Oval EL1812 Instructions Manual

BATCH COUNTER
Ins. No.
E-216-5N-E
Every OVAL batch counter is fabricated, tested, inspected, and shipped from our factory under stringent quality control. In order to maintain its design performance throughout its life, this manual offers the operator the necessary installation, operation and maintenance information. Be well familiar with these instructions before you place the counter in service and keep this manual at the field location for ready reference. Also refer to the instruction manual for the pulse generator (flowmeter) used.
1
E-216-5N-E
1. BEFORE YOU BEGIN ........................................................................................ 4
1.1 Confirmation of product name plate ............................................................... 4
1.2 Transportation Considerations ....................................................................... 4
1.3 Storage Considerations ................................................................................. 4
2. GENERAL ........................................................................................................... 5
2.1 Features and Functions ................................................................................. 5
3. PART NAMES ..................................................................................................... 5
4. INSTALLATION ................................................................................................... 6
4.1 Outline Dimensions ........................................................................................ 6
4.2 Installation ...................................................................................................... 6
4.2.1 Installation Location (Indoor only) ............................................................ 6
CONTENTS
4.2.2 Panel ........................................................................................................ 6
4.2.3 Installation ................................................................................................ 6
5. WIRING .............................................................................................................. 7
5.1 Cables for Field Wiring .................................................................................. 7
5.2 Wiring Connections ........................................................................................ 7
5.3 Identifying the External Connection Terminal Block ....................................... 7
5.4 External Connection Terminals ...................................................................... 8
5.5 Flow rate input and used Terminals ............................................................... 9
5.6 Example of wire connection diagram of flowmeter signal .............................. 9
5.7 Example of Hookup ....................................................................................... 10
6. FRONT DISPLAY PART AND BATCH PROCESSING PART ............................. 12
6.1 Functions of front display part and batch processing part ............................. 12
7. BLOCK DIAGRAM .............................................................................................. 13
8. OPERATION ....................................................................................................... 14
8.1 Preparation Before Operation ........................................................................ 14
8.2 Preoperational Checks .................................................................................. 14
8.3 Operation Sequence ...................................................................................... 14
8.4 How to set the batch setting quantity ............................................................. 15
8.5 Batch processing and various functions ........................................................ 17
8.6 Alarm processing ........................................................................................... 29
2
E-216-5N-E
9. CHANGE OF SETTING VALUE ............................................................................ 31
9.1 Parameter setting ............................................................................................. 31
9.2 Configuration of internal device ........................................................................ 35
9.3 Removal of inner assembly .............................................................................. 35
9.4 Installation of internal assembly ....................................................................... 36
9.4.1 How to assemble power supply / input board and output board ................. 36
9.4.2 How to assemble display unit ...................................................................... 36
9.5 Change of setting on input board and CPU board ............................................ 37
10. TROUBLESHOOTING......................................................................................... 38
10.1 Inspection Items .............................................................................................. 38
10.2 Q&A about Counter Behavior in Standby Mod ............................................... 39
10.3 Inspection of fuse ............................................................................................ 39
11. GENERAL SPECIFICATIONS ............................................................................. 40
12. PRODUCT SYMBOL ........................................................................................... 41
Shown in this manual are the signal words
NOTE, CAUTION and WARNING, as described in the examples below:
NOTE:
Notes are separated from the general text to bring the users
attention to important information.
CAUTION:
Caution statements signal the user about hazards or unsafe
practices which could result in minor personal injury or product or
property damages.
WARNING:
Warning statements signal the user about hazards or unsafe
practices which could result in severe personal injury or death.
3
E-216-5N-E
Product name plate
COM
1. BEFORE YOU BEGIN
This device is shipped after sufficient inspection at factory. After receiving this device, check if there is no damage on the external appearance. When received, it should be carefully inspected for any indication of rough handling during transit. In this section, instructions necessary for handling this instrument are described. Make yourself familiar with these instructions. As for other instructions, refer to respective sections. If you have something to inquire, contact the nearest OVAL authorized service station in your district.
1.1 Confirmation of product name plate
This device is shipped according to the specifications. The product name plate is attached to the right side surface of batch counter. Check the standard specifica­tions and description of product number of device correspond t o the ordered specifications.
