• Be sure to read this Sheet thoroughly before installation.
• The warnings and precautions indicated in this Sheet contain important information pertaining to your safety. Be sure to observe
them.
• After installing the unit, perform a test run to make sure the unit operates normally. Then, explain to the customer how to operate and
maintain the unit.
• Hand this Sheet, together with the Operating Manual to the customer.
Request the customer to keep them on hand for future use, such as for relocating or repairing the unit.
• This unit is used together as a set with the EV kit (optional).
Before installation, also read the Installation instruction Sheet of the EV kit thoroughly.
WARNING!
• Request your dealer or a professional installer to install the unit in accordance with this Sheet.
An improperly installed unit can cause serious accidents such as water leakage, electric shock, or fire.
If the unit is installed in disregard of the instructions in the Installation instruction Sheet, it will void the
manufacturer’s warranty.
• For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall, water leakage, electric
shock, or fire.
• To install a unit that uses the R410A refrigerant, use dedicated tools and piping materials that have been
manufactured specifically for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than the R22, failure to use
dedicated piping material or improper installation can cause rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or fire.
• Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become abnormally high and
cause the piping to rupture.
This mark indicates procedures which, if improperly performed, might lead to the death or serious
injury of the user.
• Be sure to install the unit as prescribed, so that it can withstand earthquakes and typhoons or other strong
winds.
Improper installation can cause the unit to topple or fall, or other accidents.
• If there is a refrigerant leakage, make sure that it does not exceed the concentration limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such as oxygen starvation.
• If a refrigerant leakage occurs during operation, immediately vacate the premises and thoroughly ventilate
the area.
If the refrigerant is exposed to fire, it will create a hazardous gas.
• Electrical work must be performed in accordance with this Sheet by a person certified under the national or
regional regulations. Be sure to use a dedicated circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause serious accidents
such as electric shock or fire.
• For wiring, use the prescribed type of wires, connect them securely, making sure that there are no external
forces of the wires applied to the terminal connections.
Improperly connected or secured wires can cause serious accidents such as overheating the terminals,
electric shock, or fire.
• Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through
exposure to dust or water.
• Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can cause serious accidents such as electric shock or
fire.
• After the installation, make sure there is no refrigerant leakage.
If the refrigerant leaks into the room and becomes exposed to a source of fire such as a fan heater, stove, or
burner, it will create a hazardous gas.
En-2
Page 3
CAUTION!
• Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fall or the unit to leak water.
• Area filled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen.
It will deteriorate plastic parts, causing the parts to fall or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas,
acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
• Area containing equipment that generates electromagnetic interference.
It will cause the control system to malfunction, preventing the unit from operating normally.
• Area that can cause combustible gas to leak, contains suspended carbon fibers or flammable dust, or
volatile inflammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a fire.
• Do not use the unit for special purposes, such as storing food, raising animals, growing plants, or preserving
precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
• Ground the unit.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod, or a telephone ground wire.
Improper grounding may cause electric shock.
• Install a ground leakage breaker.
If a ground leakage breaker is not installed, it may cause electric shock or fire.
• Perform drain work in accordance with this Sheet, and ensure that the drain water is properly drained.
If the drain processing is improperly installed, water may drip down from the unit, wetting the furniture.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm
to the user, or damage to property.
• Do not touch the fins with bare hands.
En-3
Page 4
2. PRECAUTIONS FOR USING THE ALTERNATIVE REFRIGERANT
PRECAUTIONS FOR USING THE R410A REFRIGERANT
Pay careful attention to the following points :
• Since the working pressure is 1.6 times higher than that of R22 models, some of the piping and installation and service tools are
special. (See the table in the SPECIAL TOOLS FOR R410A section.)
Especially, when replacing a conventional refrigerant (other than R410A) model with a new refrigerant R410A model, always
replace the conventional piping and flare nuts with the R410A piping and flare nuts.
• Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with R22, R407C
and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2 UNF 20 threads per inch.]
• Be more careful than the installation of the refrigerant (other than R410A) models, not to enter foreign matters (oil, water, etc.) and
other refrigerant into the piping. Also, when storing the piping, securely seal the openings by pinching, taping, etc.
• When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and always
charge from the liquid phase side whose composition is stable.
SPECIAL TOOL FOR R410A
Tool name
Gauge manifold
Charging hose
Vacuum pump
Gas leakage detector
Pressure is huge and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high pressure display range –0.1 to 5.3 MPa and a low
pressure display range –0.1 to 3.8 MPa.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Contents of change
PRECAUTIONS FOR USING THE R407C REFRIGERANT
The basic installation work procedures are the same as R22 models.
