OSRAM SYLVANIA ENCELIUM User Manual

76-017-DB
11/13
OSRAM and Logo are registered trademarks of OSRAM
GmbH.
© 2013 O SRA M SYL VAN IA 0 1
-13
Important Safeguards
Overview
www.sylvania.com/encelium
Installation Notes
The Phase Cut Dimming Modules are to be installed in
dry,
indoor locations ONLY.
Troubleshooting
There are no user-serviceable parts inside of the Ph
ase Cut Dimming Module. Please return the device to OSRAM Sylvania Inc if service is required.
Regulatory Approvals
ote: This equipment has been tested and found to comply
N with the limits for part 18 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment under FCC rules.
The contents of this Wiring and Installation Manual
are subject
to change without notice.
United States OSRAM SYLVANIA
100 Endicott Street Danvers, MA 01923 1-800-LIGHTBULB
Trade Phone: 800-255-5042 Fax: 800-255-5043
National Accounts Phone: 800-562-4671 Fax: 800-562-4674
OEM/Special Markets Phone: 800-762-7191 Fax: 800-762-7192
Retail Phone: 800-842-7010 Fax: 800-842-7011
SYLVANIA Lighting Services Phone: 800-323-0572 Fax: 800-537-0784
Display/Optic Phone: 888-677-2627 Fax: 855-543-1043
Canada OSRAM SYLVANIA LTD.
2001 Drew Road Mississauga, ON L5S 1S4 1-800-LIGHTBULB
Trade Phone: 800-263-2852 Fax: 800-667-6772
OEM/Special Markets/Display/Optic Phone: 800-265-2852 Fax: 800-667-6772
Retail Phone: 800-720-2852 Fax: 800-667-6772
SYLVANIA Lighting Services Phone: 800-663-4268 Fax: 866-239-1278
Mexico OSRAM MEXICO
Tultitlan/Edo de Mexico Phone: 011-52-55-58-99-18-50
ENCELIUM® Products United States
Phone: 201-508-1570 Fax: 201-508-1589
Canada Phone: 905-731-7678 Fax: 905-731-1401
www.sylvania.com
/Sylvania
/sylvania
ENCELIUM
Energy Management System
Phase Cut Dimming Module
Wiring and Installation Manual
The Phase Cut Dimming Module (PCDM) provides an i
nterface between the Phase Cut dimmable (forward and reverse phase) ballasts/LED drivers and the ENCELIUM GreenBus II™ communication network. The PCDM is automatically addressed as soon as it is connected to an Energy Control Unit (ECU). Individually addressable, the PCDM enables each group or zone of fixtures to be independently controlled and configured to best meet the needs of the facility.
The PCDM is designed to control popular load types such as Incandescent/Halogen lamps, Fluorescent ballasts, LED fixtures, and LED/CF lamps. The phase cut dimmable fixtures connected to a PCDM can then be controlled by any of the Encelium low voltage wall station controllers, the Touch Screen panel or from Polaris 3D™ software through the GreenBus II™ communication network. PCDM has a built-in relay which provides ON/OFF switching control in addition to smoothly dimming the fixtures.
The following model is available:
ndoor Locations:
I
EN-PCDM-GB2
When using electrical equipment, basic safety precau
tions should always be followed
including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
The use of accessory equipment is not recommended by OSRAM Sylvania as it may cause an
unsafe condition.
Do not use this equipment for other than the intended use.
SAVE THESE INSTRUCTIONS
ENCELIUM and Polaris 3D are registered trademarks of OSRAM SYLVANIA, Inc GreenBus II are trademarks of OSRAM SYLVANIA, Inc. SEE THE WORLD IN A NEW LIGHT is a registered trademark of OSRAM SYLVANIA, Inc.
76-017-DB
11/13
OSRAM and Logo are registered trademarks of OSRAM
GmbH.
Phase Cut Dimm
ing Module
Installation
GreenBus II™ Wiring
Communication Circuit (24VDC, Class 2)
reenBus IITM is a low-cost, high reliability communication means to report sensor information back to
G the ENCELIUM Energy Management System and to obtain optimum brightness settings for each individual light fixture from the system – optimized to result in minimum energy costs for any given building.
The GreenBus II
TM
wiring originates at an Energy Control Unit (ECU) and propagates in a daisy-chain or
“T” fashion from module to module (or other compatible equipment).
GreenBus II GreenBus II
TM
uses proprietary connectors and jacks for ease of installation only.
TM
is a proprietary standard. Connect to ENCELIUM Energy Management System
only. Do not connect to other circuits.
Black – Line in W
Earth Ground
hite – Neutral
Red – Relay output & Dim Control (connect to load)
Relay Contact; recommended relay switching capacity 120VAC, 450W or 277VAC, 900W maximum
GreenBus II TM Communication (Communication Circuit, Low Voltage)
Connect to ENCELIUM Energy Management System only. Do not connect to other circuits.
Maximum 100 total devices
GreenBus II
TM
must be laid out as per ENCELIUM EMS supplied drawing. If changes are required, determine an optimum wiring path utilizing the supplied prefabricated cables, based on the position of light fixtures and sensors. As the modules obtain power via the GreenBus IITM, the number of modules on each chain is limited. It is suggested to leave room for future system upgrades and to limit the number of modules per chain to 100 units during initial installation.
In a typical installation, Phase Cut Dimming Modules connect to Incandescent/Halogen lamps, Fluorescent ballasts, LED fixtures, and LED/CF lamps that are capable of being dimmed via phase cut method (forward and reverse phase).
The Phase Cut Dimming Module is typically connected to an individual or group of fixtures/lamps.
The mechanical construction allows for simple installation of the Phase Cut Dimming Module on top of a standard square 4 11/16” junction box. Only a 4 11/16” junction box can be used, as the mounting holes on the Phase Cut Dimming Module properly align with the holes on the junction box. ENCELIUM GreenBus II™ communication wiring is still accessible from the outside of the junction box, while all necessary wiring to the load (single or multiple ballasts/ LED fixtures) is done on the inside.
Wire as shown. Refer to local code, etc.
Refer to local code, etc.
Refer to local code, etc.Refer to local code, etc.
Absolute maximum load ratings
120VAC: 450W, 3.8A max 277VAC: 900W, 3.3A max
Due to the internal relay, power feed to module may be live even if lights are off. Turn off power at circuit breaker or fuse before installing or servicing module. Observe lockout procedures.
ENCELIUM and Polaris 3D are registered trademarks of OSRAM SYLVANIA, Inc GreenBus II are trademarks of OSRAM SYLVANIA, Inc. SEE THE WORLD IN A NEW LIGHT is a registered trademark of OSRAM SYLVANIA, Inc.
Loading...