OutBack Power FLEXmax 100, FLEXWare SD-AFCI Quick Start Manual

Page 1
Specifications
Quick Start Guide
Specifications
Device
Voltage
Total Current
DC Input
Compatibility
Overcurrent
Protection
Power Draw
Enclosure Rating
Ambient Temp.
LED indicators
Knockouts
Combiner
600 Vdc
64 Adc
24 Vdc ± 3%
Up to 6 PV input strings per combiner
(6) 600 Vdc DIN rail
fuse holders
0.10 Adc
UL Type 3R
–25 to 60°C
Arc Fault
2", ½”, ¾”
RSI
24 Vdc ± 3%
N/A
24 Vdc ± 3%
Controls up to 6 combiner boxes
N/A
0.06 Adc
UL Type 3R
–25 to 60°C
SOLAR ON
SOLAR OFF
A
FCI
½”
Listings
o UL1741
 including PVRSE
o UL1699B
o CSA C22.2
 including PVRSE
Compliance
o FCC Part 15, Class B
NOTES:
 The DC input and output circuits
are isolated from the enclosure.
 The photovoltaic system grounding shall be
installed according to the requirements of Sections
690.41 through 690.47 of the National Electric Code (ANSI/NFPA 70). The installer is responsible for all system grounding.
 Use only UL514B-compliant wet location or
rain-tight conduit hubs for entry into the enclosure.
FLEXmax 100
Rapid Shutdown Solution (RSD-AFCI)
IMPORTANT
This document is for use by qualified personnel familiar with photovoltaic (PV) systems. Users of this document should meet all local and governmental code requirements for licensing and training for the installation of electrical power systems with AC and DC voltage
up to 600 volts. This product is only serviceable by qualified personnel
The RSD-AFCI works in conjunction with the FLEXmax 100 charge controller. It allows a system to meet the 2014 National Electric Code requirements for PV systems.
o End-to-end solution listed to UL1741 with PV rapid shutdown equipment (PVRSE)
o Type 3R enclosures rated for indoor or outdoor installation
o Flexible design — install the combiner box vertically or horizontally and mount to racking or under an array
o Interoperability with compatible third-party PV rapid shutdown devices (PVRSE with dry contact)
.
Dimensions
14.75"
(37.5 cm)
All ½”
5.0” (
14.1"
(35.8 cm)
7.3” (
6.6” (17.8 cm)
12.7 cm)
18.5 cm)
3.75” (9.5 cm)
12.0"
(30.5 cm)
15.5"
(39.4 cm)
PV DISCONNECT
13.75"
(34.9 cm)
AFCI SELF TEST
AFCI ANNUNCIATOR
5.75" (14.6 cm) with feet
fully extended
11.3"
(28.7 cm)
4.5"
(11.4 cm)
2"
19.5" (49.5 cm)
½”
½”
and
¾”
Components Included:
o Combiner Box
 FWPV6-FH600-SDA
o Rapid Shutdown Initiator Box
 RSI
IMPORTANT
An isolated Class 2 DC power supply with the following specifications must be used to power the RSI:
24 Vdc ± 3% maximum over input voltage, ambient
temperature, output load, and initial accuracy
Up to 1.5 Adc
Accessories Available:
o Box of (10) 15A Fuses
 FUSE-15-600VDC
o Box of (10) 20A Fuses
 FUSE-20-600VDC
o 30A, 1000 Vdc Fuse Holder
 FH-30-1000VDC-DIN
Combiner
Adjustable mounting feet
Lockable PV disconnect
Lockable latch
Securing Screw
Arc fault test button
AFCI annunciator
RSI
Lockable
rapid shutdown
switch
LED
indicators
900-0238-01-00 REV B ©2018 OutBack Power. All Rights Reserved.
Page 2
Installation (SAVE THESE INSTRUCTIONS)
A
This document contains important instructions that shall be followed during installation and maintenance of the power system.
Wiring
Wiring:
Mounting:
IMPORTANT
The surface and fastening hardware must be able to support the weight of all products.
1) Remove any necessary knockouts.
2)
3)
nt the RSI box using the holes located in the mounting brackets. (See A
Mou
 Secure th
he RSI box should be installed near the service meter. It must be moun
 T
vertically a
nt the combiner box using the four mounting feet. During shipping
Mou
e RSI appropriately for the mounting ty
nd must be at least 36" (91.4 cm) above the ground.
pe.
are attached facing inward. They should usually be repositioned facing outward f mounting as shown in B. The feet are slotted for exact spacing requirements in differing locations
 Secure th
 Th
e combiner box can be mounted horizontally, vertically, or at a intermed groun
d. See C.
.
e combiner appropriately for the mounting
type.
ny
iate angle. It must be mounted at least 36" (91.4 cm) above th
 To meet PVRSE requirements, mount the combiner within 10' (3m) of t
array. (Required distance may vary with local code requirements.)
PV
.)
ted
, these feet
or
e
he
B
B
C
A
B
B
NOTE:
These instructions assume the use of FLEXmax 100 charge controller, one combiner, the RSI, and a battery source. (The FLEXmax 100 must be installed according to the appropriate instructions.)
1) Ensure all electrical so
2) Wire all system compo and load cen
 Conn
ter internal wiring are
ect the red and black terminals (3 and 4) on the RSI port labeled J2 (24 Vdc
urces to the system are disconnected. These include utility grid, PV, and batteries.
nents as noted below. See the next sheet for wiring illustrations.
not depicted.
supply) to the red and black terminals (1 and 2) on the combiner port labeled J1.
 Connect the white terminal (2) on the RSI J2 port to the white terminal (3)
the combin
er J1 port.
 Connect the green terminal (1) on the RSI J2 port to the green terminal (4)
the combin
er J1 port.