However, pay careful attention to the following points :
• Mixing R407C with R22, R410A can cause the refrigerant oil to deteriorate. Therefore, do not use tools that were used on an R22,
R410A unit.
• The R407C refrigerant does not contain chlorine. Therefore, a gas leakage detector designed for the R22 refrigerant will not react
to R407C.
En-4
Page 5
3. ACCESSORIES
Do not discard any accessories needed for installation until the installation work has been completed.
Name and Shape
Wall hook bracket
Q’ty
1
Application
For indoor unit
installation
Name and Shape
Wire assebly
Q’ty
Application
For wired remote control
installation
1
Binder
Cloth tape
Tapping screw
Adapter
For remote control cord
binding
1
For indoor unit
installation
1
For wall hook bracket
installation
8
Use as needed
ø12.7-ø9.52 (AS7/9)
1
Please refer to “4-4.2” on
Page 11.
Air cleaning filter
Air cleaning filter frame
Seal A
2
2
For indoor unit
installation
1
En-5
Page 6
4. INSTALLATION WORK
4-1. SELECTING AN INSTALLATION LOCATION
WARNING
Install at a place that can withstand the weight of the indoor unit and install positively so that the unit will not
topple or fall.
CAUTION
• Do not install where there is the danger of combustible gas leakage.
• Do not install near heat sources and the location with high temperature.
• Mount with the lowest moving parts at least 2.3 m above floor or grade level.
• Do not install the unit near a source of heat, steam, or flammable gas.
• If children may approach the unit, take preventive measures so that they cannot reach the unit.
• Avoid the places for installation, where there is oily smoke, machine oil (i.e. factory), salty environment with
direct sea breeze, and too much of dust.
• Install the unit where drainage does not cause any trouble.
• Welding parts may be fretted if the unit is installed where corrosive gas such as sulphurous acid gas is
generated.
• Control may not operate correctly if the unit is installed near machinery which generates electromagnetic ray.
• Install the unit in a well-ventilated place avoiding rains and direct sunlight.
• Install the unit where air from the outlet and noise do not disturb the neighbour.
• Install the indoor and outdoor units, power wiring, signal wiring and remote control wiring 1 m away from
television and radio to avoid distorted images and noise. (However, distorted noise may not be avoidable
even if units and wiring mentioned above are installed 1m away from television and radio depending on
conditions of electrical waves).
Decide the mounting position with the customer as follows:
(1) Install the indoor unit level on a strong wall, which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed. The air should be able to blow all over the room.
(3) Install the unit where the connection pipe can be easily installed.
(4) Install the unit where the drain pipe can be easily installed.
(5) Take servicing, etc. into consideration and leave the spaces shown in Fig. 4.1. Also install the unit where the filter can be removed.
(6) Install the indoor unit where vibrations and noise are not amplified.
En-6
Page 7
4-2. INSTALLATION DIMENSIONS
Provide a service space for inspection purposes.
Do not place any wiring or illumination in the service space, as they will impede service.
Fig. 4.1 Installation Dimensions
60 mm or over
1,500 mm or over
2,300 mm or over
50 mm
or over
Wall hook bracket
90 mm
or over
(Wall cap)
Drain hose
O.D 15.8 - 16.7 mm
I.D 13.8 mm
En-7
Page 8
4-3. INSTALLING THE UNIT
1. DETERMINING THE PIPING DIRECTION
The piping can be connected in the five directions indicated by 1, 2, 3, 4, and 5 in (Fig. 4.2).
When the piping is connected in direction 2 or 5, cut along the piping groove in the side of the front cover with a hacksaw.
When connecting the piping in direction 3, cut a notch in the thin wall at the front bottom of the front cover.
Fig. 4.2
(Rear)
5 Left outlet
2 Right outlet
3 Bottom outlet
1 Rear outlet
4 Left rear outlet
2. INSTALLING THE WALL HOOK BRACKET
CAUTION
Install the wall hook bracket horizontally and perpendicularly.
(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically. If the wall hook bracket is tiled, water will drip
to the floor.
(2) Install the wall hook bracket so that it is strong enough to withstand the weight of an adult.
• Fasten the wall hook bracket to the wall with 6 or more screws through the holes near the outer edge of the bracket.
• Check that there is no rattle at the wall hook bracket.
Fig. 4.3
Wall hook bracket
Tapping screw
Wall hook bracket
Center notch
Hook
String
3. CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING
WARNING
If the wall pipe is not used, the cord interconnecting the indoor and outdoor units may touch metal and cause
electric leakage.
(1) Cut a 65 mm diameter hole in the wall at the position shown in Fig.4.4.
(2) When cutting the wall hole at the inside of the wall hook bracket, cut the hole within the range of the left and right center marks
40 mm below the wall hook bracket.
