OSRAM DIM MULTIeco User Manual

DIM MULTIeco
A
Control unit Fitting instructions
Description
Purpose and application
The DIM MULTIeco control unit controls the lighting at the work­place and in ofces according to the level of daylight and the presence of persons to increase comfort and save energy.
The control unit can be installed in luminaires (e.g. oor stan­ding luminaires) or in suspended ceilings.
Function
The control unit can be operated in two different operating modes, see also “Setting the operating mode”:
Brightness control
The sensors measure the brightness in the area to be regulated and keep this to an adjustable set value by introducing articial light according to the amount of daylight available.
The sensors also detect the presence of people.
When the level of daylight is sufcient or people are no longer present, the connected luminaires switch off after an adjustable delay period.
Brightness control, presence detection and automatic switch-on can be activated and deactivated using various modes.
Brightness reduction
If persons are present, the luminaires are dimmed to an adju­stable brightness value.
If no persons are present, the brightness drops to a xed stand­by value of 50%, 30% or 10% after an adjustable delay time.
Automatic switch-on and automatic switch-off during periods of prolonged absence can be activated and deactivated using various modes.
VI 2011
DIM_MULTIeco_ma0611en_we1.02.indd
OSRAM GmbH Kunden Service Center Customer-Service-Center (CSC)
Steinerne Furt 62 86167 Augsburg Germany
Tel : +49 (0) 1803 677 - 200 (kostenpichtig / charges apply) Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083215072732
4008321507273
L
G
N
L’
F
1…10 V+
E
1…10 V -
D
Installation
DIM MULTIeco
Design
The control unit is made up of the following components:
Sensor
B
C
• Adjusting screw for switch-off delay time (A)
• Sensor connection (B)
• DIP switch (C)
• Pushbutton connection (D)
• Control line connection (E)
• Load contact (F) optional
• Power supply connection (G)
Safety instructions
The control unit must only be installed and put into operation by a qualied electrician. The applicable safety regulations and accident prevention regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
• Only work on the control unit when it is de­energised.
CAUTION!
Destruction of the control unit and other devices through incorrect mounting!
• Do not operate any other control units on the control line.
• Use the LMS CI BOX mounting kit for ceiling installation.
• Ensure that the external pushbutton is designed for the mains voltage.
• Do not wire the control and pushbutton lines with an external voltage, especially not a mains voltage of 230 V.
• Do not exceed the maximum number of electro­nic control gears.
Page 1 of 2
Installation (cont.)
L
N
PE
J
~ ~
QTi DIM EVG
1…10 V+ 1…10 V -
~ ~
QTi DIM EVG
1…10 V+ 1…10 V -
L N L‘ 1…10V+ 1…10V -
Sensor
DIM MULTIeco
Connecting the control unit
Left: Individual operation with max. 2 sensors
Right: Networked operation with up to 4 DIM MULTIeco control
LN
L N
H
J
N
K
K
O
L N
J
Sensor
DIM MULTIeco
Sensor
DIM MULTIeco
H
L
123 4
M
1
4
2 3
H
units and central presence detection
H Sensor
J Pushbutton
K Lamp
L Y-Connector
M Y-Connector Screw
N To luminaire group 1
O To luminaire group 2
Appendix
Pin
1 2 3 4
Technical data
Operating voltage 100-240 VAC / 50-60 Hz
Supply connection
Control connections
Pushbutton input Potential-free make contact, max. line
Sensor connection Max. 2 sensors, max. line length
Max. load contact load capacity L’
Fuse External 16 A
Power consumption Operation: 1 W
Ambient temperature 0 °C … +50 °C
Adjustable light value 20-600 lux (measured at sensor)
Protection type IP 20
Protection class II
Dimensions (L x W x H)
Hole distance for mounting
(DC operation permissible)
L, N (PE not required)
1…10 V control signal as per EN 60929 Annex E2, a maximum of 10 electronic ballasts can be connected
length 50 m
25 m
Pin assignment: 1: Supply voltage (+ 3.3 V) 2: Light measurement 3: Motion signal 4: Ground
5 A resistive load
Max. number of ECGs: 10 (depends on the ECG type to be connected)
Standby: < 0.5 W
118 x 30 x 21 mm
110 mm
The CE requirements to EN 60928 are fullled. The EMC requi­rements to EN 61547 are fullled.
Conformity with the relevant EU directives is conrmed by the CE symbol.