Ormazabal PF201, PF301, PF202, PF 302, PF203 General Instructions Manual

...
IG-021-GB
version 07
General Instructions
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
PF
29.08.2008
Transformer Substations
Secondary Distribution
Switchgear
Primary Distribution
Switchgear
Protection and
Automation
Low Voltage
Boards
Distribution
Transformers
Legal Deposit: BI-2359/08
ATTENTION!
When MV equipment is operating, certain components are live, other parts may be in movement, and some may reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on the following criteria:
Elimination of hazards wherever possible.
Where elimination of hazards is not technically or economically feasible, appropriate protection functions are
incorporated in the equipment.
Provision of information on residual risks to facilitate the design of operating procedures which prevent such
risks, training for the personnel in charge of the equipment, and the use of suitable measures for personal protection.
Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their useful lives is reached, they are duly processed in accordance, as far as possible, with the environmental restrictions established by the competent authorities.
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of the forthcoming IEC standard 62271-1. It must only be operated by qualified and supervised personnel, in accordance with the requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on activities in or near electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the situation according to current legislation.
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
The equipment must be handled and transported appropriately from the factory to the place of installation.
All intermediate storage should occur in conditions which do not alter or damage the characteristics of the
equipment or its essential components.
Service conditions must be compatible with the equipment rating.
The equipment must be operated strictly in accordance with the instructions given in the manual, and the
applicable operating and safety principles must be clearly understood.
Maintenance should be performed properly, taking into account the actual service and environmental conditions in the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Guarantee
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual belongs to the manufacturer.
In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject to change without prior notification.
These characteristics, as well as the availability of components, are subject to confirmation by Ormazabal’s Technical - Commercial Department.
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
CONTENTS
1. DESCRIPTION AND MAIN CHARACTERISTICS ........................................................ 4
2. TRANSPORT................................................................................................................. 5
2.1. ACCESS ...................................................................................................................... 5
2.2. TRANSPORT............................................................................................................... 5
3. INSTALLATION............................................................................................................. 8
3.1. LOCATION .................................................................................................................. 8
3.2. PLANNING .................................................................................................................. 8
3.3. PREPARING THE GROUND....................................................................................... 9
3.3.1. Excavation Dimensions........................................................................................ 9
3.3.2. Types of Ground .................................................................................................. 9
3.4. LEVELLING PROCESS ............................................................................................ 10
3.4.1. Levelling Tools ................................................................................................... 10
3.5. HANDLING PANELS AND CONCRETE COMPONENTS........................................ 13
3.5.1. PF-200 / 300 & PF-2015 / 3015 SERIES CONCRETE COMPONENTS ........... 14
3.6. ASSEMBLING TOOLS.............................................................................................. 15
3.7. PF ENCLOSURE ASSEMBLY PROCESS ............................................................... 15
3.7.1. Assembling Bottom Plates ................................................................................. 17
3.7.2. Assembling the Vertical Panels.......................................................................... 20
3.7.3. Remaining Vertical Panels................................................................................. 26
3.7.4. Floor Plates, Slabs and Transformer Platform ................................................... 30
3.7.5. Cubicles and Transformer.................................................................................. 34
3.7.6. Low Voltage Board............................................................................................. 34
3.7.7. Transformer Protection Fences.......................................................................... 35
3.7.8. Covers................................................................................................................ 35
3.7.9. Ventilation grilles................................................................................................ 37
3.7.10. Doors.................................................................................................................. 38
3.7.11. Low Voltage Auxiliary Feeder ............................................................................ 39
3.8. CONNECTING THE EARTH CIRCUIT...................................................................... 40
3.8.1. Panel Reinforcing Mesh..................................................................................... 40
3.8.2. Earthing Circuit................................................................................................... 42
3.8.3. Earthing Ring ..................................................................................................... 43
4. MAINTENANCE .......................................................................................................... 44
4.1. REMOVING THE SIDE COVERS.............................................................................. 44
4.2. REMOVING THE CENTRAL COVERS ..................................................................... 44
4848
Page 3 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
1. DESCRIPTION AND MAIN CHARACTERISTICS
Ormazabal’s PF Modular Enclosures for walk-in type outdoor Transformer Substations are designed according to standard EN 61330 for use in electrical power distribution networks up to 36 kV.