When cutting the wall hole at the outside of the wall hook bracket, cut the hole at least 10 mm below over.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.
(4) Always align the center of the wall hole. If misaligned, water leakage will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap with vinyl tape, and stick the pipe through the
hole. (The connection pipe is supplied in the installation set.) (Fig. 4.4)
(6) For left piping and right piping, cut the hole a little lower so that drain water will flow freely. (Fig. 4.4)
Fig. 4.4
Wall hook bracket
Lower
65 mm dia. hole
5 to 10
mm low
Center mark
65 mm dia. hole
10 mm
or over
Lower
Fasten with
vinyl tape
(Wall cap)
(Wall pipe)
(Inside)Wall(Outside)
En-8
Page 9
4. FORMING THE DRAIN HOSE AND PIPE
CAUTION
• In order to align the drain hose and drain cap, be sure to insert securely and vertically. Incline insertion will
cause water leakage.
• When inserting, be sure not to attach any material besides water. If any other material is attached, it will
cause deterioration and water leakage.
• After removing drain hose, be sure not to forget mounting drain cap.
• Be sure to fix the drain hose with tape to the bottom of piping.
[Rear piping, Right piping, Bottom piping]
(1) Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape. (Fig. 4.5)
(2) Install the piping so that the drain hose is at the bottom.
(3) Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.
[For Left rear piping, Left piping]
(1) Interchange the drain cap, insulation and the drain hose. (Fig. 4.6)
(2) Align the marks on the wall hook bracket and shape the connection pipe. (Fig. 4.7)
(3) Bend the connection piping at the bend radius of 70 mm or more and install no more than 35 mm from the wall.
Fig. 4.5Fig. 4.6
For left outlet piping, cut off the
piping outlet cutting groove with a
hacksaw.
Remove the drain cap by pulling
Right piping
Bottom piping
Bind with vinyl tape
Pipe (top) Rear piping
Indoor unit drain hose (bottom)
Insulation
Indoor unit
drain hose
Drain cap
at the projection at the end of the
cap with pliers, etc.
And remove the insulation.
Fig. 4.7
Installation method of Drain cap
Please put the heat insulation inside
Connection pipe
(Liquid pipe)
●
all along.
●
Use a hexagonal wrench (4mm at
opposite side) to insert the drain
Bend (R70) with
a pipe bender
Align the marks.
Connection pipe (Gas pipe)
cap, till the drain cap contacts the
tip of drain cock.
Hexagonal
wrench
[Removal method of drain hose]
Remove the screw at the left of drain hose and pull out drain hose. (Fig. 4.8)
[Installation method of drain hose]
Vertically insert the drain hose toward the inside, so that the drain fixture (blue) can accurately align with the screw hole around the drain
cock.
After inserting and before replacing, please reinstall and fix the removed screws. (Fig. 4.9)
Fig. 4.8
Fig. 4.9
No gap
No gap
Drain Cock
Insulation
Drain cap
Screw
Drain fixture (blue)
Drain hose
Screw hole
• Be sure to install around the drain hose connector.
• As the screw is inside, be sure to use screwdriver treated with magnet.
Drain fixture(blue)
Drain cock
Screw
Drain hose
En-9
Page 10
5. Installing the indoor unit
(1) After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on the hooks at the top and bottom of the
wall hook bracket. (Fig. 4.10)
(2) Remove the intake grille.
1 Open the intake grille. (Fig. 4.11)
2 Pull down the knob. (Fig. 4.12)
3 Lift the intake grille upward, until the axle at the top of the intake grille is removed.
(3) Remove the front panel.
1 The thumb is hung on the lower part as shown in the figure, and it pulls to the front, pushing [–] mark, and bottom hooks (two
position) is removed from wall hook bracket. (Fig. 4.13)
2 The front panel bottom is pulled to the front, and bottom hooks is removed indoor unit. (Fig. 4.13)
3 The front panel is pulled to the front, raising the upper surface, and a front panel is removed. (Fig. 4.14)
(4) Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate the bottom of the indoor unit from the wall.
(Fig. 4.15)
Fig. 4.10Fig. 4.11
Connection pipe
(2 mm dia.)
Indoor unit
Fig. 4.12
(Fitting)
Top hooks
Bottom hooks
Intake grille
Knob
Wall hook
bracket
Intake grille
2
1
Fig. 4.13
Push
[–]
mark
Fig. 4.14Fig. 4.15
Front panel
Indoor unit
Screws
(4 position)
Push
Wall hook bracket
2
1
Front panel
Spacer
En-10
Wall hook bracket
Page 11
4-4. PIPE INSTALLATION
Refer to the Installation Instruction Sheet of the outdoor unit for pipe dimension of indoor unit.