Fig. 1.1 Example of attachment of product name plate
When you make an inquiry, please inform us of product name, product symbol (TYPE), and production number (SERIAL No.) etc. described on the product name plate.
1.2 Transportation Considerations
(1) The batch counter should be transported and stored in the same package used for transportation from our
factory if circumstances permit.
(2) Avoid giving impact shocks to the batch counter during transportation.
1.3 Storage Considerations
If the batch counter upon receipt is to be stored for extended periods of time before installation, unexpected problems could arise. In a case like this, the following considerations should be taken:
(1) The batch counter can best be stored in the original package used for transit from the factory. (2) Select a storage location that meets the following requirements:
• Free from rainwater and moisture
• Least vibration and impact shock
• In the room temperature and humidity environment (around 25°C and 65% R.H.)
4
E-216-5N-E
85〜264VAC
1A
Front view
Front display part
Push button switch operation par t
Rear view
D-SUB connector
Externally connected terminal block ×2
Left side view
Fuse rating silk
Fuse socket
Power supply specications silk
Right side view
Input board SW part
CPU board SW part
Product name plate
Terminal block connection diagram silk
2. GENERAL
Combined with a flowmeter and a shutoff valve, the batch counter passes a predetermined amount of the process fluid in batching operations. Built around a single chip microprocessor, this versatile, compact, and lightweight counter is designed for ease of operation. It saves time and effort in many processes, such as blending materials, dosing with additives, transferring materials from one tank to another, or shipping from an outlet, at chemical, food, paint plants or elsewhere where streamlined production lines are desired.
2.1 Features and Functions
(1) Easy operation.
a. As setting, start, stop, and reset of batch quantity are carried out with touch panel in front of measuring
instrument and push button switches, assured operation is possible.
b.
The display part is equipped with color LCD module with 3.5-inch touch panel. Although it is small, it is easily viewable.
c.
Start and stop, and reset are operated with push button switches and setting of batch quantity is operated with touch panel to prevent wrong operation.
(2) Wrong setting can be prevented.
As the operation of touch panel can read out nine types of batch quantities that have been registered, wrong setting can be prevented.
(3) Correct quantitative control is possible.
a.
As an operation signal that opens or closes the valve at 2 stages, correct quantitative measurement is possible.
b.
As the overshoot quantity due to response delay of valve can be corrected by setting the forecasted overshoot quantity, correct quantitative operation is possible.
(4) A system can be configured easily.
As start stop, and reset operations are enabled by external signal and the batch completion output can be obtained, the interlocking with other control system is enabled easily.
(5) The safety of process can be ensured.
a.
The valve is operated by 2-stage open and 2-stage close. The generation of static electricity in piping or tank when the operation is started is prevented and piping shock due to water hammering when the valve is closed is prevented.
b.
If a defect is generated in the process and the pulse is not input or fluid leaks exceeding the setting batch quantity, an alarm signal will be output.
(6) This device is of high reliability and the maintenance can be implemented easily.
a. As the internal configuration is unitized, this device is of high reliability and the maintenance can be
implemented easily. b. All I/O systems are isolated by photocoupler / relay etc. c. When the power supply is turned OFF, total flow value and each setting value will be held in FeRAM.
3. PART NAMES
Fig. 3.1 Name of each part
5
E-216-5N-E
96
96
13
129.1
112
17.1)
91.5
Packing
COM
min.120
min.174
920.3
920.3
Panel
Batchcounter
600
1800
2200
450
Optimumrange
Availablerange
min.120
min.174
920.3
920.3
4. INSTALLATION
4.1 Outline Dimensions
4.2 Installation
Unit: mm
Fig. 4.1 Outline Dimensions
4.2.1 Installation Location (Indoor only)
Choose to install in the place where: (1) Mechanical vibration, shock and corrosive gases least
exist.
(2)
The air is dry and at around room temperature and stable. (3) A place not exposed to the direct sunlight. (4)
A place where dust is almost none
NOTE:
1. In installation and through daily operation, pay due care so as dust not to accumulate in the place.
2.If chemical solvent etc. may be attached to
the front surface, it is recommended to use the protection sheet or touch pen separately to protect the decorative sheet on the front surface.