PF consists of prefabricated concrete panels that can be combined in various configurations.
Depending on their configuration, these enclosures comprise some of the following elements:
Front, back and side concrete modular panels.
Covers (roof panels).
Transformer platforms.
Bottom plates.
IG-021-GB
version 07
29.08.2008
Supplementary floor plates.
Hinged personnel access door, folding 180º over the outside wall, with a two-fixing-
point lock and a fastening rod to hold it open.
Hinged transformer door, folding 180º over the outside wall, and with a ventilation
grille in its lower section. An interlocking lock may be fitted.
Ventilation grilles: for transformer powers under or equal to 630 kVA, an air exhaust
grille is fitted in the rear upper part of the enclosure and an air intake grille is fitted in the lower part of the transformer door. For transformer powers of 1000 kVA, 4 extra grilles are incorporated in the sides.
Moulded holes for LV and MV cable input/output. Some of these holes can be used
for the output of the earthing circuit cables.
Oil collection pit with a fire-extinguisher device.
Document holder for documentation relating to the Transformer Substation.
Page 4 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
2. TRANSPORT
2.1. ACCESS
The site must be visited in advance to check if vehicles (tow-truck or separate truck and crane) can have access and if there is sufficient space for the PF unloading and assembly operations, taking into account the distances to overhead lines, slopes, etc.
2.2. TRANSPORT
The panels are transported in trucks, taking the appropriate precautions to avoid breakage caused by differential settlements.
The elements required to assemble the PF Transformer Substation are grouped into two classes, according to how they are transported:
a) Horizontally-transported components
Transformer platforms, PF-200/300 series bottom plates and supplementary floor plates are transported lying flat on the truck bed, separating them with wooden battens to avoid damage to the edges.
Apart from these components, other miscellaneous material such as floor slabs, grilles, doors, etc., are transported on wooden pallets on the truck bed.
They are tied down using slings suitable for the load.
Figure 2.1: Fixing slings
Figure 2.2: Fixing slings
4848
Page 5 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
b) Vertically-transported components
Front and side panels
[1]
, PF-2015 / 3015 series bottom plates and the remaining floor plates are transported on trestle (reference 160026), as shown in figure 2.3. On occasions, floor plates can be transported horizontally.
The load is tied down on the truck using slings or cables that are tensed using the truck’s reels. In turn, the concrete components have rubber and/or metal protection parts, as shown in figure 2.4, to avoid any damage as the straps are tightened.
Figure 2.3: Trestle160026
Figure 2.4: Protection parts Figure 2.5: Vertically-transported components
IMPORTANT:
Before unloading, check the orientation of the loaded components. This will make unloading and assembly easier.
IG-021-GB
version 07
29.08.2008
[1]
If the front and rear panels are transported vertically, instead of horizontally, they can be moved directly from
the truck to their final positions.
Page 6 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Figure 2.6: 2360 mm wide panel placed vertically
Figure 2.7: 3540 mm wide panel placed vertically
Figure 2.8: Panels supported by a trestle
Side panels must be rested on the ground in order to insert the rubber strip required for sealing the enclosures
[2]
.
[2]
See section 3.7. PF Enclosure Assembly Process.
4848
Page 7 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Preferably, the truck used to transport the components should have a bed height no more than 900 mm; there are two possible cases:
200/2015 Series panels
The maximum height of these panels when transported vertically is 3000 mm, enabling them to be transported on low loaders up to 900 mm high without requiring a special permit.
When this is not possible, a special transport permit should be obtained. In this case, the truck bed height should be no more than 1400 mm, in order not to exceed the maximum permitted height of 4500 mm.
300/3015 Series panels
[3]
The maximum height of these panels when transported vertically is 3,400 mm, as a result of which they exceed 4000 mm in height both when carried on 900 mm high low loaders and in other types of truck. Therefore, a special permit is required to transport them, and the maximum permitted height of 4500 mm must never be exceeded.
3. INSTALLATION
IG-021-GB
version 07
29.08.2008
Assembly and installation of PF TS must only be carried out by qualified personnel with sufficient experience and training. All safety rules for unloading and handling elevated loads must be observed. Operators must use the obligatory personal protection equipment, helmets and protective footwear.