1. FLARE PROCESSING
(1) Cut the connection pipe with pipe cutters so that the pipe is not deformed.
(2) Holding the pipe downwards so that cutting cannot enter the pipe and remove the burrs.
(3) Remove the flare nut from the indoor unit pipe and assemble as shown in Table 4.1 and insert the flare nut onto the pipe, and flare
with a flaring tool.
Outer diameter of
pipe d mm
ø 6.35170 to 0.51.0 to 1.59.116.0 to 18.0
ø 9.52220 to 0.51.0 to 1.513.230.0 to 42.0
ø 12.70260 to 0.51.0 to 1.516.649.0 to 61.0
ø 15.88290 to 0.51.0 to 1.519.763.0 to 75.0
ø 19.05360 to 0.51.0 to 1.524.090.0 to 110
Flare nut width
L1 mm
Clutch type flare
tool for R410A
(Clutch type)
Table 4.1
Dimensions A mm
Clutch type flare
tool for R22, R407C
(Clutch type)
Dimension D mm
tolerance
0.0 mm
(
-0.4 mm
)
Tightening torque
N · m
Fig. 4.16
Flare nut width
L1
Die
d
A
Pipe
D
Be sure the flared
part is not crazed or
cracked.
d
2. CONNECTION PIPES
CAUTION
• Be sure to connect the EV kit (optional) that is suitable to the indoor unit.
For installation instructions, refer to the installation instruction sheet of the EV kit.
• Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper, the flare
nut cannot be tighten smoothly. If the flare nut is forced to turn, the threads will be damaged.
• Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection
pipe.
• Hold the torque wrench at the grip, keeping it in the right angle with the pipes as shown in Fig. 4.17, in order
to tighten the flare nut correctly.
When the flare nut is tightened properly by your hand, hold the body side coupling with a separate spanner, then tighten with a torque
wrench (Fig. 4.17, Table 4.1).
Fig. 4.17
Torque wrench
Tighten with two wrenches.
Wrench (fixed)
Flare nut
AS
AS E12/14LUTR-EV14
Table 4.2 Selecting the EV kit
MODELAPPLICABLE EV kit
E07/09LUTR-EV09
Indoor unit
pipe
(body side)
In order to use the R407C or R22 refrigerant, the pipe diameter will not match on the AS E07/09L. Therefore, it is necessary to install
an adapter (standard part).
Connection pipe
En-11
Page 12
4-5. FIELD SETTING
1. SETTING THE ADDRESS
Manual address setting method
CAUTION
• When setting the DIP switch, use an insulated screw driver.
• When handling the PCB, static electricity charged in the body may cause malfunction of the PCB. Follow the
cautions below:
• Touch metal part of the indoor and outdoor units for more than 10 seconds to discharge static electricity
charged in the body.
• Do not touch terminals of parts and patterns implemented on the PCB.
(1) Remove the cord clamp. (Fig. 4.18)
(2) Remove screws of the heat exchanger, and then remove grounding wire. (Fig. 4.19)
(3) Remove three thermistors. (Fig. 4.19)
(4) Remove the connector. (Fig. 4.19)
(5) Remove screw, then remove the control unit. (Fig. 4.20)
Fig. 4.18Fig. 4.19Fig. 4.20
Control unit
Screw
Thermistor
Cord clamp
Screw
Screw
Grounding
Connector
Screw
wire
(6) Set the switches on the PCB.
1 Indoor unit addresses
Dip SW (SW4-1 and SW4-2) ................................ Factory setting “OFF”
• If working in an environment where the wireless remote controller can be used, the addresses can also be set using the remote
controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address and refrigerant circuit address to “00”. (For
information on setting using the wireless remote controller, refer to “4-8. INFRARED ADDRESS SETTING”.)
