OutBack Power FXR2012E, FXR2348E, VFXR2612E, VFXR3024E, FXR2024E Owner's Manual

...
FXR Series Inverter/Charger
FXR2012E FXR2024E FXR2348E
VFXR2612E VFXR3024E VFXR3048E
Operator’s Manual
About OutBack Power Technologies
OutBack Power Technologies is a leader in advanced energy conversion technology. OutBack products include true sine wave inverter/chargers, maximum power point tracking charge controllers, and system communication components, as well as circuit breakers, batteries, accessories, and assembled systems.
Grid/Hybrid™
As a leader in off-grid energy systems designed around energy storage, OutBack Power is an innovator in Grid/Hybrid system technology, providing the best of both worlds: grid-tied system savings during normal or daylight operation, and off-grid independence during peak energy times or in the event of a power outage or an emergency. Grid/Hybrid systems have the intelligence, agility and interoperability to operate in multiple energy modes quickly, efficiently, and seamlessly, in order to deliver clean, continuous and reliable power to residential and commercial users while maintaining grid stability.
Applicability
These instructions apply to OutBack inverter/charger models FXR2012E, FXR2024E, FXR2348E, VFXR2612E, VFXR3024E, and VFXR3048E only.
Contact Information
Address: Corporate Headquarters
17825 – 59th Avenue N.E. Suite B Arlington, WA 98223 USA
Telephone:
Email: Support@outbackpower.com
Website: http://www.outbackpower.com
+1.360.435.6030 +1.360.618.4363 (Technical Support) +1.360.435.6019 (Fax)
European Office Hansastrasse 8 D-91126 Schwabach, Germany
+49.9122.79889.0 +49.9122.79889.21 (Fax)
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER TECHNOLOGIES:
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
OutBack Power Technologies cannot be responsible for system failure, damages, or injury resulting from improper installation of their products.
Information included in this manual is subject to change without notice.
Notice of Copyright
FXR Inverter/Charger Operator’s Manual © 2015 by OutBack Power Technologies. All Rights Reserved.
Trademarks
OutBack Power, the OutBack Power logo, FLEXpower ONE, Grid/Hybrid, and OPTICS RE are trademarks owned and used by OutBack Power Technologies, Inc. The ALPHA logo and the phrase “member of the Alpha Group” are trademarks owned and used by Alpha Technologies Inc. These trademarks may be registered in the United States and other countries.
Date and Revision
October 2015, Revision B (firmware revision 001.006.xxx)
Part Number
900-0169-01-00 Rev B
Table of Contents
Introduction .......................................................................................................... 7
Audience ................................................................................................................................................................................. 7
Symbols Used ........................................................................................................................................................................ 7
General Safety ....................................................................................................................................................................... 7
Welcome to OutBack Power Technologies ................................................................................................................. 8
Inverter Functions ................................................................................................................................................................ 8
Inverter Controls ................................................................................................................................................................... 9
MATE3 System Display and Controller ..................................................................................................................................... 9
On/Off Switch .................................................................................................................................................................................. 10
Operation ............................................................................................................ 11
LED Indicators ..................................................................................................................................................................... 11
Battery Indicators ........................................................................................................................................................................... 11
Status Indicators ............................................................................................................................................................................. 12
Inverter Functionality ...................................................................................................................................................... 13
AC Input Connection ....................................................................................................................................................... 13
Description of AC Input Modes .................................................................................................................................... 13
Generator .......................................................................................................................................................................................... 14
Support .............................................................................................................................................................................................. 14
Grid Tied ............................................................................................................................................................................................ 15
Grid Interface Protection Menu .................................................................................................................................................................... 16
Frequency and Phase Coordination ............................................................................................................................................................ 17
UPS ...................................................................................................................................................................................................... 17
Backup ............................................................................................................................................................................................... 18
Mini Grid ............................................................................................................................................................................................ 18
GridZero ............................................................................................................................................................................................ 19
Description of Inverter Operations ............................................................................................................................. 23
Inverting ............................................................................................................................................................................................ 23
DC and AC Voltages .......................................................................................................................................................................................... 23
AC Frequency ...................................................................................................................................................................................................... 24
Search ..................................................................................................................................................................................................................... 24
Input ................................................................................................................................................................................................... 25
AC Current Settings ........................................................................................................................................................................................... 26
AC Source Acceptance ..................................................................................................................................................................................... 26
Generator Input .................................................................................................................................................................................................. 28
Transfer .................................................................................................................................................................................................................. 28
Battery Charging ............................................................................................................................................................................ 29
Charge Current .................................................................................................................................................................................................... 29
Charge Cycle ........................................................................................................................................................................................................ 30
Advanced Battery Charging (ABC) ............................................................................................................................................................... 31
Charging Steps .................................................................................................................................................................................................... 31
New Charging Cycle .......................................................................................................................................................................................... 33
Equalization .......................................................................................................................................................................................................... 36
Battery Temperature Compensation .......................................................................................................................................................... 37
Offset .................................................................................................................................................................................................. 38
Multiple-Inverter Installations (Stacking) ............................................................................................................................... 39
Stacking Configurations .............................................................................................................................................................. 40
Parallel Stacking (Dual-Stack and Larger) ................................................................................................................................................. 40
Three-Phase Stacking ....................................................................................................................................................................................... 40
Power Save ........................................................................................................................................................................................................... 42
900-0169-01-00 Rev B 3
Table of Contents
Auxiliary Terminals ........................................................................................................................................................................ 45
System Display-Based Functions ................................................................................................................................. 48
Advanced Generator Start (AGS) .............................................................................................................................................. 48
Grid Functions ................................................................................................................................................................................. 48
High Battery Transfer (HBX) ............................................................................................................................................................................ 48
Grid Use Time ...................................................................................................................................................................................................... 49
Load Grid Transfer ............................................................................................................................................................................................. 49
Firmware Updates ............................................................................................................................................................. 49
Metering ............................................................................................................. 51
