OutBack Power Technologies is a leader in advanced energy conversion technology. OutBack products include true sine wave
inverter/chargers, maximum power point tracking charge controllers, and system communication components, as well as circuit
breakers, batteries, accessories, and assembled systems.
Applicability
These instructions apply to OutBack inverter/charger models FX2012MT, FX2024M, FX2524MT, FX2532MT, FX2536MT, FX3048MT,
VFX2812M, VFX3524M, VFX3232M, VFX3236M, and VFX3648M only.
European Office
Hansastrasse 8
D-91126
Schwabach, Germany
+49.9122.79889.0
+49.9122.79889.21 (Fax)
Disclaimer
UNLESS SPECIFICALLY AGREED TO IN WRITING, OUTBACK POWER TECHNOLOGIES:
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION
PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT, INDIRECT, CONSEQUENTIAL OR
INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE
ENTIRELY AT THE USER’S RISK.
OutBack Power Technologies cannot be responsible for system failure, damages, or injury resulting from improper installation of
their products.
Information included in this manual is subject to change without notice.
OutBack Power, the OutBack Power logo, FLEXware, and OPTICS RE are trademarks owned and used by OutBack Power
Technologies, Inc. The ALPHA logo and the phrase “member of the Alpha Group” are trademarks owned and used by Alpha
Technologies Inc. These trademarks may be registered in the United States and other countries.
Symbols Used ................................................................................................................................................................................ 5
Welcome to OutBack Power Technologies ......................................................................................................................... 6
General Safety ............................................................................................................................................................................... 6
Sealed Mobile Models ............................................................................................................................................................................. 7
Vented Mobile Models ............................................................................................................................................................................ 7
Inverter Model Names ............................................................................................................................................................................. 7
Components and Accessories .............................................................................................................................................................. 8
Renewable Energy ................................................................................................................................................................................. 10
Battery Bank ............................................................................................................................................................................................. 10
Terminals and Ports .................................................................................................................................................................. 15
DC Wiring ..................................................................................................................................................................................... 18
AC Wiring...................................................................................................................................................................................... 21
AC Sources ................................................................................................................................................................................................ 22
ON and OFF Wiring ................................................................................................................................................................... 23
AUX Wiring .................................................................................................................................................................................. 24
Generator Control .................................................................................................................................................................................. 25
AC Configurations ..................................................................................................................................................................... 27
Functional Test ........................................................................................................................................................................... 41
Powering Down ...................................................................................................................................................................................... 43
Adding New Devices ............................................................................................................................................................................. 43
This book provides instructions for the physical installation and wiring of this product.
These instructions are for use by qualified personnel who meet all local and governmental code
requirements for licensing and training for the installation of electrical power systems with AC and DC
voltage up to 600 volts. This product is only serviceable by qualified personnel.
Symbols Used
WARNING: Hazard to Human Life
This type of notation indicates that the hazard could be harmful to human life.
CAUTION: Hazard to Equipment
This type of notation indicates that the hazard may cause damage to
the equipment.
IMPORTANT:
This type of notation indicates that the information provided is important to
the installation, operation and/or maintenance of the equipment. Failure to
follow the recommendations in such a notation could result in voiding the
equipment warranty.
NOTE:
This type of notation indicates that the information provided is important to
understanding the operation and limits of the equipment. Failure to follow the
recommendations in such a notation could result in improper or failed
operation.
MORE INFORMATION
When this symbol appears next to text, it means that more information is available in other
manuals relating to the subject. The most common reference is to the FX and VFX Mobile Series Inverter/Charger Operator’s Manual. Another common reference is the system display manual.
900-0197-01-00 Rev A5
Page 6
Introduction
WARNING: Limitations on Use
WARNING: Reduced Protection
CAUTION: Equipment Damage
12-, 24-, 32-, 36-, and 48-volt models
Welcome to OutBack Power Technologies
Thank you for purchasing the OutBack FX Mobile Series Inverter/Charger. This product offers a complete
power conversion system between batteries, shore power, and generator.
Output power from 2.0 kVA to 3.6 kVA
Designed to be integrated as part of a full system
using FLEXware™ components
Battery (DC)-to-AC inverting with single-phase
120 Vac output at 60 Hz
Shore power (AC)-to-battery (DC) charging
(FX systems are battery-based)
Rapid transfer between shore power (AC source)
and inverter output with minimal delay time
Uses the MATE™, MATE2™ or MATE3™ System Display
and Controller or the AXS Port™ SunSpec
Modbus Interface (all sold separately) for user interface
Supports the OPTICS RE™ online tool
cloud-based remote monitoring and control application
1
for a
~Requires the MATE3 or the AXS Port
~Visit www.outbackpower.com to download
Uses the HUB4™ or HUB10.3™ Communications Manager (sold separately) for stacking
~Stackable in series (OutBack or Classic), parallel, series/parallel, and three-phase configurations
Automatic neutral-to-ground bond switching
Listed to ANSI/UL 458 (5th Edition) and CSA 22.2 by ETL
Figure 1 FX Mobile Series Inverter/Charger with Turbo Fan
General Safety
This equipment is NOT intended for use with life support equipment or other medical
equipment or devices.
If this product is used in a manner not specified by FX product literature, the product’s
internal safety protection may be impaired.
Only use components or accessories recommended or sold by OutBack Power
Technologies or its authorized agents.
1
Outback Power Technologies Intuitive Control System for Renewable Energy
6 900-0197-01-00 Rev A
Page 7
Introduction
Models
Sealed Mobile Models
Sealed inverter models are designed for dusty and humid environments and can survive casual exposure
to the elements. However, enclosed protection is still recommended. These inverters are internally
ventilated and do not use outside air for cooling. To compensate, most sealed models are also equipped
with the OutBack Turbo Fan assembly which uses external air to remove heat from the chassis.
FX2012MT (2.0 kVA output, 12 Vdc)
FX2024M (2.0 kVA output, 24 Vdc)
FX2524MT (2.5 kVA output, 24 Vdc)
FX2532MT (2.5 kVA output, 32 Vdc)
FX2536MT (2.5 kVA output, 36 Vdc)
FX3048MT (3.0 kVA output, 48 Vdc)
Vented Mobile Models
Vented inverter models are intended for indoor or protected installation only. On average, the wattage of
vented models is rated higher than sealed models. This is due to the greater cooling capabilities of the
vented models.
VFX2812M (2.8 kVA output, 12 Vdc)
VFX3524M (3.5 kVA output, 24 Vdc)
VFX3232M (3.2 kVA output, 32 Vdc)
VFX3236M (3.6 kVA output, 36 Vdc)
VFX3648M (3.6 kVA output, 48 Vdc)
Inverter Model Names
FX mobile model numbers use the following naming conventions.
The model number includes “FX” as the inverter series.
Vented models are preceded with “V”, as in “VFX3648M”.
The first two digits show the power of that model. For example, “FX2012MT” is 2000 watts.
The second pair of digits shows the inverter’s nominal DC voltage. For example, “FXR2524MT” is 24 volts.
Models equipped with a Turbo Fan end with the letter “T”. This designation indicates a sealed model. Vented FX
inverter models are not equipped with Turbo Fans. (Model FX2024M is a sealed model without a Turbo Fan.)
Mobile models (all models featured in this manual) use the letter “M” as either the last or second to
last character (as in “FX2012MT” or “VFX2012M”). These models are meant to be installed in a vehicle and should
not be installed anywhere else. Similarly, a non-mobile inverter should not normally be installed in a vehicle.
For this reason this manual refers to “M” series inverters as “mobile”.
installed accordingly.
IMPORTANT:
Installing an inverter in the wrong application invalidates its listing, may violate
installation codes, and may void the inverter’s warranty.
2
Other inverters, if they are referenced, are referred to as “permanently installed.”
900-0197-01-00 Rev A
2
The instructions assume they are
7
Page 8
Introduction
Components and Accessories
Table 1 Components and Accessories
Components to be Installed Accessories Included
Battery Terminal Cover, red FX Mobile Series Installation Manual (this book)
Battery Terminal Cover, black FX Mobile Series Operator’s Manual
AC Plate “WARNING ELECTRICAL SHOCK” sticker
DC Cover (DCC) or Turbo Fan Silicone Grease Packet
Remote Temperature Sensor (RTS)
DCC (DC Cover)
This covers the DC terminal area on vented inverters. The
DCC provides space to mount other components such as a
DC current shunt.
AC Plate
This plate is used for installations which do not utilize OutBack’s
optional FLEXware conduit boxes. The knockouts are used to
install strain relief for flexible cable.
NOTE: This plate is not to be connected to conduit.
Battery Terminal Cover
These protect the terminals from accidental contact. They are
made of stiff plastic with a snap-on design.
Always keep covers installed during operation.
Turbo Fan Cover
Included in place of the DCC on sealed inverters. Convectively cools
chassis with the external OutBack Turbo Fan to allow maximum power.
NOTE: Do not install the Turbo Fan on a vented inverter.
NOTE: The DC Cover or Turbo Fan does not replace the battery terminal
covers. These covers must be installed in addition to the DCC or fan.
