oventrop ovsol Installation Manual

Page 1
OVSOL
Solar System Manual
Solar hot water system installation guide for flat plate and evacuated tube systems.
Page 2
table of contents
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Section One:
General Guidelines and Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Section Two:
Solar thermal system design guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section Three:
Collector Layout Orientation and Siting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Section Four:
Evacuated tube Collector Dimensions and Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . 11
Evacuated tube collector shipping contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Evacuated tube collector mounting systems and shipping contents . . . . . . . .. . . . . . . . . . . 13
Section Five: Flush Roof Mounting
Flush Mounting on Asphalt Shingles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Flush Mounting on Tile Roofs. . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Flush Mounting on Metal Seamed Roofs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Multiple Collector Arrays . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Piping the collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Section Six:
Adjustable Angle Roof Mounting Assembly for rack mounting kits 540 00 28-16, -8 . . . . . . 24
Piping the collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Section Seven: Flat Plate collector installation
Flat Plate collector Dimensions and Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Flat Plate collector mounting systems and shipping contents . . . . . . . . . . .. . . . . . . . . . . 35
Flat Plate collector tilt mounted nstallation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Flat Plate collector ush mounted installation instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Flat Plate collector strut mounted installation instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Section Eight: System Piping
System Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Piping single tanks systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Piping two tanks systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Section Nine: Component Installation
Tank dimensions and capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Regusol pumping station installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Controller Installation and Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Section Ten: System Commissioning and Operation
Fill, Flush, and Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Commissioning / Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Section Eleven:
System Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Section Twelve:
Oventrop Warranty . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
082809
1
Page 3
system components
The OVSOL System for solar energy described in this manual, when properly installed and maintained, meets the minimum standards established by the SRCC.
This certication does not imply endorsement or warranty of this product by the SRCC.
System Contents
System Model
OVSOL 5-16-SC - 1 - 1 80 gallon - - -
OVSOL 5-16-SCE - 1 - 1 - 80 gallon - -
OVSOL 5-16-DC - 1 - 1 - - 80 gallon -
OVSOL 5-16-DCE - 1 - 1 - - - 80 gallon
OVSOL 5-24-SC - 1 1 1 119 gallon - - -
OVSOL 5-24-SCE - 1 1 1 - 119 gallon - -
OVSOL 5-24-DC - 1 1 1 - - 119 gallon -
OVSOL 5-24-DCE - 1 1 1 - - - 119 gallon
OVSOL FP-2-SC 2 - - 1 80 gallon - - -
OVSOL FP-2-SCE 2 - - 1 - 80 gallon - -
OVSOL FP-2-DC 2 - - 1 - - 80 gallon -
OVSOL FP-2-DCE 2 - - 1 - - - 80 gallon
OVSOL FP-3-SC 3 - - 1 119 gallon - - -
OVSOL FP-3-SCE 3 - - 1 - 119 gallon - -
OVSOL FP-3-DC 3 - - 1 - - 119 gallon -
OVSOL FP-3-DCE 3 - - 1 - - - 119 gallon
OVF-32 OV 5-16 OV 5-8
Regusol
EL 130
SIngle Coil
Tank Capacity and Type
Single Coil
Electric
Dual Coil
Dual Coil
Electric
OVF-32 - Oventrop 4’ x 8’ at plate collector
OV 5-16 - Oventrop evacuated tube collector with 16 tubes OV 5-8 - Oventrop evacuated tube collector with 8 tubes
2
082809
Page 4
introduction
OVSOL System
This manual provides installation instructions for OVSOL System for solar domestic hot water heating. The OVSOL solar energy system described in this manual, when properly installed and maintained, meets the minimum standards established by the SRCC.
This certication does not imply endorsement or warranty of this product by the SRCC.
Planning before the installation and use of the solar collector array should include:
l Solar hot water system design.
l Properly sized solar storage tank.
l Properly sized and insulated solar loop (plumbing circuit).
l An air bleed valve at the highest point in the collector circuit located for convenient access.
l Roof penetrations for piping to and from the collector.
l System components for closed loop solar systems—tank, heat exchanger, solar loop circulator,
pressure relief valve, solar controller, expansion tank, ll and drain valves, pressure and temperature
gauges.
l Propylene glycol (antifreeze) to provide protection from frost and high idle mode temperatures of
375 °F.
Requirements for each installation should be fully detailed by a system schematic and specications.
The assembly and installation instructions described in this manual have been carefully prepared. It is very
important to read these instructions thoroughly before proceeding with the collector installation. An effort has
been made to conform procedures in this manual to the specications of various governmental and agency solar
programs. Also, many programs allow substitution of manufacturers’ standards for program standards. If this is the case, the enclosed manual can be used to comply with program standards. Cases where it is unclear whether the enclosed manufacturers’ standards can be substituted for program standards should be brought to
the attention of the particular program administrator or to Oventrop Corporation for clarication.
Be certain to follow all applicable building and safety codes for installations of solar thermal collectors. Compliance with local codes is essential. Local code requirements must be met for penetrating structural
members and re-rated assemblies. Collectors and piping must be installed in such a way that the performance of any structural member or re-rated assembly is not reduced. Be especially aware of safety regulations when
working upon rooftops. It is the buyer’s responsibility to secure all permits and approvals before purchasing and attempting the installation of this equipment.
Specications are subject to change without notice.
Installing Contractor
Company________________________________________
Installer’s name___________________________________
Address_________________________________________
City, State, Zip____________________________________
Phone Number____________________________________
082809
3
Page 5
section one
Guidelines and Precautions
Installing Collector Arrays
It is not recommended to install more than three 16-tube collectors in a series (64 tubes). Larger
installations will require parallel piping for balanced ow through each array. Balancing valves should
be installed on multiple arrays. One roof mounting kit is needed for each single collector module. Each additional collector will require an expansion kit.
Closed Loop and Drainback
OVSOL collectors can be installed for both closed loop and drainback solar heating applications.
Freeze Tolerance Limits
Freeze tolerance limits are based upon the freeze and burst protection of the antifreeze used in the solar closed loop, or the mixture of the glycol-to-water ratio. Oventrop NT-40 is a 40% glycol-to-water mix with freeze protection to -6o F and burst protection to -60o F. Oventrop NT-50 is a 50% glycol-to-water mix with freeze protection to -30o F and burst protection to -60o F. For additional protection, the Regusol 130 EL control has an antifreeze function (“OCF”) that can be programmed to enable the circulator to protect the antifreeze from freezing or thickening.
Shedding Snow
In regions of snow accumulation, evacuated tube collector tilt angles above 50° will shed snow from col­lectors even after severe storms. Therefore, in heavy snow areas, it is critical that collectors be sloped to
at least a 50° tilt angle. If collectors are installed on a at roof in an area that receives heavy snowfall, the
lower end of the units should be at least 18” above the roof level to minimize chances of snow build-up on the bottom of the collectors.
Transport of Collector
The collector should be transported to the roof in parts and then assembled together on the rooftop.
Lightning Protection
In areas of high incidence of lightning, one lightning rod should be considered. If there is a ready-made lightning protection device, please connect it with the collector.
Minimum Inclination Angle of Collector (for Evacuated tube collectors only)
In order to ensure heat pipe delivery, a minimum inclination angle of 25° is necessary for OV SOL-5 collec­tors. If the tilt angle of the roof is not above 25°, please build necessary roof mounting racks.
Precautions
Temperatures in excess of 390 °F are possible in the condenser (top metal protruding bulb) when exposed to bright sunlight or diffused insolation. DO NOT TOUCH the condenser. Store the tubes in a safe location, away from the sun, during the installation of the roof mounting rack. Tubes are installed as the last step. Oventrop Corporation will not be liable for burns or personal injury due to the touching of a hot condenser. Handle the tubes with care to avoid accidental bending of the heat pipe at the condenser which may cause damage to the heat pipe or the vacuum seal.
The maximum solar loop operating pressure is 87 psi. The pressure relief valve must be set to open below 87 psi. A 75 psi pressure relief valve is suggested. Normal operating pressures for a solar closed loop are 25 to 35 psi.
4
082809
Page 6
section two
Solar thermal system design guidelines
Solar hot water systems are simple in principal but complicated in practice. This guide is designed to describe and explain the process for designing a solar hot water system. There are many ways to design a solar hot water system to achieve the same end result. The two system types that Oventrop uses are external heat exchanger systems (i.e. the Regusol X) and Immersed coil heat exchangers (i.e. internal coil tanks). All of Oventrop’s systems are based on one of these two variants.
Solar Design Basics Incoming solar radiation at the earth’s surface on a perfectly clear day is approximately 300 BTU/H
per square foot. With that said, solar collector performance depends on several factors. These factors include, but are not limited to: ambient temperature at the location of the solar collector,
required operating temperature of the working uid in the collector, incoming solar radiation
(energy), geographical location of the collector, shading of the collector, and inclination angle of the collector.
The difference in temperature between the working uid and the ambient temperature drives the heat loss of the solar collector. This temperature difference has the greatest inuence on the solar collector’s thermal efciency. This efciency measures the solar collector’s ability to convert incoming solar radiation to usable heat in the form of a hot working uid. This hot working uid can
be used for any application. The availability of solar radiation (energy) is dependent on weather, time of year, site shading, and collector inclination angle. Throughout the year, the distance of the sun from the horizon will
change from the longest on the rst day of summer to the shortest on the rst day of winter. This
translates to a 47-degree change in the sun’s angle with respect to the collector throughout the year. The optimal inclination angle to minimize this change and maximize year-round performance is equivalent to the latitude at which the collector is located. Shading at the collector site determines the amount of available solar radiation to which the collector is exposed. Understanding that all of the above factors affect the performance of the solar thermal collector, one cannot make a location independent generalization of collector performance. Design conditions are calculated as the maximum instantaneous solar radiation, in other words, the most energy the system can handle at any given time. For design conditions we assume the collector
is at an operating efciency of 75%, on a clear day, facing south, with no shading. Due to this efciency the maximum output of the solar collector at design is rated at 225 BTU/H per square foot. This value is in no
way a guarantee or estimate of any Oventrop collector’s performance. The table below shows the design
BTU/H
rating of each Oventrop solar collector.
Collector Type Design Conditions BTU/H rating
OV 5-16 Evacuated tube collector 6,277 BTU/H OVF-21 Flat plate collector 4,230 BTU/H OVF-32 Flat plate collector 6,615 BTU/H OVF-40 Flat plate collector 8,280 BTU/H
Table 2, below, shows the design ow rates for each Oventrop collector type.
Collector Type Design Flow Rate per collector
OV 5-16 Evacuated tube collector 0.75 GPM
OVF-21 Flat plate collector 0.525 GPM OVF-32 Flat plate collector 0.80 GPM OVF-40 Flat plate collector 1.0 GPM
082809
5
Page 7
These ow rates were chosen based on the collection area of each solar collector and the incoming solar radiation at design conditions. The ow rates allow the collectors to achieve an 18 degree Fahrenheit temperature
rise across the solar loop.
‘The sun is the source, the system is the battery.’
Solar energy is only available for a limited time during each day. It is because of this that the energy must be captured and stored for later use. The amount of energy stored is related to the system operating temperature
(i.e. radiant oor heat at 100F or fan coil units at 180F), the storage volume, and to the maximum temperature in the storage vessel. Maximum energy storage [BTU’s] is calculated using equation 1, below.