MATE3 Screens ................................................................................................................................................................... 51
Inverter Screen ................................................................................................................................................................................ 51
Battery Screen ................................................................................................................................................................................. 52
Troubleshooting .................................................................................................. 53
Basic Troubleshooting ..................................................................................................................................................... 53
Error Messages ................................................................................................................................................................... 58
Warning Messages ............................................................................................................................................................ 59
Temperatures .................................................................................................................................................................................. 60
GT Warnings..................................................................................................................................................................................... 60
Disconnect Messages ...................................................................................................................................................... 61
Sell Status ............................................................................................................................................................................. 62
Specifications ...................................................................................................... 63
Electrical Specifications ................................................................................................................................................... 63
Mechanical Specifications .............................................................................................................................................. 66
Environmental Specifications ....................................................................................................................................... 66
Temperature Derating .................................................................................................................................................................. 67
Regulatory Specifications ............................................................................................................................................... 67
Certifications .................................................................................................................................................................................... 67
Compliance ...................................................................................................................................................................................... 67
Summary of Operating Limits ....................................................................................................................................... 69
Limiting Charge Current (Multiple Inverters) ....................................................................................................................... 69
Firmware Revision ............................................................................................................................................................. 71
Default Settings and Ranges ......................................................................................................................................... 72
Definitions ............................................................................................................................................................................ 78
Index ................................................................................................................... 79
4 900-0169-01-00 Rev B
Table of Contents
List of Tables
Table 1 Battery Indicator Values ............................................................................................................................. 11
Table 2 Summary of Input Modes .......................................................................................................................... 21
Table 3 Charge Currents for FXR Models ............................................................................................................. 29
Table 4 Offset Interaction with AC Source .......................................................................................................... 38
Table 5 Aux Mode Functions ................................................................................................................................... 47
Table 6 Comparison of Grid Functions ................................................................................................................. 49
Table 7 Troubleshooting ........................................................................................................................................... 53
Table 8 Error Troubleshooting ................................................................................................................................ 58
Table 9 Warning Troubleshooting ......................................................................................................................... 59
Table 10 Inverter Temps .............................................................................................................................................. 60
Table 11 GT Warnings ................................................................................................................................................... 60
Table 12 Disconnect Troubleshooting ................................................................................................................... 61
Table 13 Sell Status Messages .................................................................................................................................... 62
Table 14 Electrical Specifications for 12-Volt FXR Models ............................................................................... 63
Table 15 Electrical Specifications for 24-Volt FXR Models ............................................................................... 64
Table 16 Electrical Specifications for 48-Volt FXR Models ............................................................................... 65
Table 17 Mechanical Specifications for FXR Models .......................................................................................... 66
Table 18 Environmental Specifications for all FXR Models ............................................................................. 66
Table 19 Operating Limits for all FXR Models ...................................................................................................... 69
Table 20 Chargers On and Current Settings ......................................................................................................... 70
Table 21 Charge Curre
Table 22 FXR Settings for 12-Volt Models .............................................................................................................. 72
Table 23 FXR Settings for 24-Volt Models .............................................................................................................. 74
Table 24 FXR Settings for 48-Volt Models .............................................................................................................. 76
Table 25 Terms and Definitions ................................................................................................................................. 78
nts for Calculations ............................................................................................................ 71
900-0169-01-00 Rev B 5
Table of Contents
List of Figures
Figure 1 FXR Series Inverter/Charger with Turbo Fan ......................................................................................... 8
Figure 2 MATE3 and AXS Port ................................................................................................................................... 10
Figure 3 LED Indicators ................................................................................................................................................ 11
Figure 4 Inverter Status LED Indicators .................................................................................................................. 12
Figure 5 Charging Stages Over Time ...................................................................................................................... 30
Figure 6 Charging Stages Over Time (24/7) ......................................................................................................... 30
st
Figure 7 Repeated Charging (1 Figure 8 Repeated Charging (3
Figure 9 OutBack HUB10.3 and MATE3.................................................................................................................. 39
Figure 10 Example of Parallel Stacking Arrangement (Three Inverters)....................................................... 40
Figure 11 Example of Three-Phase Stacking Arrangement (Three Inverters) ............................................ 41
Figure 12 Example of Three-Phase Stacking Arrangement (Nine Inverters) .............................................. 41
Figure 13 Power Save Levels and Loads .................................................................................................................. 42
Figure 14 Power Save Priority (Parallel) ................................................................................................................... 44
Figure 15 Power Save Priority (Three-Phase) ......................................................................................................... 44
Figure 16 Home Screen .................................................................................................................................................. 51
Figure 17 Inverter Screens ............................................................................................................................................ 51
Figure 18 Battery Screen ................................................................................................................................................ 52
Figure 19 AC Test Points ................................................................................................................................................ 53
Figure 20 Temperature Derating ................................................................................................................................ 67
and 2nd Cycles) ................................................................................................ 34
rd
, 4th, and 5th Cycles) ........................................................................................ 35
6 900-0169-01-00 Rev B
Introduction
Audience
This manual provides instructions for setup and operation of the product. It does not cover installation. The manual is intended to be used by anyone required to operate the FXR Series Inverter/Charger. Operators must be familiar with all the safety regulations pertaining to operating power equipment of this type as required by local code. Operators are advised to have basic electrical knowledge and a complete understanding of this equipment’s features and functions. Do not use this product unless it has been installed by a qualified installer in accordance with the FXR Series Inverter/Charger Installation Manual.
Symbols Used
WARNING: Hazard to Human Life
This type of notation indicates that the hazard could be harmful to human life.
CAUTION: Hazard to Equipment
This type of notation indicates that the hazard may cause damage to the equipment.
IMPORTANT:
This type of notation indicates that the information provided is important to the installation, operation and/or maintenance of the equipment. Failure to follow the recommendations in such a notation could result in voiding the equipment warranty.
MORE INFORMATION
When this symbol appears next to text, it means that more information is available in other manuals relating to the subject. The most common reference is to the FXR Series Inverter/Charger Installation Manual. Another common reference is the system display manual.
General Safety
WARNING: Limitations on Use
This equipment is NOT intended for use with life support equipment or other medical equipment or devices.
WARNING: Reduced Protection
If this product is used in a manner not specified by FXR product literature, the product’s internal safety protection may be impaired.
CAUTION: Equipment Damage
Only use components or accessories recommended or sold by OutBack Power Technologies or its authorized agents.
900-0169-01-00 Rev B 7
Introduction
Welcome to OutBack Power Technologies
Thank you for purchasing the OutBack FXR Series Inverter/Charger. It is designed to offer a complete power conversion system between batteries and AC power.
As part of an OutBack Grid/Hybrid™ system, it can provide off-grid power, grid backup power, or grid-interactive service which sells excess renewable energy back to the utility.