8 900-0197-01-00 Rev A
Figure 2 Components
Page 9
Planning
o
y
Applications
OutBack inverter/chargers are designed to use a battery bank to store energy. In shore-based mobile and
marine connections, the shore power is used as the primary source. When the shore power is removed,
the inverter takes over to run the loads from the batteries. The settings can be changed to accommodate
many applications. Changes are made with the system display.
Mobile FX inverter/chargers work together with power from the utility grid (shore power), generator,
vehicle alternator, and/or renewable energy sources such as photovoltaic (PV) modules. When not using
the batteries, the inverter can charge it from an AC source. The alternator, PV harvest, or other DC sources
can also be used to recharge the batteries.
The FX inverter has one set of terminals for a single AC source. However, it can use two AC sources when
an external transfer switch is installed. The inverter can be independently programmed for each source. It
is common to use shore power and an AC generator. Other combinations of AC sources are possible.
Shore
Power
AC Generator
AC IN
Mobile FX or VFX
Inverter/Charger
r
Charge
Controller
PV Arra
Alternator
Loads
Programming
Selection of all inverter programming is performed using a system display such as the MATE, MATE2, or
MATE3. The system display can customize a wide range of parameters.
900-0197-01-00 Rev A9
AC OUT
Figure 3 Applications (Example)
DC IN
or
DC OUT
or
Battery
Bank
Page 10
Planning
Renewable Energy
The inverter cannot connect directly to PV, alternators, or other DC sources. The batteries are the
inverter’s primary source of power. However, if the DC sources are used to charge the batteries, the
inverter can use their energy by drawing it from the batteries.
A renewable source is always treated as a battery charger, even if all of its power is used immediately.
The renewable source must have a charge controller, or some other regulation method, to prevent
overcharging. OutBack Power’s FLEXmax family of charge controllers can be used for this purpose, as
can other products.
Battery Bank
When planning a battery bank, consider the following:
Cables
determine the placement of the battery bank. Local codes or regulations may apply and will take priority over
OutBack recommendations.
Battery Type
~ The cycle was designed for lead-chemistry batteries intended for deep discharge. These include batteries for RV, marine,
~ Lithium-based batteries and other advanced battery technologies may require special considerations. Please contact
Nominal Voltage
depending on inverter model. Before constructing a battery bank, check the inverter model and confirm
nominal battery voltage.
Charger Settings and Maintenance
usually recommended for safety reasons. It may be necessary to use a fan to ventilate the battery enclosure.
Batteries must be regularly maintained according to the instructions of the battery manufacturer.
: Recommendations for battery cable size and length are shown on page 18. The maximum length will
: The FX inverter/charger uses a three-stage charge cycle.
golf-cart, and forklift applications. They also include gel-cell batteries and absorbed glass-mat (AGM) batteries. OutBack
Power recommends the use of batteries designed specifically for renewable energy applications. Automotive batteries
are strongly discouraged and will have a short life if used in inverter applications.
OutBack Technical Support at +1.360.618.4363 before implanting advanced technologies.
: These inverters are designed to work with specific battery bank voltages, which are different
: A vented battery enclosure may be required by electric code and is
IMPORTANT:
Battery charger settings need to be correct for a given battery type. Always follow
battery manufacturer recommendations. Making incorrect settings, or leaving them at
factory default settings, may cause the batteries to be undercharged or overcharged.
CAUTION: Hazard to Equipment
Batteries can emit vapors which are corrosive over long periods of time. Installing
the inverter in the battery compartment may cause corrosion which is not covered
by the product warranty. (Sealed batteries may be an exception.)
Bank Size:
Battery bank capacity is measured in amp-hours. Determine the required bank specifications as
accurately as possible, beginning with the items below. This avoids underperformance or wasted capacity.
These ten items are obtainable in different places, summarized in Table 2 on the next page. Some of the
information is specific to the site or application. Some can be obtained from the battery manufacturer.
Information on OutBack products is available from OutBack Power Technologies or its dealers.
A. Size of load:
B. Daily hours of use:
C. Days of autonomy:
D. Application: This often helps define or prioritize the previous three items. Off-grid systems often require enough
capacity to last for an extended period before recharging. Grid-connected systems frequently need only enough
capacity for short-term backup during outages.
10
These are the most basic and
essential factors used to
determine bank size.
900-0197-01-00 Rev A
Page 11
Planning
E. Conductor efficiency: Wire size and other factors will waste
power due to resistance and voltage drop. Typical
acceptable efficiency is 96 to 99%.
F. Inverter efficiency: FX specifications list “Typical Efficiency”
to help estimate operating loss.
G. System DC voltage: Each inverter model requires a specific DC voltage to operate.
H. Battery voltage: Most individual battery voltages are less than the system DC voltage. The batteries may need to be
placed in series to deliver the correct voltage.
I. Capacity: Battery capacity, which is measured in
amp-hours, is not usually a fixed number. It is
specified based on the rate of discharge. For example,
the OutBack EnergyCell 200RE is rated at 134.5 Ahr
when discharged at the 5-hour rate (to terminal
voltage 1.85 Vpc). This is a high rate of discharge that
would hypothetically drain the battery in 5 hours.
The same battery is rated at 191 Ahr when used at the
100-hour rate. Use the appropriate discharge rate
(correlated to the expected loads) to measure the
capacity of a battery. Use battery specifications for
terminal voltage 1.85 Vpc whenever possible.
NOTE: Capacity ratings are for batteries at 25°C.
Capacity is reduced at cooler temperatures.
J. Maximum depth of discharge (DoD): Most batteries cannot be discharged below a certain level without damage. The
bank requires enough total capacity to keep this from happening.
Table 2Battery Bank Elements
Item Source of information
A. Load Size Site-specific
B. Daily Hours Site-specific
C. Days of Autonomy Site-specific
D. Application Site-specific
E. Conductor Efficiency Site-specific
F. Inverter Efficiency Inverter manufacturer
G. System Vdc Inverter manufacturer
H. Battery Vdc Battery manufacturer
I. Capacity Battery manufacturer
J. Maximum DoD Battery manufacturer
To Calculate Minimum Battery Bank Size (refer to Table 2 for letter designations):
Any losses are essentially amp-hour
capacity that the system cannot use. The
battery bank size can be increased to
account for losses.
1.
The load size, item A, is measured in watts. Compensate this figure for efficiency loss. Multiply the
conductor efficiency by the inverter efficiency (E x F). (These items are represented as percentages, but
may be displayed as decimals for calculation.) Divide item A by the result.
2. Convert the compensated load into amperes (Adc). Divide the step 1 result by the system voltage (item G).
3. Determine the daily load consumption in ampere-hours (amp-hours, or Ahr). Multiply the step 2 result by
the daily usage hours (item B).
4. Adjust the total for required days of autonomy (the days the system must operate without recharging)
and the maximum DoD. Multiply the step 3 result by C and divide by J.
The result is the total amp-hour capacity required for the battery bank.
5. Determine the number of parallel battery strings required. Divide the Ahr figure from step 4 by the
individual battery capacity (I). Round the result to the next highest whole number.
6. Determine the total number of batteries required. Divide the system voltage by the battery voltage
(G ÷ H). Multiply the result by the step 5 result.
The result is the total required quantity of the chosen battery model.
EXAMPLE #1
A. Loads: 0.5 kW (500 W)
B. Hours of use: 6
C. Days of autonomy: 1
D. Grid-interactive system (FX2012MT inverter)
E. Conductor efficiency: 98% (0.98)
F. Inverter efficiency: 90% (0.9)
G. System voltage: 12 Vdc
H. Batteries: OutBack EnergyCell 200RE (12 Vdc)
I. Capacity at 8-hour rate: 148.8 Ahr
J. Maximum DoD: 80% (0.8)
A. Loads: 1 kW (1000 W)
B. Hours of use: 3
C. Days of autonomy: 1
D. Off-grid system (FX3048MT inverter)
E. Conductor efficiency: 97% (0.97)
F. Inverter efficiency: 93% (0.93)
G. System voltage: 48 Vdc
H. Batteries: OutBack EnergyCell 200RE (12 Vdc)
I. Capacity at 8-hour rate: 148.8 Ahr
J. Maximum DoD: 50% (0.5)
The FX inverter can accept single-phase input from a generator that delivers clean AC power in the range of
voltage and frequency specified for that model.
~ Inverters stacked for split-phase output (120/240 Vac) can work with both output lines of a split-phase generator.
See pages 30, 32, and 36.
~ Inverters stacked for three-phase output can work with three-phase generators. See page 38.
The inverter/charger can provide a start signal to control an automatic start generator. If automatic generator
starting is required, the generator must be an electric-start model with automatic choke. It should have two-wire
start capability. For other configurations, additional equipment may be required.
1) A ÷ [E x F] 1000 ÷ (0.97 x 0.93) = 1108.5 W
2) 1 ÷ G 1108.5 ÷ 48 = 23.1 Adc
3) 2 x B 23.1 x 3 = 69.3 Ahr
4) [3 x C] ÷ J [69.3 x 1] ÷ 0.5 = 138.6 Ahr
5) 4 ÷ I 138.6 ÷ 148.8 = 0.93 (rounded to 1)
6) [G ÷ H] x 5[48 ÷ 12] x 1 strings = 4 batteries
In any configuration, the inverter may need to be specifically programmed using the system display.