Maximum Stored Energy = 8.33 x Storage volume [Gal] x (Max. tank temp. – System operating temp.)
Where, Storage volume is in gallons and all temperatures are in Fahrenheit. Optimization of this equation has determined the design number of gallons per collector. The table below shows the number of gallons of storage recommended per collector.
Collector Type Gallons of Storage per Collector
OV 5-16 Evacuated tube collector 66 Gallons OVF-21 Flat plate collector 27 Gallons OVF-32 Flat plate collector 41 Gallons OVF-40 Flat plate collector 53 Gallons
These storage values are calculated for a national average. Since daily solar radiation varies signicantly from the
South to the North, these storage values are not required, only recommended. Less storage can be used in the northern latitudes and more storage can be used in the southern latitudes. The storage values should only vary plus or minus 5% from the recommended values listed above. Another way to think of solar storage is as the fuel tank of the system. It is used to store energy that can be used over the entire day. In this way the daily load is matched to the daily collector output. Oventrop solar hot water systems are designed to optimize the transfer of energy from the collectors to the solar storage vessel.
Small systems
Internal coil tanks are used for Oventrop smaller systems. This allows for the ease of installation for system packages. Oventrop has pre-packaged solar domestic hot water systems for daily loads of 80 and 115 gallons. Depending on location these packaged systems will provide between 30 and 70 percent of the annual domestic hot water load.
Using a similar conguration as the pre-packaged systems, larger domestic hot water loads can be accommodated.
Variations of small systems are sized by tank size and can be arranged for up to 160 gallons and 230 gallons of daily usage. These small systems are comfortably in the design range of the Regusol EL 130 solar pumping station. This
pumping station is designed for a maximum ow rate of four (4) gallons per minute. Because the Regusol EL 130 is constructed in ¾”, the maximum ow rate is based on the maximum trouble free ow through ¾” pipe.
Medium systems
Medium systems are above the ow range established for the Regusol EL 130 and have increasingly larger storage
requirements. It is for these reasons that the Regusol-X pumping station with heat exchanger was developed.
External heat exchangers provide exibility of design and reduce cost when considering larger storage volume and
collector arrays. The Regusol-X is designed to be used with any storage vessel that is built for hot water storage; it does not require internal heat exchangers.
6
082809
Page 8
The design limits for the Regusol-X are based on the pressure drop through the heat exchanger, the pump capacity, and the maximum output of the heat exchanger. The table below lists the maximum number of collectors allowed to be used with each Regusol-X.
For Single Speed Pumps
Maximum number
Collector Type
OV 5-16 Evacuated tube collector 3 6 8
OVF-21 Flat plate collector 7 9 12 OVF-32 Flat plate collector
OVF-40 Flat plate collector
Using an external heat exchanger allows for either multiple or single tank congurations. As long as the storage is sized correctly the tanks can be in any conguration.
For Three Speed Pumps
Collector Type
OV 5-16 Evacuated tube collector 4 7 8
OVF-21 Flat plate collector 7 10 12 OVF-32 Flat plate collector
OVF-40 Flat plate collector
of collectors on one
Regusol EL130*
5 4
Maximum number
of collectors on one
Regusol EL130*
5 4
Maximum number
of collectors on one
Regusol-X 15**
6 8
5 6
Maximum number
of collectors on one
Regusol-X 15**
6 8
5 6
Maximum number
of collectors on one
Regusol-X 25**
Maximum number
of collectors on one
Regusol-X 25**
* No more than three (3) OV 5-16 tube collectors are to be piped in series through the Regusol EL130 without a booster pump. ** No more than two (2) OV 5-16 tube collectors are to be piped in series through the Regusol X without a booster pump.
082809
7
Page 9
Oventrop Solar Systems Sizing Chart
The following solar sizing charts shows various combinations of solar collector quantities to Regusol pumping stations an the design solar storage volume.
Tank selections are up to the designer for Regusol X systems and larger.
For Single Speed Pumps
Collector
Type
Number of
collectors
1 OVSOL 5-16 package
1.5 OVSOL 5-24 package
2 Regusol EL130 160 Regusol EL130 54 OVSOL FP-2 package Regusol EL130 106 3 Regusol EL130 230 Regusol EL130 81 OVSOL FP-3 package Regusol EL130 159 4 Regusol X-15 264 Regusol EL130 108 Regusol EL130 160 Regusol EL130 212 5 Regusol X-15 330 Regusol EL130 135 Regusol EL130 205 Regusol X-15 265 6 Regusol X-15 396 Regusol EL130 162 Regusol X-15 246 Regusol X-25 318 7 Regusol X-15 462 Regusol EL130 189 Regusol X-25 287 8 Regusol X-25 528 Regusol X-15 216 Regusol X-25 328
9 Regusol X-15 243 10 Regusol X-25 270 11 Regusol X-25 297 12 Regusol X-25 324
OV 5-16 Evacuated tube
collector
Pumping
Station
Storage in
Gallons
OVF-21 Flat plate collector OVF-32 Flat plate collector OVF-40 Flat plate collector
Pumping
Station
Storage in
Gallons
Pumping
Station
N/A
Storage in
Gallons
Pumping
Station
Storage in
Gallons
For Three Speed Pumps
Collector
Type
Number of
collectors
1 OVSOL 5-16 package
1.5 OVSOL 5-24 package
2 Regusol EL130 160 Regusol EL130 54 OVSOL FP-2 package Regusol EL130 106
3 Regusol EL130 230 Regusol EL130 81 OVSOL FP-3 package Regusol EL130 159
4 Regusol EL130 264 Regusol EL130 108 Regusol EL130 160 Regusol EL130 212
5 Regusol X-15 330 Regusol EL130 135 Regusol EL130 205 Regusol X-15 265
6 Regusol X-15 396 Regusol EL130 162 Regusol X-15 246 Regusol X-25 318
7 Regusol X-25 462 Regusol EL130 189 Regusol X-25 287
8 Regusol X-25 528 Regusol X-15 216 Regusol X-25 328
9 Regusol X-15 243 10 Regusol X-15 270 11 Regusol X-25 297 12 Regusol X-25 324
OV 5-16 Evacuated tube
collector
Pumping
Station
Storage in
Gallons
OVF-21 Flat plate collector OVF-32 Flat plate collector OVF-40 Flat plate collector
Pumping
Station
Storage in
Gallons
Pumping
Station
N/A
Storage in
Gallons
Pumping
Station
Storage in
Gallons
8
082809
Page 10
section three
Collector Layout, Orientation, and Siting
Place the collector where it will receive the maximum amount of sunlight available in your location. OVSOL collectors may be installed on a roof, against a south facing wall, or on the ground.
Orientation
Orientation and tilt are critical to performance. The OVSOL collectors should be oriented (faced) as close to true south as practical, although they may be faced as much as 20° east or west of true south with less
than 5% loss in capacity. Because the earth’s magnetic eld is not aligned parallel to the earth’s north-
south axis, there are some parts of the United States where the needle of a magnetic compass can point as much as 20° east or west of true north. There are several ways to determine true south in your area. You
can consult a local surveyor, a plot map in your
local tax ofce, or a recent isogonic chart of the
United States published by the U.S. Coast and Geodetic Survey. Adjust your magnetic com­pass reading according to the meridian nearest to you. Do not use old charts, as there are annual variations in the readings. When using a magnetic compass, beware of standing near large metallic objects or power lines because they will affect the compass readings.
Shading
Trees, chimneys, dormers, other buildings,
new construction, and even fences may shade the collector array, especially in the winter when sun angles
are low and shadows are long. Be sure the collectors are placed where they will be not shaded by these
obstructions. As a rule, no more than 5% of the collector area should be shaded between the hours of 9:00 a.m. and 3:00 p.m. It is highly advised to make use of a solar site selector while determining suitability for a collector site.
Angle of Inclination or Tilt Angle
For domestic water, use an optimum tilt of the site’s latitude plus 5°, although the slope may be 10° greater or less with a capacity loss of under 5% for the system. For a solar space heating system, a steeper tilt angle is important for optimal winter performance. The steeper tilt will favor winter system operations when the sun is low in the sky. Therefore, for space heating systems chose a tilt of latitude plus 15°. The variation of 10° either way will not seriously affect the total annual performance of the system, all other things being equal.
The following chart will help you determine the tilt angle of roof pitches. For space heating systems, always
082809
9
Page 11
have collectors sloped at optimal tilt for winter performance. Install a collector rack for tilt angle support whenever necessary.
Roof Pitch Tilt Angle
4/12 18° 6/12 26° 10/12 39°
Integrating with Building Architecture
Maintaining a pleasing appearance to the building’s architecture is important for adding solar collectors to a roof or on the ground. Most homes are not oriented well for solar gain, so getting the collectors at just the right orientation and tilt may not integrate well with the roof lines.
Roof Pitch Tilt Angle
12/12 45° 14/12 49°
22/12 61°
With domestic hot water systems, there may be greater variations to tilt and orientation without large annual
losses, and in some cases may justify  ush-mounting collectors. Space heating systems must have a
steep slope and be oriented within 30° of true south. For these larger space heating systems, the layout
should integrate into the roo ine. For new construction, integrating OVSOL collectors into the building’s
roof system should be addressed by the solar designer to the architect.
Shedding Snow
A tilt angle of 50° or more is necessary in regions of heavy snowfall and accumulation. Tilt angles of 50° and above will shed snow from OVSOL evacuated tube collectors even after severe storms. It is critical in
heavy snow areas that the collectors be sloped to at least a 50° tilt angle. If collectors are installed on a  at
roof in an area which receives heavy snowfalls, the lower end of the units should be at least 18” above the roof level to minimize chances of snow build-up on the bottom end of the collectors.
Shading
To avoid shading by collectors on each other, the front to front dimension must be 2.5 times the highest point of the front collector.
10
082809
Page 12
section four
Collector Dimensions and Technical Data Dimensions of OVSOL 5 8 or 16 tube collectors
Technical Data:
OVSOL 5 - 8: 87.9L x 38.6W x 7.4D inches
OVSOL 5 -16: 87.9L x 76.4W x 7.4D inches
Gross collector area: OVSOL 5 - 8 22.28 sq. ft. OVSOL 5 - 16 44.67 sq. ft.
Net absorber area: OVSOL 5 - 8 19.37 sq. ft. OVSOL 5 - 16 38.75 sq. ft.
Gross weight: OVSOL 5 - 8 110 lbs. OVSOL 5 - 16 220 lbs
082809
Inclination angle: 25° to 90°
Typical operating temperature: 158 - 248 °F
Stagnation temperature: 375 °F
Pressure drop per module at 1.0 gpm: 0.47 ft/hd
Aluminum nitride absorber
Vacuum grade: 10 mbar
Connection: Dn22 mm tting
11
Page 13
Oventrop OV - 5 Evacuated Tube Solar Thermal Collector
(Eight tube model - 540 00 08, Sixteen tube model 540 00 16)
Contents:
OV - 5, evacuated tube with heatpipe
540 00 08 contains eight (8) tubes 540 00 16 contains sixteen (16) tubes
Dimensions: 79L x 4D inches
2 x Stainless steel collector support rail, 85L x 1.5W x 1.0D inches
Aluminum heatpipe manifold header 540 00 08 contains eight (8) tube connections Dimensions: 76L x 6D inches
Bottom collector support rail with steel spring clips 540 00 08 contains eight (8) tube connections Dimensions: 76L inches
540 00 16 contains sixteen (16) tube connections Dimensions: 38L inches
540 00 16 contains sixteen (16) tube connections Dimensions: 38L x 5-1/4D inches
Evacuated tubes are shipped eight (8) to a box.
