PAC AL, AL-0252P, AL-0502P, AL-0502PS, AL-0752P Installation Manual

...
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
INTRODUCTION
The Mueller PAC Fre-Heater Model AL is designed to recover heat removed by refrigeration or air conditioning systems and to utilize that heat for heating water. It is a heat recovery system which heats and stores hot water all in one unit. It is easily connected to an existing refrigeration unit, either air or water cooled. PAC Fre-Heater is a de­superheater which removes most or all of the latent heat of the hot discharged gas from the compressor and uses the existing condenser to remove the remaining heat and condense the refrigerant . It is not intended to and should not be used to totally replace the normal air- or water-cooled condenser.
PAC water tanks are rated for 150 psi working pressure and refrigeration circuits are rated for a maximum working pressure of 400 psi.
PAC have a placement for supporting heater by the placement of this element located in the under of the tank. The placement of this element allows the maximum utilization of the refrigerant heat recovery system and minimizes the usage of electricity in directly heating the water.
The outer jacket of all PAC Fre-Heaters is highly corrosion-resistant stainless steel and will remain bright and rust-free with a minimu m of care . Do no t us e ab r a si v e c l ea ni n g ma t er i al s or compounds on the outer jacket as they will scratch the surface. After using any cleaning compounds always rinse with clear water. In coastal areas where the air contains a high salt content, the bright appearance of the Fre-Heater can be maintained by rubbing it with oil or a light grease as soon as it is installed.
Capacity
PAC Fre-Heater is designed for use with air- or water-cooled refrigeration units. The size of the units and refrigeration systems on which each model may be used are shown in Table 1.
2
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Table 1 - PAC Technical Specifications
Model
Water
Connection
Sizes
No. of
Refrig.
Circuits
Water
Connection
Sizes
(inch)
Refrig.
Connection
Sizes
(inch)
Dimension
(cm..)
Weight
(kilogram)
AL-0252P 25 1
1/2”
THREAD
3/8” FLARE 38x44 12
AL-0502P 50 1
1/2”
THREAD
3/8” FLARE 45x53 16
AL-0502PS 50 2
1/2”
THREAD
3/8” FLARE 45x53 16
AL-0752P 75 1
1/2”
THREAD
3/8” FLARE 45x77 21
AL-0752PS 75 2
1/2”
THREAD
3/8” FLARE 45x77 21
AL-1002P 100 1
3/4”
THREAD
3/8” FLARE 52x79 25
AL-1002PS 100 2
3/4”
THREAD
3/8” FLARE 52x79 25
AL-1502P 150 1
3/4”
THREAD
3/8” FLARE 52x110 27
AL-1502PS 150 2
3/4”
THREAD
3/8” FLARE 52x110 27
Fre-Heater Location
The Fre-Heater should be located inside. If it is necessary to locate the Fre­Heater outside, it must be under a cover. The Fre-Heater must be protected from water dripping or spraying, or in any way collecting on the top surface, as this can result in the failure of the heat exchanger. When selecting a location for PAC Fre-Heater, the ability of that location to bear the loaded weight of the Fre-Heater should be a prime consideration. The loaded weights of all PAC Fre-Heaters are listed in Table 1.
PAC Fre-Heater should be located as near as practical to the refrigeration unit(s). The Fre-Heater should not be located where cooling tower or evaporative condenser water will be in continual direct contact with the exterior surface. Careful planning of the Fre-Heater location and plumbing can reduce installation costs and save time during installation and on maintenance in the future.
3
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 1 : PAC Fre-heater Model AL-0252P
Front Side
Back Suspension
4
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 2 : PAC Fre-Heater Model AL-0502P, AL-0502PS
Front Side
Back Suspension
5
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 3 : PAC Fre-Heater Model AL-0752P, AL-0752PS
Front Side
Back Suspension
6
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 4 : PAC Fre-Heater Model AL-1002P, AL-1002PS
Front Side
Back Suspension
7
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 5 : PAC Fre-Heater Model AL-1502P, AL-1502PS
Front Side
Back Suspension
8
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 6 : PAC Connections Model AL-0252P
9
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 7: PAC Connections Model AL-0502P
Figure 8 : PAC Connections Model AL-0502PS
10
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 9 : PAC Connections Model AL-0752P
Figure 10 : PAC Connections Model AL-0752PS
11
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 11 : PAC Connections Model AL-1002P
Figure 12 : PAC Connections Model AL-1002PS
12
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 13 : PAC Connections Model AL-1502P
Figure 13 : PAC Connections Model AL-1502PS
13
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
SECTION 2.0 - INSTALLATION
2.1 Installing Water Piping
PAC Fre-Heater is equipped with 3/4" or 11/2" connections for cold water inlet and hot water outlet, depending on the specific model
The water inlet connection is labeled “Cold” and the outlet connection is labeled “Hot”
The pipe from the “Hot” outlet should go to the conventional water heating system if one is used. See Figures.