3.1. LOCATION
The site location should be defined exactly, indicating the levels of alignment and height to reference points, such as: roads, kerbs, milestones, pavilions, fences, electricity pylons, etc.
It is recommended, although it is not essential, to get a drawing or sketch with the customer’s letter head and stamp and/or signature, indicating these distances.
3.2. PLANNING
On the location sketch or drawing (or on another one), mark out the spaces available for the crane and the transport truck.
In addition, indicate the existence of any circumstance or object that could impede or obstruct the smooth operation of the installation (posts, cables, ditches, walls, pipelines, etc.), marking their positions on the drawing with the corresponding measurements.
[3]
The maximum height limit for vehicles, including the load, is specified in the Spanish Royal Decree 2822/1998
dated the 23rd December, which approved the General Vehicle Regulations (Article 14, Annex IX).
Page 8 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Confirm that the crane is sufficiently powerful to unload the components comprising the transformer substation (the maximum weight of any individual part is about 2500 kg) and that it can move them the distances required to install the transformer substation.
3.3. PREPARING THE GROUND
3.3.1. Excavation Dimensions
The excavation dimensions depend on the enclosure model:
MODEL LENGTH (L) [mm] WIDTH [mm] DEPTH [mm]
PF201 / PF301 PF202 / PF302 PF203 / PF303 PF204 / PF304
PF205 / PF305 PF2015 / PF3015 PF2030 / PF3030
PF3035
3420 3420 650 5680 3420 650
8040 3420 650 10400 3420 650 12760 3420 650
4500 3420 650
8040 3420 650
9220 3420 650
L
NOTE: For other configurations, the distance L must be increased by 2360 mm for each
additional 200/300 series panel, and by 3540 mm for each additional 2015/3015 series panel. Consult Ormazabal’s Technical - Commercial Department.
3.3.2. Types of Ground
The type of ground on which the PF Modular Transformer Substation will rest is an essential factor, given the weight of the equipment. The ground could subside or become uneven, or could provide differential settlements, causing cracks in the enclosure.
There are two types of ground:
A) Hard Grounds: Grounds where the soil is settled and properly compacted by natural
causes, with a strength of at least 1 kg/cm
2
.
When the excavation is finished, a sand layer of approximately 100 mm should be laid down and compacted until a person can walk on it without leaving footprints (only a surface mark).
Once the levelling boards
[4]
have been removed, the gaps they leave should be filled with sand. Take the measures appropriate to each case to prevent the filling sand from eroding.
[4]
See section 3.4. Levelling process
4848
Page 9 of 48
IG-021-GB
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
29.08.2008
B) Soft Grounds: These are sandy areas, landfills, etc., with a strength of less than
0.9 – 1 kg/cm
2
.
In these cases, foundations suitable for the ground conditions must be prepared, and this may imply the construction of a reinforced concrete bed to distribute the load over a wider surface
[5]
.
Thereafter, it should be levelled using sand, as in the previous case.
3.4. LEVELLING PROCESS
This is a fundamental operation which has a decisive influence in both the assembly and the stability of the PF Modular Transformer Substation.
3.4.1. Levelling Tools
1 Spirit Level
1 Pickaxe
1 Round-end spade
1 Square-end spade
1 Wooden or Plastic lump hammer
1 Levelling board set (reference 3947251-10)
A) Normal Conditions
The levelling boards are placed according to the measurements on the drawing below (the level of 3100 mm is a minimum value).
0 Level
A B
150
Figure 3.1: Levelling Specifications
Once the levelling rods have been positioned, the levelling boards should be used to check that the ground is in perfect condition.
3100
20
Dimensions in millimeters
Levelling board
550
80
version 07
[5]
Consult Ormazabal’s Technical-Commercial Department.
Page 10 of 48
IG-021-GB
version 07
29.08.2008
B) Sloping Grounds
The excavation should be prepared in such a way that the base platform is on a hard area.
In these cases, it is essential that rainwater from the higher ground be channelled, to avoid it washing the ground away from under the enclosure.
If there are any doubts concerning this subsequent channelling, it is best to use a mixture of sand and cement when levelling the ground.
Example:
650
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Dimensions in millimeters
0 Level
Landfill or vegetal matter
Hard ground
100
100
Minimum level
4848
Figure 3.2: Sloping Grounds
Page 11 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
C) Ground with a High Water Table
When there is a high water table, proceed as follows:
1) Establish the water table level.