12
2 x Aluminum heatpipe manifold header bracket
082809
Page 14
Flush Mounting Kit - Tile Roof 540 00 28-TK
Contents:
4 - Metric thread hex head bolt
540 00 28-TK also contain one bag of piping connection hardware (not shown). The bag contains:
2 - 22 mm connection tee ttings
1 - Manually operated air vent 1 - Temperature sensor thermowell 2 - 22 mm to 3/4 inch adapter pipe 1 - Tube of heatpipe condenser thermal grease
4 - Steel “tile” roof hooks Dimensions: 6L x 2W x 4-1/2H inches
Flush Mounting Kit - Shingle Roof 540 00 28-FM
Contents:
4 - Metric thread hex head bolt
4 - Roof mounting ashing kits
Mounting hole
4 - Steel “shingle” roof hooks Dimensions: 6L x 2W x 4-1/2H inches
540 00 28-FM also contain one bag of piping connection hardware (not shown). The bag contains:
2 - 22 mm connection tee ttings
1 - Manually operated air vent 1 - Temperature sensor thermowell 2 - 22 mm to 3/4 inch adapter pipe 1 - Tube of heatpipe condenser thermal grease
082809
13
Page 15
Adjustable Rack for evacuated tube collectors
- for eight (8) tube collector, 540 00 28-8
- for sixteen (16) tube collector, 540 00 28-16
Contents:
2 - Back support rail (A) 66 inches
1 - Back cross brace 58 inches (540 00 28-16 only)
1 - Back cross brace 50 inches
1 - Back cross brace 32 inches (540 00 28-8 only)
4 - Roof mounting bracket and  ashing kits
22 - Split lock washer Dimensions: 5/16 D.nom. inches
22 - Hex nut Dimensions: 5/16 D.nom. inches
2 - Hinge A
2 - Hinge B
4 - Hinge C
44 - Steel  at washer
Dimensions: 3/8 D.nom. inches
8 - Aluminum spacer bushing Dimensions: 1.0H x 1.0D inches
6 - 5/16 x 2.5 inch hex head bolt
8 - 5/16 x 2 inch hex head bolt
8 - 5/16 x 1 inch hex head bolt
4 - 1/2 x 1.5 inch hex head bolt
540 00 28-8 and 540 00 28-16 also contain one bag of piping connection hardware (not shown). The bag contains:
2 - 22 mm connection tee  ttings
1 - Manually operated air vent 1 - Temperature sensor thermowell 2 - 22 mm to 3/4 inch adapter pipe 1 - Tube of heatpipe condenser thermal grease
14
082809
Page 16
Flush mounting kit - Metal Seam Roof 540 00 28-MS
Contents:
4 - Metric thread hex head bolt
4 - Steel roof hooks Dimensions: 6L x 2W x 4-1/2H inches
540 00 28-MS also contain one bag of piping connection hardware (not
Mounting hole
4 - Metal seam clamp kit
Metal seam clamp kit contains: 1 - Aluminum clamp block 1 - 3/8 x 3/4 inch hex head bolt 1 - Flat washer, 3/8 inch 4 - 3/8 x 3/4 inch set screw
shown). The bag contains:
2 - 22 mm connection tee ttings
1 - Manually operated air vent 1 - Temperature sensor thermowell 2 - 22 mm to 3/4 inch adapter pipe 1 - Tube of heatpipe condenser thermal grease
Connection Kit for evacuated tube collectors 540 00 21, for 540 00 08 and 540 00 16
Contents:
1 - Extruded aluminum manifold sleeve Dimensions: 2W x 5-1/4D inches
1 - 22 mm straight compression coupling
1 - Bottom support rail connection L-bracket Dimensions: 8L x 1.0W x 1.0H inches
2 - Metric thread hex head bolt
082809
2 - Metric thread at washer
2 - Metric thread hex head nut
15
Page 17
section ve
Collector Assembly
Flush Roof Mounting Collector foot measuring details for Shingle Roof Kit (540 00 28-FM, Tile Roof Kit (540 00 28-TK), and Metal Seam Roof Kit (540 00 28-MS)
Measure the Installation Area
Once the collector location is determined, lay out the four mounting feet of each collector within the dimensions listed below:
8 tube collector: ‘A’ = 16 to 25 inches;
‘B’ = 63 to 80 inches
center manifold on collector feet spacing
16 tube collector: ‘A’ = 48 to 66 inches; ‘B’ = 63 to 80
inches
B 63” - 80”
Flush Mounting on Asphalt Shingles (for mounting with supplied ashing kit see next page)
Shingle Roof Kit (540 00 28-FM)
Mounting of Collector Feet
Collector feet may be lag bolted into the roof rafters. Since most roof trusses or rafters are built on 16-inch centers, locate the comers so that the width dimension falls on the 16-inch center. To locate the nearest
rafters, use a stud nder. Once the rafter is located, drill a small diameter pilot hole to verify the rafter’s center line. Be sure to lift the upper shingle and predrill into the underlying (covered) row to prevent water
leaks. Lift shingles carefully to avoid tearing. Always seal pilot holes not being used.
8 tube: 16” - 25”
16 tube: 48” - 66”
A
Roof Hooks
Mark the pilot hole for the center line of the roof rafter or truss. Next, pre-drill two holes for each collector foot into the center line of the rafter using a drill bit smaller in diameter than the lag bolt supplied. Apply a generous amount of polyurethane sealant around and within the pre-drilled hole. Screw the collector feet in place. Avoid over-tightening and stripping the lag bolts. You may apply a small amount of sealant to the lag bolt heads to prevent water leakage. The important thing is to locate the collector feet atop roof joists so that the weight of the collector is supported. Select rafters so that two tubes will overhang to the right and left for an 8-tube module. For a 16-tube module, you may allow up to four tubes to overhang to the left and right of the rafters. The overhangs are necessary for better weight distribution.
16
082809
Page 18
Flashing
The bracket is to be fastened to the base plate through the
hole closest to the vertical.
Installing the collector feet and ashing
No need to remove any shingles to install the ashing. Base plate is rst screwed into a roof rafter or block and ashing is slided under the roof shingle covering the
installed base plate.
Tools Required:
- Cordless drill with #2 square drive bits
- Tape measure, stud nder, chalk line
1. Locate the rafters and snap horizontal and vertical lines to mark the installa-tion position for each upper mounting foot. Blocks, installed in the attic, may have to be posi­tioned between the rafters to make sure the base plate has a structural member to screw into.
Base Plate
Sealant must be applied to
any penetration of the roof
082809
2. Install the base plate with the square drive screws. Mark the screw locations and apply polyurethane sealant at
the penetrations. The baseplate must be securely at-
tached atop the roof and into the roofs structural member.
3. Install ashing by sliding it into place under then next row of shingles. cover base plate with the ashing pocket .
4. Install the collector foot onto the ashing using
neoprene-bonded washer and stainless locking nut.
17
Page 19
Flush Mounting on Tile Roofs Tile Roof Kit (540 00 28-TK)
Mounting of Collector Feet
On a tiled roof, it is generally easy to locate the rafters by simply lifting out individual tiles at the desired foot placement. You will see the where the sheeting has been nailed into the roof rafters below. This is your visual
indicator for the rafters. Predrill small pilot holes to nd
the center line of the rafters.
Install four collector feet by lag bolting feet into roof rafter.
If necessary, use perforated plates to extend the tile roof hooks from the roof rafters, or lag bolt into spanners or blocks between the rafters, to get the width needed between collector feet.
Place the feet vertically so that the rst angle on the roof
hook clears the top edge of the tile resting below.
Apply a generous amount of polyurethane sealant in and around the lag bolt holes before tightening bolts into place. Seal any other test holes made for pre-siting rafters.
The collector feet must be aligned vertically and horizontally.
Perforated plate
Reinstall tiles around the collector feet.
See page 9 for ush mounting frame assembly
instructions.
18
082809
Page 20
Flush Mounting to a Metal Seam Roof Metal Seam Roof Kit (540 00 28-MS)
Mounting of Collector Feet
For each collector support rail, attach the rectangular
blocks in the hole fourth from the top and rst from the
bottom as shown by the image below.
On the top end in holes 1 and 3, using the square nuts, attach the manifold bracket.
Secure the rails to the seams of the roof as seen in the illustrations. Select seams so that two tubes will overhang to the right and left for an 8-tube module. For a 16-tube module, you may allow up to four tubes to overhang to the left and right of the seams. The overhangs are necessary for better weight distribution.
Once the rails are secured to the roof seams, the tube support rail should be bolted into the second holes from the bottom.
After installing the tube support rail, slide the manifold through the manifold brackets at the top of the collector.
Insert the two outer tubes and check for square lines.
Insert remaining tubes from one side to the other.
The bracket is to be fastened to the metal seam clamp through
the hole closest to the vertical.
082809
19
Page 21
Assembling the Collector Frame
Place the collector rail on the collector top and bottom feet and install rail where it can be lined up with the col­lector feet bolt holes. If possible, choose the fourth hole from the top of the verticle frame to set the bolt into the top collector foot. Tighten bolts.
Attach the manifold support into the rst and third holes of the vertical collector frame. Bolt the manifold support
into the collector frame with square nuts.
Bolt the bottom tube support with square nuts on the
second hole from the bottom of the vertical collector frame; tighten bolts to avoid the bottom support from slipping. Line up the collector clips at the bottom tube
support rail to the manifold dry well ttings for the
evacuated tubes to line up square. There may need to be a verticle adjustment, so don’t tighten the bolt
completely until a tube has been pre-t.
Install one vacuum tube on either end. Using corner-to­corner measurements, ensure the collector assembly is squared.
Install each vacuum tube from one end to the other.
20
082809
Page 22
Multiple Collector Array Dimensions
ManifoldManifold
Rail
A
16 tube: 48”
A
Distance Between Rails
Adding Collectors Collector Extension Kit
If there is more than one collector, you may add a coupler between the manifold ends to connected them together.
Disassemble the end cover with screwdriver.
Rail
C
16 tube: 28”
C
Distance Between Collectors (Rails)
Rail
16 tube: 48”
Distance Between Rails
Rail
A
A
Connect two header boxes with compression couplings supplied — keep distance of 2 - 1/8” between the two header boxes for the manifold connector cuff.
082809
21
Page 23
Collector Extension Kit continued
Insulation in the collector cuff cavity. Use high
temperature (300F+) elastomeric foam insultube, or comparable.
Install and attach the connection cuff.
Tighten the screw slot bolt and nut to clamp the connection cuff.
2- 1/8”
The bottom rails are connected with a bottom support connection. Screw nut and bolt the bottom support connector into place between the two collector bottom rails.
22
082809
Page 24
Connect Piping to the Manifold
With each roof mounting kit, there are adapters to pipe to the manifold. Included are:
l Two compression tees to attach to the supply and return
terminations on each collector manifold or collector array;
l Two copper pipe adapters that adapt from 22mm copper
pipe size (at compression tee) to 3/4” copper pipe. Also
included in some roof kits are two stainless steel exible
hoses and additional compression couplings for copper pipe adapters.