En-12
Page 13
Table 4.3
Switch SettingSwitch Setting
INDOOR UNITINDOOR UNIT
Indoor unit
address
Refrigerant
circuit
address
10OFFOFFOFFA60ONONOFFC
11OFFOFFOFFB61ONONOFFD
12OFFOFFOFFC62ONONOFFE
13OFFOFFOFFD63ONONOFFF
14OFFOFFOFFE64OFFOFFON0
15OFFOFFOFFF65OFFOFFON1
16ONOFFOFF066OFFOFFON2
17ONOFFOFF167OFFOFFON3
18ONOFFOFF268OFFOFFON4
19ONOFFOFF369OFFOFFON5
20ONOFFOFF470OFFOFFON6
21ONOFFOFF571OFFOFFON7
22ONOFFOFF672OFFOFFON8
23ONOFFOFF773OFFOFFON9
24ONOFFOFF874OFFOFFONA
25ONOFFOFF975OFFOFFONB
26ONOFFOFFA76OFFOFFONC
27ONOFFOFFB77OFFOFFOND
28ONOFFOFFC78OFFOFFONE
29ONOFFOFFD79OFFOFFONF
30ONOFFOFFE80ONOFFON0
31ONOFFOFFF81ONOFFON1
32OFFONOFF082ONOFFON2
33OFFONOFF183ONOFFON3
34OFFONOFF284ONOFFON4
35OFFONOFF385ONOFFON5
36OFFONOFF486ONOFFON6
37OFFONOFF587ONOFFON7
38OFFONOFF688ONOFFON8
39OFFONOFF789ONOFFON9
40OFFONOFF890ONOFFONA
41OFFONOFF991ONOFFONB
42OFFONOFFA92ONOFFONC
43OFFONOFFB93ONOFFOND
44OFFONOFFC94ONOFFONE
45OFFONOFFD95ONOFFONF
46OFFONOFFE96OFFONON0
47OFFONOFFF97OFFONON1
48ONONOFF098OFFONON2
49ONONOFF199OFFONON3
Dip Switch Dip Switch Dip Switch
SW4-1SW4-2SW6SW4-1SW4-2SW6
SW5-1SW5-2SW5-3SW7SW5-1SW5-2SW5-3SW7
0OFFOFFOFF050ONONOFF2
1OFFOFFOFF151ONONOFF3
2OFFOFFOFF252ONONOFF4
3OFFOFFOFF353ONONOFF5
4OFFOFFOFF454ONONOFF6
5OFFOFFOFF555ONONOFF7
6OFFOFFOFF656ONONOFF8
7OFFOFFOFF757ONONOFF9
8OFFOFFOFF858ONONOFFA
9OFFOFFOFF959ONONOFFB
• The indoor unit address can only be set to 0-63.
Rotary Switch
Indoor unit
Dip Switch Dip Switch Dip Switch
adress
Refrigerant
circuit
address
Rotary Switch
En-13
Page 14
2. CUSTOM CODE SETTING
Fig. 4.23
Selecting the custom code prevents the indoor unit mix-up.
(Fig. 4.23)
(Up to 4 codes can be set.)
CUSTOM CODE SETTING FOR INDOOR UNIT
Set the DIP SW 3-1, 3-2, referring to the Table 4.4.
Fig. 4.22
DIP SWITCH (SW1~5)
SW5
SW4
SW3
SW2
SW1
SW8
SW7
SW6
CUSTOM CODE SETTING FOR WIRELESS REMOTE CONTROLLER
1
START/STOP
23
Example : SW3
SW
SW
3-4
3-3
MASTER
CONTROL
SW
3-2
SW
3-1
OFF
ON
Indoor
unit
Remote
controller
DIP SW 3-1
DIP SW 3-2
Confusion
Table 4.4
Custom code
A (Factory setting)
OFF
OFF
4
Code change
A B C D
A B C D
B
ON
OFF
MASTER
CONTROL
C
OFF
ON
D
ON
ON
Press until only the clock is
displayed.
Press for more than 5 seconds
to display the current custom
code. (Initially set to
)
Change the custom code
between
code on the display to the air
conditioner custom code.
to match the
Press again to return to the
clock display. (The custom
code will be changed.)
3. SETTINGS ACCORDING TO THE REFRIGERANT USED
Fig. 4.24
SW5
SW4
SW3
SW2
SW1
SW8
SW7
SW6
SW
3-4
SW
3-3
SW3
SW
3-2
SW
3-1
OFF
ON
Refrigerant
Used
DIP SW 3-4
DIP SW 3-3
Table 4.5
R410A
OFF
(Factory
setting)
OFF
(Factory
setting)
R407C
ON
ON
R22
OFF
(Factory
setting)
ON
CAUTION
Do not operate any switches other than prescribed, as it can cause the unit to operate improperly or malfunction.
En-14
Page 15
4. CONNECTING THE WIRED REMOTE CONTROLLER (IF NECESSARY)
In order to connect the wired/simple remote control to the external switch controller, the wire assembly (standard parts) which is
attached to the indoor unit needs be connected to the end of remote controller cord.
(1) Use a tool to cut off the terminal on the end of the remote controller cord, and then remove the insulation from the cut end of the
cord as shown in Fig. 4.25.
(2) Connect the remote controller cord and wire assembly as shown in Fig. 4.26.
(3) Connect the wire of wired remote control unit to the PCB of Control unit.
(4) Fasten the remote control cord to the EV kit cord with the binder as shown in Fig. 4.27.
