OutBack Power RADIAN, GSLC175PV1-120/240, GS8048A, MATE3 depicted, GS4048A Quick Start Manual

...
CAUTION: Equipment Damage
These procedures should be done by a qualified installer who is trained on programming inverter power systems. Failure to set accurate parameters for the system could potentially cause equipment damage. Damage caused by inaccurate programming is not covered by the limited warranty for the system.
IMPORTANT
Check the firmware revision of all OutBack devices before use. The Radian inverter and MATE3 system display may not communicate or operate correctly unless their firmware is above a specified revision number.
For models GS8048A and GS4048A, the firmware must be revision 001.005.xxx or higher. The MATE3 must be revision 002.017.xxx or higher.
Quick Start Guide
900-0162-01-00 Rev A.vsd\Page-1\2014-01-24 ©2014 OutBack Power Technologies. All Rights Reserved.
Setup and Programming
Contact Technical Support:
Telephone: +1.360.618.4363 Email: Support@outbackpower.com Website: www.outbackpower.com
RADIAN Series
HUB 10.3
Communications
Manager
MATE3 System
Display and
Controller
Radian Inverter/Charger
GS Load Center
(GSLC)
FM80 Charge
Controllers
(x2)
WARNING: Fire/Explosion Hazard
Do not place combustible or flammable materials within 12 feet (3.7 m) of the equipment. This unit employs mechanical relays and is not ignition­protected. Fumes or spills from flammable materials could be ignited by sparks.
WARNING: Personal Injury
Use safe lifting techniques and standard safety equipment when working with this equipment.
IMPORTANT:
Clearance and access requirements may vary by location. Maintaining a 36” (91.4 cm) clear space in front of the system for access is recommended.
Consult local electric code to confirm clearance and access requirements for the specific location.
IMPORTANT:
Not intended for use with
life support equipment.
AC Source
Utility Grid or AC Generator
Main Electrical Panel (or overcurrent device for the AC source)
Electrical Distribution Subpanel (Load Panel)
Photovoltaic (PV) Array
Battery Bank
Customer-Supplied Components
Inverter/Charger
GS Load Center
System Display and Controller
MATE3 depicted (with FW-MB3 mounting bracket)
GS8048A GS4048A
Radian System Products
Major Components
Optional OutBack Components
FLEXnet DC Monitor (FN-DC)
Remote Temperature Sensor (RTS)
Charge Controller
FLEXmax 80 depicted (with FW-CCB2 mounting bracket)
PV Combiner Box PV12 depicted
Communications
Manager
HUB10.3 depicted
GSLC175-PV-120/240 GSLC175PV1-120/240 (both depicted)
EnergyCell depicted
Note: See the MATE3 manual for details on generator control.
The MATE3 Configuration Wizard allows quick setup of parameters that apply to all systems. The Configuration Wizard is reached from the MATE3 Main Menu as shown to the right.
The firmware revision of all devices can be confirmed by navigating from the MATE3 Main Menu as shown below. Upgrades to the firmware revision can be downloaded from the OutBack website www.outbackpower.com.
S
Firmware Revision
Configuration Wizard
Off Grid
Grid Tied Backup
This advances the display to the
Setup Complete screen.
C
C
C
S S S
C
This advances the display to the Setup Complete screen if the FLEXnet DC is not installed. If the FLEXnet DC is installed, the display advances to the Shunt screens.
If FN-DC is installed...
If FN-DC is installed...
If FN-DC is installed...