Perform all programming according to the specifications of the generator and the required operation of the
inverter. Parameters to be programmed may include generator size, automatic starting requirements, and
potential fluctuations in generator AC voltage.
Mobile generators are usually equipped with a bond between the neutral and ground connections. Mobile FX
inverter models have neutral-ground switching. This function establishes a bond on the inverter when no
generator is present, but removes it when the generator is running. See page 15 for more information on
neutral-ground bonding.
Generator Sizing
A generator should be sized to provide enough power for all the loads and the battery charger.
The generator size should assume maximum loads and maximum charging at the same time.
Available generator power may be limited by ratings for circuit breakers and/or generator connectors.
The generator must be able to provide current to all inverters on a given phase or output. Minimum generator
3
is usually recommended to be twice the power of the inverter system. For example, a 2 kVA inverter should
size
have a 4 kVA (or larger) generator. Many generators may not be able to maintain AC voltage or frequency for
long periods of time if they are loaded more than 80% of rated capacity.
In addition, if a split-phase 120/240 Vac generator is powering a single-phase 120 Vac inverter system with no
other compensation, it is
required
heavily loaded on one output line may suffer severely from balancing issues. The OutBack FW-X240 or PSX-240
balancing transformers may compensate for this condition.
IMPORTANT:
In general, the generator output should match the stacking and output of the inverters.
A three-phase generator should not be used with a 120/240 Vac inverter system.
3
This is the generator size after derating for environment, use, and other factors.
A purely 240 Vac generator will cause damage if used with a 120 Vac inverter system.
12
to be at least twice the power of the inverters. A split-phase generator that is
900-0197-01-00 Rev A
Page 13
Installation
Location and Environmental Requirements
Sealed (FX) models are resistant to water and other elements but are not designed for permanent outdoor
installations. If installation on the outside of a vehicle is required, the FX inverter must be installed under
cover and protected from direct exposure to the environment. Vented (VFX) models are not resistant to
water and other elements. They must be installed in a weather-proof enclosure or enclosed area.
The inverter can often be mounted in any position or orientation. If there is any exposure to moisture or
condensation, the inverter must not be mounted upside-down. This ensures that water will not accumulate
under the DC cover. However, it can still be mounted in other positions or orientations.
For installations where the inverter may be exposed to moisture or condensation, a sealed model must be used
and mounted either with the base down (shelf mounting) or with the AC wiring compartment facing down
(wall mounting). If mounted with the base down, water cannot be allowed to accumulate around the inverter’s
base. There is a drainage system on the base of the inverter to dispel condensation. If submerged, water can
enter this drain and cause failure.
Vented inverters must be installed in a weather-proof enclosure or enclosed area. These models are not
designed for exposure to water or excessive wind-blown dust and debris.
When inverters are installed with an OutBack FLEXpower system, the system must be installed in the upright
orientation due to the requirements of the circuit breakers.
Any inverter will perform more efficiently in locations offering plenty of air circulation. The recommended
minimum clearance is 2 inches (5 cm) on all sides of the inverter.
Any inverter will function to all of its specifications if operated in a range of –4°F to 122°F (–20°C to 50°C).
The inverter will function, but will not necessarily meet its specifications, if operated in a temperature range of
–0°F to 140°F (–40°C to 60°C). This is also the allowable temperature range for storage.
The FX series of inverters carry an Ingress Protection (IP) rating of 20 and a Relative Humidity (RH) rating of 93%
(non-condensing).
Inverter specifications are listed in the FX Mobile Series Inverter/Charger Operator’s Manual.
Tools Required
Wire cutters/strippers
Torque wrenches
Assorted insulated screwdrivers
Digital voltmeter (DVM) or standard voltmeter
900-0197-01-00 Rev A13
Page 14
Installation
Mounting
One person can install the FX inverter, but installation may be easier with two people.
The unithas four mounting holes, one in each corner. Use fasteners in all corners for a secure installation.
Due to the variance in other mounting methods, OutBack only endorses the use of FLEXware mounting
products or previous versions of OutBack mounting plates. Use M6 x 20 mm machine screws, one per corner,
to attach the inverter to the mounting plate. Follow the instructions with each mounting system.
Mount and secure each component before attaching any wiring.
When the inverter is used with other metal chassis, make sure that all chassis are grounded appropriately.
(See the grounding instructions on page 15.) Grounding other chassis may involve metal-to-metal contact, or
separate ground wires.
If using an OutBack FLEXware Mounting Plate, avoid large air gaps behind the plate. These can result in
louder mechanical noise during heavy inverting or charging. Mount the plate on a flat, solid
mounting surface.
IMPORTANT:
Use correct fasteners to secure the inverter to the mounting surface,
regardless of the type of surface. OutBack cannot be responsible for
damage to the product if it is attached with inadequate fasteners.
Dimensions
Length 16.25” (41 cm)
Height
without
Turbo
12” (30.5 cm)
Width
8.25” (21 cm)
Height
with Turbo
13” (33 cm)
14
Figure 4 Dimensions
900-0197-01-00 Rev A
Page 15
Terminals and Ports
Installation
DC TERMINALS
These terminals connect to the
battery cables and the DC system.
See page 18 for instructions.
CONTROL WIRING TERMINAL BLOCK
These terminals receive control wires for a
variety of functions including generator control.
See pages 24 and 25 for instructions and the
Operator’s Manual for more information.
The Terminal Block can be unplugged from the
AC board for convenience. While installed, keep
screws tight and the block itself secured tightly
to the AC board to prevent malfunction.
INVERTER ON/OFF
These terminals receive wires for a manual on/off
The jumper alongside these terminals overrides
them and turns the inverter on. (See page 23 for
instructions.) With the jumper installed, a switch
cannot turn the inverter off, but the system
display can turn it off or on. The system display
cannot turn it on if the jumper is not installed.
These terminals deliver 12 Vdc up to 0.7 amps
(8.4 watts). The output can be switched on and
off for many functions. The default function is to
The functions for the AUX output can be
programmed using the system display.
switch to control the inverter.
ON/OFF JUMPER
AUX OUTPUT (AUX+/AUX-)
drive a cooling fan or the Turbo Fan.
See page 24 for details.
DC and AC
GROUND TERMINALS
These terminals connect to
a grounding system for
both batteries and AC. See
page 15 for instructions.
AC TERMINAL BLOCK
These terminals receive AC
input and output wires. See
page 21 for instructions.
XCT+/XCT-
Non-operational terminals.
Do not connect anything
to them.
MATE/HUB and RTS PORTS
These ports receive the RJ45
and RJ11 plugs from the
system display and Remote
Temp Sensor. See page 23
for instructions.
The ports are mounted
sideways. When viewed
from the left side, they
appear as shown below.
AUX LED INDICATOR
Orange LED indicator turns on when
12 Vdc output is present.
Figure 5 Terminals, Ports, and Features
WARNING: Shock Hazard
The inverter’s AC output is defaulted to ON from the factory. It will deliver AC voltage as
soon as the power is connected.
900-0197-01-00 Rev A
LED INDICATORS
These indicators display the inverter status and battery voltage.
The three BATTERY LED indicators (green, yellow, and red) are based on
DC voltage, and provide a very general idea of battery state.
The green INVERTER LED indicator shows if the inverting function is on.
The yellow AC IN LED indicator shows if an AC source is present.
The red ERROR LED indicator shows either a Warning or an Error. A
Warning is an alert for a problem that is not severe enough for
shutdown. An Error usually accompanies inverter shutdown.
15
Page 16
Installation
Wiring
It will be necessary to remove knockouts from the AC Plate to run wires. The AC Plate has one knockout of
½” size and two knockouts of ¾” size. Install appropriate bushings to protect the wires.
Use copper wire only. Wire must be rated at 75°C or higher.
Grounding
Table 3 Ground Conductor Size and Torque Requirements
WARNING: Shock Hazard
Mobile models perform automatic neutral-to-ground bond switching. When this
function is engaged, the chassis ground is electrically common with the output
neutral conductor. When disengaged, the chassis ground is isolated from the AC
system. See pages 17, 21, and 22.
Make sure that no more than one bond is present in the AC system at any time.
WARNING: Shock Hazard
For all installations, the negative battery conductor should be bonded to the grounding
system at only one point. If the OutBack GFDI is present, it can provide the bond.
IMPORTANT:
Not all OutBack products can be used in a positive-ground system. If it is necessary to
build a positive-ground system with OutBack products, contact OutBack Technical
Support at +1.360.618.4363 before proceeding. Additionally, consult the online forum
at www.outbackpower.com/forum/, where this subject has been discussed extensively.
Table 3 contains OutBack’s recommendations for minimum safe cable sizes. Other codes for mobile
or marine applications may supersede OutBack’s recommendations. Consult applicable codes for final
size requirements.
16
900-0197-01-00 Rev A
Page 17
Installation
The inverter’s DC ground is a box lug located next to the negative DC battery terminal. This lug accepts
up to 1/0 AWG (70 mm or 0.109 in) wire. Local codes or regulations may require the DC ground to be run
separately from the AC ground. Also, if present, it will be necessary to remove the DC Cover or Turbo Fan
before making the ground connection. (See page 20.)
