Page 1
DUO
DUO
N
0V
L
6 mm
0,34 - 1,5mm
2
B
Presence sensor
(light and motion sensor)
Fitting instructions
Description
5
E
1
5
D
1
DUO
Purpose and application
The DUO sensor detects the presence of persons and measures the intensity of ambient light.
The sensor is designed for installation on ceilings or in luminaires using a T5/T8 holding clip and is ideal for the expansion
of existing electrical installations.
The following application types are available, depending on how
the sensor is connected (see the connection diagram):
• Alternative 1: One sensor switches a load area by means of
light and/or motion detection.
• Alternative 2: One sensor switches a load area by means
of light and/or motion detection. Additional motion detection
sensors are used to expand the detection area (slave mode).
Function
The sensor operates fully automatically and the values detected
by the sensor (motion, light value) control the switching
behaviour on the basis of the parameters set by the user. The
measured light value depends on the incidence of daylight, the
articial lighting and the properties of the surface (light/dark).
The following parameters can be set:
• Switch-off delay time (if no motion is detected)
• Light value
• Function mode
Design
A
4
32
F
B
1
ON
C
The sensor is made up of the following components:
Upper section of housing:
• Motion sensor (A)
• LED (B)
• Light sensor (C)
• Adjusting screws:
– Setpoint for brightness (D)
– Switch-off delay time (E)
• DIP switch on the back (F)
IX 2009
DUO_ma0909en_we1.01.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083214963550
4008321496355
G
Lower section of housing:
• Connections (G):
B
N
0V
B
DUO
2
N
L
0V
6 mm
0,34 - 1,5mm
L
– L, N: Supply lines
– Switch contact
– Parallel circuit for joint motion detection
G
Page 1 of 4
Page 2
Installation
2,4 m
H
3,7 m 2,7 2,1 1,5 0,9 0 0,9 1,5 2,1 2,7 3,7 m
Safety instructions
The sensor must only be installed and put into operation by
a qualied electrician. The applicable safety regulations and
accident prevention regulations must be observed.
WARNING!
Exposed, live cables.
Danger of electric shock!
• Only work on the sensor when it is de-
energised.
CAUTION!
Destruction of the sensor and other devices through
incorrect mounting!
• Adhere to the connection diagram.
• Protect the sensor and switch contact jointly or
individually via external circuit breakers.
• Only operate the sensor when it is closed (the
upper and lower sections of the housing are
rmly connected).
• Supply the sensor via an AC power supply
only.
• When mounting in luminaires, use a UV-
resistant cable.
Selecting the installation location
H Optimal mounting height: 2.5 – 3 m. As the mounting height
increases, the detection area increases and sensitivity is
reduced.
J Monitoring cone: Entire workplace; not on window surfaces
K Avoid exposure to direct light.
L Place devices that radiate heat outside of the monitoring
cone.
M Avoid drafts (e.g. from ventilators)
100°
100°
J
K
L
M
Page 2 of 4
Page 3
Installation (cont.)
ON
Attaching the sensor to the ceiling
Determine a suitable installation location (see „Selecting the
installation location“).
Screw the lower section of the housing onto the ceiling.
Note: Follow step 5 to correctly align the unit.
Connect the sensor; see „Connection diagram“.
Attach the upper section of the housing to the lower section.
Make sure that the light sensor is facing the room.
Attaching the sensor to the uorescent
lamps
Precondition: T5 or T8 lamps with a min. grid of 60 mm.
Determine a suitable installation location (see „Selecting the
installation location“).
Insert the lamp clip into the lower section of the sensor
housing
Attach the sensor to the lamp end with the lamp clip to avoid
weighing down the lamp excessively. Minimum distance to
the lampholder due to heat development of the coils: 8 cm.
If necessary, adjust the sensor installation depth to the depth
of the grid luminaire by sliding the lamp clip in or out.
N With lamp clip for 26 mm uorescent lamp
O With lamp clip for 16 mm uorescent lamp
Pull the upper section of the housing off of the attached
lower section.
Connect the sensor; see „Connection diagram“.
Reattach the upper section of the housing to the lower
section.
220 - 240 V~ 50/60 Hz
L
N
PE
220 - 240 V~ 50/60 Hz
L
N
PE
F1
6A/10A
L
N
P
DUO
0V
B
L N PE
Q
F1
6A/10A
L
N
P P
DUO
0V
B
S
L
N
F1
6A/10A
DUO
Connection diagram
Alternative 1:
One sensor switches a load area by means of light and/or
motion detection.
P Switch contact
Q Load (ECG, lamps, etc.)
Alternative 2:
One sensor switches a load area by means of light and/or moti on detection. A maximum of 5 additional sensors exclusively for
motion detection are used to expand the detection area.
Precondition: DIP switches (F) 1 and 2 are set to OFF in the
slaves.
R To additional sensors (a total of 6 sensors switched in
R
0V
B
0V
B
S
parallel!).
S Motion signal
T Sensor in slave mode (motion detection only)
U Sensor in master mode
L N PE
Q U T
1 2 3 4
ON
OFF
F
Limiting the motion detection area
The supplied lens cover can be used to limit the detection area
and to adjust it to local conditions.
Page 3 of 4
Page 4
Appendix
Technical data
Operating voltage 220-240 V/50-60 Hz
Fuse External 6 A (10 A)
Power consumption Switched on: Approx. 1 W
Maximum total line
length
Switch output Floating contact (internal relay, make
Switch output load
capacity
Detection area Max. Ø 12 m
Installation height Max. 5 m (ideal: 2.5 - 3 m)
Switching hysteresis Approx. 15%
Operating temperature 0 °C ... +50 °C
Protection class II
Protection type IP 20
Weight Approx. 150 g
Dimensions (L x W x H) 58.5 x 70.5 x 47 mm
(no DC operation)
Switched off: Approx. 0.7 W
100 m
contact)
Resistive load: 10 A/250 V AC,
Ohmic lamp load: 5 A
Inductive load: 5 A
30 x single-lamp ECG 18 W
20 x two-lamp ECG 18 W
30 x single-lamp ECG 36 W
20 x two-lamp ECG 36 W
20 x single-lamp ECG 58 W
10 x two-lamp ECG 58 W
6 A/30 V DC
Dimensioned drawing
Conformity with the relevant EU directives is
conrmed by the CE symbol.
Page 4 of 4