Generator Installed Y Generator Type AC Size 5.0 kW Generator Start Manual AUX Output Device Port 1
Back Continue
New Configuration >> Existing Configuration >> Restore Configuration >>
System Type Grid Tied System Voltage 48 VDC Array Wattage 1000 Battery Type FLA Capacity 500 Ah
Back Continue
Absorb Voltage 57.6 VDC Time 1.0 Float Voltage 54.4 VDC Time 1.0 Equalize Voltage 60.0 VDC Time 3.0 Re-Float Voltage 44.0 VDC
Back Continue
New Configuration Initialized
Back Continue
Shunt A Connection Inverter
Back Continue
Shunt B Connection Charge Controller
Back Continue
Shunt C Connection Charge Controller
Back Continue
Period 1 Enable N Weekday Use 0:00 Drop 0:00 Weekend Use 0:00 Drop 0:00
Back Continue
Period 2 Enable N Weekday Use 0:00 Drop 0:00
Back Continue
Period 3 Enable N Weekday Use 0:00 Drop 0:00
Back Continue
Shunt A Connection Inverter
Back Continue
Shunt B Connection Charge Controller
Back Continue
Shunt C Connection Charge Controller
Back Continue
Mode Disabled Grid Connect 48.0 VDC Delay 60 Min Grid Disconnect 52.0 VDC Delay 60 Min Grid Connect SOC 60% Disconnect SOC 95%
Back Continue
Shunt B Connection Charge Controller
Back Continue
Shunt C Connection Charge Controller
Back Continue
Period 3 Enable N Weekday Use 0:00 Drop 0:00
Back Continue
Mode Disabled Grid Connect 48.0 VDC Delay 60 Min Grid Disconnect 52.0 VDC Delay 60 Min Grid Connect SOC 60% Disconnect SOC 95%
Back Continue
Period 1 Enable N Weekday Use 0:00 Drop 0:00 Weekend Use 0:00 Drop 0:00
Back Continue
Generator Installed N Generator Type AC Size 5.0 kW Generator Start Manual AUX Output Device Port 1
Back Continue
AC Output Voltage 240 VAC AC Phase Single AC Input Breaker Size 50 A Maximum Output Load 33 A
Back Continue
Period 2 Enable N Weekday Use 0:00 Drop 0:00
Back Continue
Generator Installed N Generator Type AC Size 5.0 kW Generator Start Manual AUX Output Device Port 1
Back Continue
Absorb Voltage 57.6 VDC Time 1.0 Float Voltage 54.4 VDC Time 1.0 Equalize Voltage 60.0 VDC Time 3.0 Re-Float Voltage 44.0 VDC
Back Continue
AC Output Voltage 240 VAC AC Phase Single AC Input Breaker Size 50 A Maximum Output Load 33 A
Back Continue
System Type Backup System Voltage 48 VDC Array Wattage 1000 Battery Type FLA Capacity 500 Ah
Back Continue
Shunt A Connection Inverter
Back Continue
AC Output Voltage 240 VAC AC Phase Single AC Input Breaker Size 50 A Maximum Output Load 33 A
Back Continue
Absorb Voltage 57.6 VDC Time 1.0 Float Voltage 54.4 VDC Time 1.0 Equalize Voltage 60.0 VDC Time 3.0 Re-Float Voltage 44.0 VDC
Back Continue
System Type Off Grid System Voltage 48 VDC Array Wattage 1000 Battery Type FLA Capacity 500 Ah
Back Continue
Settings >> Configuration Wizard >> Device Data Logs >> Event Logs >> Firmware Update >>
System >> Inverter >> Charge Controller >> Battery Monitor >> MATE3 >>
System
System Information >> Save / Store Information >> Firmware Version >> Date and Time >> LCD Display >>
MATE3 002.017.018 1: GS8048A 001.005.002 2: GS8048A 001.005.002
Settings >> Configuration Wizard >> Device Data Logs >> Event Logs >> Firmware Update >>
Settings
Configuration Wizard
New Configuration
!
Masters of the Off-Grid.™ First Choice for the New Grid.
Installation
900-0162-01-00 Rev A.vsd\Page-2\2014-01-24 ©2014 OutBack Power Technologies. All Rights Reserved.
RADIAN Series
16" (40.6 cm)
Plywood (Optional)
Wall Board
Wall Stud
Wall Bracket
Wall Stud
4.1"
(10.4 cm)
5.0"
(12.7 cm)
6.0"
(15.2 cm)
8.0"
(20.3 cm)
AC Circuit Breakers
1
GFDI
2 3 4
DC Terminals - Inverter
AC Terminals - Inverter
5
DC Circuit Breakers
6
PV Circuit Breakers
Charge Controller Terminals
7 8
Mechanical Interlock (Bypass)
9
10
Communication Ports Auxiliary Terminals
11 12 13 14 15
AC OUT Bus Bar L1
16 17 18 19
AC OUT Bus Bar L2 GRID IN Bus Bar L1 GRID IN Bus Bar L2 GEN IN Bus Bar L1 GEN IN Bus Bar L2 AC Neutral Ground
20
DC Positive (+) Plate (not used on GSLC175PV1-120/240) PV Negative (–) Terminals
21 22
PV Positive (+) Bus Bars DC Negative(–) Plate (GS-SBUS)
N E U
L1 L2 GRID
L1 L2 GEN
N E U
N E U
L1 L2 OUT
RELAY AUX
+ ­12V AUX
Switch INV
Remote
Battery Temp
FM80 #1 FM80 #2
MATE3
HUB
10.3
GS8048A
GSLC175-PV-120/240
1
2 2
3
4
5
7
8
8
9
9
9
9
9
10
10
10
6
ON/OFF
INV
1112131415
16
17
18
19
20
21
21
22
20
AC Wire Sizes and Torque Values
OutBack recommends that conductors be
#6 AWG THHN copper, or larger, rated to 75°C
(minimum) unless local code requires otherwise.