Figure 1 FXR Series Inverter/Charger with Turbo Fan
Inverter Functions
Battery-to-AC inverting which delivers power to run backup loads and other functions
Provides single-phase output Adjustable range of output voltage Settable nominal output frequency
AC-to-battery charging (OutBack systems are battery-based)
Accepts a wide variety of single-phase AC sources
Uses battery energy stored from renewable resources
Can utilize stored energy from many sources (PV arrays, wind turbines, etc.) OutBack FLEXmax charge controllers will optimize PV power production as part of a Grid/Hybrid system
Rapid transfer between AC source and inverter output with minimal delay time
8 900-0169-01-00 Rev B
Introduction
Uses the MATE3™ System Display and Controller or the AXS Port™ SunSpec Modbus Interface (sold separately) for user interface as part of a Grid/Hybrid system
MATE3 must have firmware revision 003.007.xxx or higher
Supports the OPTICS RE™ online tool
Requires the MATE3 or the AXS Port Visit www.outbackpower.com to download
Uses the HUB10.3™ Communications Manager for stacking as part of a Grid/Hybrid system
~ Stackable in parallel and three-phase configurations
Certified to IEC 62109-1 and IEC 62109-2
Field-upgradeable firmware (from www.outbackpower.com); requires MATE3 or AXS Port
Seven selectable input modes for different applications
Generator Support Grid Tied (available in 24-volt and 48-models only) UPSBackup Mini Grid GridZero
Single AC input with dual input programming; individualized modes and priorities can be selected when switching from utility grid to AC generator
external transfer device required system display required for individual programming
: This product has a settable AC output range. In this book, many references to the output refer
NOTE
to the entire range. However, some references are made to 230 Vac or 50 Hz output. These are intended as examples only.
1
for a cloud-based remote monitoring and control application
Inverter Controls
The FXR inverter has no external controls. It can operate normally without an external control or interface. Basic modes and settings are pre-programmed at the factory. (See the menu tables beginning on page 72.) However, external communication devices such as the OutBack MATE3 or AXS Port can be used to operate or program the inverter.
MATE3 System Display and Controller
The MATE3 System Display and Controller (sold separately) is designed to accommodate programming and monitoring of a Grid/Hybrid power system. The MATE3 provides the means to adjust the factory default settings to correctly match the installation where needed. It provides the means to monitor system performance and troubleshoot fault or shutdown conditions. It also has data logging and interface functions using the Internet.
Once settings are modified using a MATE3, the MATE3 can be removed from the installation. The settings are stored in the nonvolatile memory of the FXR inverter. However, it is highly recommended
1
Outback Power Technologies Intuitive Control System for Renewable Energy
900-0169-01-00 Rev B 9
Introduction
to include a MATE3 as part of the system. This provides the means to monitor system performance and respond quickly should it be necessary to correct a fault or shutdown condition.
The MATE3’s Configuration Wizard is capable of automatically configuring inverters to a series of preset values. This is often more efficient than attempting to manually program each setting in each inverter. Affected fields include system type, battery charging, and AC source configuration.
IMPORTANT:
The MATE3 system display must have firmware revision 003.007.xxx or higher.
IMPORTANT:
Some functions are not based in the inverter, but are part of the MATE3 firmware. They will not function if the system display is removed. These functions are listed beginning on page 48.
IMPORTANT:
The FXR inverter is only compatible with the MATE3 System Display and Controller. It is not intended for use with the OutBack MATE or MATE2 products.
The FXR inverter can use the OPTICS RE online tool as a system display. OPTICS RE must be used in conjunction with the MATE3 or with the AXS Port SunSpec Modbus Interface.
Figure 2 MATE3 and AXS Port
On/Off Switch
If a system display is not in use, the inverter can be equipped with a switch to turn it on and off. This switch is not sold as an inverter accessory; a common toggle switch can be used. The switch is wired to the
INVERTER ON/OFF
for more information on wiring the switch.)
This switch turns only the inverter on and off. It does not turn the charger or any other function on or off. All inverter functions will operate according to their programmed settings. Functions included with a system display will not be available.
10 900-0169-01-00 Rev B
auxiliary terminals. (See the FXR Series Inverter/Charger Installation Manual
LED Indicators
Operation
AUX Indicator (see page 45)
Battery
Indicators
Status Indicators
Figure 3 LED Indicators
Battery Indicators
The Battery LED indicators show the approximate battery state. (See
IMPORTANT
Battery indicators and the Inverter Status indicators are independent. They may accompany each other depending on conditions. Common combinations are noted on page 12.
A green indicator (FULL) means the batteries have an adequate charge at that time. It does not always mean
they are full. It may be accompanied by a yellow Status indicator when an AC source is charging.
A yellow indicator (OK) means the batteries are somewhat discharged. A red indicator (LOW) means the batteries are greatly discharged and may require attention. It may be
accompanied by a red Status indicator to indicate a low battery error.
Table 1 Battery Indicator Values
Color 12 Vdc Unit 24 Vdc Unit, ± 0.2 Vdc 48 Vdc Unit, ± 0.4 Vdc Battery Status
GREEN 12.5 Vdc or higher 25.0 Vdc or higher 50.0 Vdc or higher ACCEPTABLE
YELLOW 11.5 to 12.4 Vdc 23.0 to 24.8 Vdc 46.0 to 49.6 Vdc MARGINAL
RED 11.4 Vdc or lower 22.8 Vdc or lower 45.6 Vdc or lower LOW
note below.) The
NOTES
 
900-0169-01-00 Rev B
:
Gaps in the table (higher-voltage units) are due to the resolution of the inverter’s DC meter. These voltage settings are not the same as the Low Battery Cut-Out (LBCO) set point. (See page 23.) The Battery indicator
settings cannot be changed. Voltages higher than shown in the GREEN row usually show that the batteries are charging.
IMPORTANT:
Due to different system states, battery voltage does not always indicate an accurate state of charge. It is accurate if batteries have been at rest for several hours at room temperature (25°C or 77°F, or as specified by the battery manufacturer). If they have their voltage may not reflect their true state. The OutBack FLEXnet DC is a battery monitor that can be added to the system to provide accurate measurements.
loads, a charging source, or are at another temperature,
any
11
Operation
1
2
3
Solid
Flashing
Off
Solid:
Flashing
.
Off
Solid: Error. The inverter has shut down due to a critical problem which may be internal or external.
Flashing
Off
Status Indicators
STATUS INVERTER (Green):
: The FXR inverter is on and providing power.
If accompanied by a solid yellow inverter is also connected to the utility grid with an AC input mode that uses both inverter power and grid power (
Support, Grid Tied
See page 13 for descriptions of AC input modes.
, or
GridZero
indicator (2), the
AC IN
).
: The inverter has been turned on but is idle.
The inverter is likely in Search mode. See page 24.
: The inverter is off. It is not waiting to provide power.
See the system display manual to turn the inverter on.
Any power present is from another source such as the utility grid or generator.
The inverter may also be a slave that is in Silent mode due to the Power Save function. If so, the master inverter may still be providing power to the system.
See page 42 for a description of Power Save.
AC IN (Yellow):
The AC source is connected and providing power.
The FXR inverter may or may not be charging the batteries, depending on settings.
May be accompanied by green
STATUS INVERTER
indicator (1).
: The AC source is present but has not been accepted.
If flashing continues, the FXR inverter is refusing the source. See the Troubleshooting section on page 53
: No AC source is detected.