2) Excavate no deeper than necessary, then level the ground as in sections A) and
B), above.
Example:
Water table
Figure 3.3: Ground with a High Water Table
IG-021-GB
version 07
29.08.2008
Dimensions in millimeters
0 Level
350
550
100
Page 12 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
D) Grounds at Risk of Flooding
In these cases, the enclosure bottom plate should be raised to 100 mm above the predicted flood level, and then level the foundations as in section A).
Example:
Dimensions in millimeters
45º
100 200
300
X
Figure 3.4: Grounds at Risk of Flooding
The landfill should be such that the distance X is at least 400 mm and the slope angle is 45°.
A one-meter wide pavement around the enclosure is recommended.
Since these cases are found near rivers, the landfill must be firmly retained (with concrete, rockfill, etc) to provide stability to the prefabricated enclosure.
3.5. HANDLING PANELS AND CONCRETE COMPONENTS
Predicted Flood Level
Landfill height
0 Level
Handling the concrete components correctly requires the following tools:
Lifting beam (reference 160023, “PF 4 T Unloading Beam”)
Sling set (reference 160024, “PF Unloading Slings”)
Turning Eyebolts RD20 (reference160027)
4848
Page 13 of 48
GENERAL INSTRUCTIONS FOR PF
d
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
PF 4 T Unloading Beam
PF Unloading Slings
ref 160024
Turning Eyebolts RD20
Figure 3.5: Panel handling tools
To lift the components as evenly as possible, the lifting beam should be used to handle all the concrete components.
The chains' angle of pull should be as vertical as possible (at least 60º from horizontal).
Figure 3.6: Angle from the horizontal > 60º
3.5.1. PF-200 / 300 & PF-2015 / 3015 SERIES CONCRETE COMPONENTS
ref. 160023
ref 160027
IG-021-GB
version 07
29.08.2008
PF enclosure concrete components have RD20 threaded inserts embedded in the concrete; therefore, the components can be lifted and handled with a crane by anchoring RD20 threaded turning eyebolts.
Figure 3.7: 200 series side panel transported horizontally an handled with threaded eyebolts
Figure 3.8: 200 series front panel transported vertically and handled with threaded eyebolts
Page 14 of 48
IG-021-GB
version 07
29.08.2008
Figure 3.9: Anchoring with threaded turning eyebolts
3.6. ASSEMBLING TOOLS
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Proper assembly of the PF Modular Transformer Substations requires the following elements to be available:
PF Assembling Prop (reference 160028)
The number of required props depends on the number of modules forming the enclosure. PF-203 requires 3 props; PF-304 requires 4 props; PF-305 requires 5 props, etc.; therefore, the number of required props equals the number of modules making up the enclosure.
1 ratchet wrench set
1 low-profile ratchet wrench (reference 394253-31, ‘PF Assembling Ratchet’)
2 ladders
1 brush
1 set of spanners and screwdrivers
Painting utensils, for painting the transformer substation or for retouching painted
panels.
For correct assembly of the panels, the enclosure foundations must be levelled with the greatest care according to the instructions in section 3.4.
3.7. PF ENCLOSURE ASSEMBLY PROCESS
By way of example, the assembly process for a PF-205 enclosure with 2 transformers and 1 personnel access door is explained below.
The panels used to assemble the PF Modular Transformer Substations are grouped into two classes, according to how they are assembled:
a) Horizontally-assembled panels: These are the bottom plates, floor plates and
covers.
b) Vertically-assembled panels: These are the front, back and side panels.
4848
Page 15 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Before handling the panels, their assembling position, as well as the way they are transported in the truck, must be considered. Taking this into account, the following cases can be found:
a) Horizontally-assembled panels
These panels are transported on a trestle (although in exceptional cases bottom and floor plates may also be transported lying flat on the truck bed), and they have two inserts in the long edge where a crane can be attached to lift them off the truck and lay them flat on the ground.
Once on the ground, or on the truck bed itself if they are transported flat, they should be lifted using the 4 inserts in the panel and placed in their final positions.
Figure 3.10 Figure 3.11 Figure 3.12
b) Vertically-assembled panels
These panels are transported on a trestle, and they have 2 inserts in the long edge and 2 in the short edge for their handling.