Box Lug
Figure 6 DC Ground Lug
One ground terminal is labeled CHASSIS GROUND.
This terminal connects to an external ground bar or
bus. The other terminal, labeled NEU/GROUND BOND,
is not common with CHASSIS GROUND, but is joined
to it by a copper jumper. No external connection is
made to NEU/GROUND BOND.
As long as the copper jumper is present, the FX
inverter will automatically perform neutral-ground
bond switching.
If removed, the inverter’s neutral and ground will
be isolated.
If only one mobile inverter is present, leave the
copper jumper in place.
If more than one mobile inverter is present, remove
the copper jumper from every Slave unit.
See the inverter Operator’s Manual for the general
operation of neutral-ground bond switching.
See page 22 for more information on the inverter’s
switching function.
Figure 7 Chassis Ground
900-0197-01-00 Rev A17
Page 18
Installation
DC Wiring
WARNING: Shock Hazard
Use caution when working in the vicinity of the inverter’s battery terminals.
CAUTION: Equipment Damage
Never reverse the polarity of the battery cables. Always ensure correct polarity.
CAUTION: Fire Hazard
The installer is responsible for providing overcurrent protection.
Install a circuit breaker or overcurrent device on each DC positive (+)
conductor to protect the DC system.
Never install extra washers or hardware between the mounting surface
and the battery cable lug. The decreased surface area can build up heat.
See the hardware diagram on page 19.
IMPORTANT:
The DC terminals must be encased in an enclosure to meet the requirements
of some local or national codes.
Table 4 contains OutBack’s recommendations for minimum safe cable sizes.
Other codes may supersede OutBack’s recommendations. Consult applicable
codes for final size requirements.
Table 4 DC Conductor Size and Torque Requirements
Inverter
(Wattage/Voltage)
FX2012MT
FX2024M
FX2524MT
FX2532MT
FX2536MT
FX3048MT
VFX2812M
VFX3524M
VFX3232M
VFX3236M
VFX3648M
Nominal DC Amps
(Derated 125%)
200
100
125
94
83
75
280
175
120
107
90
Conductor Size4
(Minimum)
4/0 AWG (120 mm) or 0.186 in 250 Adc
2/0 AWG (70 mm) or 0.109 in 175 Adc
2/0 AWG (70 mm) or 0.109 in 175 Adc
1/0 AWG (70 mm) or 0.109 in 125 Adc
1/0 AWG (70 mm) or 0.109 in 125 Adc
1/0 AWG (70 mm) or 0.109 in 125 Adc
4/0 AWG (120 mm) or 0.186 in 300 Adc
4/0 AWG (120 mm) or 0.186 in 175 Adc
Battery positive and negative cables should be no longer than 10 feet (3 meters) each, to minimize voltage loss
and other possible effects.
Turn off DC circuit breakers or remove fuses before proceeding.
Tie, tape, or twist cables together to reduce self-inductance. Run positive and negative cables through the same
knockouts and conduit.
The inverter’s battery terminal is a threaded stud which accepts a ring terminal lug. Use crimped and sealed
copper ring lugs with 5/16 inch (0.79 cm) holes, or use compression lugs.
Install all overcurrent devices on the positive cable.
4
Cable sizes are for each inverter in a system. In a system with multiple inverters, each inverter requires its own cables and overcurrent devices of
the size indicated.
18
900-0197-01-00 Rev A
Page 19
To install DC cables and hardware:
1. Install all DC cables.
Do not install hardware in a different order from Figure 8. The battery cable lug should be the first item
installed on the stud. It should make solid contact with the mounting surface.
Do not close the main DC disconnect until wiring is complete and the system is prepared for commissioning.
13 mm Nut
Flat Washer
Installation
M8 x 1.25 Stud
Lock Washer
Mounting Surface
Battery Cable Lug
Insulator
Figure 8 Required Order of Battery Cable Hardware
CAUTION: Fire Hazard
Never install extra washers or hardware between the mounting surface and the
battery cable lug. The decreased surface area can build up heat.
2. Install the battery terminal covers. These are made of stiff plastic with a snap-on design.
If it is necessary to remove the covers, remove
carefully using a flat screwdriver.
Insert the screwdriver into the slot on the
side of each cover and unsnap the cover..
900-0197-01-00 Rev A19
REMOVAL SLOT
Figure 9 Battery Terminal Covers
Page 20
Installation
DC Cover or Turbo Fan Attachment
COVER ATTACHMENT
FX inverters are equipped with either the DC
Cover or the Turbo Fan.
To attach either cover, put the cover in place.
Insert a screw at each corner using a
Phillips screwdriver.
As part of attaching the Turbo Fan, follow the
wiring instructions in Figure 11.
Figure 10 DC Cover Attachment
TURBO FAN WIRING
Install the wires in the AC Wiring Compartment to
make the Turbo Fan operational. The AUX+ and
AUX– terminals receive the red (+) and black (–)
wires. Tighten with a Phillips screwdriver.
To safely run the wires into the AC compartment,
pass the wires through the notch in the
compartment cover.
Notch
Edge of Cover
Compartment
Figure 11 Turbo Fan Wiring
If it is necessary to remove the Turbo Fan:
1. Remove the compartment cover.
If necessary, the green terminal block can be unplugged
by pulling it gently away from the AC board.
Make certain the AUX programming is
correct for proper fan operation.
2. Unscrew the AUX+ and AUX– terminal screws.
3. Remove the wires.
4. Remove the screws at the four corners of the Turbo Fan.
5. Remove the Turbo Fan.
20
900-0197-01-00 Rev A
Page 21
AC Wiring
WARNING: Shock Hazard
All AC source neutral and ground conductors should be mechanically bonded. The
inverter’s neutral and ground conductors should be left isolated. The inverter
performs automatic neutral-ground bond switching during operation.
Ground fault circuit interrupter (GFCI) devices must be installed in a recreational
vehicle wiring system to protect all branch circuits.
WARNING: Fire Hazard
To reduce the risk of fire, do not connect to an AC load center (circuit breaker panel)
having multi-wire branch circuits connected.
IMPORTANT:
The installer is responsible for providing overcurrent protection.
approved 30 Aac circuit breaker on the inverter’s output.
This page contains OutBack’s recommendations for minimum safe cable sizes.
Other codes, particularly for mobile or marine applications, may supersede
OutBack’s recommendations. Consult applicable codes for final size requirements.
All system wiring must comply with national and local codes and regulations.
Installation
Install an
The inverter’s AC terminal block has six positions for AC wires. The minimum recommended size is #10
AWG (6 mm) or 0.009 in wire. The terminals should be tightened to a torque value of 25 in-lb (2.8 Nm).
AC HOT OUT
The AC HOT OUT terminal
connects to the output load
panel. The terminal can
AC NEUTRAL OUT
The AC NEUTRAL OUT
terminal connects to
the neutral bus on the
load panel.
AC NEUTRAL IN
The AC NEUTRAL IN
terminal connects to
the circuit breaker or
bus from an AC input
source, such as shore
power or generator.
Do not connect the AC NEUTRAL IN and AC NEUTRAL OUT terminals together.
These terminals are isolated from each other while inverting. When an AC source
is connected, the neutral terminals switch to become electrically common.
The neutral bus from the input source must be kept isolated from the load panel’s
output neutral bus. Loads must not bridge the input and output terminals, even if
the inverter does not power them. An example would be an air conditioner with
its hot wire connected to the AC source and its neutral wire connected to the
inverter’s output load panel.
Figure 12 AC Terminals
carry up to 30 amps using
the inverter’s transfer relay.
Use the inverter wattage to
size the actual maximum
output load. Size the circuit
breaker accordingly.
AC HOT IN
The AC HOT IN terminal
brings current from the
AC source. It powers both
battery charger and loads.
Use the source size to
determine actual current
draw. Size all circuit breakers
accordingly.
900-0197-01-00 Rev A
21
Page 22
Installation
AC Sources
The inverter has a single set of AC terminals which are intended to connect to a single AC source.
It cannot be directly wired to more than one AC source at the same time.
used, it is usually required to have a selector switch that changes from one to the next. The switch should
be the “break before make” type which disconnects from one source before contacting another. It must
also be a double-pole type which switches both the hot and neutral wires.
In mobile or marine installations, the AC source neutral and ground conductors are expected to be
mechanically bonded.
If multiple sources are
Figure 13 AC Sources
In Figure 13, the shore power and generator are disconnected. The internal transfer relay automatically
bonds the inverter’s output neutral and ground connections as shown. This function can be disabled.
Figure 14 AC Sources and Transfer Relay
When either AC source is connected and accepted, the internal transfer relay switches to transfer the AC
source power to the loads. The internal transfer relay also opens the internal neutral-ground bond.
The AC Source bond is used instead. Figure 14 shows the shore power connected and shows the
shore power bond.
See the Operator’s Manual for the inverter’s criteria for accepting an AC source.
22 900-0197-01-00 Rev A
Page 23
T
T
ON and OFF Wiring
he INVERTER ON/OFF jumper bridges two pins. The ON/OFF jumper
parallels the two INVERTER ON/OFF terminals on the Control Wiring
Terminal Block. If either set of connections is closed, the inverter is ON.
Because the jumper is factory-installed, the inverter usually remains ON
unless given a command by the system display.