Although the manufacturer g u a r a n t e e s
3.
stated
performance at ambient temperatures
from –10 to 50, it is recommended that the instrument be placed in service at room
(5)
Pr o vi de a s uf f ic i e n t wo r ki n g s pa ce be hi n d t he
temperature.
instrument – at least 50 centimeters from the back panel of the instrument to facilitate wiring and servicing.
.
Unit: mm
Fig. 4.2 Panel Cut
Unit: mm
4.2.2 Panel
(1) Use a rigid steel sheet with a minimum thickness of
1.6 mm as min. Recommended thickness is 3.2mm.
(2) If it is required to mount the computers side by side,
dimensions in Fig. 4.2 are suggested.
(3) Recommended mounting height is given in Fig. 4.3.
4.2.3 Installation
(1)
Install the ancillary packing on the batch counter insert it from the front surface of panel. (Fig. 4.1)
(2) Hook the enclosure hold-down fittings to the slots in
the re a r o f t he enc l o sure instrument is positioned on a level plane, then secure the instrument to the panel with panel mount fittings.
6
, a n d conf i r m
th a t t he
and
Fig. 4.3 Hight
E-216-5N-E
85〜264VAC
Short-circuit board If the interlock is not used, attach the short-circuit board in between 25 (I.Lock) and 26 (COM.1).
D-SUB connector
Short-circuit board If the externally operated input STOP is not used, attach the short-circuit board in between 19 (STOP) and 20 (COM.1).
Terminal Nos.
1 to 8, 17 to 24
Terminal Nos.
9 to 16, 25 to 32
1A
5. WIRING
NOTE: See “WIRING” in the pulse generator instruction manual.
5.1 Cables for Field Wiring
(1) For flowmeter input signal cable, electrostatically shielded, polyethylene insulated, vinyl-sheathed control
cables (CEVS, 1.25 to 2mm2, 2- or 3-conductor), or equivalent, must be used.
For output signal cables, insulated, vinyl-sheathed cables (CVV, CVVS JIS C 3401) are suggested. (2) Cable shields must be connected to terminal “G” of the counter. At the probe end, leave the shield wire end
unprepared.
(3) For the connection cable to D-SUB connector, use 25-pin soldering type (male). Create it as a dedicated part.
For an electric wire, use the electric wire "equivalent to UL1007, 0.5mm2 ".
5.2 Wiring Connections
(1) Conduit work is suggested for field wiring.
NOTE: In conduit work, use separate conduit for power cables and signal cables in order to minimize the
possibility of stray current pickup.
(2) Route cables sufficiently away from other power lines or power circuits, if any, to reduce the possibility of
inductive interference to a minimum.
(3) Use crimp-style terminal lugs for connections and ensure good electrical contact. Connection terminals are
found at rear of the counter (Fig. 5.1).
(4) In applications where an inductive load (valve, counter, etc.) is driven, do not fail to use a surge suppressor
(see Fig. 5.2).
(5) For the wiring, ensure approx. 30cm of allowance to enable the easy maintenance.
5.3 Identifying the External Connection Terminal Block
On the rear surface of this device, there are terminal block fixed to input board (terminals No.1 to 8, 17 to 24), terminal block fixed to output board (terminals No.9 to 16, 25 to 32), D-SUB connector fixed to power supply board (25-pin female).
CAUTION: Before making wiring connections, verify the validity of flowmeter (pulse generator) and receiving
instrument combination by referring to their product No., tag No., etc.
Fig. 5.1 External wire connection terminal diagram
7
E-216-5N-E
Signal DescriptionNo
Flow rate
input
SUP.
SIG.
COM.1
COM.2
L1
L2
GND1
NC
NC
START
RESET
STOP
COM.1
ALARM
COM.5
I.Lock
COM.1
PUMP
Select 1
PUMP
COM.6
END
END
SV a
COM.3
SV b
MV a
COM.4
MV b
SIG.