 Connect the PV array positive (+), negative (–) and ground to the combin
fuse hold
ers and terminal bus bars (TBB).
NOTE: PV input wiring must be outdoor rated. It must be suitable for b
t locations and UV exposure.
we
 Connect the combiner positive (+), negative (–) and ground to the load center
bus bars. Connect the RSI ground to the load center ground bar.
3) Tigh
ten all connections to the torque values on the table to the left.
er
oth
Note that battery connections
on
Combiner
on
1 2 3 4 1 2 3 4
RSI
1 2 3 4 1 2 3 4
J1 J2
J1 J2
Torque Requirements by Wire Size (copper conductors only)
Negative (–)
Cable Size*
2/0 AWG (70 mm2)
1/0 to #1 AWG (50 mm2)
#2 to #3 AWG (35 mm2) 50 in-lb (5.7 Nm) 50 in-lb (5.7 Nm) 50 in-lb (5.7 Nm)
#4 AWG (25 mm2)
#6 AWG (16 mm2)
#8 AWG (10 mm2)
Combiner TBB
(large holes)
50 in-lb (5.7 Nm)
50 in-lb (5.7 Nm)
45 in-lb (5.1 Nm)
45 in-lb (5.1 Nm)
40 in-lb (4.5 Nm)
35 in-lb (4.0 Nm)#10 AWG (6 mm2)
35 in-lb (4.0 Nm)#14 to #12 AWG (2.5 to 4 mm2) 20 in-lb (2.3 Nm) 35 in-lb (4.0 Nm)20 in-lb (2.3 Nm) 35 in-lb (4.0 Nm)
NOTES
 The large cable gland in the combiner box requires a torque value of 29.2 ft-lb (39.5 Nm) to retain the Type 3R rating. The small
cable gland requires a torque value of 19.2 ft-lb (26.0 Nm). Tighten each sealing nut until it is almost even with the rest of the gland. (See the next sheet.)
 Minimum rating for all wires is 90°C. The exception is for PV source circuits above 50°C, which require wire rated for 105°C to
avoid der
ating.
Negative (–)
Combiner TBB
(small holes)
25 in-lb (2.8 Nm)
20 in-lb (2.3 Nm)
Ground TBB
35 in-lb (4.0 Nm)
35 in-lb (4.0 Nm)
25 in-lb (2.8 Nm)
20 in-lb (2.3 Nm)
Ground Lug
(combiner)
50 in-lb (5.7 Nm)
45 in-lb (5.1 Nm)
45 in-lb (5.1 Nm)
40 in-lb (4.5 Nm)
35 in-lb (4.0 Nm)
Contactor
Terminal
50 in-lb (5.7 Nm)
50 in-lb (5.7 Nm)
45 in-lb (5.1 Nm)
45 in-lb (5.1 Nm)
40 in-lb (4.5 Nm)
35 in-lb (4.0 Nm)
4) Conn
ect PV and other sources. Apply power to the system as appropriate.
CAUTION: EQUIPMENT DAMAGE
!
The 24-volt negative conductor is not grounded and is not to be connected to chassis or any other grounding system.
Other Wire Sizes
Connection Minimum* Maximum*
Combiner Fuse Holder
Communication Connectors #22 AWG (0.5 mm2) #16 AWG (1.5 mm2)
PV Input Glands
*AWG size conversions are listed to the closest equivalent mm2 commercial size.
#14 AWG (2.5 mm2)
#8 AWG (25 mm2)
Up to 7.7 mm diameter
900-0238-01-00 REV B ©2018 OutBack Power. All Rights Reserved.
Page 3
Installation
Communications Wire Length
Wire Size
#16 AWG
#18 AWG 125'
#20 AWG
#22 AWG
GS Load Center
Length
200'
80'
50'
Wiring Drawing
Photovoltaic (PV) Array
FWPV6-FH600-SDA
FLEXmax 100
Charge Controller
1 0
5
6
9
Example of Class 2
power supply
Ground
Electrode
Conductor
RSI
J3
J4
J5
J6
J2 J1
DC LEGEND
PV Negative
PV Positive
Ground
Not used
J2 (Combiner)J1 (Power Supply)
24V RSI Supply Positive (+)
24V RSI Supply Negative (–)
24V Combiner Supply Positive (+)
24V Combiner Supply Negative (–)
PV Arc Fault
PV RSI Safe
J3 to RAPID SHUTDOWN Terminals
900-0238-01-00 REV B ©2018 OutBack Power. All Rights Reserved.
J4 to Relay
Relay to AUX
Page 4
Multiple Combiners
Additional Applications
Multiple Combiners
Up to six combiners can be used with a single Rapid Shutdown Initiator. The RSI can be used as an emergency shutoff for all of the six systems. Six combiners can be powered by a single RSI and power supply.
Connect the control wires of additional combiners in series with the first combiner (designated below). The J1 terminals for are connected to the RSI as shown on the previous page. The J2 terminals are connected to the J1 terminals on . The J2 terminals on are connected to the J1 terminals on
1
2
2
if present, and so on.
NOTE: J1 and J2 are interchangeable in the combiner and can be reversed if necessary. (See the connections between
4
and below.) This statement is only true for combiner boxes.
1
2 3
1
3
Surge Protector
An optional surge protection device can be installed in the combiner. A knockout has been provided to accommodate this type of device. This image shows the underside of the combiner and the location of the knockout.
3
PV Conduit PV Cable
Glands
NOTE: Any installed devices must be liquid-tight to sustain the combiner’s environmental rating.
Surge
Protector
Communications
Conduits
To RSI
J2 J1
6
J1 J2 J2J1
J2 J2J1
5
J2 J1 J2J1
4