Installation
Jumper On
Jumper Off
Removing the jumper will turn the inverter OFF.
This requires long-nose pliers or a similar tool.
Once the jumper has been removed, the INVERTER ON/OFF
terminals on the Control Wiring Terminal Block can be used to
wire a manual on/off switch.
Figure 15 ON/OFF Jumper and Connections
Accessory Wiring
he AC Wiring Compartment Board has ports for both
the Remote Temperature Sensor (RTS) and the system
display. The system display port is labeled MATE/HUB.
If a HUB Communications Manager is in use, it occupies
the inverter’s MATE/HUB port.
RTS cable
RJ11,
4-conductor,
telephone)
MATE cable
RJ45, 8-conductor,
CAT5 non-crossover
RTS port
MATE/HUB port
See the
Operator’s
Manual for more
information on
the RTS.
Additional ports
900-0197-01-00 Rev A23
When a HUB product occupies the inverter’s MATE/HUB port,
the system display connects directly to the HUB product.
If the system display is a MATE2, do not connect it during initial
startup. See the MATE Owner’s Manual for more information.
Inverters plug into ports 1 and above. Charge controllers and
other devices plug into unassigned ports not used by inverters.
See Stacking on page 28 for information on connecting
MATE
port
inverters. See the HUB product literature for other devices.
Figure 16 Accessory Connections
Page 24
Installation
AUX Wiring
The AUX+ and AUX– terminals are a switched 12 Vdc supply. The AUX can respond to different criteria
and control many functions. These include cooling fans, vent fans, load diversion, fault alarms, and the
Advanced Generator Start (AGS) function.
The terminals can supply up to 0.7 amps at 12 Vdc (8.4 watts). This is sufficient to drive a small fan or a
relay controlling a larger device. The terminals accept wire up to #14 AWG (2.5 mm). The
contains electronic overcurrent protection, which resets after being overloaded. No additional fuses are
required for the
The default setting for the AUX output is to control the Turbo Fan included with sealed models.
(See Figure 17.) The AUX output can only control one function at a time. It cannot be used for anything
else if the Turbo Fan is connected.
The control logic for the AUX output is not always located in the same device. Inverter AUX functions are
located within the inverter itself and are described accordingly. Although inverter-based functions require
the system display for programming, they will function even if the display is removed. However, AGS
programming is located within the system display and will not work if the display is removed. Other devices
may also be able to control the terminals. For generator control, see page 25.
AUX
terminals.
AUX
circuit
In this example, the AUX
directly drives a 12-volt
vent fan. The + and – wires
on the fan are connected to
the AUX+ and AUX–
terminals.
Fan
AUX LED
INDICATOR
The AUX indicator
illuminates when
the AUX output
becomes active.
Figure 17 AUX Connections for Vent Fan (Example)
24 900-0197-01-00 Rev A
Page 25
Generator Control
The AUX terminals can provide a signal to control an automatic-start generator. The control function
can be
Advanced Generator Start
(AGS), which is situated in the system display. AGS can start the
generator using settings from the system display, or it can use battery readings from the FLEXnet DC
battery monitor. Alternately, the control function can be
Gen Alert
, which is a simpler function based
directly in the FX inverter. The choice of control function depends on system needs and the capabilities
of each device.
The generator must be an electric-start model with automatic choke. It is recommended to have
“two-wire” start capability. A two-wire-start generator is the simplest type, where the cranking and
starting routine is automated. It usually has a single switch with two positions that is turned ON to start,
OFF to stop.
Two-Wire-Start
Installation
The 12 Vdc signal provided by the
output can be switched on and off to provide a start signal. It is
AUX
possible to send a 12-Vdc signal directly to the generator. However, this should never be done if it
connects the
output directly to the generator’s own battery. It is more common to use the
AUX
AUX
terminals to energize the coil of a 12 Vdc automotive or similar relay.
OBR-16-DIN, the OutBack FLEXware Relay Assembly depicted in Figure 18, is sold for this purpose. The
relay contacts can serve in place of the generator’s start switch. The battery shown below is depicted for
clarity. In most cases, it is part of the generator’s internal starting circuit and is not an external component.
The drawing below is one example of a possible arrangement. Specific arrangements, relays, and other
elements depend on the requirements of the installation and of the generator.
Relay
Contact
Generator
1
Battery
Figure 18 Two-Wire Generator Start (Example)
900-0197-01-00 Rev A
Relay
Coil
Starting
Terminals
1
Two-Wire-Start
Generator
25
Page 26
Installation
Three-Wire-Start
A “three-wire-start” generator has two or more starting circuits. It usually has a separate switch or position
for cranking the generator. A three-wire generator has fewer automated functions than a two-wire. It
usually requires multiple controls for starting, running, or stopping. The AUX terminals cannot control this
type of generator without using a three-wire to two-wire conversion kit.
Atkinson Electronics
(http://atkinsonelectronics.com)
is one company that makes these kits. The
Atkinson GSCM-Mini is intended to work with OutBack inverters.
The drawing below is one example of a possible arrangement. Specific arrangements, relays, and other
elements depend on the requirements of the installation and of the generator.
Atkinson
GSCM-Mini
Figure 19 Three-Wire Generator Start (Example)
26 900-0197-01-00 Rev A
Three-Wire-Start
Generator
Page 27
k
AC Configurations
Single-Inverter
When installing an inverter AC system, the following rules must be observed.
All overcurrent devices must be sized for 30 Aac or less.
All wiring must be sized for 30 Aac or more.
All output circuit breakers must be sized appropriately for loads and inverter power.
The AC input (generator or utility grid) must be a single-phase source of the proper voltage and frequency.
Installation
LEGEND
Hot
Neutral
Ground
TBB = Terminal Bus Bar
System
Display
CAT5 Cable
AC Source
(Shore Power or AC Generator)
AC Conduit Box
AC
GND
HUB/
MATE
HOT
AC
Hot
NEU
Neutral
Inverter/Charger
AC
Neutral
GROUND
AC
Hot
NOTES:
1. Neutral (common) conductor may be
connected from only one inverter
neutral terminal to a common bus bar in
the AC conduit box.
2. Colors depicted here may be different
from wiring standards.
Input
Circuit
Breaker
Ground TBB
(may be within AC
Conduit Box)
Primary
System
900-0197-01-00 Rev A27
Mechanical
Interloc
Output
Circuit
Breaker
NEU GND HOT
AC Loads
Figure 20 Single-Inverter Wiring
Bypass
Circuit
Breaker
Page 28
Installation
Multiple-Inverter AC Installations (Stacking)
Installing multiple inverters in a single AC system allows larger loads than a single inverter can handle.
This requires stacking. Stacking inverters refers to how they are wired within the system and then
programmed to coordinate activity. Stacking allows all units to work together as a single system.
Examples of stacking configurations include “classic series”, “OutBack series”, “parallel”, “series/parallel”,
and “three-phase” configurations.
Stacking Connections
Stacking requires an OutBack communications manager and a system display.
If the MATE or MATE2 System Display is used, it must have firmware revision 4.1.6 or above.
A system of four or fewer units may use the HUB4 Communications Manager.
A system of up to ten units requires the HUB10.3 Communications Manager.
All interconnections between the products are made using CAT5 straight-through (non-crossover) cable.
HUB10.3
Communications
Manager
MATE2 System Display
Additional Ports
Port 1
MATE Port
MATE3 System Display
Figure 21 OutBack HUB10.3, MATE2 , and MATE3
Each inverter must be assigned a stacking mode depending on the configuration. Modes are described
below. Mode names sometimes vary with inverter model; see Table 5 on page 29.
The master provides the primary output phase. Other inverters in the system base their phase on that of the
master. If the master shuts off, all other inverters also shut off. The master must sense and connect to an AC
source before other inverters can connect.
~ In all cases, the master inverter must be connected to port 1 on the communications manager.
~ In a parallel-stacked or OutBack-stacked system, the master tends to be the most heavily used unit.
~ The selection for three-phase master is different from the single-phase master.
28 900-0197-01-00 Rev A
Page 29
Installation
There are two types of slave modes. The names used here are derived from their references onscreen.
A “classic” slave is used for stacking when the slave operates semi-independently of the master. Although the
master sets the phase relationship, the slave creates an output independent of the master. It is not possible to
balance the outputs with the FW-X240 transformer using this method. This type of system is used for the most
basic form of series stacking (two inverters only) and for three-phase stacking.
~ Classic-stacked inverters can go into Search mode independently of the master if necessary.
An “OutBack” slave is used for parallel or series/parallel systems. In parallel stacking, all slaves are in phase with
the master. In series/parallel systems, some slaves are in phase with the master and some are 180° out of phase.
The FW-X240 autoformer can balance the loads of OutBack-stacked inverters.
~ All slave outputs are pulse-width-matched to be precisely synchronized with the master inverter. This avoids potential
backfeed situations.
~ OutBack slaves can be placed in Power Save mode when not in use. They are activated by the master inverter as
needed. For this reason, the master is normally the only inverter to enter Search mode. See the Operator’s Manual for
descriptions of Power Save and Search mode.
In many cases the port assignments for secondary inverters (ports 2 to 4 or 2 to 10) is important. In
general it is always important to keep track of units and ports for programming purposes. See the
communications manager and system display literature for more information.