If they are transported horizontally (figure 3.13), they must be lifted by the long
edge and laid onto the ground (figure 3.14) in order to transfer the hooks to the short edge and lift the panel to the vertical position as required for its final position (figure 3.15).
Figure 3.13 Figure 3.14 Figure 3.15
IG-021-GB
version 07
29.08.2008
Page 16 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
If they are transported vertically (figure 3.16), they should be lifted by the short side
and placed directly in their final position (figure 3.17).
Figure 3.16 Figure 3.17
3.7.1. Assembling Bottom Plates
After checking that the ground is correctly levelled, the enclosure assembly starts by placing the first bottom plate in its final position. Check that the plate is properly levelled by means of a hose level. If the enclosure consists of more than one module, insert a 20 x 10 mm adhesive rubber strip (reference 090006-33) in the joint between the different bottom plates.
Figure 3.18 Figure 3.19
Great care should be taken when installing this strip, since the sealing of the Transformer Substation depends on it.
4848
Page 17 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
The strip should be inserted so that it projects up 3 - 4 mm in the slot area where the front and rear panels will rest.
Figure 3.20: Area where the rubber strip
should project 3 - 4 mm
After the second or subsequent bottom plates are put into place, the plates should be firmly bolted together using M16 x 40 nuts and bolts. After this, a flexible earthing cable must be bolted in the angle bar of one of the slots in order to make up the earthing ring.
Figure 3.21 Figure 3.22: M16 x 40 nuts and bolts to join bottom plates
Figure 3.23
IG-021-GB
version 07
29.08.2008
Page 18 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
For example, PF-205 uses 5 bottom plates and they are fitted as shown in the figure below:
Once the bottom plates are bolted together, brush clean the slots where the vertical panels will rest.
Figure 3.24: Cleaning the slots
Next, insert the sealing strip between the bottom plates and the vertical panels, placing it in the centre of the slots.
Double 20 x 10 mm rubber strips should be laid, and when two or more bottom plates are used, the strips should run the entire length in one piece, leaving 3 - 4 mm projecting at each end.
Figure 3.25
Figure 3.26: Area where the rubber strip Figure 3.27
should project 3-4 mm
4848
Page 19 of 48
IG-021-GB
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
version 07
29.08.2008
3.7.2. Assembling the Vertical Panels
Assembly of the vertical panels starts with a front panel on one of the end bottom plates.
Figure 3.28 Figure 3.29
In order to assemble the vertical panels, the assembling props must be employed (reference 160028, 'PF Assembling Prop').
The 2-piece telescopic PF panel assembling prop uses the available slots in both the vertical panels and the bottom plates, so that the enclosures can be safely assembled. These props must always be used in enclosures with 2 or more modules (PF-203/303, PF-204/304, etc.)
Page 20 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Place the first back panel corresponding to one of the enclosure ends (in this example, the left end) in its position in the bottom plate.
Fix the panel using the PF panel assembling prop, without releasing it from the chains that keep it fastened to the crane.
In the bottom plates, the prop is fixed bolting 2 M10 screws in the end holes available in the slot bars.
4848
Page 21 of 48
GENERAL INSTRUCTIONS FOR PF
r
r
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
In the vertical panel, the prop is fixed using an auxiliary assembling bar so that the panels can be properly fastened.
When the next panel is joined, this bar will be removed.
Auxiliary assembling ba
IG-021-GB
version 07
29.08.2008
Once the prop is laid and fixed to the first panel, the panel can be released from the crane.
Fit the panel joining angle bars (reference 394256-64) to fix the panel to the bottom plate. For this purpose, use M16 x 120 nuts and bolts with a plastic DUBO washer at the back.
Panel joining angle ba
ref. 394256-64
Page 22 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Figure 3.30 Figure 3.31: M16 x 120 nuts and Figure 3.32: Plastic DUBO washer
bolts to join front/rear panels
After attaching the first front panel, a side panel must be added to close off the corner.
All side panels have a 20 x 10 mm rubber strip placed as follows:
A continuous strip is placed around both sides and the bottom edge of the panel
(see figure 3.33.)
A second strip is placed around the inner bottom, reaching up the sides to a
height of 600 mm (see figures 3.34 and 3.35).