If a source is supposed to be present, see the Troubleshooting section on page 53.
ERROR (Red):
This indicator is accompanied by an error message in the system display.
See page 58 for a description of error messages.
: Warning. The inverter has detected a non-critical problem but has not yet shut down.
A warning does not always lead to a shutdown — if it does, it becomes an error.
This indicator is accompanied by a warning message in the system display.
See page 59 for a description of warning messages.
: No problems are detected.
12 900-0169-01-00 Rev B
Figure 4 Inverter Status LED Indicators
Operation
T
Inverter Functionality
The FXR inverter can be used for many applications. Some of the inverter’s operations occur automatically. Others are conditional or must be enabled manually before they will operate.
Most of the inverter’s individual operations and functions can be programmed using the system display. This allows customization or fine tuning of the inverter’s performance.
Before operating the inverter:
The operator needs to define the application and decide which functions will be needed. The FXR inverter is programmed with many AC input modes. Each mode has certain advantages which make it ideal for a particular application. Some modes contain functions unique to that mode.
The modes are described in detail following this section. To help decide which mode will be used, the basic points of each mode are compared in Table 2 on page 21.
Apart from the input modes, FXR inverters possess a set of common functions or operations. These operations are described in detail beginning on page 23. Most of these items operate the same regardless of which input mode is selected. The exceptions are noted where appropriate.
Each distinct mode, function, or operation is accompanied by a symbol representing the inverter and that operation:
DC
RANSFER
AC IN AC OUT
These items represent the input from the AC source, the output to the AC loads, DC functions (inverting, charging, etc.), and the transfer relay. Arrows on each symbol represent power flow.
The symbols may have other features depending on the operation.
AC Input Connection
The FXR inverter has one set of input connections. Only one AC source can be physically wired to it at any time. However, two different AC sources can be used with an external transfer switch. It is common for backup or grid-interactive systems to use the utility grid as the primary source, but switch to a gas- or diesel-powered generator in emergencies. The inverter can be programmed with separate input criteria for each source.
The inverter’s two input selections can be programmed for separate input modes (see below). The selection ( beginning on page 72.)
NOTE:
of inverter requirements. Each selection can accept any AC source as long as it meets the requirements of the FXR inverter and the selected input mode. If necessary, the accept grid power. The opposite is also true.
The input types are labeled for grid and generator due to common conventions, not because
Grid
or
) can be chosen in the
Gen
AC Input and Current Limit
menu. (See the menu tables
selection can
Gen
Description of AC Input Modes
These modes control aspects of how the inverter interacts with AC input sources. Each mode is intended to optimize the inverter for a particular application. The names of the modes are
Support, Grid Tied, UPS, Backup, Mini Grid
in Table 2. See page 21.
, and
GridZero
. The modes are summarized and compared
Generator
,
900-0169-01-00 Rev B 13
Operation
When multiple inverters are stacked together in parallel, the master inverter’s input mode is imposed on all slaves. (See the stacking section on page 39.) The slave settings are not changed; they retain any mode that was previously programmed. However, the slave will ignore its programmed mode and use that of the master. This also applies to any parameters in the mode menu (
Connect Delay
, and so on).
The following pages compare the various functions of each input mode.
Voltage Limit
,
Generator
The
Generator
mode allows the use of a wide range of AC sources, including generators with a rough or imperfect AC waveform. In other modes, a “noisy” or irregular waveform may not be accepted by the inverter. (Self-excited induction generators may require this mode when used with the inverter.)
Generator
allows these waveforms to be accepted. The charging algorithm of this mode is designed to work well with AC generators regardless of power quality or regulation mechanism. The generator must still comply with the inverter’s nominal input specifications. (See page 25.)
:
Generator
Generator
Connect Delay
menus, depending on which input is being programmed.
mode does not mean that the inverter requires a generator input when using this
. It is available in both the
mode may allow the inverter to accept the power.
Grid AC Input Mode and Limits
input type; either selection can be used.
Gen
and the
BENEFITS:
The FXR inverter will charge the batteries from the generator even when the generator is undersized, of low quality, or has other problems. See page 28 for recommended parameters for sizing a generator.
If the utility grid is unstable or unreliable,
A programmable delay time is available which will allow a generator to stabilize before connection. In the MATE3, this menu item is
Gen AC Input Mode and Limits
NOTES
Any AC fluctuations that are accepted by the inverter will be transferred to the output. The loads will be exposed to these fluctuations. It may not be advisable to install sensitive loads under these conditions.
The name of mode. The use of this mode does not require the use of the Conversely, the inverter is not required to be placed in this mode because a generator is installed.
Support
The
Support
amount of current available from the source is limited due to size, wiring, or other reasons. If large loads need to be run, the FXR inverter augments (supports) the AC source. The inverter uses battery power and additional sources to ensure that the loads receive the power they demand.
In the MATE3 system display, the input. The effect if the AC demand on either input exceeds the
BENEFITS
Large inverter loads can be powered while staying connected to the AC input, even if the input is limited. The added battery power prevents overload of the input source, but the batteries are not in constant use.
The FXR inverter will offset the loads with excess renewable energy if it is available from the batteries. See page 38 for more information.
14
mode is intended for systems that use the utility grid or a generator. In some cases the
dictates the maximum AC draw for the Grid
AC Limit
setting.
Gen Input AC Limit
Grid Input AC Limit
sets the maximum draw for the Gen input. The Support function takes
:
900-0169-01-00 Rev B
Operation
NOTES
:
IMPORTANT:
The inverter will draw energy from the batteries when the loads exceed the appropriate discharge to the Low Battery Cut-Out point. The inverter will shut down with a Low Battery error. (See pages 23 and 58.) To prevent the loss of power, load use should be planned accordingly.
IMPORTANT:
A “noisy” or irregular AC source may prevent inverter will transfer the power, but will not support the source, charge the batteries, or interact with the current in any other way. This problem is more common with generators smaller than the wattage of the inverter.
AC Limit
A programmable delay time is available which will allow an AC source to stabilize before connection. In the MATE3, this menu item is
Gen AC Input Mode and Limits
Connect Delay
menus, depending on which input is being programmed.
Because the inverter limits the current draw from the AC source, it will reduce the charge rate as necessary to support the loads. If the loads equal the appropriate
. With sustained loads and no other DC source, the batteries may
Support
. It is available in both the
AC Limit
from working normally. The
Grid AC Input Mode and Limits
setting, the charge rate will be zero.
and the
If the AC loads
exceed
the
AC Limit
setting, the Support function is activated. Instead of charging, the
inverter will take power from the batteries and use it to support the incoming AC current.
The
Support
function is not available in any other input mode.