Programming involves using the system display to assign a status and stacking value to the inverter on
each port. Each inverter is assigned to power a specified phase of the system. These assignments can be
changed at any time as long as the master is plugged into port 1.
IMPORTANT:
Table 5 Stacking Modes for Mobile FX Inverters
Mode Name
(MATE3 or MATE)
1-2phase Master
1-2ph Master
Classic Slave
OB Slave L1
OB Slave L2
3phase Master
3ph Master
3phase Slave
5
Two inverters only
6
Three inverters only
900-0197-01-00 Rev A
3ph Slave
or
or
or
The master inverter must always be connected to port 1 on the
communications manager. Connecting it elsewhere, or connecting a slave
to port 1, will result in backfeed or output voltage errors which will shut the
system down immediately.
Installing multiple inverters without stacking them (or stacking them
incorrectly) will result in similar errors and shutdown.
Although stacking allows greater capacity, the loads, wiring, and
overcurrent devices must still be sized appropriately. Overloading may
cause circuit breakers to open or the inverters to shut down.
Table 5 shows all applicable modes for each inverter model.
When Used Function
Classic stack ,
OutBack stack
5
Classic stack (series)
Slave inverter for Classic series stack
OutBack stack (parallel or
series/parallel)
OutBack stack (series or
series/parallel)
Three-phase stack6 Phase A inverter for three-phase stack
6
Three-phase stack
Master inverter for all series and
parallel stacking
Slave inverter (in phase with master)
for parallel stack
Slave inverter (out of phase with master)
for OutBack series stack
Phase B or C inverter (phase is assigned
by port) for three-phase stack
29
Page 30
Installation
Stacking Configurations
Classic Series Stacking (Dual-Stack)
In series stacking, two inverters create two separate 120 Vac output phases. One inverter is the master.
The other is a slave that is intentionally 180° out of phase with the master. Each of these outputs can be
used to power a separate set of 120 Vac loads. Collectively they form a “split-phase” configuration which
produces 240 Vac. “Classic” series stacking is the simplest way to achieve this output.
The two outputs operate independently of each other. The 120 Vac loads on each output cannot exceed a given
inverter’s size. The second inverter cannot assist.
Only two inverters, one per output, may be classic series stacked. They must be the same model.
LOAD PANEL
1-2phase
Master
2.0 kVA
2.0 kVA 120 Vac
120 Vac
Classic
OR
Slave
2.0 kVA
2.0 kVA 120 Vac
120 Vac
Figure 22 Example of Classic Series Stacking Arrangement
When installing a series inverter system, observe the following rules.
Series stacking requires both a system display and a communications manager. Port assignments and jumper
positions vary with model and stacking configuration.
The master inverter is the L1 output. It must be connected to communications manager port 1. It is
programmed as
The L2 inverter must be programmed as
1-2phase Master
. Other inverters must not be selected as master.
Classic Slave
Manager literature for port assignments.
All overcurrent devices must be sized for 30 Aac or less. All wiring must be sized for 30 Aac or more.
All output circuit breakers must be sized appropriately for loads and inverter power.
during programming. See the HUB Communications
4.0 kVA
240 Vac
The AC input (generator or shore power) must be 120/240 Vac (split-phase).
30 900-0197-01-00 Rev A
Page 31
Installation
HUB 10.3
10 9 8 7 6 5 4 3 2 1 MATE
CAT5 Cables
System
Display
AC Neutral
IN
Inverter
GND
HUB/ MATE
L1 Master
(Shore Power or AC Generator)
AC Source
AC Conduit Box
Neutral TBB
Input
Circuit
Breaker
AC
Hot IN
(L1)
Neutral
Hot L1
TBB
HUB/ MATE
AC
IN
Inverter
L2 Slave
Hot IN
Hot L2
TBB
AC
(L2)
Input
Circuit
Breaker
Ground TBB
(may be within AC
Conduit Box)
AC
Neutral
OUT
GND
AC
Hot OUT
(L1)
Primary
System
Ground
LEGEND
Hot L1
Hot L2
Neutral
Ground
TBB = Terminal Bus Bar
GND
Neutral
TBB
AC Loads
Hot L1
TBB
NOTES:
1. Neutral (common) conductor may be connected from only one inverter neutral terminal to a
common bus bar in the AC conduit box.
2. Colors shown here may be different from wiring standards.
Figure 23 Classic Series Wiring
AC
Neutral
OUT
Hot L2
TBB
Output
Circuit
Breakers
Hot OUT
GND
Mechanical
Interlock
AC
(L2)
Bypass
Circuit
Breakers
900-0197-01-00 Rev A31
Page 32
Installation
OutBack Series Stacking (Dual-Stack)
In OutBack’s unique series stacking, two inverters create a “split-phase” configuration. This configuration
creates two separate 120 Vac output legs. One output is the master. The other is a slave that is
intentionally 180° out of phase with the master. The collective voltage is 240 Vac, as in Classic stacking.
However, the output loads are balanced with the FW-X240 autotransformer.
The slave output is controlled directly by the master and cannot operate independently.
In the event of a load imbalance in a 120/240 Vac system, the FW-X240 transformer can transfer power from one
output to the other. The transfer balances the loads on each inverter. It also allows heavy 120 Vac loads on
either leg to use the full power of both inverters. (The loads below are marked “2+ kVA” per output. This means
the power of a 2 kVA inverter is assisted by the other output.)
The slave can go into Power Save mode when not in use. The FW-X240 autotransformer allows the master to
power loads on either output. This reduces idle power consumption and improves system efficiency.
Additional inverters can be added for combination series/parallel operation. See page 36. All inverters must be
the same model.
LOAD PANEL
OB Slave L2
2+ kVA
120 Vac
2+ kVA
120 Vac
OR
4.0 kVA
240 Vac
1-2phase
Master
2.0 kVA 120 Vac
FW-X240
2.0 kVA 120 Vac
Figure 24 Example of OutBack Series Stacking Arrangement
When installing an OutBack series system, the following rules must be observed.
Series stacking requires an FW-X240 autotransformer, a system display and a communications manager. Port
assignments and jumper positions vary with model and stacking configuration.
The inverter that is mounted physically lowest is designated as the master. It is the L1 output. Mounting the
master below the other inverters allows the master to avoid heat buildup and remain relatively cool.
The master must be connected to communications manager port 1. It is programmed as
Other inverters must not be selected as master.
1-2phase Master
.
The L2 inverter must be programmed as
Manager literature for port assignments.
All overcurrent devices must be sized for 30 Aac or less. All wiring must be sized for 30 Aac or more.
All output circuit breakers must be sized appropriately for loads and inverter wattage.
The AC input (generator or shore power) must be 120/240 Vac (split-phase).
32 900-0197-01-00 Rev A
OB Slave L2
during programming. See the HUB Communications
Page 33
Installation
HUB 10.3
10 9 8 7 6 5 4 3 2 1 MATE
CAT5 Cables
System
Display
AC
Neutral
IN
Inverter
L1 Master
AC
Neutral
OUT
HUB/
MATE
GND
(Shore Power or AC Generator)
AC Source
AC Conduit Box
Input
Circuit
Breaker
Neutral
TBB
Neutral
GND
AC
Hot IN
(L1)
AC
Hot OUT
(L1)
Hot L1
AC
Neutral
MATE
IN
Inverter
L2 Slave
AC
OUT
TBB
HUB/
GND
Hot L2
TBB
AC
Hot IN
(L2)
AC
Hot OUT
(L2)
Input
Circuit
Breaker
Output
Circuit
Breakers
Mechanical
Interlock
Bypass
Circuit
Breakers
AC Conduit Box)
Primary System
Ground
Ground TBB
(may be within
Neutral TBB
X-240
Transformer
LEGEND
Hot L1
Hot L2
Neutral
Ground
TBB = Terminal Bus Bar
NOTES:
1. Neutral (common) conductor may
25 Amp
Dual-Pole
Breaker
GNDHot L1
Neutral
TBB
TBB
Hot L2
TBB
be connected from only one inverter
neutral terminal to a common bus
bar in the AC conduit box.
AC Loads
2. Colors shown here may be different
from wiring standards.
Figure 25 OutBack Series Wiring (Two Inverters)
900-0197-01-00 Rev A33
Page 34
Installation
Parallel Stacking (Dual-Stack and Larger)
In parallel stacking, two or more inverters create a single, common 120 Vac bus.
All inverters share a common input (AC source). The inverters run loads on a common output bus. The master
inverter provides the primary output. The slaves are connected to the same output and assist the master.
The slave outputs are controlled directly by the master and cannot operate independently.
Slave inverters can go into Power Save mode when not in use. The master will activate individual slaves based
on load demand. This reduces idle power consumption and improves system efficiency.
Up to ten inverters may be installed in a parallel arrangement. The example on this page shows three inverters.
The wiring diagram on the next page shows four. All inverters must be the same model.
LOAD
1-2phase Master
2.0 kVA 120 Vac
OB Slave L1
2.0 kVA 120 Vac
OB Slave L1
2.0 kVA 120 Vac
PANEL
6.0 kVA
120 Vac
Figure 26 Example of Parallel Stacking Arrangement (Three Inverters)
When installing a parallel inverter system, observe the following rules.