A water bypass line should always be provided so the Fre-Heater(s) can be bypassed for service without shutting down the total water heating system.
NOTE: Be sure there are no leaks at the water connections which might cause the insulation to become wet.
IMPORTANT NOTE: To reduce the risk of excessive temperatures and pressures in this water heater, a pressure/temperature relief valve has been installed by the manufacturer and should not be removed. This valve should be provided with a
3
/4" drain line oriented so that any discharge from the valve will exit within 6" above or at any distance below the structural floor and cannot contact any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Any additional protective equipment required by local codes must also be installed. In the event that the pressure/temperature relief valve is damaged or otherwise needs replacement, a combination temperature and pressure relief valve, certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment, as meeting the requirements for Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSIZ 2 1.22-1971, should be installed. The valve must be marked with a maximum set pressure of 150 psig for use on all PAC Fre-Heaters.
!
14
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
If a water mixing valve is installed in the system, make sure that check valves are in both hot and cold water lines. If this precaution is not taken, hot water may be drawn into the cold water system under certain system operating conditions.
In many multi-unit installations, it is advantageous to install a circulating pump and form a loop plumbing circuit through the Fre-Heaters. This will usually increase the heat recovery efficiency of the system by keeping the total system water volume at a uniform temperature and picking up the most available heat from any refrigeration units which may be running. Consult a plumbing supply house for a hot water circulating pump suitable for your particular installation. All pumps used in a Fre-Heater water circulation system must be suitable for potable water use. . Multiple Fre-Heater installations may be piped in parallel if care is taken to assure equal flow through all of the Fre-Heaters. Parallel plumbing is usually reserved for installations having a common refrigeration compressor on all of the Fre­Heaters. Refer to in the Figure.
Under certain circumstances, it may be necessary to operate a high temperature or booster heater loop at temperatures above those attainable or desirable in the Fre-Heater. At those times a piping scheme should be used. This allows the Fre-Heater to operate at its optimum heat reclaim while the system temperature is at a higher level.
Figure 14 : Installing Water Piping
15
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 15 : Installing PAC Fre-Heater (through one circuit into another)
Figure 16 : Installing PAC Fre-Heater in parallel series
16
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Refrigeration Connections
 Mueller Fre-Heaters are shipped with a dry nitrogen holding charge that
must be removed from the Fre-Heater piping before installation of refrigerant piping.
 Good refrigeration practices must be used while installing the Fre-Heater.
These practices are of common knowledge to the experienced refrigeration serviceman, and only a certified, experienced refrigeration serviceman should undertake the refrigeration connection portion of a Fre-Heater installation.
 Inlet and outlet stubs are copper tube for Freon applications and stainless
steel male pipe thread for ammonia applications. The sizes of refrigeration connections for various PAC Fre-Heaters are shown in Table 1.
 On runs 8 metres or less, refrigeration lines to and from the Fre-Heater
should be the same size as the compressor discharge line.
 Avoid long runs whenever possible. However, if necessary to have runs of
more than 8 metres, the lines should be upsized by one tube size. Should there be any question about refrigeration line sizing, the equipment manufacturer’s recommendation should be followed.
 In most instances, refrigeration line runs of over 16 metres should not be
used. If they are, particular care must be taken to avoid oil traps and excessive pressure drop in the lines.
 The refrigeration lines going to and from PAC Fre-Heaters could reach
temperatures of 150°C. The refrigeration lines must be insulated to prevent a burn hazard for personal injury or combustible substances. The insulation will also add to the efficient operation of the Fre-Heater.
 If in making tubing connections, it is necessary to cut openings into the
air-conditioning or refrigeration cabinet, the following must be observed and provided for. Particular care must be taken if the equipment is located outdoors.
Integrity and rain tightness of the cabinet must be maintained.
Do not cut into a control box or enclosure containing live
mechanical parts or electrical wiring. Make openings below any enclosures containing live mechanical parts or electrical wiring.
Tubing must be protected against mechanical damage by the
cabinet. The use of protective bushings is recommended.
Tubing connections must be made by means of high-
temperature soldering or brazing.
17
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Tubing must be routed such that no possibility of contacting
moving parts occurs.
Provide protection for tubing if the likelihood of accidental
damage occurring exists.
Always use a gear-type tubing bender when making bends
tubes. A conduit bender will flatten the tubing and restrict the flow of refrigerant.
When installing tubing through walls or along a structural
member, be sure the tubing is isolated from these members to avoid any transmissions or vibrations that might occur.
Table 1 for the per circuit condensing unit capacity range of the various PAC Fre-Heater units. To assure proper condensing unit operation, stay within the capacity range specified.