NOTE: Use 1/2” copper supply and return for collectors with up to 24 tubes (one 8- and one 16-tube collector) and 3/4” copper for collectors with a 4- to 16-tube collector array. Preferably use Type L. Do not use PEX plastic tubing.
PEX tubing cannot withstand temperatures above 200°F and will fail. Always insulate outdoor tubing with high
temperature Insultube and weather proong against UV
degradation. Use insulation with a wall thickness of at least 3/4”.
Thermowell must
be soldered in
place.
Install compression tees at supply and return on collector manifold. Make sure the compression ring is well onto the copper pipe terminating the manifold so that the compression ring will not slide off the pipe as the compression nut is tightened.
Install the Thermowell, which is for the collector sensor, on the return outlet tee. Solder the threaded Thermowell into the tee before installing the compression tee to the header. Smear some heat transmission paste on the sensor and insert the sensor into the Thermowell. Lock sensor into place with set screw on the Thermowell.
Install the manual air vent on the manifold’s supply inlet tee. If the piping rises above the collector on a closed loop system, add an additional manual air vent at the highest point of the loop.
Supply side
manual air vent
22mm pipe size to compression tee
082809
copper pipe adapter
3/4 inch solder to copper pipe
23
Page 25
Section Six
Adjustable Rack Mounting Kit
540 00 28-16
Roof Mounting Assembly
Rack Assembly
Measure the Installation Area
Once the collector location is determined, lay out the four mounting feet of each collector within the dimensions listed below:
Center manifold on collector feet spacing
Measures (B) the “on center” distance be­tween the front and back collector mount­ing feet.
The width between the feet should be 48 inches on center for a 16 tube collector. For the 8 tube collector, the width between the feet should be 32” on center.
B
Maximum
dimensions
8 tube: 32”
16 tube: 48”
and 540 00 28-8
Roof Pitch Tilt Angle
4/12 18° 6/12 26° 10/12 39°
Roof Pitch Tilt Angle
12/12 45° 14/12 49°
22/12 61°
The column (“A” Inches) measures the length of the rear support legs.
The column (“B” Inches) measures the dimension
between front and rear feet (center to center) where the hinge leaf barrels will be set for accurate tilt.
The width between the feet should be maximum 48” on center for 16 tube collector. For the 8 tube collector, the width between the feet should be maximum 32” on center.
Collector mounting feet
Rack Angle in degrees
0 N/A N/A 75”
10 11” 4 74”
15 17” 8 72”
20 23” 10 70”
25 30” 14 68”
30 35” 16 65”
35 41” 19 62”
40 46” 22 58”
45 51” 24 53”
50 56” 27 48”
55 60” 28 43”
60 63” 31 40”
65 67” 32 40”
70 72” 34 40”
“A”
Inches
number
of total
slots
“B”
Inches
24
082809
Page 26
Installing the upper mounting brackets
Installing the collector feet and ashing
No need to remove any shingles to install the ashing. Base plate is rst screwed into roof rafter or block and ashing is slided under the roof shingle covering the
installed base plate.
Tools Required:
- Cordless drill with #2 square drive bits
- Tape measure, stud nder, chalk line
1. Locate the rafters and snap horizontal and vertical lines to mark the installa-
tion position for each upper mounting foot. Blocks, installed in the attic, may have
to be positioned between the rafters to make sure the base plate has a structural member to screw into.
2. Install the base plate with the square drive screws. Mark the screw locations and apply polyurethane sealant at the penetrations. The baseplate must be securely attached atop the roof and into the roofs structural member.
3. Install ashing by sliding it into place under then next row of shingles. cover base plate with the ashing pocket .
4. Install the collector foot as shown below using neoprene-bonded washer and stainless locking nut.
Collector Feet
Flashing
Base Plate
Sealant must be applied to
any penetration of the roof
082809
25
Page 27
Collector Frame Assembly Instructions
Adjustable rack collector mounting kit - 540 00 28-16 and 540 00 28-8
1
3
A
2
Maximum
dimensions
For adjustable tilt mounting
Steps 1 through 6 should be completed before beginning assembly on the roof
26
082809
Page 28
Steps 1, 2, and 3:
Attaching hinge leaves A and C to the stainless steel collector support rail.
Parts: 5/16 x 2.0 inch bolts, 5/16 inch nuts, 3/8 inch washers, 1.0 inch aluminum spacers, hinge leaves A, hinge leaves C, assembled collector frame from step 1
1
Step 1a: Attach the header manifold bracket with bolts through holes 1 and 3 at the top of the rail using the supplied square nuts
2
Step 2: Attach hinge leaf C
through the rst two(2) holes
at the bottom of the rail
Step 1b: Attach manifold by sliding the mounted manifold bracket and rail along the manifold
#5
#1
3
Step 3: Attach hinge leaf A through the sixth(6) and seventh(7) holes from the center of the rail.
082809
27
Page 29
Step 4:
Sizing and cutting the back support rails to length ‘A’
Parts: Back support rail (A) 66 inches
Roof Pitch Angle
Rise
Collector
Rack Tilt Angle
Run
Collector tilt angle
66” piece cut to dimension “A”
Roof line
Rack Angle in degrees
0 N/A N/A 75”
10 11” 4 74”
15 17” 8 72”
20 23” 10 70”
25 30” 14 68”
30 35” 16 65”
35 41” 19 62”
40 46” 22 58”
45 51” 24 53”
50 56” 27 48”
55 60” 28 43”
60 63” 31 40”
65 67” 32 40”
70 72” 34 40”
The column (“A” Inches) measures the length of the rear support legs.
“A”
Inches
number
of total
slots
“B”
Inches
48” for 16 tube collector 31” for 8 tube collector
Maximum
dimensions
The column (“B” Inches) measures the
dimension between front and rear feet (center to center) where the hinge leaf barrels will be set for accurate tilt.
The width between the feet should be maximum 48” on center for 16 tube collector. For the 8 tube collector, the width between the feet should be maximum 32” on center.
5
75”
A
6
B
28
082809
Page 30
Steps 5 and 6:
Attaching hinge leaves B and C to the piece of strut cut to length in step 7.
Parts: 5/16 x 1.0 inch bolts, 5/16 inch nuts, 3/8 inch washers, hinge leaves A, hinge leaves C, 66 inch piece of strut cut to length in step 4
5
Step 5: Attach hinge leaf B to the top end of the back support rail
6
Step 6: Attach hinge leaf C to the bottom end of the back support rail
082809
29
Page 31
Steps 7, 8, and 9:
Attaching hinge leaves A to B and leaves C to the aluminum bracket feet.
Parts: 5/16 x 2.5 inch bolts, 5/16 inch nuts, 3/8 inch washers, piece from step 6 (back support rail), piece from step 3 (assembled collector frame)
7
Step 7: Align hinge leaf C (from back support rail) with the holes in the walls of the rear foot bracket and insert bolt.
8
Step 8: Align hinge leaf C (from front collector rail) with the holes in the walls of the front foot bracket and insert bolt.
9
Step 9: Align hinge leaf B (from back support rail) with hinge leaf A (from front collector rail) and insert bolt.
48” for 16 tube collector 31” for 8 tube collector
Maximum
dimensions
30
9
8
75”
7
B
A
082809
Page 32
Steps 7, 8, and 9:
Attaching hinge leaves A to B and leaves C to the aluminum bracket feet.
Parts: 1/2 x 1.5 inch bolts, 1/2 inch nuts, 1/2 inch washers, pieces from step 9 (assembled collector frame)
10
Step 10a: Using the 1/2 inch bolt sets, attach the 50” (32” for 8 tube collector) back cross bracing piece, horizontally, to the collector
10
Step 10b: Using the 1/2
inch bolt sets, attach the 58” (50” for 8 tube collector) back cross bracing piece, diagonally, to the collector
10
Maximum
dimensions
082809
31
Page 33
11
12
13
Installing the vacuum tubes
Grease condenser with heat transmission paste. Note: Use a glove or a cloth to apply the paste.
Do not touch a hot condenser which could be as high as 390 °F! Keep tubes covered before installation. When tubes are exposed to the sun, the temperature of the condenser could reach 390 °F or higher.
Align the tube and slide the condenser gently into the manifold while turning the tube gently back and forth. Adjust vacuum tube. Keep blue selective coating side facing upward. The rubber gasket atop the vacuum tube must be set within manifold hole in header to securely seal heat pipe in manifold.
Put the end cap of the tube into the clip. If necessary, adjust the location of the bottom support. The end of the tube should rest on the rubber strip of the bottom support. Close clip. Clip is sharp, use gloves to close clip.
32
Install one vacuum tube on either end, and check the whole collector for square lines.
Install each vacuum tube from one end to the other.
082809
Page 34
Connect Piping to the Manifold
With each roof mounting kit, there are adapters to pipe to the manifold. Included are:
l Two compression tees to attach to the supply and
return terminations on each collector manifold or collector array;
l Two copper pipe adapters that adapt from 22mm
copper pipe size (at compression tee) to 3/4” copper pipe. Also included in some roof kits are two stainless steel
exible hoses and additional compression couplings for
copper pipe adapters.
NOTE: Use 1/2” copper supply and return for collectors with up to 24 tubes (one 8- and one 16-tube collector) and 3/4” copper for collectors with a 4- to 16-tube collector array. Preferably use Type L. Do not use PEX
plastic tubing. PEX tubing cannot withstand temperatures above 200°F and will fail.
Always insulate outdoor tubing with high temperature
Insultube and weather proong against UV degradation.
Use insulation with a wall thickness of at least 3/4”.
Install compression tees at supply and return on collector manifold. Make sure the compression ring is well onto the copper pipe terminating the manifold so that the compression ring will not slide off the pipe as the compression nut is tightened.
Install the Thermowell, which is for the collector sensor, on the return outlet tee. Solder the threaded Thermowell into the tee before installing the compression tee to the header. Smear some heat transmission paste on the sensor and insert the sensor into the Thermowell. Lock sensor into place with set screw on the Thermowell.
Install the manual air vent on the manifold’s supply inlet tee. If the piping rises above the collector on a closed loop system, add an additional manual air vent at the highest point of the loop.
Supply side
manual air vent
22mm pipe size to compression tee
082809
copper pipe adapter
3/4 inch solder to copper pipe
33
Page 35
Section Seven
Oventrop Flat Plate solar thermal collector
(3’x7’ model OVF-21 - 540 03 07, 4’x8’ model OVF-32 - 540 04 08, 4’x10’ model - OVF-40 - 540 04 10)
Model (Part Number) 3’ x 7’ (540 03 07) 4’ x 8’ (540 04 08) 4’ x 10’ (540 04 10)
Gross Collector Area 21.5 sqft 32.7 sqft 40.7 sqft Frame Height 86 inches 98 inches 122 inches Frame Width 36 inches 48 inches 48 inches Frame Depth 3-1/8 inches 3-1/8 inches 3-1/8 inches Total Width 38 inches 50 inches 50 inches Weight 76 lbs. 116 lbs. 151 lbs.