1
Signal DescriptionNo
9
Select 2
10
Select 4
11
Select 8
12
SET
13
COM.1
24
GND2
25
2
3
5
6
7
8
17
18
19
20
21
22
23
24
25
26
27
28
29
30
32
31
9
10
11
12
13
14
15
16
4
Pulse output
Power supply
Batch
completion
output
External
operation
input
Alarm output
GND1
GND1
Interlock
Pump
operation
signal
External CH.
input
Valve
operation
signal (SV)
Valve
operation
signal (MV)
Contact pulse/ open collector
Open collector output
85 to 264VAC 50/60Hz
Connection terminal (※2)
No-contact relay output contact Form "a" contact
External CH. input shielded grounding ※ Not conducted with GND1
1
2
3
4
5
6
7
8
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
25
13
12 11
10
9
24
9
10
11
12
13
14
15
16
Output board side
17P M3.5
Input board side
17P M3.5
D-SUB connector
Female 25P
(※1)
Terminal block
D-SUB connector female 25P
※ Each COM.1 terminal is conducted.
Each GND1 terminal is conducted.
※2: Grounding of equipment
Be sure to ground it to prevent electric shock/ fire and block external noise.
※1: D-SUB connector type
DBLC-J25SAF-23L6E Japan Aviation Electronics Industry, Limited
※3: To use the external operation input, it is
necessary to prepare the connector of D-SUB25 pin by yourself and connect the circuit for selecting a channel to D-SUB terminal on the rear surface of this machine.
※ The frame of D-SUB connector is
conducted with GND1.
※ External operation and batch setting volume
For "preset value" setting, refer to section 8.4.
Limit flow rate signal 1-stage open
Relay contact Form "c" contact
Relay contact Form "a" contact
Shielded grounding
Shielded grounding
Upper limit flow rate signal fully opened
STOP is short-circuited when it is not used
(※3)
Interlock is short-circuited when it is not used
Pump control output Relay contact Form "c" contact
Combination of select and CH.
Select 1 Select
2
Select
4
Select
8
CH.1 CH.2 CH.3 CH.4 CH.5 CH.6 CH.7 CH.8 CH.9 CH.F
ON OFF ON OFF ON OFF ON OFF ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON OFF OFF OFF ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON
2-wire current pulse (4/20mA)
3-wire voltage pulse (PG30)
2-wire current pulse (PG30S)
4-40-inch screw
14
1
5.4 External connection terminals
Terminal block and D-SUB connector
8
5.5 Flow rate input and used terminals
12VDC3-wiretypevoltagepulse(PG30) 12VDC2-wiretypecurrentpulse(PG30S)
24VDC2-wiretypecurrentpulse(4/20mA)
33
13.5
13.5
13.5
3-wiretypeopencollector
Opencollector
Contactpulse
Pulse generator
Pulse generator
Pulse generator
Pulse generator
Pulse generator
Pulse generator
E-216-5N-E
Signal type
Transmitter
Contact-closure pulse / 2-wire voltage pulse
Open collector pulse 12VDC 2-wire type
current pulse
PG20, Coriolis flowmeter
PG30S
24VDC 2-wire type
Current pulse
PA14, 15, 25
NPG60A
1 ○ + ○ SUP.
Terminal
2 ○ + ○ - ○ SIG. 3 ○ -
mark: used terminal
5.6 Example of wire connection diagram of flowmeter signal
3-line type open collector
3-wire voltage pulse
PG30, NPG60A
flow pet
○ COM.
CAUTION: In the wiring, connect the wires properly, while checking the combination of product number
and measuring instrument number etc. of flowmeter (transmitter) and receiver.
9
E-216-5N-E
IftheexternaloperationinputSTOPisnotused, STOP(19)toCOM.(20)shouldbealwaysshort­circuited.Iftheinterlockisnotused,I.LOCK(25) toCOM.(26)shouldbealwaysshort-circuited.
Terminal connection diagram (silk on left side of this device)
Output to remote totalizer counter, etc.
Open collector
200msec.min.
200msec.min.
200msec.min.
200msec.
min.
200msec.
min.
