Motion detector Fitting instructions
VI 2009 HIGH-BAY_ma0906en_we1.01.indd
HIGH BAY
DE
BA
C
Description
Purpose and application
The HIGH BAY motion detector detects the movements of people and vehicles, such as fork lifts.
The sensor is attached to ceilings and is ideal for mounting at great heights and for wide detection areas. The unit is mounted directly in a dry lining box or using the „Mounting Adapter“, optionally available from OSRAM, to ensure that the installation conforms to the CE guidelines.
The HIGH BAY motion detector can be connected to any control component with a oating input that is designed for permanent contact (switch).
Function
The motion detector detects motion within a detection area of 360° and switches on the connected luminaires when motion is registered. When motion is no longer registered, the luminaires switch off after an adjustable delay period.
Design
The sensor is made up of the following components:
Housing (A)
Connection cable (B):
L: phase (black) – N: neutral conductor (blue) – Floating switch contact (2x white)
• Motion sensor (C)
• Button for setting the delay (D)
• LED (E)
Installation
Safety instructions
The motion detector must only be installed and put into opera­tion by a qualied electrician. The applicable safety regulations
and accident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the motion detector when it is
de-energised.
CAUTION!
Destruction of the motion detector and other devices through incorrect mounting!
• Adhere to the connection diagram.
• Do not exceed the maximum line length.
• Do not route sensor lines together with power
supply or lamp lines.
Page 2 of 4
Installation (cont.)
F
G
H
max. 13 m
max. 10 m
0 m
3 m
6 m
9 m 10 m
12 m 13 m
9 m 6 m 3 m 0 3 m 6 m 9 m
max. Ø 12 m
max. Ø 18 m
Selecting the installation location
F Maximum mounting height
Detection of movement of persons: 10 m
(à detection area Ø 12 m)
Detection of movement of vehicles: 13 m
(à detection area Ø 18 m)
G Place devices that radiate heat outside of the monitoring
cone.
H Avoid drafts (e.g. from ventilators)
Attaching the motion detector to the ceiling
Note: The mounting adapter, available as an accessory, can be used for attachment. Follow the separate tting instructions.
Unlock and remove the plastic cover by turning it anticlock-
wise.
Screw on the motion detector, using the mounting adapter
as an aid, if necessary.
Connect the sensor; see the connection diagram.
Adjust the delay, if necessary; see the separate operating
instructions.
Replace the plastic cover and lock it by turning it clockwise.