Figure 3.33
600
Figure 3.34 Figure 3.35
4848
Page 23 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
A 20 x 10 mm rubber strip is also placed along the edge of the bottom plate where
the side panel supports will rest (see figure 3.36).
Figure 3.36
This side panel is attached to the bottom plate using M16 x 120 screws, with an M16 plastic DUBO washer on the outside.
Figure 3.37: M16x120 nuts and bolts to attach side panels
Figure 3.38
IG-021-GB
version 07
29.08.2008
Page 24 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Next, the side panels and the front panels are attached using M16 x 30 screws.
Figure 3.39
Figure 3.40 Figure 3.41
View after laying and fixing the first side panel
4848
Page 25 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.7.3. Remaining Vertical Panels
Next, the remaining vertical panels are assembled, leaving the second side panel till last.
When assembling the panels, always bolt the end screws first, followed by the central screws, since in panels with doorways, the doorframe concrete is very thin.
The front panels are joined together using M16 x 40 nuts and bolts (see figures 3.42 and
3.43); and the front panels are joined to the bottom plate using the 394256-64 flatbar: 'PANEL JOINING ANGLE BAR’ and M16 x 120 nuts and bolts, with the plastic DUBO washer (see figures 3.36, 3.37 and 3.38.)
The rubber strips are installed in the front panels as follows (see figure 3.44):
A continuous strip is fitted along the full length of the panel side.
IG-021-GB
version 07
29.08.2008
A second strip is fitted at the inner lower part, reaching up a height of 600 mm.
Figure 3.42
600 mm
Figure 3.43 Figure 3.44
Page 26 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
In PF-205 enclosures, after fitting the side panel, 2 front panels are fitted following the above stated premises (section 3.7.3) to join panels to each other and to bottom plates.
Put a new prop in the second front panel in the opposite direction to the first one. As in the first panel, use the auxiliary assembling bar to fasten a prop end to the panel and the other end straight to the opposite bottom plate slot.
To assemble the second back panel, release the prop to remove the auxiliary assembling bar.
4848
Page 27 of 48
GENERAL INSTRUCTIONS FOR PF
A
r
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Lay the second back panel and fit the prop again using the screws and fixing the 2 panels.
Afterwards, lay the next back panel (in this case, it is the third one) and follow the same procedure as in the first panel to fit the assembling prop.
Fit the third assembling prop, in the same direction as the first one, using the auxiliary assembling bar.
uxiliary assembling ba
IG-021-GB
version 07
29.08.2008
Page 28 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
From here on, follow the same assembling sequence until all front and back vertical panels have been fitted.
The props must be fitted in alternate directions.
4848
Page 29 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Before laying the closing panel, remove the last prop fitted to finish so that the enclosure closing can be finished.
3.7.4. Floor Plates, Slabs and Transformer Platform
IG-021-GB
version 07
29.08.2008
The floor plates are installed according to the assembling drawing, if any, as required by the transformer substation configuration.
The procedure is as follows:
The floor plate supports are bolted to the front and rear panels using M12 x 180 screws
with a plastic DUBO washer on the outside.
Note: Remember that there are floor plates of different thicknesses that require supports of
different heights. Great care should be taken to use the correct supports for each floor plate.
Figure 3.45 Figure 3.46
Figure 3.47: M12x180 nuts and bolts
to join floor plate supports
Page 30 of 48
IG-021-GB
t
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Put two 20 x 10 mm rubber strips on these supports, in the areas where the floor plates
will rest.
In order to insert the floor plates, start releasing the first prop.
s
1
Prop
Afterwards, introduce the first floor plate through the enclosure upper part.
Figure 3.48 Figure 3.49
Fit the floor plate and then fasten the prop to the panels. Now the prop must be fixed to
the front panel slot located just above the floor plate, instead of the bottom plate. Keep the same fixing slot in the back panel.
4848
Page 31 of 48
IG-021-GB
t
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
version 07
29.08.2008
Fixing the first prop after laying the floor plate.
1
s
Prop
Follow the same procedure to lay the next floor plates and transformer platforms,
according to the specific configuration of each transformer substation.
See the prop position after fitting the floor plates and transformer platforms.
Page 32 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
Put a 4 x 15 mm rubber strip around the slots where the slabs will rest (reference
090005-22), so that the slabs can be better settled.