Grid Tied
IMPORTANT:
Selling power to the utility company requires the authorization of the local electric jurisdiction. How the utility company accommodates this will depend on their policies on the issue. Some may pay for power sold; others may issue credit. Some policies may prohibit the use of this mode altogether. Please check with the utility company and obtain their permission before using this mode.
The
Grid Tied
using power from the utility grid for charging and loads, the inverter can also convert excess battery power and sell it to the utility grid. Excess battery power usually comes from renewable energy sources, such as PV arrays, hydroelectric turbines, and wind turbines.
NOTE:
This mode is not available in 12-volt FXR models. It does not appear on the system display’s
list of available input modes.
mode allows the FXR inverter to become grid-interactive. This means that in addition to
The grid-interactive function uses Offset operation. See page 38 for more information.
BENEFITS
Excess power is returned to the utility grid.
The inverter will offset the loads with excess renewable energy if it is available from the batteries. If the excess energy is greater than the AC demand (the load size), the excess will be sold to the grid.
900-0169-01-00 Rev B
:
15
Operation
NOTES
  
:
The inverter has a delay before selling will begin. This function, the setting of one minute. During this time, the inverter will not connect to the utility grid. The timer is adjustable in the
Grid Interface Protection
Upon initial connection to the utility grid, the inverter may be required to perform a battery charging cycle. This may delay the operation of the grid-interactive function.
The grid-interactive function only operates when excess DC (renewable) power is available.
The grid-interactive function is not available in any of the other input modes.
When power is returned to the utility grid, it may be possible to reverse the utility meter. However, this depends on other loads in the system. Loads on the main panel (not on the inverter’s output) may consume power as fast as it is sold. The meter would not run backwards, even if the system display showed the inverter selling power. The result of selling would be to reduce AC power consumption, not reverse it.
The amount of power an inverter can sell is not necessarily equal to its specified output wattage. The
Maximum Sell Current
the
Grid Interface Protection
The amount of power that is sold is controlled by the utility grid voltage. The wattage sold equals this
voltage multiplied by the current. For example, if the inverter sells 15 amps and the voltage is 231 Vac, the inverter will sell 3.47 kVA. If the voltage is 242 Vac, the inverter will sell 3.63 kVA. Additionally, output will vary with inverter temperature, battery type, and other conditions.
This recommendation is specifically for the inverter’s grid-interactive function. In some cases, the
source may be sized larger to account for environmental conditions or the presence of DC loads. This depends on individual site requirements.
can be decreased if it is necessary to limit the power sold. This item is available in
menu (see below).
menu (see below).
Re-Connect Delay Timer
, has a default
Grid Interface Protection Menu
Due to varying requirements in different locations around the world, the grid-interactive settings are adjustable. These adjustments are made in the
This menu is only available to operators with installer-level access. There are firm rules concerning the acceptable voltage range, frequency range, clearance time during power loss, and reconnect delay when exporting power to the utility. Generally it is expected that the end user cannot alter the settings.
The installer password must be changed from the default in order to get access to these settings. Once this password has been changed, the settings can only be accessed with the MATE3 installer password.
See the tables beginning on page 72 for the locations of all menu items in the MATE3 menus.
The grid-interactive function can only operate while the utility grid power is stable and within specific limits.
In Grid Tied mode, the inverter will operate in accordance with the Grid Interface Protection settings.
The default settings and ranges are listed in the tables which begin on page 72.
If the AC voltage or frequency vary outside the Grid Interface Protection limits, the inverter will
disconnect from the utility grid to prevent selling under unacceptable conditions. These limits override the AC source acceptance limits described on page 26, which are used in other input modes. The inverter will not reconnect until the source is acceptable for the duration of the Re-Connect Delay Timer.
If the inverter stops selling or disconnects due to Grid Interface Protection, the MATE3 will show the
reason. Sell Status messages are listed on page 62. Disconnect messages are listed on page 61. Often these messages will be the same.
Before operating in Grid Tied mode, contact the utility company that provides power to the installation.
They can provide information regarding the rules that must be followed in order to export power back to the utility. The items in the following list are the selectable Grid Interface Protection options. The utility company may need to review these items to make certain their standards are met.
Grid Interface Protection
menu.
16 900-0169-01-00 Rev B
Operation
The utility may simply name a standard to be followed. It may be necessary to look up the requirements for a local standard and program them accordingly.
STAGE 1 Voltage (basic settings)
Over Voltage Clearance Time (seconds)
Over Voltage Trip (AC Voltage)
Under Voltage Clearance Time (seconds)
Under Voltage Trip (AC Voltage)
STAGE 2 Voltage (if required by utility)
Over Voltage Clearance Time (seconds)
Over Voltage Trip (AC Voltage)
Under Voltage Clearance Time (seconds)
Under Voltage Trip (AC Voltage)
See the tables beginning on page 72 for the default settings and ranges.
Frequency Trip
Over Frequency Clearance Time (seconds)
Over Frequency Trip (Hertz)
Under Frequency Clearance Time (seconds)
Under Frequency Trip (Hertz)
NOTE: The Frequency Trip settings are dependent on the inverter’s operating frequency, which must be set correctly.
Mains Loss
Clearance Time (seconds)
Reconnect Delay (seconds)
Frequency and Phase Coordination
Several other inverter adjustments are located in the
Grid Interface Protection
items can only be changed with installer-level access.
The FXR inverter’s operating frequency can be selected to either 50 or 60 Hz using the
Protection
See page 24 for more information on the inverter’s frequency.
The FXR inverter’s stacking function includes the option called menu item is source is required to deliver appropriate input to all inverters in a stacked system. If the master or subphase master inverters do not sense an acceptable AC source, the entire system disconnects from the source. None of the inverters will reconnect until the source is acceptable for the duration of the appropriate timer.
If the inverter is in Grid Tied mode, the Re-Connect Delay timer is used. If the inverter is any other AC input mode, the Connect Delay timer is used.
See pages 25 and 27 for more information on input acceptance and the transfer function.
menu. This setting changes the inverter’s input acceptance parameters, as well as its output.
Multi-Phase Coordination
Coordinated AC Connect/Disconnect
. The default setting is No. If selected to
menu. These sensitive
Grid Interface
. The selectable
, the AC
Yes
See page 39 for more information on the stacking function and subphase master inverters.
See the tables beginning on page 72 for the default settings and ranges.
UPS
In
UPS
Failure
mode, the FXR parameters have been optimized to reduce the response time. If the utility grid becomes unstable or is interrupted, the inverter can transfer to inverting with the fastest possible response time. This allows the system to support sensitive AC loads with minimal interruption.
BENEFITS
Constant power is provided to the loads with virtually no drop in voltage or current.