A refrigeration unit exceeding the single circuit capacity of a specific PAC Fre-Heater may be connected to two or more Fre-Heater circuits on one or more F re -H ea te rs ha vi ng a combined circuit capacity equal to the refrigeration unit
When making multiple Fre-Heater circuit connections to a single refrigeration unit, the piping to the Fre-Heater circuits should be in parallel. Series (through one circuit into another) piping of the Fre-Heater should not be used.
A refrigerant line discharge muffler is not necessary for proper operation or warranty coverage in a Fre-Heater installation. However, if the Fre-Heater is to be installed in an area where any machine noise would be objectionable, a discharge muffler should be considered as a method of eliminating the normal compressor pulsation noise present in all refrigeration systems.
Typical refrigeration unit piping is shown in Figures
If there is a hot gas defrost valve, an oil separator, and/or a discharge muffler in the compressor discharge line, the Fre-Heater must be installed downstream of it/them. See Figure for an illustration of this.
In the event of extended compressor operation with little or no water usage, it is possible to generate water temperatures which exceed the 100°C setting of the pressure-temperature relief valve. This will result in repeated dumping of hot water through the relief valve.
18
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
To avoid the repeated release of hot water by the pressure/temperature relief valve, should be installed. Installation and operation instructions for the above bypass system are included with these instructions for your reference and the port size is large enough to allow unrestricted refrigerant flow.
For maximum refrigeration unit efficiency and Fre-Heater heat recovery, head pressure controls must be used.
On air-cooled refrigeration units, you must install head-pressure­operated fan controls; and on water-cooled refrigeration units, you must install a head-pressure-operated water valve, if they are not already on the refrigeration units. On many low temperature applications, an auxiliary cooling fan must be installed on the compressor if the condenser fan is cycled to maintain head pressure. Consult the compressor manufacturer for their recommendation if you are in doubt of sufficient air flow for compressor cooling.
Refrigerant Charge
It may be necessary to add additional charge in some refrigeration systems. Check the sight glass and, if necessary, add refrigerant to clear the sight glass. Final charging of the system must be done after the water in the Fre-Heater becomes warm.
Test Run
Turn on the water supply and fill the Model PAC Fre-Heater with water. Ensure that all water and refrigeration connections are leak­free. The unit is then ready for use. Refrigerant charge should be checked after the system has achieved normal operating conditions. Be sure to check for proper operation of any and all controls, valves, etc., installed with or changed during the installation of the Fre­Heater, both in the refrigeration and water systems.
19
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 17 : Installing Refrigerant Charge with Air-Condition
Fig ure 18 : Typical Refrigeration Connections for Single
Refrigeration Unit and Single-Circuit Piping
20
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 18 : Typical Dual Refrigeration Unit Piping
21
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 19 : Fre-Heater Location with Hot Gas Defrost Valve, Oil
Separator, and/or Discharge Muffler in System
22
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 20 : Installing Refrigerant Charge by Heat-Exchanger
23
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Maintenance
In order to achieve the maximum life from your PAC Fre-Heaters the following should be done annually:
1. Remove and check at least one of the two anode rods. Both anode
rods should be replaced
2. Check the operation of the pressure/temperature relief valve by
manually operating it to see that it will freely flow water should it be required to do so. If there is any doubt that it will not function properly, replace it.
3. Check all water fittings, valves, etc. to be sure there are no water
leaks. Repair as necessary.
4. Check the operation of all controls such as the hot gas bypass valve
aquastat, electric element controls, refrigeration head pressure controls, or any other controls necessary for the proper operation of the Fre-Heater and the refrigeration and/or air conditioning systems it is connected to.
24
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Efficiency
Figure 21 :
Result of Electric Power of Compressor with out PAC
25
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 22 : Result of Electric Power of Air-condition and Temperature of
Refrigerant by PAC setting have water in but not flow out
Figure 23 : Result of Electric Power of Air-condition and Temperature of
Refrigerant by PAC setting and water flow out
26
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
Figure 24 : Temperature of water flow out from the Mueller
27
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
APPENDIX
THE COLUMN TOWER
28
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
THE COLUMN TOWER
- If you would like to open an effluent from PAC, you
should turn off the water in and out, then turn on the effluent drain from the tank.
- If the temperature in PAC are between 35-36
Celsius, then there are some water flow out from Pressure Relief Valve. You should adapt to Pressure Relief Valve for flow out the water that higher temperature.
- If the temperature in PAC is more than 80 Celsius
but there are not the effluent flow out from Pressure Relief Valve, you should unscrew for release water in the temperature that you want.
- If the Pressure Relief Valve can not set for that
period so should change a new Pressure Relief Valve.
29
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER
30
Loading...