Orion MUA II D User Manual

www.orioncontrols.com
Operator Interfaces
Technical Guide
For MUA II D Controllers
( SS1013 or Y200405 MUA II D Controller Code)
(Use SS1010 System Manager Code & SS1009 Service Tool Code)
Table Of Contents
Introduction ..................................................................................................................................................... 3
Modular System Manager........................................................................................................................................................... 3
System Connections........................................................................................................................................ 4
Modular System Manager........................................................................................................................................................... 5
General Programming Information ................................................................................................................. 6
Operator Interfaces Comparison ................................................................................................................................................ 6
Modular System Manager........................................................................................................................................................... 7
System Manager Passcodes ...................................................................................................................................................... 9
Scheduling ................................................................................................................................................................................ 10
Setting Time & Date...................................................................................................................................................................11
Space Sensor Overrides ........................................................................................................................................................... 12
Alarm Search ............................................................................................................................................................................ 12
Programming The MUA II D Controller ......................................................................................................... 13
Configuration ............................................................................................................................................................................ 13
Setpoints................................................................................................................................................................................... 14
Status........................................................................................................................................................................................ 18
Scheduling ................................................................................................................................................................................ 19
Outputs Force ........................................................................................................................................................................... 20
Notes:............................................................................................................................................................. 21
WattMaster Controls Inc.
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152
8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1 100
Toll Free Phone: 866-918-1 100 PH: (816) 505-1100 · F AX: (816) 505-1 101 · E-mail: mail@wattmaster .com
PH: (816) 505-1100 · F AX: (816) 505-1 101 · E-mail: mail@wattmaster .com Visit our web site at www.orioncontrols.com
Visit our web site at www.orioncontrols.com Form: OR-SMST-TGD-01B
Form: OR-MUAIID-SMST -TGD-01C Copyright 2002 W attMaster Controls, Inc.
Copyright 2004 W attMaster Controls, Inc. AAON® is a registered trademark of AAON, Inc., T ulsa, OK.
AAON® is a registered trademark of AAON, Inc., T ulsa, OK. WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions. This document is subject to change without notice.
This document is subject to change without notice.
Introduction
Technical Guide
Modular Service Tool
2.02"
4.75”
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
1.63"
Figure 1: Modular Service Tool Dimensions
Description
The MUA II D Modular Service Tool is a system operator interface that provides a direct link to enable the system operator to view the status, configure and to adjust the setpoints of any controller on the control system communications loop. The Service Tool is housed in an attractive beige colored plastic enclosure. The display area is cov­ered with a clear plastic bezel for protection of the display screen. The Service T ool has a four line by 20 character display panel with adjust­able contrast control and a 27 key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, uti­lizing non-cryptic plain English language messages. Menu driven pro­gramming allows for easy setup and operation without the need for specialized training. The Wendy’s Modular Service Tool is supplied with (4) AA (1.5V) Volt alkaline batteries a wall mount DC power supply and a communication cable terminated with an 8 pin DIN con­necter for connection to the Service T ool. The cable allows the user to setup and program any MUA II D controller with a 8 pin DIN connec­tor socket by simply plugging in the service tool to the socket on the controller.
The Service Tool is designed to be carried by the system installer or service technician. Its rugged plastic housing, provides superior protec­tion for the electronic components housed inside. The MUA II D Modular Service Tool is a top quality service tool that will stand up to the de­mands of the typical job site environment for many years.
UP
PREV
ESC
13
4
708
DEC
NEXT
DOWN
CLEAR
ENTER
2
5
6
9
MINUS
-
10.00”
Modular System Manager
9.00"
13
2
5
6
4
708
9
DEC
MINUS
-
UP
PREV
ESC
DOWN
ENTER
Figure 2: Modular System Manager Dimensions
Description
The MUA II D Modular System Manager provides a direct link to en­able the system operator to view the status and to adjust the setpoints of any controller on the control system communications loop. The System Manager is designed to be used with the MUA II D controllers. The System Manager is housed in an attractive beige colored plastic enclo­sure. The System Manager is equipped with a four line by 20 character backlighted display panel and a 24 key membrane keypad for data se­lection and entry. All keypad operations are simple and straight for­ward, utilizing non-cryptic plain English language messages. Menu driven programming allows for easy setup and operation without the need for specialized training. The System Manager also has 2 integral LED’s for user notification of system alarm conditions and override initiations. Protection from unauthorized users is provided by the Sys­tem Manager’s integral multi-level passcode authorization programming.
On a Networked System the Modular System Manager is connected to the communications and power loop of the system via modular cables that simply plug into the System Manager board and the Power/Comm Distribution Board. This virtually eliminates wiring errors and makes installation fast and easy. When it is to be connected to a Stand Alone system, a cable with modular connectors on one end and stripped wire ends on the other end is provided to facilitate connecting communica­tions and power to the System Manager from the 24 VAC power source and the HVAC unit controller communication wiring terminals.