NOTES
Due to the need for the FXR inverter to react quickly to AC source fluctuations, it must remain fully active at all times. The inverter requires a continuous consumption of 42 watts.
For this reason, the Search function does not operate in this mode. (See page 24.)
900-0169-01-00 Rev B 17
:
:
Operation
Backup
Failure
The
Backup
This source will pass through the FXR inverter’s transfer circuit and will power the loads unless utility power is lost. If utility grid power is lost, then the inverter will supply energy to the loads from the battery bank. When the utility power returns, it will be used to power the loads again.
BENEFITS
This mode will continuously maintain the batteries in a fully-charged state, unlike the does not have the overhead consumption of the
Mini Grid
In
Mini Grid
(and renewable) energy. The inverter only connects to the AC source (usually the utility grid) when the batteries run too low.
The FXR inverter runs on battery-supplied power for as long as the batteries can be sustained. It is expected that the batteries will also be charged from renewable sources such as PV. When the batteries become depleted, the system reconnects to the utility grid to operate the loads.
The inverter will reconnect to the utility grid if the battery voltage decreases to the set point and remains there for the begin on page 72.
mode is intended for systems that have utility grid available as the primary AC source.
:
Support
mode.
UPS
mode, the FXR inverter automatically rejects an AC source and runs solely from battery
time period. These items are shown in the tables which
Delay
mode. It
Connect to Grid
While connected to the utility grid, the FXR charger can be set either on or off. If the charger is turned on, the inverter will proceed through a full charging cycle. Upon reaching float stage, the inverter will disconnect from the grid.
If the inverter is connected to the utility grid and the charger is turned off, another DC source such as renewable energy should be present to charge the batteries. The inverter will observe the batteries as if it was performing the charge. When the batteries reach the required voltages and charging times to achieve float stage, the inverter will disconnect from the grid. This means that the regulator for the renewable source must be set to the same settings as the inverter (or higher). Check the settings of both devices as needed.
See page 28 for more information on the battery charging cycle.
BENEFITS
Mini Grid
possible if certain conditions are met. See below.
NOTES
The FXR inverter will offset the loads with excess renewable energy if it is available from the batteries.
See page 38 for more information on Offset operation. However, the Offset function is inapplicable when the inverter disconnects from an AC source. The renewable energy supports the inverting function instead.
This mode has similar priorities to the high-battery transfer (HBX) function used by the MATE3 system
display. However, it is not compatible with HBX and cannot be used at the same time. When using Mini Grid mode, the system display should disable HBX to prevent conflicts.
:
mode allows a system to minimize or eliminate dependence on the utility grid. This is only
:
18 900-0169-01-00 Rev B
Operation
Mini Grid
system display. These functions do not have similar priorities to inverter’s connection and disconnection with the grid.
When deciding whether to use
Mini Grid logic is based in the FXR inverter and can function in the absence of the MATE3. HBX logic is
Mini Grid can use utility grid power to fully recharge the batteries every time it reconnects to the grid.
HBX set points have a wide range of settings. Mini Grid uses settings intended to protect the batteries
HBX works more efficiently with a larger renewable source, but there is no specification for renewable
Mini Grid is one of seven inverter-level functions (modes) which share a single input. Selecting it
 See Table 6 on page 49 for a comparison summary. Pages 48 and 49 have more information on HBX,
mode is also incompatible with the
Mini Grid
based in the MATE3 and cannot function unless the MATE3 is installed and operating.
HBX can only do so under specific circumstances.
from excessive discharge; however, most of its settings are automatic and do not allow customization.
size. Mini Grid cannot work properly unless the source is larger than the size of the loads. If this condition is not met, Mini Grid will not disconnect the inverter from the utility grid.
prevents any other input mode from being used. HBX is a system-level function which can be combined with the settings of other input modes.
Grid Use Time, Load Grid Transfer, and other functions of the system display.
Grid Use Time
mode or
HBX
and
Load Grid Transfer
Mini Grid
Mini Grid
, the user should consider the aspects of each.
should not be used with these functions.
or
functions of the MATE3
, but they do control the
HBX
GridZero
In
GridZero
mode, the FXR inverter remains grid-connected, but prioritizes the use of battery or renewable sources to run loads. It uses only renewable energy to recharge the batteries. The inverter tries to “zero” the use of the utility grid, drawing on AC power only when needed to supplement stored DC sources. Note that the inverter draws up to 1 Aac regardless of the DC sources.
In the MATE3 system display, the selectable options are
DoD Volts
battery power to the loads when the batteries exceed the
DoD Volts
and
DoD Amps
. The inverter sends
setting. (12-, 24-, and 48-volt systems must exceed the setting by 0.2, 0.4, and 0.8 Vdc respectively.) As the battery voltage decreases to
DoD Volts
, the inverter reduces the current toward zero. It will maintain the batteries at this setting.
The FXR inverter can manage large quantities of power. To prevent damage to the batteries from rapid discharge, the rate of discharge can be limited using the
DoD Amps
setting. This item should be
set lower than the current provided by the renewable source.
When
DoD Volts
the loads. However, it will also leave less of a battery reserve in the event of a grid failure.
When
DoD Volts
reserve. However, not as much renewable energy will be sent to the loads.
is set low, this mode allows more renewable energy to be delivered from the batteries to
is set high, the batteries will not be discharged as deeply and will retain more of a backup
The renewable energy source needs to exceed the size of all loads and possible losses. The renewable source must also charge the batteries. The inverter does not charge the batteries in
BENEFITS
This mode seamlessly blends the use of battery power and grid power. It puts renewable energy to the most effective use without selling power to the utility grid.
GridZero
The inverter remains connected to the utility grid in case the grid is needed. If large loads require the use of grid power, no transfer is necessary to support the loads.
:
mode minimizes dependence on the grid as long as certain conditions are met.
GridZero
mode.
900-0169-01-00 Rev B 19
Operation
NOTES
:
IMPORTANT:
Setting
DoD Volts
not have sufficient reserve to provide backup in the event of a grid failure. To prevent the loss of power, load use and the
too low will severely discharge the batteries. The battery bank may
DoD Volts
setting should be planned accordingly.
If the renewable energy source is not greater than the size of the inverter loads, this mode will not work well over time. The renewable source must be capable of charging the batteries as well as running the loads. This occurs when renewable energy production exceeds the
DoD Amps
setting.
The inverter will offset the loads with excess renewable energy if it is available from the batteries. See page 38 for more information on Offset operation. However, the behavior of Offset in different because it uses the
DoD Volts
exclusively.
Grid Zero
mode is
The inverter’s battery charger cannot be used in this mode. However, the charger menu settings and timer operations are not changed when this mode is selected.