Power: 85 to 264VAC 50/60Hz
Operation
Stopped
STOP (contact b)
RESET (contact a)
START (contact a)
Alarm output LED lamp etc. can be driven
Pump can be operated / stopped for batch processing
CORIOLIS FLOWMETERS
OVAL FLOWMETER
ALTImass Type S
ALTImass Type U
ULTRA
MK
Flow signal input.
(std.)
Pump output
SV MV COM
SV
MV
COM
Valve
R
C
R
C
Surgesuppressor
Air supply ?
Combinationfilter/reducingvalve
Two-stage shuto valve
3-wayDirectionalvalve
Valve operation output
Remote Control Input
Short-circuited when an interlock is not used
Function such as LED light up when batching completes is enabled
Output to External Totalizer
OVAL owmeters, Coriolis owmete rs, etc.
CAUTION:
* The owme ter sh own h ere
is a n exa mple.
Itisrecommendedtoattachthesurgesuppres­soretc.totheinductionloadsidetoprotectthe contact.
CAUTION:
5.7 Example of Hookup
Fig. 5.2 Exampl of Wiring Connections (Terminal block)
10
E-216-5N-E
Selector1 Selector2 Selector4 Selector8
SET
COM.1
GND2
Selector1
Selector2
Selector4
Selector8
CH.1
ON
OFF
OFF
OFF
CH.2
OFF
ON
OFF
OFF
CH.3
ON
ON
OFF
OFF
CH.4
OFF
OFF
ON
OFF
CH.5
ON
OFF
ON
OFF
CH.6
OFF
ON
ON
OFF
CH.7
ON
ON
ON
OFF
CH.8
OFF
OFF
OFF
ON
CH.9
ON
OFF
OFF
ON
CH.F
OFF
ON
OFF
ON
9 10 11 12 13 24 25
25 24
13 12 11 10
9
Rearsurfaceofenclosure
D-SUBconnector
Eachselection
(contacta)
SET
(contacta)
200msecormore
HeldbyONorOFF
Pushbuttonswitchetc.
(forfixingCH.)
Selectorswitch
(forselectingCH.)
Fig.5.3 Example of Hookup(D-SUB connector)
11
E-216-5N-E
Status display part
Integration display part
Batch quantity setting value display part
Valve / pump
status display part
LCD module communication
monitoring part
Batch processing part
(push button switch)
Setting button part
Channel display part
6. FRONT DISPLAY PART AND BATCH PROCESSING PART
6.1 Functions of front display part and batch processing part
The display part has status indication lamps such as RUN and END. There are integration display, batch quantity setting value, and channel display part in the center of upper stage. There are operation indication lamps of valve and pump on the left side. The batch processing part has three push button switches; START, STOP, and RESET and the control at batch processing is enabled only by three push button switches.
Status display part
Valve / pump status display part
LCD module communication monitoring part
Integration display part
Batch quantity setting value display part
Channel display part
Setting button part
Batch processing part (push button switch)
Fig. 6.1
Name Function
RUN
END Lights up when the batch is completed: green ALARM Lights up when an alarm is generated: red I.Lock Lights up when the interlock signal is turned ON; batch is enabled when it is turned ON: blue MV Upper limit flow rate signal lights up when it is turned ON; goes out when it is turned OFF: red SV Restricted flow rate signal lights up when it is turned ON; goes out when it is turned OFF: red PUMP Pump control signal lights up when it is turned ON; goes out when it is turned OFF
COM Communication status between CPU board and LCD module can be monitored: blue LED
COUNT Batch quantity total flow value display 6 digits Measurement unit Integrated flow Displayed when any - (- blank), mL, L, kL, m3, g, kg, t, USG, barrel is set PRESET Batch setting quantity display 6 digits TOTAL Displays the total value by touching TOTAL button 9 digits *1 CH. No. Displays the selected channel number 2 digits *2 ERR. CODE Displays error number when an alarm is generated *3 CH.SEL Shifts to [CHANNEL SELECT] screen PRESET Shifts to [PRESET SETTING (CH.F)] screen only when CH.F (free) is selected TOTAL Displays the total value by touching the button MENU Shifts to [MENU] screen STOP Batch processing temporarily stops when an alarm is generated: buzzer stops RESET Bach completion is reset when an alarm is generated: alarm is reset START
Displays the batch processing status ; lights up when batch operation is ongoing; blinks when the operation is interrupted: yellow
Displayed when any of ×1000, ×100, ×10, ×1, ×0.1, ×0.01, ×0.001 is set
Batch processing starts when the operation is temporarily stopped: batch processing is restarted
NOTE: *1: Displayed while you touch the TOTAL button. Display time can be set by setting parameter.