Figure 3.50
The transformer platform locations depend on the TS configuration. Before installing them, a 20 x 10 mm sealing rubber strip should be placed around the bottom edge.
Figure 3.51 Figure 3.52
When the transformer is to be introduced through the transformer door rather than through the roof, the transformer platform should be located as close as possible to the door, in order to facilitate this operation.
Next, the fire barrier tray for the platform must be put into place and adjusted with its 6
supports.
A layer of pebbles is added to the tray, to act as fire barrier.
Figure 3.53: Fire barrier tray
4848
Page 33 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.7.5. Cubicles and Transformer
Depending on the Transformer Substation configuration, including the interior equipment, the various props may have to be released to lay this equipment.
If possible, the cubicles and transformer should be installed in the positions corresponding to the configuration before the covers are put on.
Figure 3.54
3.7.6. Low Voltage Board
IG-021-GB
version 07
29.08.2008
To install the LV boards, the 20 mm thick layer of the floor plates should be broken and the LV boards should be attached to the floor plate using M12 x 120 screws.
Figure 3.55
Page 34 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.7.7. Transformer Protection Fences
The transformer protection fences are inserted through the roof using the crane and are attached to the floor plate and to the front and rear panels.
Figure 3.56 Figure 3.57
3.7.8. Covers
The covers are lowered onto the vertical panels using the crane.
Figure 3.58 Figure 3.59
Figure 3.60: M16 x 40 nuts and bolts to join the covers
Figure 3.61
Once the first roof panel is in place, and if two or more modules are being used, two 20 x 10 mm rubber strips must be inserted into the joint between the different covers, and these must be tightly bolted together using M16 x 40 nuts and bolts.
4848
Page 35 of 48
GENERAL INSTRUCTIONS FOR PF
t
t
r
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
After laying the cover, this module's prop can be removed, if it has not already been done.
s
1
Prop 1
s
Cove
Finish the process by assembling all the covers and releasing the corresponding props.
IG-021-GB
version 07
29.08.2008
Page 36 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.7.9. Ventilation Grilles
Before mounting the ventilation grilles, a 4 x 15 mm rubber strip should be placed on the top edge of the concrete in order to prevent water from getting in.
Figure 3.62 Figure 3.63
Figure 3.64 Figure 3.65
The grilles are inserted from outside to inside, engaging the bottom edge first and then bolting the angle bars at the top of the grilles firmly to the concrete wall.
4848
Page 37 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.7.10. Doors
The doors are hung on the hinges, which first have to be mounted in the holes that exist in the panels for this purpose.
Figure 3.66
Figure 3.67 Figure 3.68
Figure 3.69: Installed door
IG-021-GB
version 07
29.08.2008
Page 38 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.7.11. Low Voltage Auxiliary Feeder
A 140 mm diameter hole, located in the front panel and close to the doors, allows the LVB to be fed by an external temporary feeder.
This auxiliary input is located 2000 mm above level 0 and can be closed using a cover that assures an IP 23D rating.
This cover can only be removed by manually loosening the wing nut and unscrewing it from inside the enclosure.
The following figure shows an example of LV feeder hole location in relation to a transformer door.
TRANSF. DOOR
Location of LV auxiliary input in PF enclosures
STAFF DOOR
Dimensions in millimeters
For PF Transformer Substations with 2 transformers, a LV auxiliary input is available for each of the transformers.
4848
Page 39 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.8. CONNECTING THE EARTH CIRCUIT
3.8.1. Panel Reinforcing Mesh
The panel reinforcing mesh is connected to earth via some of their slots or via inserted nuts.
Each type is described below:
Bottom plates The reinforcing mesh in the bottom plates is connected to earth via all of their slots.
Front Panels These have earth connections in the 2
Side Panels These have earth connections in the 2
Floor plates These have an M12 threaded insert for the earth connection.
Covers
The covers have earth connections in their end slots, except for single-module covers, that have an M12 nut for the earth connection.
To allow correct earthing, PF Modular Transformer Substations have an interior protective earthing circuit that allows the entire concrete enclosure to form an equipotential surface.
The reinforcing meshes in the different concrete components are connected together as follows:
1. The vertical panels are joined mechanically.
nd
and 4th slots, counted from the bottom.
nd
and 4th nuts, counted from the bottom.