Parallel stacking requires both a system display and a communications manager. Port assignments and jumper
positions vary with model and stacking configuration.
The inverter that is mounted physically lowest is always the master. It is the primary output. Mounting the
master below the other inverters allows the master to avoid heat buildup and remain relatively cool.
The master must be connected to communications manager port 1. It is programmed as
Other inverters must not be selected as master.
All other inverters, regardless of number, must be programmed as
HUB Communications Manager literature for port assignments.
All overcurrent devices must be sized for 30 Aac or less. All wiring must be sized for 30 Aac or more.
All output circuit breakers must be sized appropriately for loads and inverter power.
The AC input (generator or shore power) must be 120 Vac at 60 Hz (single-phase)
1-2phase Master
OB Slave L1
during programming. See the
.
34 900-0197-01-00 Rev A
Page 35
k
(L1)
(L1)
Installation
HUB 10.3
10 9 8 7 6 5 4 3 2 1 MATE
CAT5 Cables
System
Display
AC
Neutral
IN
Inverter
L1 Master
HUB/
MATE
GND
AC
Hot IN
(L1)
AC Source
(Shore Power or
AC Generator)
AC Conduit Box
Input
Circuit
Breaker
Neutral
TBB
AC
Neutral
IN
HUB/
MATE
AC
Hot IN
(L1)
Hot L1 TBB
Input
Circuit
Breaker
Inverter Inverter
L1 Slave
AC
Neutral
IN
HUB/
MATE
LEGEND
TBB = Terminal Bus Bar
Input
Circuit
Breaker
AC
Hot IN
AC
Neutral
IN
Inverter
L1 Slave
Hot L1
Neutral
Ground
HUB/
MATE
AC
Hot IN
Input
Circuit
Breaker
Primary
System
Ground
Ground TBB
(may be within
AC Conduit Box)
GND
AC
Neutral
OUT
Hot OUT
GND
Neutral TBB
AC
(L1)
AC
Neutral
OUT
AC Loads
GND
AC
Hot OUT
(L1)
Hot L1 TBB
AC
Neutral
OUT
Output
Circuit
Breakers
AC
Hot OUT
(L1) GND
Mechanical
Interloc
Bypass
Breakers
GND
AC
Hot OUT
(L1)
AC
Neutral
OUT
Circuit
NOTES:
1. Neutral (common) conductor may
be connected from only one inverter
neutral terminal to a common bus
bar in the AC conduit box.
2. Colors shown here may be different
from wiring standards.
Figure 27 Parallel Wiring (Four Inverters)
900-0197-01-00 Rev A35
Page 36
Installation
Series/Parallel Stacking (Quad-Stack or Larger)
In series/parallel stacking, inverters use OutBack series stacking create separate 120 Vac output phases
and 240 Vac collectively. However, in this configuration, each output has parallel inverters. One output
contains the master; the other uses a slave. Each output has at least one additional slave.
The 120 Vac loads on each output can exceed the size of a single inverter. They can be powered by all the
inverters on that output.
The slave outputs cannot operate independently. The slaves can go into Power Save mode when not in use.
Up to ten inverters may be installed in a series/parallel arrangement. All inverters must be the same model.
OB Slave L1
3 kVA 120 Vac
3 kVA 120 Vac
OB Slave L2
3 kVA 120 Vac
3 kVA 120 Vac
FW-X240
LOAD PANEL
6 kVA
120 Vac
6 kVA
120 Vac
OR
240 Vac
1-2phase Master OB Slave L2
Figure 28 Example of Series/Parallel Stacking Arrangement (Four Inverters)
When installing a multiple-inverter series/parallel system, observe the following rules.
Series/parallel stacking requires one or more FW-X240 autotransformers, a system display and a communications
manager. Port assignments and jumper positions vary with model and stacking configuration.
12 kVA
A system of four mobile FX or VFX inverters can use a single FX-X240 balancing transformer. If more than four
inverters are used, the output must be balanced with additional transformers. Two transformers are required for
series/parallel systems of up to eight inverters. For a ten-inverter system, three transformers are required.
The inverter that is mounted physically lowest is always the master. It is the primary L1 output. Mounting the
master below the other inverters allows the master to avoid heat buildup and remain relatively cool.
The master must be connected to communications manager port 1. It is programmed as
Other inverters must not be selected as master.
All other inverters on the L1output, regardless of number, must be programmed as
programming.
All inverters on the L2 output, regardless of number, must be programmed as
See the HUB Communications Manager literature for port assignments.
All overcurrent devices must be sized for 30 Aac or less. All wiring must be sized for 60 Aac or more.
All output circuit breakers must be sized appropriately for loads and inverter power.
The AC input (generator or shore power) must be 120/240 Vac (split-phase).
36 900-0197-01-00 Rev A
1-2phase Master
OB Slave L1
OB Slave L2
.
during
during programming.
Page 37
D
k
e
e
D
D
Installation
HUB 10.3
10 9 8 7 6 5 4 3 2 1 MATE
CAT5 Cables
System
Display
AC
Neutral
IN
Inverter
L1 Master
HUB/
MATE
GND
AC
Hot IN
(L1)
Input
Circuit
Breaker
AC Source
(Shore Power or
AC Generator)
AC Conduit Box
Neutral TBB
AC
HUB/
Neutral
MATE
IN
Inverter
L1 Slave
Hot L1 TBB
Input
Circuit
Breaker
AC
Hot IN
(L1)
Neutral
Hot L2 TBB
HUB/
AC
MATE
IN
Inverter
L2 Slav
TBB = Terminal Bus Bar
Input
Circuit
Breaker
AC
Hot IN
(L2)
LEGEND
HUB/
AC
MATE
Neutral
IN
Inverter
L2 Slav
Hot L1
Hot L2
Neutral
Ground
AC
Hot IN
(L2)
Input
Circuit
Breaker
Primary
System
Ground
Ground TBB
(may be within
AC Conduit Box)
AC
Neutral
OUT
AC
Hot OUT
(L1)
GN
AC
Neutral
OUT
AC
Hot OUT
(L1) GND
AC
Neutral
OUT
AC
Hot OUT
GN
(L2)
AC
Neutral
OUT
Mechanical
Interloc
Output
Circuit
Breakers
Neutral TBB GND
Hot L1 TBB
Hot L2 TBB
Bypass
Circuit
Breakers
NOTES:
1. Neutral (common) conductor may
be connected from only one inverter
AC Loads
neutral terminal to a common bus
bar in the AC conduit box.
2. Colors shown here may be different
from wiring standards.
Figure 29 Series/Parallel Wiring (Four Inverters)
Hot OUT
(L2) GN
AC
900-0197-01-00 Rev A37
Page 38
Installation
Three-Phase Stacking
In three-phase stacking, inverters create three separate 120 Vac output phases in a wye configuration.
The output of each inverter is 120° out of phase from the others. Any two outputs produce 208 Vac between
them. The outputs can be used to power three-phase loads when all inverters work together.
The 120 Vac loads on each output cannot exceed a given inverter’s wattage. The other outputs cannot assist.
Only three inverters, one per phase, may be installed in a three-phase arrangement. All inverters must be the
same model.
LOAD PANEL
Master (A)
2.0 kVA 120 Vac
2.0 kVA
120 Vac
3phase Slave (B)
2.0 kVA 120 Vac
2.0 kVA
120 Vac
OR
6.0 kVA
208 Vac
3phase Slave (C)
2.0 kVA 120 Vac
2.0 kVA
120 Vac
Figure 30 Example of Three-Phase Stacking Arrangement (Three Inverters)
When installing a three-phase system, observe the following rules.
Three-phase stacking requires both a system display and a communications manager. Port assignments and
jumper positions vary with model and stacking configuration.
The master must be connected to communications manager port 1. It is the Phase A output. It is programmed as
3phase Master
The Phase B and Phase C inverters must be programmed as
Manager literature for port assignments.
All overcurrent devices must be sized for 30 Aac or less. All wiring must be sized for 30 Aac or more.
All output circuit breakers must be sized appropriately for loads and inverter power.
The AC input (generator or utility grid) must be a three-phase wye configuration source of the proper voltage
and frequency.
. Other inverters must not be selected as master.
3phase Slave
. See the HUB Communications
38 900-0197-01-00 Rev A
Page 39
k
Installation
HUB 10.3
10 9 8 7 6 5 4 3 2 1 MATE
CAT5 Cables
System
Display
(Shore Power or AC Generator)
AC Source
AC Conduit Box
Neutral TBB
Neutral
AC
MATE
IN
Inverter
AC
Neutral
IN
Inverter
HUB/
MATE
GND
AC
Hot IN
(A)
Phase A (Master)Phase B
AC
Neutral
OUT
GND
AC
Hot OUT
(A)
AC
Neutral
OUT
GND
HUB/
Phase A
TBB
AC
Hot IN
(B)
AC
Hot OUT
(B)
Input
Circuit
Breaker
Phase B
TBB
Input
Circuit
Breaker
AC
Neutral
IN
Inverter
AC
Neutral
OUT
Phase C
TBB
Input
Circuit
Breaker
HUB/
MATE
Phase C
Hot OUT
GND
AC
Hot IN
(C)
AC
(C)
Ground TBB
(may be within
AC Conduit Box)
Primary System
Ground
LEGEND
Phase A
Phase B
Phase C
Neutral
Ground
TBB = Terminal Bus Bar
Figure 31 Three-Phase Wiring (Three Inverters)
GND
Neutral
TBB
AC
Phase A
TBB
Phase B
TBB
Phase C
TBB
Mechanical
Interloc
Output
Circuit
Breakers
Bypass
Circuit
Breakers
NOTES:
1. Neutral (common) conductor
may be connected from only
one inverter neutral terminal to
a common bus bar in the AC
conduit box.
