OSRAM QT-FQ Technical Information

QUICKTRONIC FLAT
QT-FQ 1x80/230-240 F / CW QT-FQ 2x80/230-240 F / CW
Technical information
edition: January 2003
subject to change without any notes
21mm height
Lamp start with optimised filament preheat within 1 sec.
Suitable for applications in which lamps are switched on and off frequently
Cut-off technology
Automatic shutdown of lamps in the event of a defect and at the end of their life
Automatic restart after lamp replacement
Combi-Wiring (CW) terminals for manual or automatic wiring
Suitable for luminaires with protection class I and II
Suitable for emergency installations acc. to VDE 0108
Technical data:
reference
QT-FQ 1x80/230-240 F / CW * QT-FQ 2x80/230-240 F / CW
Lamps 1xFQ 80W / 1x DL 80W 2xFQ 80W / 2xDL 80W Lamp wattage [W] 1x80 / 1x80 2x80/ 2x80 System wattage [W] 87.5 / 87.5 171 / 170 Line current [A]: 0.38 / 0.38 0.75 / 0.75 Luminous flux at 25°C [lm] 6150 / 6150 6150 / 6150 Luminous flux at 35°C [lm] 7000 / 7000 7000 / 7000 Wire preparation CW terminals: [mm]
8.5 ... 9.5
Ignition time t < 1sec. Line voltage [V] 230 ... 240 V Voltage range (AC) 198 V … 264 V Voltage range (DC) 198 V – 264 V Line frequency [Hz] 50 … 60 Hz
Operating frequency: [kHz] ap. 45-50 kHz Inrush current Radio interference suppression:
I
= 27A TH = 170µs IP = 39A TH = 260µs
P
acc. to EN 55015
Harmonic content: acc. to EN 61000-3-2 Immunity: acc. to EN 61547 Power factor
λ = 0.97 λ = 0.97 Temperature range ta: -20°C … +50°C Case temperature tc: max. +70°C max. +75°C Design (l x w x h) 360 x 30 x 21 mm 423 x 30 x 21 mm Distance between mounting holes:
350 mm 415 mm
Weight: 330 g 400g Approval marks:
Loading...