The Network Pro UPS features a rack/tower convertible design, single
AVR boost and single buck, pure sine wave output, user-friendly LCD
display, built-in customer option slot, hot swappable battery, and
USB/RS232 communications interface. The Network Pro provides a
flexible rack/tower form factor for use with critical file servers, minicomputers,
network switches, hubs, and other business critical equipment.
Sine wave output provides clean output power to connected equipment.
User-friendly LCD panel displays system status including load level,
battery level, AVR-Boost/Buck and fault status for easy monitoring and
service.
90% high efficiency design when used in Normal mode meets high
efficiency energy saving standards and reduces noise and heat.
User-replaceable hot-swappable battery design saves time and money
by allowing quick battery changes without downtime.
Cold start function enables UPS to power up without connecting to
incoming utility power.
Optional Communication Software allows not only the control of the
UPS and graceful shutdown when the Utility Fails, but also allows the
user to remotely test the major operating functions of the UPS,
communicate via SNMP/web/network optional card, access UPS
functions via the web and alert users via SMS messages against
specific events.
User-friendly design can easily be installed by end user.
Plug-and-play USB/RS232 interface conveniently offers a USB or
RS232 port for connecting to a computer or other hardware.
2 IMPORTANT SAFETY INSTRUCTION
2.1 An Important Notice
1. The UPS has its own internal energy source (battery). If the UPS is
switched on when no AC power is available, there could be voltage at
the output receptacles.
2. Make sure that the AC Utility outlet is correctly grounded.
3. Do not open the case, as there are no serviceable parts inside. Your
warranty will be voided if the case is opened.
4. Do not try to repair the unit yourself; contact your local supplier or
Orion Power Systems Technical support if the unit needs repair.
5. Please make sure that the input voltage of the UPS matches the
supply voltage.
6. To eliminate any overheating of the UPS, keep all ventilation
openings free from obstruction.
7. Make sure the UPS is installed within the proper environment as
specified. (0-40℃ and 30-90% non-condensing humidity)
8. Do not install the UPS in direct sunlight.
9. The UPS is designed for indoor installation only. Do not install the
UPS outdoors or in an environment that is not climate controlled.
10. Dusty, corrosive and salty environments can damage the UPS.
11. Install the UPS away from objects that give off excessive heat and
areas that are excessively wet.
12. If liquids are spilled onto the UPS or foreign objects are dropped into
the unit, the warranty will be void.
13. The battery will discharge if the system is disconnected from AC
power for long periods (>3 months). If left uncharged, the battery
may require replacement for the UPS to provide battery backup.
2
3
14. The battery should be recharged every 2-3 months if the UPS is not
in service. This can be done by plugging in the UPS for a minimum
of 8 hours every 2-3 months. If this is not done, the batteries will need
to be replaced – this is not covered under the warranty. When the
UPS is installed and in use, the batteries will be automatically
recharged and kept in top condition.
15. This UPS supports electronic equipment in offices,
telecommunications, process control, and non life-support medical
and security applications. The UPS should not be installed in the
following areas:
a. Medical equipment directly related to human life support
b. Elevator, Metro (Subway) system or any other equipment related to
human safety.
c. Nuclear power plants.
16. Do not install the UPS in an environment with flammable gases.
17. Make sure the UPS is completely powered off before moving. There
is a risk of electrical shock if the UPS is moved while in use.
18. SAVE THESE INSTRUCTIONS – This Manual Contains Important
Instructions that should be followed during Installation and
Maintenance of the UPS.
19. Symbol for ON/Off is displayed and defined.
20. Intended for installation in a temperature-controlled, indoor area free
of conductive contaminants.
21. Maximum ambient temperature 40℃ (or 0~40℃ for ambient
Operating).
22. For Model 3000 - "CAUTION - To reduce the risk of fire, connect
only to a circuit provided with 30 amperes maximum branch circuit
overcurrent protection in accordance with the National Electric Code,
ANSI/NFPA 70"
23. For Models 2200, 1500, 1000 and 750 - "CAUTION - To reduce the
risk of fire, connect only to a circuit provided with 20 amperes
maximum branch circuit overcurrent protection in accordance with
the National Electric Code, ANSI/NFPA 70".
24. CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY
AN INCORRECT TYPE. DISPOSE OF USED BATTERIES
ACCORDING TO THE INSTRUCTIONS.
25. Replacement of batteries located in a SERVICE ACCESS AREA
A) Servicing of batteries should be performed or supervised by
personnel knowledgeable about batteries and the required
precautions.
B) When replacing batteries, replace with the same type and
number of batteries or battery packs.
C) CAUTION - Do not dispose of batteries in a fire. The batteries
may explode.
D) CAUTION – Do not open or mutilate batteries. Released
electrolyte is harmful to the skin and eyes. It may be toxic.
E) CAUTION – A battery can present a risk of electrical shock and
high short circuit current. The following precautions should be
observed when working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source prior to connecting or
disconnecting battery terminals.
f) Determine if battery is inadvertently grounded. If inadvertently
grounded, remove source from ground. Contact with any part
of a grounded battery can result in electrical shock. The
likelihood of such shock can be reduced if such grounds are
removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded
supply circuit).
26. CAUTION: Lead acid batteries may cause chemical hazard.
2.2 Storage Instruction
For extended storage, the batteries should be charged for 12 hours
every 3 months by plugging the UPS power cord into the wall receptacle and
turning on the input breaker on the front panel. Repeat this procedure every
2 months if the UPS is stored in a high temperature environment.
4
5
3 SET UP
3.1 Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is
damage to the shipping carton or the UPS. If shipping damage is present,
please keep all packaging materials until the shipping claim has been
resolved. The package is recyclable; save it for reuse or dispose of it
properly.
3.2 Storage and Operation of UPS
The UPS should be stored and operated in a well-ventilated and
climate-controlled low-humidity environment.
3.3 Unpacking
1. Take the UPS out of the packing foam.
2. Remove the packing materials.
3. Standard Package includes:
a. User Manual
b. 1pc x AC Input Power Cord ( Not available for hard wiring connection
models)
c. For 230v International models with IEC connectors, the UPS should
include 1pc (for 1k/1.5kVA) or 2pcs (for 2.2k/3kVA) IEC output cables.
d. 1set x UPS communication kit (optional)
Accessories for Tower and Rack Mount
6
7
3.4 Selecting Installation Position
In order to minimize the possibility of damage to the UPS and extend
the life of the UPS, it is necessary to select a proper environment to install
the unit. Please follow the instructions below:
1. Keep at least 20cm(8 inches) clearance
from the rear panel of the UPS from the
wall or other obstructions.
2. Do not block air-flow to the ventilation
openings on the front and rear of the unit.
3. Please ensure the installation site
environmental conditions meet the UPS
specifications to avoid overheating and
excessive moisture and to prolong
battery life.
4. Do not place the UPS in a dusty or
corrosive environment or near any
flammable objects.
5. This UPS is not designed for outdoor
use.
3.5 UPS Setup
The UPS offers a flexible form factor
enabling integration into a wide variety of
environments.
The UPS uses a 2U rack/tower
convertible design for 1KVA to 3KVA
systems.
If you are installing the UPS in a tower,
continue to the following section, “Tower
setup” otherwise; continue to “Rack-Mount
setup”.
3.6 Tower Setup
Stand alone unit
8
9
3.7 Rack-Mount Setup
Step1
Step2
Step3
Step4
Step5
10
11