Fig. 4.25Fig. 4.26Fig. 4.27
PCB
White
Red
White
Red
Black
Black
Insutated
connection
Connector
To EV kit
Binder
10 mm or less
20 mm
Remote
controller cord
Remote
controller
cord
5. INSTALLING THE CONTROL UNIT
• Refer to Fig. 4.19 and 4.20 to install the control unit, thermistor, and grounding wire.
En-15
Page 16
4-6. ELECTRICAL WIRING
WARNING
• Perform wiring work in accordance with standards so that the air conditioner can be operated safely and
positively.
• Connect the connection cable firmly to the terminal board. Imperfect installation may cause a fire.
• The terminal board numbers should be the same among the indoor units. Also, match the terminal board
numbers of the indoor unit with those of the outdoor unit. If connected improperly, all the PCB may be
damaged.
Make sure that the total electric current* of the indoor units connected to a single power supply is 15 A or less. Exceeding
15 A may cause a fire.
* Determine the total electric current by adding the rated current shown on the rating label of each indoor unit.
CAUTION
• Do not connect power supply wires to the transmission or remote control terminals, as this will damage the
product.
• Never bundle the power supply cord and transmission cord together. Bundling these cords together will
cause miss operation.
• When handling the PCB, static electricity charged in the body may cause malfunction of the PCB. Follow the
cautions below:
• Establish a ground for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor and outdoor units for more than 10 seconds to discharge static electricity
charged in the body.
• Do not touch terminals of parts and patterns implemented on the PCB.
1. ELECTRICAL REQUIREMENT
Table 4.6
Voltage rating230 V
Operating range198 - 264 V
Table 4.7
Recommended
cable size
2
(mm
)
Power supply cord
Transmission cord
Remote controller
cord
*: Use shielded cable in accordance with local rules for remote controller cable.
• To peel the film from the lead wire, use a dedicated tool that will not damage the conductor wire.
Connect to
one side
NO GOOD
• When installing a screw on the terminal board, do not cut the wire by overtightening the screw. On the other
hand, an undertightened screw can cause faulty contact, which will lead to a communication failure.
En-17
Page 18
(1) Connect the connection cable.
(2) Install the cord clamp.
Fig. 4.32
OKNO GOOD
Screw holeScrew holeCodeCode
Do not route the cords over the screw hole.
Fig. 4.33
EV kit cord
Power supply cord
Transmission cord
Connect
Cord clamp
EV kit cord
After connecting the EV kit cord, slide the
tube (included with the EV kit) over the
connector to protect it.
Connect Tube
Binder (Small)
En-18
Screw
Page 19
4-7. FINISHING
• After completing the refrigerant leak check (for details, refer to the Installation instruction Sheet of the outdoor unit), install the
insulation.
(1) Insulate between pipes.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them
with vinyl tape so that there is no gap. (Fig. 4.34)
• For left and left rear piping, butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them
with and vinyl tape so that there is no gap. (Fig. 4.34)
• For left and left rear piping, wrap the area which accommodates the rear piping housing section with cloth tape. (Fig. 4.35)
• For left and left rear piping, bind the connection cord to the top of the pipe with vinyl tape.
• For left and left rear piping, bundle the piping and drain hose together by wrapping them with cloth tape over the range within
which they fit into the rear piping housing section.
(2) Temporarily fasten the connection cord along the connection pipe with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.) (Fig. 4.36)
(3) Securely fasten the EV kit cord to the indoor unit pipe.
(4) Conceal the tube protecting the EV kit connector with the product, etc., so that the customer cannot access it.
(5) Fasten the connection pipe to the outside wall with saddles, etc. (Fig. 4.37)
(6) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain water and wind cannot blow in.
(7) Install the front panel.
1. Firstly, fit the lower part of the front panel, and insert top and bottom hooks. (Three top sides, six bottom sides) (Fig. 4.38)
2. Four screws is attached.
(8) Install the intake grille.
1. The fixing axle of the intake grille is installed on the Panel.
2. Lay down the intake grille.
(9) Fasten the drain hose to the outside wall, etc. (Fig. 4.39)
Check the condition of the drain hose and make sure that it is routed correctly.
Fig. 4.34
Overlap the insulation
Connection pipe
(Heat insulation)
Bind the pipes together
so that there is no gap.
Indoor unit pipe (Heat insulation)
Vinyl tape
Fig. 4.35
Pipe
Drain hose
Wrap with cloth tape
Cloth tape
Fig. 4.36Fig. 4.37
Power supply cord
Transmission cord
EV kit cord
Wall pipe
Connection cord –
Connection
pipe
Drain hose
Fig. 4.38
Bottom hooks
Indoor unit
Bottom hole
(Six position)
(Six position)
Front panel
Top holes (Two sides)
Indoor unit
Fig. 4.39
OK
Drain
hose
Saddle
No Good
No Good
Lifted upWave
No Good
Make sure the drain water is properly drained.