34
082809
Page 36
Adjustable Rack Mounting Kit for  at plate collectors 540 00 28-FP
- for all  at plate collectors (OVF-21, OVF-32, OVF-40)
Contents:
4 - Flat Plate Quick-Lock collector clamp
2 - Flat Plate Quick-Lock collector clamp With locking screw
4 - Roof mounting  ashing kits
4 - Triangle base bracket (foot)
4 - 2 inch bolt/washer/nut set
2 - 4 inch bolt/washer/nut set
2 - Aluminum square tube Dimensions: 72L x 1.0W x 1.0H inches
082809
35
Page 37
Flush Mounting Kit for  at plate collectors 540 00 28-FPFM
- for all  at plate collectors (OVF-21, OVF-32, OVF-40)
Contents:
2 - Flat Plate Quick-Lock collector clamp
2 - Flat Plate Quick-Lock collector clamp With locking screw
4 - Roof mounting  ashing kits
4 - Triangle base bracket (foot)
4 - 2 inch bolt/washer/nut set
36
082809
Page 38
Strut Mount Clips for at plate collectors 540 00 28-FC
- for all at plate collectors (OVF-21, OVF-32, OVF-40)
Contents:
Set of 4 clips
These clips are used to attach and secure the at plate collectors to strut mounting channel assemblies.
Required but not provided are strut channel, strut locknuts, bolts and washers.
Strut clips are usually used to mount at plate collectors to horizontal bearing strut.
082809
37
Page 39
Adjustable Mounting Kit for at plate collectors 540 00 28-FP
- for all at plate collectors (OVF-21, OVF-32, OVF-40)
Installing the collector feet and ashing
COLLECTOR FOOT MUST BE ATTACHED TO THE BASE PLATE
USING THE CENTER HOLE.
No need to remove any shingles to install the ashing. Base plate is rst screwed into roof rafter or block and ashing is slided under the roof shingle covering the
installed base plate.
Tools Required:
- Cordless drill with #2 square drive bits
- Tape measure, stud nder, chalk line
1. Locate the rafters and snap horizontal and vertical lines to mark the installa-
tion position for each mounting foot. Blocks, installed in the attic, may have to
be positioned between the rafters to make sure the base plate has a structural member to screw into.
2. Install the base plate with the square drive screws. Mark the screw locations and apply polyurethane sealant at the penetrations. The baseplate must be securely attached atop the roof and into the roofs structural member.
3. Install ashing by sliding it into place under then next row of shingles. cover base plate with the ashing pocket .
4. Install the collector foot as shown below using neoprene-bonded washer and stainless locking nut. The collector foot must be tightened fully to restrict unwanted movement.
Collector Feet
Flashing
Base Plate
Sealant must be applied to
any penetration of the roof
38
082809
Page 40
Measuring and cutting the rack legs
Use an angle nder tool to set the desired collector tilt angle during installation.
Table 1 below is to help you nd distances between the front and rear feet (B), and
the cut length for the rack leg (A) at various collector tilt angles.
The table is for collector tilt angle from a horizontal plane, such as for a at roof or for ground mounting. (gure 1)
When mounting on a pitched roof (gure 2) the table can be used by subtracting the roof pitch (angle) from the collector tilt angle to nd the remaining angle for Table 1. With this method the collector legs will be perpendicular with the roof pitch (gure 2).
Table 1
Collector Tilt
Angle in degrees
from horizontal
A / B for OVF - 21
in inches
A / B for OVF - 32
in inches
5 8 / 86 9 / 98 11 / 122 10 15 / 85 17 / 97 21 / 120 15 22 / 83 25 / 95 32 / 118 20 30 / 81 34 / 92 42 / 115 25 36 / 78 42 / 89 52 / 111 30 43 / 74 49 / 85 61 / 105 35 49 / 71 56 / 80 70 / 100 40 55 / 66 63 / 75 45 61 / 61 69 / 69 50 66 / 55 55 71 / 49
A / B for OVF - 40
in inches
gure 1
082809
gure 2
39
Page 41
Mounting Hardware and Installation
The adjustable rack installation hardware is specially designed to speed collector installation. This hardware consists of four Quick-Lock collec­tor clamps for the rear top hinge, two Quick-Lock collector clamps with locking screws for the front bottom hinge, four triangle brackets (collector feet), two aluminum square tube strut for collector legs, bolts, nuts and washers. (See page 33).
After locating the mounting points for the collector feet, the base plate and
 ashing should be installed (See page 38).
Install the triangle brackets on top of the  ashing using the neoprene-
bonded washer and stainless locking nut.
The rear struts should be cut and drilled to the desired length from Table 1.
Attach two Quick-Lock collector clamps with locking screws to bottom of the collector. Keep the locking screws loose. Secure the bottom Quick-Lock clamps on the collector and drop the clamp into the triangle bracket using the bolt, washer, and nut provided. Tighten locking screws after collector is set on the triangle brackets. See diagram 1.
Attach the four Quick-Lock collector clamps to the top of the collector. Using two Quick-Lock clamps per collector leg, bolt the collector leg (mounting strut) to the top of the collector. Attach both collector legs.
Raise the collector and bolt the bottom of the collector legs to the collector foot with the bolt, washer, and nut provided. See diagram 2.
Square up the collector legs and tighten all the nuts and bolts at the collector feet and the rear collector hinge.
Quick-Lock collector clamp into front foot
front hinge Diagram 1
40
rear hinge and strut Diagram 2
082809
Page 42
Flat Plate Collector Piping
The piping of the system should be considered before a nal decision is made
on how the collectors are mounted. Piping should be made of copper tube of
the type meeting local codes, insulated with Armaex or similar, and painted
or wrapped with aluminum tape where exposed to ultraviolet radiation. Care should be taken in the spacing of collectors as attachment of piping is easiest with properly aligned collectors. The collectors and piping to the storage tank should be slightly sloped downward (3” in 8 feet) to allow draining in case of freezing conditions. A manual air vent should be installed at the top of the collector on the outlet. Soldered connections should be made with 95/5 solder.
The outlets of the collector are 1” copper pipe nipples. The copper union makes attachment of piping to collector
easy. Teon tape or high temperature, high quality pipe
sealant should be used when making threaded connec­tions. The collector inlets should be piped similarly but without the air vent.
Sensor Mounting at Collector
The controller heat sensor is mounted to the nipple outlet of the collector (Figure 14). A stainless steel screw clamp should be used. The entire nipple should be wrapped thoroughly with insulating tape so that the sensor is isolated from the outside air.
082809
41
Page 43
Flush Mounting Kit for at plate collectors 540 00 28-FPFM
- for all at plate collectors (OVF-21, OVF-32, OVF-40)
Installing the collector feet and ashing
COLLECTOR FOOT MUST BE ATTACHED TO THE BASE PLATE
USING THE CENTER HOLE.
No need to remove any shingles to install the ashing. Base plate is rst screwed into roof rafter or block and ashing is slided under the roof shingle covering the
installed base plate.
Tools Required:
- Cordless drill with #2 square drive bits
- Tape measure, stud nder, chalk line
1. Locate the front feet locations on rafters and snap horizontal and vertical lines
to mark the installation position for each lower mounting foot. Blocks, installed in
the attic, may have to be positioned between the rafters to make sure the base plate has a structural member to screw into.
2. Install the base plate with the square drive screws. Mark the screw locations and apply polyurethane sealant at the penetrations. The baseplate must be securely attached atop the roof and into the roofs structural member.
3. Install ashing by sliding it into place under then next row of shingles. Cover the base plate with the ashing pocket .
4. Install the collector foot as shown below using neoprene-bonded washer and stainless locking nut. The collector foot must be tightened fully to restrict unwanted movement.
Collector Feet
set bottom feet rst then place
collector
Base Plate
Sealant must be applied to
any penetration of the roof
42
Flashing
082809
Page 44
Flush Mounting Hardware and Installation
The  ush mount installation hardware is specially designed to speed
collector installation. This hardware consists of two Quick-Lock col­lector clamps with locking screws for the front hinge, two Quick-Lock collector clamps for the rear hinge, four triangle brackets (collector feet), bolts, nuts and washers. (See page 36).
Collector
Quick-Lock Clamp
After installing the base plate and  ashing, install the triangle brackets on top of the  ashing using the neoprene-bonded washer and stain-
less locking nut.
Next attach two Quick-Lock collector clamps with locking screws to bottom of the collector. Keep the locking screws loose. Secure the bottom Quick-Lock clamps on the collector and drop the clamp into the triangle bracket using the bolt, washer, and nut provided. Tighten locking screws after collector is set at position of location on the triangle brackets. See diagram 1.
Attach the two upper Quick-Lock collector clamps to the collector along with the two triangle brackets and roof mounting base plates. Do not overtighten bolts.
Place the top of the collector down on the roof with the base plate positioned over a rafter. Blocks, installed in the attic, may have to be
positioned between the rafters to make sure the base plate has a structural member to screw into.
Draw the base plate layout onto the roof on the shingle.
Unbolt the base plate from the triangle bracket, and the triangle bracket from the Quick-Lock.
Triangle
Bracket
Flashing
Base Plate
Square drive screws
Screw the baseplate onto it’s template on the shingle.
Install the base plate with the square drive screws. Mark the screw locations and apply polyurethane sealant at the penetrations. The baseplate must be securely attached atop the roof and into the roofs structural member.
Install  ashing by sliding it into place under then next row of shingles. Cover the base plate with the  ashing pocket .
Install the collector foot as shown below using neoprene-bonded washer and stainless locking nut.
Attach the two Quick-Locks to the collector and bolt them into the installed collector feet. Diagram 1.
Tighten all the nuts and bolts at the front and rear collector hinges.
082809
Front and rear hinge diagram 1
43
Page 45
Strut Mount Clips for at plate collectors 540 00 28-FC
- for all at plate collectors (OVF-21, OVF-32, OVF-40)
Collector clips are designed to make Oventrop ate plate collectors
versitle enough to mount on strut channel assemblies, especially those with locking strut nuts or locknuts. Required but not provided are strut channel, strut locknuts, bolts and washers.
Usually the Collectors are attached and secured to two horizontal load bearing strut channels placed 1 - 2 ft. in from the collector ends.
See gure below.
Strut Channel
Collectors
Collector Clip location
To connect the clips to the strut channel raise the collector onto the installed horizontal strut.
Attach the collector to the strut by using a collector clip, a bolt and a strut locknut. Each collector has four mounting clips.
Collector
Collector Clip
Bolt
Locknut
Strut Channel
44
082809
Page 46
Section Eight
System Piping Schematics
The OVSOL System for solar energy described in this manual, when properly installed and maintained, meets the minimum standards established by the SRCC.
This certication does not imply endorsement or warranty of this product by the SRCC.
Piping
System Model
OVSOL 5-16-SC 46
OVSOL 5-16-SCE 47
OVSOL 5-16-DC 48
OVSOL 5-16-DCE 49
OVSOL 5-24-SC 50
OVSOL 5-24-SCE 51
OVSOL 5-24-DC 52
OVSOL 5-24-DCE 53
OVSOL FP-2-SC 54
OVSOL FP-2-SCE 55
OVSOL FP-2-DC 56
OVSOL FP-2-DCE 57
OVSOL FP-3-SC 58
OVSOL FP-3-SCE 59
OVSOL FP-3-DC 60
OVSOL FP-3-DCE 61
Schematic
page #
082809
45
Page 47
OVSOL System 5-16-SC / 80 gallon, Evacuated tube, Single coil tank
System Assembly
Installing OVSOL System 5-16-SC Model Number 540 00 16K-SC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 225 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 940 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with one internal coil. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank and in series with the back-up hot water heater. Solar bypass valves
are installed for servicing the solar tank. Back-up hot water heater bypass valves may be installed to bypass the hot water heater. An anti-scald valve must be installed for hot water mixing to hot water xtures if the solar tank high
limit in the Regusol controller is set above 120
o
F.
