Ortech OD-5006, OD-5006HS, OD-8011, OD-8011HS User Manual

VENTILATION FAN
WARNING
READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner.
CAUTION
CLEANING & MAINTENANCE
OPERATION
1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switching on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equip­ ment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch circuit (ceiling installation only).
8. This unit must be grounded.
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up. DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dusting brush attachment. The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noi­ses, replace the motor with the exact service motor. The impeller should also be replaced.
Use an on/off switch to operate this fan. See “Connect Wiring” for details. For model OD-5006HS OD-8011HS The humidity control and fan can be operated separately. Use a 1 or 2 function wall control. Do not use a dimmer switch to operate the humidity control or light. See “Connect Wiring” for details.
SENSOR OPERATION
The humidity-sensing fan uses a sophisticated humidity sensor that responds to: (a) rapid to moderate (user-adjustable) increases in humidity or (b) humidity above a user-adjustable set-point (50%-100% relative humidity). The humidity sen­sor may occasionally turn the fan ON when environmental conditions change. If the fan continuously responds to chang­ing environmental conditions, “H” (means “humidity”) adjustment may be required. This figure is factory-set for about 75% (Ambient temperature of 25).
SENSITIVITY ADJUSTMENT
The “H” has been factory set for most shower applications. However, if the fan is in a tub area or is being used for damp­ness control, the “H” may need to be increased toward maximum “+”. If the control is responding too often to changing environmental conditions, movement toward less “-” “H” may be required. To adjust the “H”:
1. Disconnect power at service entrance.
2. Through the grille, locate the slot marked “H”.
3. Carefully rotate the “H” adjustment toward “+” or “-”.
OD-5006 OD-5006HS
OD-8011 OD-8011HS
OPERATION
PLAN THE INSTALLATION
TYPES OF TYPICAL INSTALLATIONS
1. Do not use in a cooking area.
2. Two ways to connect ductwork to a factory-shipped unit.
ASSEMBLY INSTRUCTIONS
1. Housing mounted to I-joists (Start at “ASSEMBLY INSTRUCTIONS 1”)
2. Housing mounted to joists (Start at “ASSEMBLY INSTRUCTIONS 1” )
3. Housing mounted to truss (Start at step “ASSEMBLY INSTRUCTIONS 2”)
2
1.MOUNT HOUSING TO JOIST OR I-JOIST. Hold the housing so that it is in contact with the bottom of the joist. Place the fan housing next to the ceiling joist. Using wood screws attach the housing loosely to the ceiling joist through the keyholes in the mounting tabs. Adjust the housing to be flush with th finished ceiling. For the grille to fit properly, the housing’s rim must not extend beyond the finished ceiling surface. When the housing is correctly adjusted, tighten the screws in the slots.
4. Turn on power and check operation by turning on the shower or other humidity source until the fan turns on.
5. Repeat above steps if necessary. When the temperature changes, humidity sensor values will have deviation.
TIMER ADJUSTMENT
The humidity sensing fan has a “T” (means timer) that can be adjusted from 5 to 60 minutes (factory-set at about 20 min­utes). This “T” controls the length of time that the fan remains ON after the sensor has stopped sensing a rise in humidity
and the humidity level is below the user-adjustable set-point. To adjust the “T”:
1. Disconnect power at service entrance;
2. Through the grille, locate the slot marked “T”;
3. Carefully rotate the “T” adjustment to desired setting (from 5 to 60 minutes).
4. Check operation by turning on a humidity source until the fan turns on.
5. Turn humidity source off and time the unit.
6. Repeat above steps if necessary.
ROOF CAP* (with built-in
damper)
ROUND
DUCT*
WALL CAP* (with built-in damper)
* Purchase
separately
POWER CABLE*
INSULATION*
(Place around and
over Fan Housing.)
Seal gaps
around
Housing.
FAN
HOUSING
ROUND
ELBOW(S) *
Seal duct joints with
tape.
Keep duct runs short
UNIT
BLACK (BLK)
SENSOR SWITCH
SWITCH BOX
POWER SUPPLY
120V AC
GROUND (GRD)
BROWN (BRN)
WHITE (WHT)
FAN
RECEPTACLE
SENSOR
RECEPTACLE
FAN SWITCH
FAN
Run 120 V AC house wiring to the location of the fan. Use only UL-approved connectors (not included) to attach the house wiring to the wiring plate. Refer to the wiring diagram, and connect the wires as shown.
ASSEMBLY INSTRUCTIONS
CONNECT ELECTRICAL WIRING
3
2. MOUNT WITH HANGER BARS Insret the hanger bars into the slots in the housing. Place the fan housing between the joists, make sure the bottom of the housing is even with the finished ceiling. Extend the hanger hars to the joist. Use screws to secure the hanger bars to the ceiling joists.
DUCT
3. ATTACH DAMPER/DUCT CONNECTOR Snap the damper/duct connector onto the fan housing. The connector must be flush with the top of the housing, and the damper flap should fall closed.
4. INSTALL ROUND DUCTWOTK Connect the round ductwork (not included) to the damper/duct connector, and run the ductwork to a roof or wall cap (not included). Using tape (not included), secure all the ductwork connections so that they are air tight.
D
For OD-5006HS OD-8011HS
For OD-5006 OD-8011
UNIT
BLACK (BLK)
SWITCH BOX
FAN SWITCH
POWER SUPPLY
120V AC
GROUND (GRD)
WHITE (WHT)
WIRE
PANEL
WIRE
PANEL
FAN
RECEPTACLE
FAN
Loading...
+ 5 hidden pages