*2: Channel display *3: Error display
12
C1: channel 1 C6: channel 6 E1: pulse non-receipt alarm C2: channel 2 C7: channel 7 E2: overrun alarm C3: channel 3 C8: channel 8 E3: leak alarm C4: channel 4 C9: channel 9 E4: interlock alarm C5: channel 5 CF: free setting channel E5: emergency stop by RESET button In case of external setting, C is displayed in small letter E7: WDT reset alarm Front setting: C1 to CF E8: electric power failure alarm External setting: c1 to cF E9: FeRAM alarm
7. BLOCK DIAGRAM
External line
terminal block
External line
terminal block
Flow rate input
Interlock
Batch completion
output
Valve operation
output SV
Valve operation
output MV
Pump output
Form "c" contact
Power supply
for transmitter
+13.5V
+24V
Pulse output
External operation input
Alarm output
Form "a" contact
Supplied power AC
Input board
SUP. 1
I. Lock 25
COM.1 26
END 9
SV a 11
SV b 13
COM.3 12
MV a 14
MV b 16
COM.4 15
PUMP 30
PUMP 32
GND1 27
GND1 28
GND1 29
NC
COM.6 31
END 10
SIG. 2
COM.1 3
SIG. 4
COM. 2 5
ALARM 21
COM. 5 22
GND1 23
L1 6
L2 7
GND1 8
NC
GND1 24
START 17
RESET 18
STOP 19
COM.1 20
2 RXD
3 TXD
7 VD_G
9 select 1
10
select
2
11
select
4
TXD+ 14
TXD− 15
RXD+ 16
RXD− 17
VD_+ 18
COM.1 24
GND2 25
Frame
grounding
12
select
8
13 SET
SIG.
Pulse input
circuit
Photocoupler
START
RESET
STOP
SIG.
ALARM
Select 1
Select 2
Select 4
Select 8
SET
Photocoupler
Photocoupler
Photocoupler
Photocoupler
Photocoupler
Photocoupler
Varistor
Buzzer
Relay
Photo MOS
Photocoupler
Photocoupler
Photocoupler
Photocoupler
Connector
ConnectorConnector
Connector Connector
Varistor
Varistor
a
COM
Relay
AC/DC
Power supply
Input: 24VDC
D−
SUB
Noise
filter
Connector
CPU
debug
circuit
WDT
reset
circuit
CPU
Electric power
failure detection
circuit
Serial
interface
Connector
Connector
Connector
Connector
Connector
Connector
Select 1, 2, 4, 8
SET,
Communication
Select 1, 2, 4, 8
SET
Select 1, 2, 4, 8
SET
+24V,
13.5V,
5V,
5V
F
CPU board
Display unit
Output board
Operation buttons on front surface
Touch operation input
LED module
Power supply board
D−SUB 25P
+24V
+13.5V
circuit
+5V
circuit
+5V
circuit
Photocoupler/relay
Power supply for
transmitter
Power supply for
transmitter
LED module
Power supply for
internal control
85 to 264V
Varistor
Varistor
Varistor
Varistor
Varistor
Relay
Relay
SIG. IN
START, RESET, STOP
SIG. OUT, ALARM
Select 1, 2, 4, 8, SET
+24V,
5V,
5V
I.Lock
END
SV, MV, PUMP
Buzzer
24V,
5V
Communication
circuit
STOP RESET START
FeRAM
circuit
LED module
communication
monitoring LED
+5V
+5V communication
※1
※1
E-216-5N-E
NOTE:
Fig. 7.1 Block
※1: To use the external operation input, it is necessary to prepare the connector of D-SUB25 pin by yourself
and connect the circuit for selecting a channel to D-SUB terminal on the rear surface of this machine.
13
Loading...
+ 29 hidden pages