46
082809
Page 48
OVSOL System 5-16-SCE / 80 gallon, Evacuated tube, Single coil electric tank
System Assembly
Installing OVSOL System 5-16-SCE Model Number 540 00 16K-SCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 225 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 920 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with one internal coil and electric backup ele­ment. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is
lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
o
F.
082809
47
Page 49
OVSOL System 5-16-DC / 80 gallon, Evacuated tube, Dual coil tank
System Assembly
Installing OVSOL System 5-16-DC Model Number 540 00 16K-DC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 225 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 970 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with two internal coils. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propylene glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
48
082809
Page 50
OVSOL System 5-16-DCE / 80 gallon, Evacuated tube, Dual coil electric tank
System Assembly
Installing OVSOL System 5-16-DCE Model Number 540 00 16K-DCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 225 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 970 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with two internal coils and an electric backup element. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propylene glycol antifreeze
is lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
082809
49
Page 51
OVSOL System 5-24-SC / 119 gallon, Evacuated tube, Single coil tank
System Assembly
Installing OVSOL System 5-24-SC Model Number 540 00 17K-SC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 and 5-8 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 337 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight:1315 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with one internal coil. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank and in series with the back-up hot water heater. Solar bypass valves
are installed for servicing the solar tank. Back-up hot water heater bypass valves may be installed to bypass the hot water heater. An anti-scald valve must be installed for hot water mixing to hot water xtures if the solar tank high
limit in the Regusol controller is set above 120
o
F.
50
082809
Page 52
OVSOL System 5-24-SCE / 119 gallon, Evacuated tube, Single coil electric tank
System Assembly
Installing OVSOL System 5-24-SCE Model Number 540 00 17K-SCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 and 5-8 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 337 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 1315 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with one internal coil and an electric backup element. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze
is lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
o
F.
082809
51
Page 53
OVSOL System 5-24-DC / 119 gallon, Evacuated tube, Dual coil tank
System Assembly
Installing OVSOL System 5-24-DC Model Number 540 00 17K-DC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 and 5-8 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 337 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 1340 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with two internal coils. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
52
082809
Page 54
OVSOL System 5-24-DCE / 119 gallon, Evacuated tube, Dual coil electric tank
System Assembly
Installing OVSOL System 5-24-DCE Model Number 540 00 17K-DCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
OVSOL 5 -16 and 5-8 Evacuated Tube Collector . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 337 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 1340 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with two internal coils and an electric backup element. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze
is lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
082809
53
Page 55
OVSOL System FP-2-SC / 80 gallon, Flat plate, Single coil tank
System Assembly
Installing OVSOL System FP-2-SC Model Number 540 04 08K-SC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Two OVF-32 Flat Plate Solar Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 550 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 920 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with one internal coil. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank and in series with the back-up hot water heater. Solar bypass valves
are installed for servicing the solar tank. Back-up hot water heater bypass valves may be installed to bypass the hot water heater. An anti-scald valve must be installed for hot water mixing to hot water xtures if the solar tank high
limit in the Regusol controller is set above 120
o
F.
54
082809
Page 56
OVSOL System FP-2-SCE / 80 gallon, Flat plate, Single coil electric tank
System Assembly
Installing OVSOL System FP-2-SCE Model Number 540 04 08K-SCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Two OVF-32 Flat Plate Solar Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 550 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 920 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with one internal coil and an electric backup element. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze
is lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
o
F.
082809
55
Page 57
OVSOL System FP-2-DC / 80 gallon, Flat plate, Dual coil tank
System Assembly
Installing OVSOL System FP-2-DC Model Number 540 04 08K-DC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Two OVF-32 Flat Plate Solar Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 550 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 970 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with two internal coils. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
56
082809
Page 58
OVSOL System FP-2-DCE / 80 gallon, Flat plate, Dual coil electric tank
System Assembly
Installing OVSOL System FP-2-DCE Model Number 540 04 08K-DCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Two OVF-32 Flat Plate Solar Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 550 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
80 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 970 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 80 gallon glass lined tank with two internal coils and an electric backup element. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze
is lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
082809
57
Page 59
OVSOL System FP-3-SC / 119 gallon, Flat plate, Single coil tank
System Assembly
Installing OVSOL System FP-3-SC Model Number 540 34 08K-SC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Three OVF-32 Flat Plate Solar Collectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 675 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight:1315 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 119 gallon stainless steel tank with one internal coil. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank and in series with the back-up hot water heater. Solar bypass valves
are installed for servicing the solar tank. Back-up hot water heater bypass valves may be installed to bypass the hot water heater. An anti-scald valve must be installed for hot water mixing to hot water xtures if the solar tank high
limit in the Regusol controller is set above 120
o
F.
58
082809
Page 60
OVSOL System FP-3-SCE / 119 gallon, Flat plate, Single coil electric tank
System Assembly
Installing OVSOL System FP-3-SCE Model Number 540 34 08K-SCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Three OVF-32 Flat Plate Solar Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 675 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 1315 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 119 gallon stainless steel tank with one internal coil and an electric ele­ment. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is
lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
o
F.
082809
59
Page 61
OVSOL System FP-3-DC / 119 gallon, Flat plate, Dual coil tank
System Assembly
Installing OVSOL System FP-3-DC Model Number 540 34 08K-DC Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Three OVF-32 Flat Plate Solar Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 675 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 1340 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 119 gallon glass lined tank with two internal coils. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze is lled into the closed loop system through the Regusol ll and ush valve. Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
60
082809
Page 62
OVSOL System FP-3-DCE / 119 gallon, Flat plate, Dual coil electric tank
System Assembly
Installing OVSOL System FP-3-DCE Model Number 540 34 08K-DCE Solar Closed-Loop Domestic Hot Water System
Oventrop Components
Three OVF-32 Flat Plate Solar Collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 675 lbs.
Regusol 130 EL Solar Transmission Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 20 lbs.
119 Gallon OVSOL glass lined Tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . lled weight: 1340 lbs.
Regusol Fill and Flush Valve Oventrop NT Propelyne Glycol Antifreeze
System Design Description
The solar closed-loop heating system consists of the Oventrop Regusol 130 EL pump and control station, one OV-5 evacuated tube collector, and an 119 gallon glass lined tank with two internal coils and an electric backup element. An expansion tank is installed at the Regusol on the safety group. Oventrop NT propelyne glycol antifreeze
is lled into the closed loop system through the Regusol ll and ush valve.
Cold water is piped to the solar tank. An anti-scald valve must be installed for hot water mixing to hot water
xtures if the solar tank high limit in the Regusol controller is set above 120
the manner of a standard indirect water heater.
o
F. The top coil is piped to the boiler in
082809
61
Page 63
Piping the Solar Tank with Integrated Back-up as a One Tank System
Use 3/4” copper pipe for plumbing the tanks. To prevent heat loss through the copper tubing, insulate all tubing with at least 1/2” wall tube insulation. This should include the cold water feed to the solar storage tank up to 6 feet from the tank. A check valve should be installed on the cold water feed line to the mixing valve to prevent hot water migration into the cold water piping.
The solar tank should include valves and piping for service. A domestic hot water expansion tank can be installed on the cold water feed to the tanks. The expansion tank
should be installed downstream from a back ow preventer, for cold water feed to the tanks.
Service Valves and Instructions for Emergency
To isolate or service the hot water system in an emergency, turn system isolation valve #1 off.
To leave the system in an unoccupied house when hot water will not be drawn, the solar system should be drained of antifreeze and the controller turned to “off” or unplugged. You may also turn the system isolation
valve #1 off if no hot water ow to the xtures is desired.
62
082809
Page 64
Piping the Solar Tank and the Auxiliary Hot Water Service for Two Tank System
Use 3/4” copper pipe for plumbing the tanks. To prevent heat loss through the copper tubing, insulate all tubing with at least 1/2” wall tube insulation. This should include the cold water feed to the solar storage tank up to 6 feet from the tank. A check valve should be installed on the cold water feed line to the mixing valve to prevent hot water migration into the cold water piping.
The solar tank should include valves and piping for service. In addition, the back-up water heater can have valves installed for solar hot water bypass.
A domestic hot water expansion tank can be installed on the cold water feed to the tanks. The expansion tank
should be installed downstream from a back ow preventer, for cold water feed to the tanks.
Service Valves and Instructions for Emergency
To isolate or service the hot water system in an emergency, turn system isolation valve #1 off.
To isolate the solar tank from the auxiliary water heater, the normally open solar bypass valves #2 and #4 are shut off, isolating the solar tank from the supply of water. The normally closed valve #3 is then opened for bypass. Under no circumstances are valves number 1, 2 & 3 to be left open during solar operation.
To leave the system in an unoccupied house when hot water will not be drawn, the solar system should be drained of antifreeze and the controller turned to “off” or unplugged. You may also turn the system isolation
valve #1 off if no hot water ow to the xtures is desired.
Piping and Insulating the Solar Loop
When piping collectors, use 3/4” copper for one to four 16-tube collector arrays. Preferably use type L.
Never use PEX plastic tubing. PEX tubing cannot withstand temperatures above 200°F, and fail in solar loops.
Always insulate solar loops with at least a high temperature elastomeric insulation. This exible rubber foam
insulation may be protected against UV degradation with a mastic or a 15-year latex paint applied to the
surface. High temperature berglass, urethane, and isocyanurates are also used on solar loops and have
jackets that enclose and protect the insulation. Use insulation with at least a 3/4” wall thickness for all outdoor
piping. Always insulate completely around pipe ttings and at the collector ttings. Pay particular attention
to insulation detail at the collector sensor. Copper pipework must be supported by pipe hangers, split ring hangers or Unistrut clamps. Check your local codes for pipe sizes and support distances for vertical and horizontal runs. The supports must not hold onto and compress the insulation. Pipe support hangers should be secured directly to the pipe.
082809
63
Page 65
Section Nine
Oventrop Stainless Steel Indirect Solar Hot Water Tanks
Indirect single and dual coil domestic hot water storage tanks are made in 60-, 80-, and 115-gallon models. Each tank has bottom heat exchanger coil connection for solar heat transfer.
Please read the Installation, Operating and Service Instructions Manual, placed with the tank.
1) Model SC- Solar heating with a single coil. The units are provided with one 3/8” ID thermal well for installation of the solar tank sensor.
Quality Design and Construction Tanks and coils are all stainless steel. Includes over 2” of urethane insulation, R-12. Thermoplastic jacket will not rust or corrode. All connections are 1” on top.
Tank ports are clearly marked.
Top View
Side View
T & P valve
cold water in hot water out
solar coil
bottom coil (solar)
return from collector
Locating the Water Heater
The water heater should be located in an area where water leakage from the tank or connections will not result in damage to
areas adjacent to the water heater or to lower oors of the structure. When such a location cannot be avoided, a suitable drain
pan must be installed under the water heater, and the drain pan must be connected to a drain. The water heater should be installed as close to the back-up hot water heater or boiler as is practical for easy access for service.
