manual for
details. This step does not apply to systems equipped with the UMC controller.) The Transformer
Ratio switch is set to 0.0 on systems not equipped with output transformers.
6) Set the Amps to Volts Ratio Switch of the UPC to 15 for the Models 140-AMX, 160-AMX, 345-
AMX, and 360-AMX. Set the Amps to Volts Ratio Switch of the UPC to 30 for the Models 390AMX and 3120-AMX. (Refer to the UPC-Series Operation Manual for details. This step does not
apply to systems equipped with the UMC controller.)
7) Calibrate the power source as stated in Section 6 of this manual.
Conversion to the 273 VAC Output Range (VR2.0) proceeds as above, except that the Magnetics Module is
wired for 2.0:1 ratio and Transformer Ratio Switch of the UPC is set for 2.0.
Likewise, conversion to the 341 V Output Range (VR2.5) proceeds as above, except that the Magnetics Module
is wired for 2.5:1 ratio and Transformer Ratio Switch of the UPC is set for 2.5.
The Transformer Ratio Switch of the UPC is set to 0.0 on systems without transformer-coupled outputs.
While the above procedure can be performed in the field, Pacific Power Source recommends that the system be
returned to the factory when transformer-coupled outputs are to be added to the system. This insures proper
connection and calibration of the entire system.
• DISCONNECT THIS UNIT FROM THE INPUT SERVICE BEFORE REMOVING TOP
COVER.
HIGH VOLTAGE HAZARD PRESENT INSIDE UNIT WHEN TOP COVER IS
REMOVED AND STILL CONNECTED TO INPUT SERVICE.
* * * W A R N I N G * * *
The 140-AMX, 160-AMX, 345-AMX, 360-AMX, 390-AMX, and 3120-AMX Power Sources have been
designed to accept most standard three phase input voltage forms. This is accomplished through the use of a
tapped input power transformer. Configuring the proper input form is simply a matter of setting jumpers in the
appropriate positions. The system is designed for use with input frequencies of 47 to 63 Hz. (Optionally, the
systems may be used with input frequencies of up to 440 Hz. Contact the factory for details.)
Figure 3.3.7 shows the location of the various jumpers which need attention relative to input voltage form. The
position of these jumpers is listed on the accompanying table.
The first step in configuring the input power form is to remove the top cover. Next, connect the jumpers as
stated in the table for the desired input voltage. Refer to the table in Figure 3.3.7 for the proper setting.
After configuring the input voltage form, check connections and insure that they are tight and in the correct
position. Replace the top cover.
- - - C A U T I O N - - -
• CONNECTION OF THIS UNIT TO IMPROPER INPUT VOLTAGES WILL CAUSE
CATASTROPHIC DAMAGE TO THE POWER SOURCE.
• READ THE INPUT VOLTAGE LABEL AND CONNECT TO THAT INPUT VOLTAGE
ONLY. IF THERE ARE ANY QUESTIONS, CONTACT THE FACTORY.
- - - C A U T I O N - - -
The AMX-Series Power Source is then connected to an appropriate distribution panel via an input power cord.
Refer to Paragraph 2.1.1 for minimum input service requirements of the various input voltage forms.
65
SECTION 3 INSTALLATION
FIGURE 3.3.8 AMX-SERIES INPUT WIRING DIAGRAM
66
3.3.8 INPUT POWER WIRING REQUIREMENTS
This paragraph describes the input wiring requirements for the AMX-Series Power Sources. Wire size and
connection techniques are discussed.
* * * W A R N I N G * * *
• LETHAL VOLTAGE PRESENT AT INPUT TERMINALS OF THIS MACHINE.
• ALWAYS CONNECT "CHS or GND" TERMINAL TO EARTH POTENTIAL.
FAILURE TO DO SO WILL CREATE A SHOCK HAZARD.
* * * W A R N I N G * * *
The Models 105-AMX, 108-AMX, 112-AMX, 305-AMX, 308-AMX, 312-AMX, and 320-AMX are supplied
with an input power cord. Install an appropriate plug onto the end of the power cord and connect to the proper
outlet. Refer to paragraph 2.1.1 for recommended input service of the configured input voltage form.
The input power of the Models 125-AMX, 140-AMX, 160-AMX, 345-AMX, 360-AMX, 390-AMX, and 3120AMX is connected to the Input Power Terminal Block located on the rear panel of the power source. In this
case the input wiring is brought to this terminal block from the distribution panel. The connection points are
labeled "A," "B," "C," "N," and "CHS." The input wiring is connected to these points in the appropriate order
with CHS being the safety ground or earth potential. The AMX-Series Power Source is not sensitive to phase
rotation of the input voltage. For all standard DELTA input voltage forms (208, 220, and 240 VAC) and WYE
input voltage forms (220/380 VAC, 240/416 VAC, and 277/480 VAC), the "N" terminal is not used. Refer to
Figure 3.3.8 for the proper wire size to be used with the configured input power form.
- - - C A U T I O N - - -
• CONNECTION OF THIS UNIT TO IMPROPER INPUT VOLTAGES WILL CAUSE
CATASTROPHIC DAMAGE TO THE POWER SOURCE.
• READ THE INPUT VOLTAGE LABEL AND CONNECT TO THAT INPUT VOLTAGE
ONLY.
IF THERE ARE ANY QUESTIONS, CONTACT THE FACTORY.
- - - C A U T I O N - - -
NOTE:
It is the user's responsibility to meet all local and national electrical codes when
installing this equipment.