Orvaldi V1000, V3000 User Manual

UPS ORVALDI
V1000-3000 on line 2U LCD
Uninterruptible Power Supply System
User Manual
1
Table of Contents
1. Important Safety Warning.............................................................................................2
1-1. Transportation.................................................................................................... 2
1-2. Preparation ........................................................................................................2
1-3. Installation.........................................................................................................2
1-4. Operation...........................................................................................................2
1-5. Maintenance, service and faults...........................................................................3
2. Installation and setup...................................................................................................4
2-1. Rear panel view..................................................................................................4
2-2. Rack-Mounted the UPS ....................................................................................... 5
2-3. Setup the UPS.................................................................................................... 5
2-4 Battery replacement ............................................................................................ 7
2-5 Battery kit assembly (option)................................................................................8
3. Operations................................................................................................................. 11
3-1. Button operation .............................................................................................. 11
3-2. LCD Panel ........................................................................................................ 11
3-3. Audible Alarm................................................................................................... 13
3-4. LCD display wordings index............................................................................... 13
3-5. UPS Setting...................................................................................................... 13
3-6. Operating Mode Description .............................................................................. 16
3-7. Faults Reference Code....................................................................................... 17
3-8. Warning indicator ............................................................................................. 17
4. Troubleshooting ......................................................................................................... 18
5. Storage and Maintenance ........................................................................................... 20
6. Specifications............................................................................................................. 21
2
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
1-1. Transportation
Please transport the UPS system only in the original package to protect against shock
and impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them. Do not connect domestic appliances such as hair dryers to UPS output sockets. The UPS can be operated by any individuals with no previous experience.  Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS
system.
When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
3
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when working with batteries:
remove wristwatches, rings and other metal objects
use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries. Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
4
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use. NOTE: There are two different types of online UPS: standard and long-run models. Please refer to the following model table.
Model Type Model Type
1K 1KL
1.5K 1.5KL 2K 2KL 3K
Standard
3KL
Long-run
2-1. Rear panel view
1K(L)/1.5K(L) IEC & 2K(L) IEC(4 batteries inside)
2K (L) IEC (6 batteries inside)
3K(L) IEC 1K(L)/1.5K(L) NEMA
2K(L) NEMA 3K(L) NEMA
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Input circuit breaker
5. Network/Fax/Modem surge protection
5
6. Emergency power off function connector (EPO)
7. USB communication port
8. RS-232 communication port
9. SNMP intelligent slot
10. External battery connection (only available for L model)
11. Input terminal
12. Output circuit breaker
2-2. Rack-Mounted the UPS
This UPS can be mounted in the 19” rack chassis. Please follow below steps to position this UPS.
Step 1 Step 2
2-3. Setup the UPS Step 1: Connect battery wires
For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect battery wires first.
Step 1 Step 2 Step 3
Remove front panel. Connect the AC input and
re-connect battery wires.
Put the front panel back to the unit.
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package.  For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input
plug is a NEMA 5-15P for 1K, 1KL, 1.5K and 1.5KL models, NEMA 5-20P for 2K and 2KL models.
Note:
For Low voltage models
: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting section). Please also install a circuit breaker (40A) between the mains and
6
AC input in 3K model for safety operation.
Step 3: UPS output connection
For socket-type outputs, there two kinds of outputs: programmable outlets and general
outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block b) Suggest using AWG14 or 2.1mm2 power cords. Suggest using AWG12-10 or
3.3mm2-5.3mm2 power cords for NEMA type. c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 4: Communication connection Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
PS. USB port and RS-232 port can’t work at the same time.
Step 5: Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line cable.
Step 6: Disable and enable EPO function
Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1 and pin 2.
It’s in closed status for UPS normal operation.