The unit is designed for installation on combustible ooring and in alcoves, closets, etc.
The minimum clearances from combustible surfaces are:
bottom coil (solar) supply to collector
The minimum clearances for service are:
solar sensor well
(tank sensor)
Tank Dimensions:
Dimensions
(inches)
Bottom----------------------------0”
Left, right, and rear sides -­Front------------------------------1” Top--------------------------------6”
Bottom--------------------------- 0”
Left, right, and rear sides -- 3” Front----------------------------- 30” Top------------------------------- 6”
Height
60 gallon 60 22.5 80 gallon 54 26.5 115 gallon 72 26.5
Diameter
64
082809
Page 66
Oventrop Glass-lined Indirect Solar Hot Water Tanks
Indirect single and dual coil domestic hot water storage tanks are made in 80-, and 119-gallon models. Each
tank has bottom heat exchanger coil connection for solar heat transfer with optional upper coil and electric
backup elements.
Please read the Installation, Operating and Service Instructions Manual, placed with the tank.
Quality Design and Construction
Tanks and coils are all glass lined. Includes over 2” of urethane insulation, R-14. All tanks have a metal jacket over the insulation. Electric Elements are 4500W ,240VAC.
HOT OUT (1” NPT)
ANODE
3/4NPTPort
Optional
Electric Heating Assembly
Bottom Sensor Immersion Well
COLD IN (1”NPT)
80SCE, 119SC ONLY
ANODE
FROM SOLAR (1” NPT)
TO SOLAR
(1” NPT)
Figure 1: 80SC/SCE, 119SC/SCE
HOTOUT(1”NPT)
ANODE
Top Sensor
Immersion Well
Immersion Well
Optional
Electric
Heating
Assembly
Bottom
Sensor
Immersion
Well
COLD IN
(1”NPT)
Figure 2: 80DC/DCE, 119DC/DCE
ANODE
T&P RELIEF VALVE
FROMBOILER(1”NPT)
TOBOILER(1”NPT)
FROM SOLAR (1”NPT)
TO SOLAR (1”NPT)
Locating the Water Heater
The water heater should be located in an area where water leakage from the tank or connections will not result in damage to
areas adjacent to the water heater or to lower oors of the structure. When such a location cannot be avoided, a suitable drain
pan must be installed under the water heater, and the drain pan must be connected to a drain. The water heater should be installed as close to the back-up hot water heater or boiler as is practical for easy access for service.
The minimum clearances from combustible surfaces are:
Bottom----------------------------0”
Sides (non-piping) ------------0” Front------------------------------0” Top--------------------------------0”
082809
The minimum clearances for service are:
Side (T&P Relief) ------------ 6” Sides (non-piping) ----------- 4” Front----------------------------- 16” Top------------------------------- 12”
Tank Dimensions:
Dimensions
(inches)
Height
80 gallon 64 24 119 gallon 65 28
Diameter
65
Page 67
Transmission station with deaerator “Regusol EL-130” Installation instructions
Transmission station “Regusol EL-130” with pre-assembled,
integrated microprocessor-driven control.
The transmission station is supplied with a detailed instruction manual of the control.
The “Regusol EL-130” is equipped with a deaerator for air elimination from the heat transfer medium.
Safety notes
The safety notes are to be observed. Installation, initial operation, maintenance and repairs
have to be carried out by authorized and qualied trade persons.
Installation notes
The transmission station is supplied pre-assembled. Pump wiring (5) is necessary.
Compression ttings for 3/4” copper pipe are included.
The transmission station always has to be mounted at a lower level than the collectors.
Assembly notes
Remove transmission station from the packaging. Pull the front insulation (1) from the control retainer (2) while pushing the control retainer against the back insulation (3). Now the control retainer can be pulled off the back insulation together with the control (4). Remove transmission station (6).
For each wall-mounting device (7), drill 5/16-inch holes at a distance of 10 5/16 inches. Fix mounting device by screwing it onto the wall and engage back insulation. Now push transmission station onto the
xing clips of the wall mounting device.
Connect the Regusol to the collectors (top connectors) and the tank
(bottom connectors) through the Regusol compression ttings.
See diagram 1 for details. Use 3/4” hard copper to pipe. The pipe ends must be cut at right angles and be free of burrs. Apply clear plumber’s grease on the compression nut thread and rings. Slide in
pipe until stop and rmly tighten the compression ttings. Hold rm
while tightening. (Continued on next page)
1
2
3
7
6
8
4
5
7
66
082809
Page 68
Screw safety group (8) onto the ball valve. Install discharging pipe from the pressure relief valve to the
oor or through exterior wall to 12” from ground level. If there is no oor drain, a bucket may be placed under
discharge pipe. Connect piping of 1/2” male pipe thread on the safety group to an expansion tank. Connect cable to the pump (diagram 2) and push control retainer with the control onto the back insulation.
Now the front insulation can be slipped over the control retainer and be pushed onto the back insulation until it clicks into position.
Air test all pipework on solar closed loop. Flush solar installa-
tion thoroughly, then ll the system with Oventrop solar uid. Adjust the ow rate with the screw slot in the ow measuring
device.
Open vent with radiator vent key on deaerator to remove any
air separated from solar transfer uid.
Make sure thermometers are left in their vertical position, as valve handles must be left open. Check that the screw slot on the supply side check valve is left in the horizontal position.
Connection to collector(s)
Return from Supply to
Thermometer
Deaerator
Connection Connection supply to tank return from tank
Mounting
bracket
Direction
of ow
Mounting
bracket
Thermometer
Pressure relief valve
Pressure gauge
Expansion tank
connection
Circulator
Diagram 1
Flow meter
9- 7/8’’
Typical ow rates are set to
3/4 to 1 gpm per collector* *16 tube model collector
Collectors
Flow restrictor screw slot
14- 3/4’’
10- 5/16’’
3- 7/8’’
SupplyReturn
Thermometers in solar collection mode (displayed on the controller) will indicate a temperature rise on the
o
return side of an average of 10 - 25
F.
This temperature rise indicates that the
Check valve slot in horizontal position
collectors are collecting and transferring solar energy.
082809
67
Page 69
Oventrop Regusol 130 EL Controller Standard Solar Domestic Hot Water System Wiring
Warning!
Do not plug in Deltasol controller until all wiring connections are made.
The unit must only be located internally. It is not suitable for installation in wet or
hazardous locations and should not be sited near any electromagnetic eld.
Sensor wires are installed separately from any 120 VAC power chords. The type of wire installed from the sensors to the controller should be sunlight­resistant shielded copper wire with at least two conductors at 18
AWG.
1. Unscrew the cross-recessed screw of the cover and remove it from the housing.
2. Wire the collector sensor and tank sensor wires (S1 & S2).
3. Wire the Regusol Wilo pump as follows:
yellow with green strip wire – ground blue wire – neutral N #17 brown wire – hot R1 #18
4. Wire the outlet plug as follows:
green wire – ground white wire – neutral N #19 black wire – load L #20
5. Replace cover.
The power supply to the controller must be made last.
single relay differential controller
sensor monitoring
on/off/autocontrol
operations hour counter
Wiring and operation instructions are included with the Regusol
Operating instructions are included with the solar controller.
Control board under cover
Diagram 2
Ground
S1 Collector sensor S2 Storage sensor low
R1 Solar pump
120 VAC Plug wired to Deltasol
Regusol EL 130 Pump
Wiring Guide
68
082809
Page 70
Operation and Programming the Regusol Controller
Display
Backward
Used for scrolling backward through the menu or to decrease the adjustment value
2
Operating Mode and Display
Forward or backward buttons will indicate following information: COL: Collector sensor temperature TST: Tank temperature hP: Operating hours counter
Press “Set” key for programming mode
Programming Mode
To begin programming mode, press forward key to hP
display.
Press and hold forward key 1 in “hP” mode for
2 seconds.
Menu mode displays next indicator (DT 0) and may now be scrolled through rest of programmable settings using keys 1 or 2 (forward or backward through the entire menu).
Values in display settings may be changed by pressing “Set” (key
3). The “Set” icon will blink while in programming mode. Raise or lower values with keys 1 or 2. Press set button once more to com­plete change. “Set” icon will stop blinking.
Program Changes
“DT 0” differential turn on set point
The rst program display will be “DT 0” differential turn on set point. DT 0 is set at 12 ºF. This indicates what turn on temperature the collectors must be above the tank to begin solar circulation. No change is necessary.
Forward
Used for scrolling forward through the menu or to decrease the adjustment value
3
Set
1
Program Changes
Mode of Operation ON / OFF / AUTO
“HND 1”
Scroll through menu to “HND 1” display, near the end of the program menu. This is for the setting switch ON, OFF, or AUTO that allows the controller the function of operation. It is a service operation switch.
ON position energizes the pump to circulate at all times. OFF position keeps the pump from circulating. AUTO allows the controller to operate the pump based on the differential temperatures (normal operation).
Default setting is AUTO. To change press “Set” (key 3). Press key 1 or 2 to change into ON, OFF or AUTO mode. Press set key 3 again to complete change and before moving into the next menu.
Always leave the controller in AUTO for normal solar collection cycling.
“S MX” storage maximum set point
“S MX” is set at 140 ºF. This setting can be turned up only if there is a anti-scald valve installed on the DHW system.
“DT F” differential turn off set point
The second indicator will be “DT F” differential turn off set point. DT F is set at 5 ºF. This indicates what turn-off temperature the collec­tors must be above the tank for solar circulation to end. No change is necessary.
082809
To change press “Set” (key 3). Press key 1 to increase or 2 to decrease the storage maximum temperature. Press set key again to set change.
69
Page 71
Operating and Programming the Regusol Controller
Program Changes
The factory settings for the following displays are suitable for all solar domestic hot water heating. For more information on these settings, read the control manual included with the Regusol 130.
“EM” limit collector temperature
Factory setting: 285o F
“OCX” system cooling
Factory setting: OFF
“OCN” Minimum collector limitation
Factory setting: OFF
“OCF” antifreeze function
Factory setting: OFF
The settings for the following displays are as follows.
“LANG” language
Factory setting: En (english)
“UNIT” Temperature in degrees
Factory setting: FAH (fahrenheit)
“OREC” option recooling
Factory setting: OFF
“O TC” tube collector special function
Factory setting: OFF
“OHQM” heat quantity balancing
Factory setting: OFF
“PROG”
Controllers program
“VERS”
This indicates the program version
70
082809
Page 72
Section Ten
Collector Flush, Leak Check, and Fill Procedure
Before proceeding with the instructions outlined in this section, the solar storage tank should be
lled with water. The collector loop then should be leak checked, ushed, and lled. A Regusol “ll and ush” valve should be installed for system charge-up. Filling or “charging up” a solar
closed loop incorporates a 1/2 HP utility pump available through most Oventrop dealers.
Leak Check and Flush
1. To ensure there are no leaks, air test the system to approximately 60 PSI. Check and repair
any leaks. When the solar loop is leak-free, release air and ush system with tap water.
2. Before lling the collector loop with antifreeze solution, it must be ushed free of any ux, copper lings, or debris. Straight tap water may be used for this purpose.
3. To perform this step, hook up a hose from tap faucet to the ll port and run another hose from the drain port to a drain or outdoors. Close center ball valve on “ush and ll.” Open water tap to begin ushing. Flush the system with tap water for approximately 10 minutes to assure there is no solder, ux, or debris left within the collector loop piping. This step may also be used to cool the collectors before lling the system with propylene glycol.