End in water
(Saddle)
Pipe
Top hole (Center)
(Outside wall cap)
Wall
(Outdoors)
Top hooks
(Two sides)
CAUTION
(Sealer putty)
Top hook (Center)
Front panel
En-19
Page 20
4-8. INFRARED ADDRESS SETTING
• This setting cannot be performed in an environment in which the wireless remote controller cannot be used (the wireless remote
controller is an optional parts).
• This setting is unnecessary if the indoor unit address and refrigerant circuit address have been set up in section 4-5.
• Turn the power of the indoor unit ON before starting the setting.
* By turning on the power indoor units initializes EEV, so make sure the piping air tight test and vacuuming have been conducted
before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the power.
1. BUTTON NAME AND FUNCTION
Fig. 4.40
OPERATION
indicator (Red)
TIMER indicator
(Green)
SWING indicator
(Orange)
MANUAL
AUTO
MANUAL AUTO
2. CONFIRMING THE CUSTOM CODE
Check the custom code of the indoor unit and change the custom code of the wireless remote controller accordingly. (To change the
custom code, refer to “4-5.2 CUSTOM CODE SETTING”.)
(1) Press and hold the “FAN CONTROL ” and the “+” buttons.
Whilst holding these 2 buttons, press the “ACL” button.
FAN CONTROL
SET TEMP (+)
ACL
(2) Press the “+” or “-” buttons to select the custom code that
matches the setting with the indoor unit. By selecting the appropriate custom code, the communication between the indoor unit and the wireless RC become possible.
CUSTOM CODE
The initial setting is “ ”
Address setting
mode display
(3) Press the “VERTICAL AIRFLOW ” button to send the code to
the indoor unit.
Pi Pi
Indoor unit
Wrong code:
No Response
3. SETTING THE ADDRESS
Press and hold the “MANUAL/AUTO” button for 3 seconds.
OPERATION
indicator (Red)
Pi Pi Pi
MANUAL
AUTO
MANUAL
AUTO
En-20
Page 21
1 INDOOR UNIT ADDRESS SETTING
(1) Press the “MASTER CONTROL ” button to access
the address setting mode.
(3) Press the “FAN CONTROL ” button to access the address
data setting mode. The address data will flash once this button is pressed.
Address data
(5) Press the “START/STOP ” button once to send the infor-
mation. A beeping noise will be heard if the command is accepted.
(2) Make sure the bottom number address code is ‘01’. If the num-
ber is other than ‘01’, press the “+” or the “-” buttons to alter.
SET “01”
(4) Press the “+” or the “-” buttons to adjust the address data. The
indoor unit address range is between 00 and 63.
Each time the “MASTER CONTROL
” button is
pressed, it switches between 1 unit and 10 units positions.
Range
00 - 63
+:UP
- : DOWN
Change digit
(6) Indoor unit will display the indoor unit address data number on
“TIMER
” (Green) and “SWING ” (Orange) light.
OPERATION
(Red)
TIMER
(Green)
SWING
(Orange)
Pi Pi
Pi ——PiPiPi——
Indoor unit
* In the following cases the setting signal is not read and a buzzer
sounds.
The indoor unit address No. is set out of range (64 or more) :
Pi Pi Pi ———— (3 sec)
The setting of the rotary switch on the PCB is not “00” : Pi Pi
Pi Pi Pi
CHECK ADDRESS SETTING
Press the “SLEEP” button.
Indoor unit
PiPi
CORRECT : Pi——PiPiPiPiPi ——
PiPi
WRONG : Pi————— (3 sec)
ContinuouslyFlashing times of
address numbers
(Example) ADDRESS : 34
OPERATION
indicator (Red)
TIMER indicator
(Green)
SWING indicator
(Orange)
(1 digit)
0.5 sec ON / 0.5 sec OFF
4 times1 - 10 sec
0.5 sec ON / 0.5 sec OFF
3 times1 - 10 sec
Flashing times of
address numbers
(10 digit)
* ADDRESS 0 setting will not indicate TIMER indicator.
En-21
Page 22
2 REFRIGERANT CIRCUIT ADDRESS SETTING
(1) Press the “FAN CONTROL ” button to select the address
code.
Address code
(3) Press the “FAN CONTROL ” button to access the address
data setting mode. The address data will flash once this button is pressed.
Address data
(5) Press the “START/STOP ” button once to send the infor-
mation. A beeping noise will be heard if the command is accepted.
(2) Press the “+” or “-” button to adjust
address code 02.
