LS/PD MULTI 3
Light and motion sensor
Fitting instructions
Description
Installation
A B C
E
Function and application
The LS/PD MULTI 3 sensor detects the presence of people and
measures the intensity of ambient light.
The sensor is installed in lamps.
Construction
The sensor is made up of the following components:
• Light sensor (A)
• Motion sensor (B)
• LED (C)
• Connection (D) for supply voltage, light measurement value,
motion signal and signal ground
• Housing (E)
D
Safety instructions
The sensor must only be installed and put into operation by a
qualied electrician. The applicable safety regulations and ac-
cident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the sensor when it is de-energized.
DALI MULTI 3
Sensor
CAUTION!
Destruction of the sensor and other devices through
incorrect mounting!
• Only use OSRAM control units of the following
types: DALI MULTI 3/ DIM MULTI 3, DALI
MULTIeco/ MULTIeco, DALI PROFESSIONAL
Sensor Coupler.
• Do not connect control line with external voltage.
• Note the maximum total line length.
• Do not route the sensor line together with the
power or lamp line.
Connecting the sensor
Connect the sensor using the supplied cable or a commercially
F
available 4-pin cable. If the cable is shortened or lengthened,
ensure that the wiring is correct.
Sensors can be connected in parallel via a Y-branch. For the
maximum number of sensors: see the separate control unit
G
manual.
F Y-branch (optional)
G Sensor
II 2009
LSPD_Multi3_ma0902en_we1.01.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40503008021384
4050300802138
Continued on the back page!

Fitting (cont.)
Selecting the installation location
H Surveillance cone: entire workplace; not on window surfaces
I Avoid exposure to direct light
80°
H
I
K
> h
L
80°
h
K Avoid drafts (e.g. from ventilators or fans)
L Installation distance = min. installation height
Appendix
5 mm
20 mm
55 mm
35 mm
45mm
21mm
15 mm
Technical data
Combined control and
supply connection
24,5 mm
Maximum total length
of signal line (incl. all
connections to the
control units)
Insulation Basic insulation as per IEC 664
Dimensions
(L x W x H)
Light sensor detection
area
Motion detection area Conical, opening angle approx. 80°
Installation height 2 - 4 m
21 mm
4-pin modular connection (4p4c)
1: Supply voltage
2: Light measurement value
3: Motion signal
4: Signal ground
Length 2.1 m
See control unit
55 x 21 x 24.5 mm
20 - 600 lx (measured at sensor),
opening angle approx. 90°
The CE requirements to EN 60928 are fullled.
The EMC requirements to EN 61547 are fullled.
Conformity with the relevant EU directives is
conrmed by the CE symbol.