The battery should be discharged whenever possible in the attempt to “zero” the grid usage. If the
setting is limited or loads are not present, the batteries will be unable to accept much renewable
Amps
recharging the next time it is available. The renewable energy will be wasted, leaving the system dependent on the utility grid more than necessary.
DoD
20
900-0169-01-00 Rev B
Operation
Table 2 Summary of Input Modes
Mode Summary Benefits Cautions Intended Charger
Generator
Support
Grid­Tied
UPS
Accepts power from an irregular or low-quality AC source
Adds battery power to augment an AC source that has limited output
Inverter sells excess power (renewable) to utility;
available in 24-volt and 48-volt models only
In grid failure, unit switches to batteries with fastest possible response time
Can use AC that may be unusable in other modes
Can charge even with a poor generator or low-quality AC source
Can use battery power in conjunction with AC source
Offset operation sends excess DC to loads
Bidirectional input
Can reduce utility bills and still provide backup
Offset operation sends excess DC to loads
Any additional Offset excess is sold to the grid
Quick backup for sensitive devices during grid outage
Will pass irregular or low-quality power to the output; could damage sensitive loads
Offset unavailable
Drains batteries during support; intended for intermittent use only
May not function with low-quality AC source
Requires utility approval
Other approvals may be required depending on electrical codes
Has exact requirements for accepting AC input
Requires renewable energy source
Uses higher idle power than other modes
Search function unavailable
Offset unavailable
Source:
Generator
Loads:
Non­sensitive devices
Source:
Grid or Generator
Loads:
Can be larger than AC source
Source:
Grid
Loads:
Any type
Source:
Grid
Loads:
PC, audio, video, etc.
Performs three-stage charge and goes silent as specified by settings
Performs three-stage charge and goes silent as specified by user settings
Performs three-stage charge and goes silent as specified by user settings
Performs three-stage charge and goes silent as specified by user settings
Backup
MiniGrid
In grid failure, unit switches batteries to support loads; this is the default mode
Stays off grid most of the time; only uses grid when batteries low
Simple use compared to other modes; often used with generators for this reason
Less idle power than
Does not drain battery as in
Support
Can minimize/eliminate dependence on grid
Offset operation sends excess DC to loads (but only when on grid)
Has none of the special
functions described in other modes
UPS
Will not work properly unless renewable source is above a certain size
Conflicts with related
Source:
Grid or Generator
Loads:
Any type
Source:
Grid
Loads:
Any type
modes in MATE3
GridZero
On-grid but actual grid use is minimized (“zeroed”) with battery and renewable power; does not sell or
Can minimize dependence on grid
Offset operation sends excess DC to loads at adjustable rate
Remains on-grid to avoid transfer problems
charge
900-0169-01-00 Rev B 21
Discharges batteries while remaining on grid
Will not work properly unless renewable source is above a certain size
Battery charger inoperative
Source:
Grid
Loads:
Any type
Performs three-stage charge and goes silent as specified by user settings
Performs three-stage charge on reconnect; if charger is disabled, inverter emulates charge cycle from external source and reacts accordingly
Charger inoperative; batteries must be charged using an external (renewable) energy source
Operation
NOTES:
22 900-0169-01-00 Rev B
Operation
Description of Inverter Operations
The items in this section are operations common to all FXR inverters. These are used in most or all of the input modes described in the preceding section.
Some of the items in this section are functions which can be manually selected, enabled, or customized. Other items are general topics or applications for the inverter. These items may not have their own menus, but their activity can still be influenced or optimized by changing certain settings.
Any of these items may need to be adjusted so that the inverter is best matched to a particular application. The operator should review these items to see which are applicable.
All items described as settable or adjustable have set points which can be accessed using the system display. The default settings and ranges of adjustment are listed in the menu tables which begin on page 72 of this manual.
Inverting
This is the FXR inverter’s primary task. The inverter converts DC voltage from batteries into AC voltage that is usable by AC appliances. It will continue to do this as long as the batteries have sufficient energy. The batteries can be supplied or recharged from other sources, such as solar, wind, or hydroelectric power.
The inverter’s design uses a transformer and a high-frequency H-Bridge FET module to achieve the required high-wattage output. The inverter can deliver the rated wattage continuously at 25°C. The maximum output is derated at temperatures exceeding 25°C. See pages 63 and 67 for these wattages.
Measure the total load wattage so that it does not exceed the inverter’s capacity. The inverter cannot maintain its AC voltage under an excessive load. It will shut down with a
V
DC and AC Voltages
The FXR inverter requires batteries to operate
are consistent enough for the inverter to operate reliably.
CAUTION: Equipment Damage
Do not substitute other DC sources in place of the batteries. High or irregular voltages
The following items will affect the inverter’s operation. These are only used when the inverter is generating AC power on its own.
Low Battery Cut-Out
DC voltage drops below a specified level for 5 minutes, the inverter will stop functioning. The MATE3 will give a
Low Battery V
on the MATE3 system display.
may damage the inverter. It is normal to use other DC sources with the batteries and the inverter, but not in place of the batteries.
: This function prevents the inverter from draining the batteries completely. When the
error. This is one of the error messages described on page 58. It appears as an event
V
. Other sources may not maintain DC voltages that
Low Output Voltage
error.
This function is intended to protect both the batteries and the inverter’s output. (Continuing to invert on a low DC voltage may produce a distorted waveform.) This item is adjustable.
Low Battery Cut-In
point for 10 minutes, the error will clear and the inverter will resume functioning. This item is adjustable.
Connecting an AC source for the inverter to charge the batteries will also clear a low battery error.
900-0169-01-00 Rev B 23
: The recovery point from Low Battery Cut-Out. When the DC voltage rises above this
Operation
Output Voltage
to be used for different nominal voltages such as 220 Vac and 240 Vac.
The inverter is also controlled by a high battery cut-out limit. If the DC voltage rises above this limit, the inverter immediately stops functioning and gives a inverter from damage due to excessive DC voltage.
The high battery cut-out voltages for each model are shown in Table 19 on page 69. This voltage is not
a changeable set point.
If the voltage drops below this point, the inverter automatically recovers. This is one of the errors on page 58. It appears as an event on the MATE3 system display.
The low battery and high battery functions are summarized in Table 19 on page 69.
: The AC output voltage can be adjusted. Along with small changes, this allows the inverter
IMPORTANT:
The output voltage can adjusted to a different nominal value for a particular region. Making this change will not affect the default input voltage range accepted by the inverter from an AC source. The input range must be adjusted manually. These changes should be made at the same time. (See AC Source Acceptance on page 26.)
High Battery V
error. The shutdown protects the
AC Frequency
Hz
CAUTION: Equipment Damage
Setting the inverter’s output frequency to deliver 50 Hz to 60-Hz loads, or setting it to deliver 60 Hz to 50-Hz loads, could damage sensitive devices. Make certain the inverter’s output frequency matches the installation.