SET “02”
(4) Press the “+” or the “-” buttons to adjust the address data. The
refrigerant circuit address range is between 00 and 99.
Each time the “MASTER CONTROL
” button is
pressed, it switches between 1 unit and 10 units positions.
Range
00 - 99
+:UP
- : DOWN
Change digit
(6) Indoor unit will display the refrigerant circuit address data
number on “TIMER
OPERATION
(Red)
” (Green) and “SWING ” (Orange) light.
TIMER
(Green)
SWING
(Orange)
Pi Pi
Indoor unit
Pi ——PiPiPi——
* In the following cases the setting signal is not read and a buzzer
sounds.
The setting of the rotary switch on the PCB is not “00” : Pi Pi
Pi Pi Pi
CHECK ADDRESS SETTING
Press the “SLEEP ” button.
Indoor unit
CORRECT : Pi——PiPiPiPiPi ——
WRONG : Pi————— (3 sec)
PiPi
PiPi
En-22
3 sec ON
1 sec OFF
(Example) ADDRESS : 25
OPERATION
indicator (Red)
TIMER indicator
(Green)
SWING indicator
(Orange)
Flashing times of
address numbers
(1 digit)
0.5 sec ON / 0.5 sec OFF
5 times1 - 10 sec
0.5 sec ON / 0.5 sec OFF
2 times1 - 10 sec
Flashing times of
address numbers
(10 digit)
* ADDRESS 0 setting will not indicate TIMER indicator and
SWING indicator .
* ADDRESS display will automatically switched from indoor
unit address to refrigerant circuit address.
3 COMPLETING ADDRESS SETTING
To prevent mistaken reception when performing address setting for another indoor unit, press the MANUAL/AUTO button
for 3 seconds to lock the setting*.
* Press the MANUAL/AUTO button again for 3 seconds to
release the setting lock.
4 COMPLETING ADDRESS SETTINGS FOR ALL INDOOR
UNITS
(1) Turn the power OFF on the indoor unit.
(2) Press the ACL button on the wireless remote control.
Page 23
5. TEST OPERATION
1. TEST OPERATION USING PCB (OUTDOOR UNIT)
• Refer to the Installation Instruction Sheet for the outdoor unit if the PCB for the outdoor unit is to be used for the test operation.
2. TEST OPERATION USING REMOTE CONTROLLER
• Refer to the Installation Instruction Sheet for the remote control unit to perform the test operation using the wireless remote control
unit.
• When the air conditioner is being test run, the OPERATION and TIMER indicators flash slowly at the same time.
6. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After installation is complete, be sure to check the
following check items again.
Table 6.1
Has the indoor unit been installed correctly?
Has there been a check for gas leaks (refrigerant pipes)?
Has heat insulation work been completed?
Does water drain easily from the indoor units?
Is the voltage of the power source the same as that indicated on the label on the indoor unit?
Are the wires and pipes all connected completely?
Is the indoor unit grounded?
Is the connection cable the specified thickness?
Are the inlets and outlets free of any obstacles?
After installation is completed, has the proper operation
and handling been explained to the user?
Is the EV kit connected?
If not performed correctly
Vibration, noise, indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn damage
No operation, heat or burn damage
Short circuit
No operation, heat or burn damage
No cooling, No heating
No cooling, No heating
CHECK BOXCHECK ITEMS
En-23
Page 24
7. ERROR CODES
If you use a wired type remote control, error codes will appear on the remote control display. If you use a wireless remote control, the
lamp on the photodetector unit will output error codes by way of blinking patterns. See the lamp blinking patterns and error codes in the
table below.
Table 7.1
Error display
Error content
(1)
(2)
(1)
(4)
(3)
(1)
(1)
Error code
E:00
E:02
E:04
E:09
E:0b
E:0A
E:11
E:18
E:18
E:13
E:32
E:06
E:1F
E:21
OPERATION
indicator
(2)
(3)
(3)
(4)
(5)
(5)
(6)
Display Method : 0.1 sec. ON / 0.1 sec. OFF flashing
TIMER
indicator
(3)
(4)
(5)
(6)
: 0.5 sec. ON / 0.5 sec. OFF flashing
( ) : Flashing times
SWING
indicator
No error
Model information abnormal
Power supply frequency abnormal
Room temperature thermistor error
Indoor unit heat exchanger thermistor (inlet) error
Indoor unit heat exchanger thermistor (middle) error
Drain abnormal
Communication error 1 (indoor unit ↔ wired / simple remote controller)
Communication error 2 (indoor unit ↔ wired / simple remote controller)
Indoor unit fan error
Outdoor unit error
EEPROM access error
Transmission error
Parallel communication error
En-24
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.