Fill Procedure
Charging the collector loop will require approximately 3
- 8 gallons of Oventrop NT­40 antifreeze (provided). It is a premixed water­propylene glycol solution of 40% propylene glycol to 60% water and will provide freeze protection to -6 oF.
No mixing is necessary.
Oventrop
Solar Collector
Array
If collector loop is to be charged during the sunlight hours, collectors should be covered for at least one hour before beginning; or the collector may be cooled with water using procedure in step 3 (above).
Connect pressure side of charge pump with washing
machine hoses to the ll
port. From suction side of charge pump, attach another hose to the bucket of the propylene glycol solution. Attach another hose from the drain port to an empty bucket. If the system was
just ushed with water, drain down the water pressure to prime the charge pump. Drain water
pressure into empty buckets.
Set up for lling with solar heat transfer uid. Turn center ball valve of “Regusol ll and ush” perpendicular to have propylene glycol ow throughout solar closed loop.
082809
71
Page 73
Turn on ll rig and pump propylene glycol. If pumping out water, have an empty bucket on the
drain port hose to collect water until the color of antifreeze returns. Then put drain port hose into antifreeze bucket for circulating antifreeze. Run the charge pump until no air bubbles are seen returning to the bucket. Periodically close drain port to allow pressure to build, then reopen to purge any air that may be trapped. Watch for air escape. Repeat this procedure until
air is no longer returning to the ll rig pail.
To complete system ll and charge, close the drain port and ll system to pressure of 30 to 35 psi. Close ll port and turn off charge pump. Turn center ball valve of “Regusol ll and ush” parallel to direction of ow to have propylene glycol ow throughout solar closed loop installa­tion with the system pump in operation. Cover ll and drain ports with hose caps.
Open air vent atop solar collector to eliminate any air trapped at the high point of the system. Next open the air vent to remove air from the deaerator at the Regusol 130 EL.
Commissioning the System
Before activating system the following checks should be made:
l
System lled with water (tank).
l
Appropriate cold and hot water bypass valves are set for series water ow through tank(s).
l
Collector and tank sensors connected.
l
Regusol is wired and solar loop is air-tested for leaks.
The collector loop can now be lled with the recommended anti-freeze. Once the solar loop is lled, place Regusol thermometer handles in the fully open position and the ll and ush valve in fully open position.
Plug in the Regusol controller for operation.
Controller will start and be in automatic mode of operation. Digital display and indicator light should illuminate. If the collector temperature is above the tank temperature by 12º F, the circulator should start and run. Flow meter will indicate circulation. If there is noise of air circulating through the pump, the system must be recharged to remove air bubbles. Solar closed loops must be free of air bubbles.
If the collector temperature is below the tank temperature, circulator should not run. If circulator is not running, set the controller to the “On” position (see Operation and Control-
ling the Regusol Controller) to check circulator operation and indication of ow. Remember to
leave the solar controller set in the “Auto” mode of operation when completed.
If circulator fails to operate, refer to Troubleshooting checks on the following pages.
It is unlikely that system malfunctions will develop within the Regusol. Should they occur, however, the following procedures will prove helpful. Several of the procedures indicated re­quire the use of test equipment, such as a volt-ohmeter with 10K scale. If this equipment is not available to you, contact your authorized Oventrop dealer or distributor for service.
72
082809
Page 74
Section Eleven
Trouble Shooting
1. Controller does not come on.
2. Circulator does not start or run in “on” position.
3. Circulators will not run with switch in “auto”
4. Circulator runs constantly in “auto”
5. Inadequate solar loop temperature.
A. Controller is not plugged in
B. Breaker tripped to off C. Blown fuse in controller
D. Inoperative controller
A. Shaft bound
B. Blown fuse or breaker C. Bad electrical connection
D. Inoperative controller
A. Same as A through D indicated above
B. Inoperative sensor circuits
C. Poorly attached or insulated sensors D. Inadequate temperature differential
A. Inoperative sensors or sensor wire circuits
B. Inoperative controller
A. Recent heavy usage of hot water C. Inoperative circulator
D. Collector shading E. Ambient conditions F. Steam lock at solar collector
A. Check to see if plug is in outlet
B. Reset breaker
C. Replace fuse D Replace controller
A. Remove plug at rear of circulators and insert screw driver into slotted end of shaft; turn to loosen shaft
B. Replace fuse; or reset breaker
C. Tighten connections D Replace controller
A. Same as A through D indicated above
B. Check sensor circuits and wiring
C. Reattach or reinsulate
D. System will not operate until preset conditions are met
A. Check sensor circuits and wiring, check for short in collector sensor circuit or open in tank sensor circuit Replace sensor wire or sensors
B. Replace controller
A. Wait until system temperature is replenished C. Remove plug at rear of circulator and insert screwdriver into slotted end of shaft, turn to loosen shaft D. Remove shading obstacles E. Wait until preset conditions are met F. Recharge solar closed loop to remove air from antifreeze solution
6. System losing temperature at night.
082809
A. Inoperative check valve(s)
B. Inoperative controller
C. Inoperative sensor circuits
A. Make sure check valves in Regusol are not stuck open
B. Replace controller
C. Check sensor circuits and wiring
73
Page 75
Trouble Shooting
Trouble Probable Cause Remedy
7. Inadequate hot water delivery temperature.
8. Tank pressure temperature relief valve blowing off.
A. Recent heavy usage of hot water
B. Inoperative mixing valve
C. Ambient conditions D. Inoperative back-up hot water heater
E. Inoperative existing system during periods of low solar insulation
A. Inoperative P/T relief valve
B. Hot water storage tanks
building too much pressure C. Water main pressure too high
A. Wait until system temperature is replenished
B. Adjust or replace mixing valve
C. Wait until preset conditions are met D. Replace back-up tank or service thermostat or element in electric hot water heater (this should be done by licensed electrician) E. Contact appropriate service
A. Replace P/T valve
B. Install hot water expansion tank
C. Install Pressure regulator on cold water supply
Sensor Test
Use an Ohm meter to measure the resistance of the sensor circuit. If an open circuit or a short circuit situation is detected, then inspect the sensor wiring before suspecting the sensor. Measure the sensor resistance without the interconnecting wire before removing the sensor. The resistance should match the chart for a given temperature.
Maintenance Procedures
Cleaning. The solar collectors will not require cleaning in a climate in which there is periodic rainfall. A light coating of dust will not seriously affect performance. In dry, dusty climates, collectors should be cleaned occasionally.
Circulators and Controller. No scheduled maintenance is required for the uid lubricated circulators or controller system. In the event of a circulator or controller malfunction, refer to troubleshooting Checks.
Collector Loop Fluid. Collector loop uid must be changed in order to maintain adequate freeze and corrosion protection. Antifeeze checks should be performed annually. Collector loop uid should be replaced
every 5 - 7 years. To prevent elevated temperatures from developing at the collectors, do not turn the system off while absent from premises for extended periods.
Solar Storage Tank. Periodically drain a small amount of water from the bottom of tank to prevent sludge or sediment buildup in the solar storage tank.
Scaling. If your water supply contains a large percentage of minerals (hard water), we strongly recommend that a water softening device be installed to protect not only the stainless steel solar storage tank and coils but also the existing hot water heater and its plumbing as well.
74
082809
Page 76
Projections for various components average life cycle
OVSOL 5 evacuated tubes: expected lifetime against vacuum loss . . . . . . . . . . . . 15 - 20 years
OVF-32 at plate collectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 - 20 years
Dual or single coil indirect glass lined tanks: good water quality . . . . . . . . . . . . . . . 20+ years
Regusol 130 EL: Oventrop PE Controller and sensors, Wilo circulator . . . . . . . . . . 10 - 15 years
All inquiries should be made to the product manufacturer:
Oventrop Corporation
PO Box 789
29 Kripes Road East Granby, CT 06026 Ph. (860)413-9173 www.oventrop-us.com
082809
75
Page 77
Section Twelve
Oventrop Corporation - Limited Warranty
Oventrop Corporation warrants to its “Customers” that all Oventrop products, used for heating and plumbing applications and sold in accordance with these warranty provisions, shall be free from defects in material and workmanship. “Customer” as used herein shall mean an end-user of Oventrop products.
Five (5) years for all solar components from the date of purchase, unless otherwise specied in writing. Ten (10) years for evacuated tube collector from date of purchase, unless otherwise specied in writing. Limited Lifetime for stainless steel indirect water heater fteen (15) years from date of purchase, unless otherwise specied in writing.
In order to be eligible for a warranty claim, products sold (1) must be installed and maintained professionally according to the relevant assembly instructions and the product manual, (2) must only be used for purposes provided in the Oventrop Corporation’s product description or assembly instructions, (3) must be exposed only to gaseous or liquid media approved for the product by Oventrop Corporation, and (4) shall not be combined with products of other manufacturers unless otherwise stated in the product manual.
Oventrop Corporation’s sole obligation hereunder shall be, at its option, to issue credit, repair or replace any component or part thereof which is proved to be defective. The limited warranty does not cover cost for transportation or labor charges (including installation and removal) unless such charges are authorized in writing in advance by the Oventrop Corporation. Any repairs without the express written consent of Oventrop Corporation shall render this limited warranty invalid. Oventrop Corporation disclaims allowances for dismounting and consequential losses and damages.
Warranty claims must be received by Oventrop Corporation within the applicable warranty period and within thirty (30) days from when the cause for the claim occurred or was discovered. Upon receipt of prompt notice of a warranty claim, Oventrop Corporation shall have ten (10) business days in which to determine whether it acknowledges responsibility for any asserted defects in material or workmanship and the appropriate action to be taken.
This limited warranty and any claims arising from the breach of warranty, or any other claim arising hereunder, shall be governed and construed under the laws of the State of New York. No other persons than Oventrop Corporation employees have any expressed or implied authority to bind Oventrop Corporation to any agreement or warranty of any kind without the express written consent of Oventrop Corporation.
Disclaimer of Warranties: OVENTROP CORPORATION DISCLAIMS ANY WARRANTY NOT PROVIDED HEREIN INCLUDING THE IMPLIED WARRANTY OF MERCHANTABILITY AND IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. IT IS EXPRESSLY UNDERSTOOD THAT OVENTROP CORPORATION IS NOT RESPONSIBLE FOR ANY CONSEQUENTIAL OR OTHER DAMAGES THAT MAY ARISE FROM USING OVENTROP CORP. SYSTEM COMPONENTS. DAMAGE RESULTING FROM WATER FREEZING IN THE TUBING DOES NOT CONSTITUTE A DEFECT IN MATERIAL OR WORKMANSHIP, AND SHALL NOT BE COVERED BY THIS WARRANTY. OVENTROP TUBING MAY NOT BE STORED IN DIRECT SUNLIGHT FOR ANY PERIOD LONGER THAN THREE WEEKS, OR THIS LIMITED WARRANTY BECOMES INVALID. OVENTROP CORPORATION DISCLAIMES ANY STATUTORY OR IMPLIED WARRANTY OF HABITABILITY. OVENTROP CORPORATION FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL, INDIRECT, SECONDARY, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE OF THE ARTICLES SOLD HEREUNDER. THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE FACE HEREOF.