The inverter’s output can operate at a frequency of either 50 or 60 Hertz. This output frequency (and the AC acceptance frequency) can be changed with the
Operating Frequency
menu item. This requires high-level access. Due to the possibility of damage, access to this setting was restricted by placing it in the
Grid Interface Protection
menu.
The installer password must be changed from the default in order to get access to this menu. Once this password has been changed, the
Grid Interface Protection
menu can only be accessed by using
the installer password. This password can be changed in the system display.
See page 17 for more information on this selection in which begin on page 72, for the location of the
Search
Operating Frequency
Grid Interface Protection
menu item.
. See the menu tables,
An automated search circuit is available to minimize the power draw when no loads are present. When enabled, the inverter does not always deliver full output. The output is reduced to brief pulses with a delay between them. These pulses are sent down the output lines to see if a resistance is present. Basically, the pulses “search” for a load. If a load is detected on the output, the inverter’s output increases to full voltage so that it can power the load. When the load is turned off, the inverter “goes to sleep” and begins searching again.
Search mode sensitivity is adjusted with the
Sensitivity
menu item. See the menu tables, which begin on page 72, for the location of this item. The sensitivity is adjusted in small increments which are measured in fractions of one ampere.
24
900-0169-01-00 Rev B
Operation
NOTE:
setting, 30 increments, is approximately sufficient to detect the load of one compact fluorescent light (CFL). A load which draws this amount or greater will “wake up” the inverter.
 
Search mode is ideal for use in small systems where it is critical to conserve battery capacity and avoid idle draw or “ghost” loads.
To set up Search mode for use:
1.
2. Activate Search mode with the system display. The inverter should “sleep” with a flashing green STATUS
Increment sizes are difficult to define due to varying load characteristics. However, the default
Search mode is not particularly useful with loads requiring continuous power. (These loads include clocks, answering machines, and similar devices.) “Sleep” operation with these loads is simply a power interruption or nuisance shutdown.
Search mode may not be useful with loads that are critical or are intentionally operated a large portion of the time even if they are not continuous. (These loads include computers and similar devices.) The inverter may “sleep” so rarely that the mode has no benefit.
Some devices may not be easily detected by Search mode.
Search is inoperative if the
Turn off all loads.
INVERTER indicator. See page 12.
input mode is in use. See page 16 for more information on this mode.
UPS
3. Determine the smallest load that is to be used and turn it on.
4. If the load operates, the inverter is active and is producing power. No further adjustments are needed.
5. If the inverter does not produce power and continues to “sleep”, the sensitivity is set too high. Turn the load
off and lower the Sensitivity menu item. Turn on the load and test whether the inverter activates.
6. Repeat step 5 as needed until turning on the load also reliably activates the inverter.
The pulse duration and the delay both have a time period that is measured in AC cycles. These two items,
Pulse Length
and
Pulse Spacing
, are adjustable in the same menu as
Sensitivity
. If
Sensitivity
does not achieve the desired results, it may be useful to perform similar adjustments on these items.
Input
When the input terminals are connected to a stable AC source, the FXR inverter will synchronize itself with that source and use it as the primary source of AC power. Its transfer relay will engage, linking the AC source directly with the inverter’s output. It can also use the source to charge batteries. (See Battery Charging on page 29.)
The loads powered by the inverter
CAUTION: Equipment Damage
Current draw in excess of the transfer relay rating can damage the transfer relay. This damage is not covered by warranty. Use protective devices of appropriate size.
The inverter has a single AC input. However, it has two sets of AC source settings. With an external transfer switch, the inverter can be used on more than one AC source. It is common to use utility grid power and a gas or diesel generator. Other combinations of AC sources are possible.
The inverter’s two input selections can be programmed for separate input modes. The selection (
) can be chosen in the
Gen
The interactions with AC input sources are controlled by the various input modes. The
900-0169-01-00 Rev B 25
Input Type
must not
exceed the size of the inverter’s transfer relay.
menu.
Grid Tied
Grid
mode
or
Operation
allows certain models to sell power using the input connection. The to assist a smaller AC source. When
GridZero
page 21 for descriptions of these and other input modes.
mode is selected, the battery charger cannot be used. See
Support
mode can use battery power
AC Current Settings
The AC current settings,
Grid Input AC Limit
A
A
A
and
Gen Input AC Limit
, control the amount of current
that the inverter draws from the source. Adjust these settings to match the input circuit breakers.
The adjustment is meant to protect a generator or source that cannot supply enough current for both charging and loads. If the combined charging and loads exceed the setting, the inverter will reduce its charge rate and give priority to the loads. If the loads exceed this number on their own, the charge rate will be reduced to zero.
The inverter’s battery charger and grid-interactive function have individual settings. However, the settings can also limit the charging or selling current.
The
GridZero
input mode requires the inverter to use DC sources, limiting the amount of AC current used.
See page 19.
The
Support
The AC input current is used to power both loads and battery charging. The combined amount should not
input mode allows the inverter to support the AC source with battery power. See page 14.
exceed the size of the AC overcurrent device or AC source. These devices should be sized appropriately during planning and installation of the inverter system.
If multiple parallel inverters are installed with an AC source of limited amperage, the total combined amperage settings for all units must be less than the AC input circuit. The Configuration Wizard in the MATE3 can perform this calculation. However, the inverters do not perform this calculation. If the Configuration Wizard or similar tools are not used, divide the input size by the number of inverters and assign an equal part of the amperage to each port.
AC Limit
AC Source Acceptance
The input source must meet the following specifications to be accepted. This is true in all modes except
 
Grid Tied
Voltage (both input selections): 208 to 252 Vac
Frequency (both input selections): If the output frequency is set to 50 Hz (default), the input acceptance range is 45 to 55 Hz. If output frequency is set to 60 Hz, the input range of acceptance is 55 to 65 Hz.
See the menu tables which begin on page 72 for programming information for these items.
:
When these conditions are met, the inverter will close its transfer relay and accept the input source. This occurs after a delay which is specified below. If the conditions are not met, the inverter will not accept the source. If it was previously accepted and then rejected, the inverter will open the relay and return to inverting power from the batteries. This occurs after a specified transfer delay, which is an adjustable menu item.
IMPORTANT:
The inverter’s output voltage can adjusted to a different nominal value for a particular region. (See page 24.) If this occurs, the source acceptance range should be adjusted to match this nominal value or the inverter may not accept the new source normally.
The voltage limits can be adjusted to allow (or exclude) a source with weak or irregular voltages. These items are adjustable in the appropriate menu of the MATE3 (
26
Grid AC Input Mode and Limits
or
900-0169-01-00 Rev B