IG-021-GB
version 07
29.08.2008
2. The joints between covers, and between these and the vertical panels, are made
Page 40 of 48
using a 50 mm
2
cross-section bare cooper wire between the suitable slots, except in the case of a single-module covers where the connection is made between the M12 nut and the slot in the front or rear panels.
Figure 3.70
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3. The connection between the system formed by the panels mentioned above and the
various floor panels is achieved using a 50 mm
2
cross-section bare copper wire, between the M12 threaded inserts in each floor plate and the nearest earthing slot to the front or rear panels.
Figure 3.71
4. The bottom plates are joined mechanically. These are connected to the vertical
panels using a 50 mm which in the vertical panels are those above the floor (2
2
cross-section bare copper wire between the suitable slots,
nd
and 4th).
Figure 3.72
4848
Page 41 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.8.2. Earthing Circuit
The doors and ventilation grilles are not connected to earth unless specified and accepted by the customer.
Once the different metallic elements in the concrete reinforcement mesh have been connected, the reinforcement mesh must be connected to the prepared internal earthing circuit.
This connection is made to one of the slots in the bottom plates, which is connected to the external earth electrodes through a hole previously moulded that is then sealed.
The Transformer Substation installation project must include a section corresponding to the execution of the earthing installation (check the Utility’s standard project), as well as justification of its sizing The requirements for this type of installation are established in the Regulations on Power Plants, Substations and Transformer Substations.
The copper connector cross-section, the terminal contact surface and tightening torques must be suitable for a default current delimited by network protections. A protection earth network of 50 mm
2
minimum cross-section copper wire is recommended.
Where maintaining the values of the step and touch voltages within the limits laid down in the applicable Regulations is not viable, the owner of the installation must apply at least one of the additional safety measures laid down in the said regulation in order to reduce personal and material hazards.
The tightening torque recommended for electrical connections in the earthing network is shown in the following table:
METRICS
M8 21 M10 38 M12 60
TIGHTENING TORQUE [Nm]
8.8 Steel A2 Stainless
IG-021-GB
version 07
29.08.2008
Page 42 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
3.8.3. Earthing Ring
The use of an earthing ring around PF Modular Transformer Substations is recommended.
The following configuration is offered as an example. The earthing network should be calculated in accordance with the standard project for Transformer Substation installation, which is available from the Utility.
EARTHING RING The construction of an earthing ring 600 mm underground is recommended. This ring should consist of a continuous bare copper wire with a 50 mm The wire should continue into the inside of the TS where it is connected to the enclosure earthing bar.
2
cross-section.
ENCLOSURE
PF-201/PF-301 2620 PF-202/PF-302 4880 PF-203/PF-303 7240 PF-204/PF-304 9600 PF-205/PF-305 11960 PF-2015/PF-3015 3700 PF-2030/PF-3030 7240 PF-3035 8420
[6]
L [mm]
[6]
For other configurations of PF TS, consult Ormazabal’s Technical - Commercial Department.
4848
Page 43 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
4. MAINTENANCE
4.1. REMOVING THE SIDE COVERS
Undo and remove the joint screws.
Using a crane, lift the cover, pulling it outwards and taking care not to pull off the
sealing rubber strip.
Rest this lifted cover on another of the covers.
Change the equipment as required.
Replace the cover, checking the sealing of the rubber strip, and reset the joint.
4.2. REMOVING THE CENTRAL COVERS
Undo and remove the joint screws.
IG-021-GB
version 07
29.08.2008
Move the side covers 100 mm outwards, taking care not to pull off the rubber strip.
Using a crane, lift up the panel that is to be removed.
Rest this lifted cover on another of the covers.
Change the equipment as required.
Replace every cover, checking the sealing of the rubber strip, and reset the joint.
Page 44 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
NOTES
4848
Page 45 of 48
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
IG-021-GB
version 07
29.08.2008
Page 46 of 48
IG-021-GB
version 07
29.08.2008
GENERAL INSTRUCTIONS FOR PF
MODULAR ENCLOSURES FOR
TRANSFORMER SUBSTATIONS
4848
Page 47 of 48
TECHNICAL - COMMERCIAL DEPARTMENT:
www.ormazabal.com
Page 48 of 48
Loading...