2. Colors shown here may be
different from wiring standards.
900-0197-01-00 Rev A39
Page 40
Installation
NOTES:
40 900-0197-01-00 Rev A
Page 41
Commissioning
Functional Test
WARNING: Shock Hazard and Equipment Damage
The inverter’s AC and DC covers must be removed to perform these tests. The components are close
together and carry hazardous voltages. Use appropriate care to avoid the risk of electric shock or
equipment damage.
It is highly recommended that all applicable steps be performed in the following order. However, if steps
are inapplicable, they can be omitted.
If the results of any step do not match the description, see the Operator’s Manual for troubleshooting.
Pre-startup Procedures
1. Ensure all DC and AC overcurrent devices are opened, disconnected, or turned off.
2. Double-check all wiring connections.
3. Confirm that the total load does not exceed the inverter’s rated power.
4. Inspect the work area to ensure tools or debris have not been left inside.
5. Using a digital voltmeter (DVM) or standard voltmeter, verify battery voltage. Confirm the voltage
is correct for the inverter model. Confirm the polarity.
6. Connect the system display, if present.
CAUTION: Equipment Damage
Incorrect battery polarity will damage the inverter. Excessive battery voltage also may damage the inverter.
This damage is not covered by the warranty.
WARNING: Shock Hazard
The inverter’s AC output is defaulted to ON from the factory. It will deliver 120 Vac as soon as DC power is
connected.
Startup
To start a single-inverter system:
1. Close the main DC circuit breakers (or connect the fuses) from the battery bank to the inverter.
The inverter will activate. Do not turn on any AC circuit breakers at this time. Confirm that the
system display is operational, if present.
2. Observe the LED indicators in the AC wiring compartment. One of the three BATTERY indicators
should be illuminated (green, yellow, or red). Any of them are acceptable at this stage. INVERTER
(green) should come on at this time. The fan will run briefly and the relay will click as a self-test.
3. If a system display is present, perform all programming for all functions. These functions may
900-0197-01-00 Rev A
include input current limits, battery charging, generator starting, and others.
41
Page 42
Installation
Figure 32 AC Terminals
4. Using a DVM or voltmeter, measure between the AC HOT OUT and AC NEUTRAL OUT terminals.
(See Figure 32.) The inverter is working correctly if the AC output reads within 10% of 120 Vac.
Proceed past the items below to Step 5.
To start a multiple-inverter (stacked) system:
1. Close the main DC circuit breakers (or connect the fuses) from the battery bank to the master
inverter. The inverter will activate. Do not turn on any AC circuit breakers at this time. Confirm that
the system display is operational.
2. Observe the LED indicators in the AC wiring compartment. One of the three BATTERY indicators
should be illuminated (green, yellow, or red). Any of them are acceptable at this stage. INVERTER
(green) should come on at this time. The fan will run briefly and the relay will click as a self-test.
Repeat steps 1 and 2 for every inverter present.
3. With the system display, perform programming for stacking and all other functions. These
functions may include input current limits, battery charging, and generator starting. All parallelstacked slave inverters will observe the master programming settings and do not need to be
programmed individually. The MATE3 Configuration Wizard may be used to assist programming.
4. Using the system display, temporarily bring each slave out of Silent mode by raising the Power
Save Level of the master.
As each slave is activated, it will click and create an audible hum.
Confirm that the system display shows no fault messages.
Using a DVM or voltmeter, measure between the AC HOT OUT terminal on the master inverter and
AC HOT OUT on each slave. Series inverters should read within 10% of 120 Vac. Parallel inverters
should read close to zero. Three-phase inverters should read within 10% of 208 Vac.
When this test is finished, return the master to its previous Power Save Level.
After output testing is completed, perform the following steps:
5. Close the AC output circuit breakers. If AC bypass switches are present, place them in the normal
(non-bypass) position. Do not connect an AC input source or close any AC input circuits.
6. Use a DVM to verify correct voltage at the AC load panel.
7. Connect a small AC load and test for proper functionality.
42900-0197-01-00 Rev A
Page 43
8. Close the AC input circuit breakers and connect an AC source.
Using a DVM or voltmeter, check the AC HOT IN and AC NEUTRAL IN terminals for 120 Vac
from the AC source.
If a system display is present, confirm that the inverter accepts the AC source as appropriate for its
programming. (Some modes or functions may restrict connection with the source. If one of these
selections has been used for the system, it may not connect.) Check the system display indicators for
correct performance.
9. If the charger is activated, the inverter will perform a battery charging cycle after powering up.
This can take several hours. If restarted after a temporary shutdown, the inverter may skip most or
all of the charging cycle. Confirm that it is charging as appropriate by using the system display.
10. Test other functions which have been enabled, such as generator start or search mode.
11. Compare the DVM’s readings with the system display meter readings. If necessary, the system
display’s readings can be calibrated to match the DVM more accurately. Calibrated settings
include AC input voltage, AC output voltage, and battery voltage.
Powering Down
These steps will completely isolate the inverter.
To remove power from the system:
1. Turn off all load circuits and AC input sources.
Installation
2. Turn off all renewable energy circuits.
3. Turn each inverter OFF using the system display or external switch.
4. Turn off the main DC overcurrent devices for each inverter.
Adding New Devices
When adding new devices to the system, first turn off the system according to the Power Down
instructions. After adding new devices, perform another functional test, including programming.
Table 6Terms and Definitions
Operation
Once the mounting, wiring, and other installation steps are completed, proceed to the FXR Series
Inverter/Charger Operator’s Manual.
Refer to the system display manual for programming instructions and menus.
Definitions
The following is a list of initials, terms, and definitions used with this product.
Term Definition
AC Alternating Current; refers to voltage produced by the inverter, utility grid, or generator
AC Plate Inverter accessory to accommodate flexible cable when conduit is not used
AGS Advanced Generator Start
AUX Inverter’s 12-volt auxiliary output
Communications
manager
900-0197-01-00 Rev A 43
Multi-port device such as the OutBack HUB 4 or HUB10.3; used for connecting multiple OutBack
devices on a single remote display; essential for stacking inverters
Page 44
Installation
T
T
T
T
Table 6 Terms and Definitions
Term Definition
CSA Canadian Standards Association; establishes Canadian national standards and the Canadian
Electrical Code, including C22.1 and C22.2
DC Direct Current; refers to voltage produced by the batteries or renewable source
DCC DC Cover; shields the DC terminal area on vented FXR inverters
DVM Digital Voltmeter
ETL Electrical Testing Laboratories; short for the company ETL Semko; refers to a certification issued by
ETL to OutBack products indicating that they meet certain UL standards
GFCI Ground Fault Circuit Interruptor; a safety device for electrical systems
GND Ground; a permanent conductive connection to earth for safety reasons; also known as Chassis
Ground, Protective Earth, and PE
HUB An OutBack communications manager product; used for system stacking and coordination
Invert, inverting
LED Light-Emitting Diode; refers to indicators used by the inverter and the system display
Master An inverter which provides the primary output phase of a stacked system; other stacked inverters
MATE, MATE2, MATE3 System display products, used for monitoring, programming and communicating with the
NEU AC Neutral; also known as Common
Neutral-to-ground bond A mechanical connection between the AC neutral (Common) bus and the ground (PE) bus; this
PV Photovoltaic
RTS Remote Temperature Sensor; accessory that measures battery temperature for charging
Slave An inverter which adds additional power to the master in a stacked system; a slave does not
Split-phase A type of utility electrical system with two “hot” lines that typically carry 120 Vac with respect to
System display Remote interface device, used for monitoring, programming and communicating with the
hree-phase, 3-phase A type of utility electrical system with three “hot” lines, each 120° out of phase; each carries the
he act of converting DC voltage to AC voltage for load use or other applications
base their output and on/off state on the master
inverter
bond makes the AC neutral safe to handle
provide an output of its own
neutral and 240 Vac with respect to each other; common in North America
inverter; also called “remote system display”
nominal line voltage with respect to neutral; each carries voltage with respect to each other
equaling the line voltage multiplied by 1.732
urbo Fan External cooling fan used in place of the DCC on sealed FX inverters
UL Underwriters Laboratories; refers to a set of safety standards governing electrical products
Utility grid
he electrical service and infrastructure supported by the electrical or utility company; also called
“shore power”, “mains”, “utility service”, or “grid”
44900-0197-01-00 Rev A
Page 45
A
AC Plate ....................................................................................... 8
AC Sources ............................................................................... 22
AC Terminals ................................................................9, 15, 21
AC Test Points ......................................................................... 42
Adding New Devices ............................................................ 43