AWG In-lb
#14 to #10 20
#8 25
#6 to #4 35
#3 35 #2 40 #1 50 1/0 50
mm
2
2.5 to 6 10
16 to 25
35 35 50 70
Nm
2.3
2.8
4.0
4.0
4.5
5.6
5.6
Wire Size Torque
Torque Requirements
Plywood
(Optional)
Wall Board
Wall
Bracket
Wall Stud
N E U
L1 L2 GRID
L1 L2 GEN
N E U
N E U
L1 L2 OUT
RELAY AUX
+ ­12V AUX
Switch INV
Remote
Battery Temp
ON/OFF
INV
28.0"
(71.1 cm)
16" (40.6 cm)
0.5" (1.3 cm)0.5" (1.3 cm)
29.1"
(74.0 cm)
45.0"
(114.3
cm)
13.7"
(34.8 cm)
Inverter Bracket
8.75"
(22 cm)
Circuit Breaker
Stud
Torque
In-lb Nm
M8 20 2.3
¼ - 20 35 4.0
5/16 - 18 50 5.6
3/8 - 16 225 25.4
DC Plates
Torque
In-lb Nm
Upper holes (+)
Shunt Bolts (–) and GS-SBUS
Lower holes (+)
60
6.8
5.6
6.8
60
50
60
Minimum DC Cable based on
the DC Circuit Breaker
Torque
In-lb Nm
50 5.6 225 25.4 225 25.4
Circuit
Breaker
Cable Size
125 1/0 (70 mm2) 175 2/0 (70 mm2) 250 4/0 (120 mm2)
35 4.080 #4 AWG (25 mm2)
35 4.060 #6 AWG (16 mm2)
Positive Battery Cable Connections
CAUTION: Equipment Damage
When connecting cables from the Radian inverter to the battery terminals, make sure to observe the proper polarity. Connecting the cables incorrectly can damage or destroy the equipment and void the product warranty.
Ensure the mounting surface is strong enough to handle 3 times the total weight of all the components. Add plywood or other reinforcing material as necessary to strengthen the surface.
Attach the wall bracket. Center the mounting holes on the wall studs. Use all 6 mounting screws to secure the bracket. Lift the inverter so that the inverter bracket is above the wall bracket. Lower the inverter so that the inverter bracket slips into the wall bracket.
If GSLC is not used: Secure the inverter to the surface using a minimum of 1 wall screw (or appropriate hardware). If GSLC is used: Unscrew the inverter bottom screws approximately ¼” (0.6 cm) to 3/16" (0.5 cm).
Align the GSLC along the bottom of the inverter. Slide the bottom screws into the keyhole slots. Mark the spots for the GSLC mounting feet. (If necessary, remove the GSLC to install wall anchors.) Install screws to secure the feet. Follow the appropriate instructions for installing other components. Different mounting locations are available.
1
3 4
2
5 6 7 8 9
Keyhole Slots
1
2
3
4
5
6
7
The FLEXmax charge controller is mounted with the FW-CCB bracket. The FW-CCB2 allows two controllers side by side (using the forward holes to allow for conduit.)
The Radian has two sets of bracket positions. The GSLC has one set.
NOTE: The FLEXmax Extreme charge controller attaches directly to the wall, not the Radian system.
It does not use OutBack brackets.
14.0"
(35.6 cm)
12.0"
(31.8 cm)
8
9
FN-DC
The Radian allows two locations for the MATE3 mounting bracket (FW-MB3).
The Radian has one mounting location for the HUB product. The GSLC also has one location.
Left Side:
Right Side:
For GSLC door clearance, space systems 0.9" (3.2 cm) apart.
When stacking multiple
inverters:
N E U
L1 L2
GRID
L1 L2
GEN
N E U
N E U
L1 L2
OUT
1
Wiring to AC terminals is displayed on the Wiring page.
FN-DC wiring is displayed on the Wiring page.
Bottom Screws
19
Negative Battery Cable
Connections
Green
> 90% (blinks if charge parameters
are met)
Color
Red
Yellow
Yellow
Yellow 80%
70% 60% 60% off, <60% solid, <50% blinks
Battery State of Charge
FN-DC LED Indicators
Bolt 3/8"
DC
Positive
(+) Plate
Battery Positive (+) Lug
Flat
Washer
Nut
Lock
Washer
Flat
Washer
Shunt
Bolt 3/8"
Lock
Washer
Flat
Washer
Battery
Negative
(–) Lug
DC
Negative (-)
Plate
(GS-SBUS)
GSLC175-PV-120/240 GSLC175PV1-120/240
DC Disconnect
Stud
Battery Positive (+) Lug
FM80
Positive (+)
Terminal
Flat
Washer
Nut
Lock
Washer
FN-DC
Positive (+)
Sense
Terminal
4
22
20
20
!