Osram ENCELIUM EXTEND Manager Installation Manual

Page 1
ENCELIUM® EXTEND Manager
Wiring and installation manual
www.osram.us/extend
Light is OSRAM
Page 2
Overview
The ENCELIUM® EXTEND Manager is a gateway that interfaces to both IT equipment (servers, LAN, etc) and field bus devices (luminaire controllers, sensors, wall switches, etc). Communication with IT equipment and other Managers is achieved using the Ethernet port. Additionally, two USB 2.0 ports are provided for data transfer and back-up purposes.
The Manager provides operating power together with communication signals via GreenBus II® to the various field bus devices of the system via eight GreenBus II communication channels.
The Manager makes each device addressable via GreenBus II (e.g. each light fixture can be individually dimmed and turned on/off). Devices will obtain their addresses during the commissioning process and no actions are required during installation.
The following model is available:
Indoor Location Part Number
EN-ECU-G4-P3D
2
Important Safeguards
When using electrical equipment, basic safety precautions should always be followed, including the following:
— READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
— Do not let power supply cords touch hot surfaces.
— Do not mount near gas or electric heaters.
— Equipment should be mounted in locations and at heights where it will not
readily be subjected to tampering by unauthorized personnel.
— The use of accessory equipment is not recommended by OSRAM SYLVANIA
as it may cause an unsafe condition.
— Do not use this equipment for other than the intended use.
SAVE THESE INSTRUCTIONS
Page 3
3
GreenBus II must be laid out as per ENCELIUM EXTEND LMS supplied drawing. If changes are required, determine an optimum wiring path utilizing the supplied prefabricated cables, based on the position of light fixtures and sensors. As the modules obtain power via the GreenBus II, the number of modules on each chain is limited. It is suggested to leave room for future system upgrades and to limit the number of modules per chain to 100 units during initial installation.
GreenBus II Wiring
Communication Circuit (24Vdc, Class 2)
GreenBus II® is a low-cost, high reliability communication means to report sensor information back to the ENCELIUM® EXTEND Networked Light Management System (LMS) and to obtain optimum brightness settings for light fixtures from the system – optimized to result in minimum energy costs for any given building.
The GreenBus II wiring originates at an ENCELIUM EXTEND Manager and propagates in a daisy-chain or “T” fashion from module to module (or other compatible equipment).
GreenBus II uses proprietary connectors and jacks for ease of installation only. GreenBus II is a proprietary standard. Connect to ENCELIUM EXTEND Networked Light Management System only. Do not connect to other circuits.
Connect to ENCELIUM EXTEND Networked Light Management System only. Do not connect to other circuits.
Maximum 100 total devices
Manager Installation
The output channels of the Manager are Class 2 circuits.
To reduce the risk of electric shock, the power supply for the equipment has a grounding type plug that has a third (grounding) pin. This plug will only fit into a grounding type outlet. If the plug does not fit into the outlet, contact a qualified electrician to install the proper outlet. Do not change the plug in any way.
Use only the power supply provided for this equipment. Damage or adverse functionality may occur if a different power supply is used. If a replacement power supply is needed, please contact OSRAM SYLVANIA Inc. Do not modify the power supply cable or connector.
The Manager is intended for mounting in an electrical room where access will be by authorized personnel only.
Page 4
Installation Notes
The Manager shall be installed in dry, indoor locations ONLY. The Manager shall be installed into a Pollution Degree 2 (or better) environment.
The Manager may be installed into a standard 19” rack or mounted to a wall. A bracket is provided for rack installations. Using the screws provided, affix the bracket securely to the Manager as shown.
If the Manager is to be installed onto a wall surface, use suitable screws to securely hold the unit. Install the unit with the input power, LAN, and GreenBus II® connections facing down. The control buttons shall be facing upward. This orientation will ensure adequate cooling for the product while installed against a wall surface.
Troubleshooting
There are no user-serviceable parts inside of the Area Lighting Controller. Please return the device to OSRAM SYLVANIA Inc. if service is required.
ENCELIUM EXTEND Manager Wiring
4
CH 1CH 2
CH 3
CH 4CH 5CH 6CH 7CH 8
No user serviceable parts inside. Contact OSRAM for service. Do Not Disconnect From Power
24V DC
Input
USB
2.0
Ethernet
10/100BaseTx
24V DC Output GreenBus II Class 2
1
6
5
4
3
2
7 8
ConfirmF7F6F5100% 25% 0%
Cycle
Mode
InstallationBackup
to USB
Restore
from USB
Confirm
F7
F6
F5
100% 25% 0%
Cycle
Mode
Installation
Backup
to USB
Restore
from USB
1
6
5
4
3
2
7
8
Page 5
© 2018 OSRAM SYLVANIA Inc.
LM S15 8 4 -18
OSRAM is a registered trademark of OSRA M GmbH. ENCELIUM EXTEND and Gree nBus II are registered trademar ks of OSRAM SY LVANIA In c. Specifications are subject to change without noti ce.
Regulatory Approval
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Modifications not expressly approved by the manufacturer could void the user’s authority to operate the equipment under FCC rules.
This equipment has been tested and found to comply with Industry Canada ICES-003 Issue 5 (CAN ICES-3 (A)/NMB-3(A)).
Software End User License Agreement
This product includes third party software under license. See www.encelium.com/ licensing. All other software incorporated in or distributed with the product is owned by and proprietary to OSRAM SYLVANIA Inc and licensed pursuant to the terms of the OSRAM SYLVANIA end user license agreement.
The contents of this Wiring and Installation Manual are subject to change without notice.
OSRAM SYLVANIA Inc.
200 Ballardvale Street
Wilmington, MA 01887 USA
888-531-7573
www.osram.us/ds