The System Manager is designed for wall mounting. Mounting holes are provided to attach the System Manager to a standard handy box. It is recommended that the System Manager be mounted at approximately eye level to allow for ease of programming and reading of the display. The System Manager is typically mounted in the building manager or superintendent’s office or in an equipment room. The attractive enclo­sure is quite suitable for mounting in any location or with most decors.
STATUS
SETPOINTS
NEXT
SCHEDULES
CLEAR
OVERRIDES
ALARMS
6.25"
1.81"
Operator Interfaces 3
Technical Guide
System Connections
Modular Service Tool
Wether you have a Stand Alone, Interconnected or Networked Orion Controls System, the Modular Service T ool always connects to an HV AC unit controller via a prefabricated cable that is supplied with the service tool. The Modular Service Tool cable is terminated on both ends with a mini DIN connector. Attach one end to the Modular Service Tool and the other end to the mini DIN connector on the HV AC unit controller. If this is an Interconnected System, all controllers that are interconnected
Male DIN Connector
with communications cable can be programmed from any HVAC unit controller on the loop. If this is a Networked System, all controllers on the entire Networked System can be programmed from one HVAC unit controller.
Be sure that the Modular Service Tool has fresh batteries installed or that it is connected to a power source using the supplied power pack before attempting any programming of the controller. See Figure 3 for connection details.
Female DIN Connector
Connector Cable
Selection
SETPOINTS
SCHEDULES
OVERRIDES
CONFIGURATION
BALANCE - TEST
Mode
PREV
STATUS
13
ALARMS
4
708
DEC
ON
Typical Controller Board
The Modular Service Tool Can Be Connected To The VAV/CAV Controller Or The VAV/Zone Controller By Plugging One End Of The Supplied Cable Into the Modular Service Tool DIN Connector And The Other End Into The DIN Connector On The Controllers.
Modular Service Tool
UP
NEXT
DOWN
CLEAR
ESC
ENTER
2
5
6
9
MINUS
-
Be Sure The Modular Service Tool Is Connected To The Supplied Power Pack Or Has Fresh Batteries Installed Before Attempting Programming Of The Controller. Be Sure The Power Is Turned Off On The Modular Service Tool Before Connecting The Cable To The Controller.
Figure 3: Modular Service Tool
4
Power On Button
Operator Interfaces
Technical Guide
U13
V62C518256L-70P
74HC573
CX8
RN1
YS101830PREV. 2PMODULARPSYSTEM MANAGER
PCB80C552-5-16WPP442860=2/5 PDfD9722V7Y
R1
R4
24C128
74HC259
U14
CX9
470uF50v
1000uF10v
470uF50v
R12
R11
COMMOUT
COMMIN
74HC540
CX10
74HC923
82B715
RS-485P
V62C518256L-70P
75176
YS101830PREV. 2PMODULARPSYSTEM
PDfD9722V7Y
74HC259
470uF50v
1000uF10v
1000uF10v
COMMOUT
COMMIN
74HC540
CX14
82B715
Modular System Manager
As previously described, when you are connecting the Modular System Manager to a Networked System, the Modular System Manager is con­nected to the communications and power loop of the system via modu­lar cables. These cables simply plug into the System Manager board and to any device with modular connectors on any local loop on the system. Devices with modular connectors include the Power/Comm Dis­tribution Board, VAV/Zone controller and the Modular Polling device. By using these plug in connections wiring errors are virtually elimi­nated and system installation is fast and easy. See Figure 4 for typical connection information. See Figure 5 for typical Power/Comm board wiring and connection information.
When the System Manager is to be connected to a Stand Alone system, a 12 ft. cable with modular connectors on one end and stripped wire ends on the other end is provided for this purpose. This is used to facili­tate connecting communications and power wiring to the Modular Sys­tem Manager from a 24 VAC power source and to the HVAC unit con­troller communication wiring terminals. See Figure 6 for wiring de­tails. If the supplied cable wire is not long enough for your installation, a standard modular cable of the correct length can be purchased through WattMaster and one of the modular connectors can be cutoff to allow for the transformer and communication terminal wiring connections. It is recommended that you do not splice the communications wire if at all possible. The transformer should be rated at 6 VA minimum power output.
WARNING!
DO NOT GROUND THE 24V TRANSFORMER THAT IS TO BE USED WITH THE POWER/COMM BOARDS. GROUNDING OF THE TRANSFORMER WILL DAMAGE THE POWER/COMM BOARD AND ALL BOARDS CONNECTED TO IT.A SEPARATE TRANSFORMER MUST BE USED FOR EACH POWER/COMMBOARD. NO EXCEPTIONS. DO NOT CONNECT ANY OTHER DEVICES TO THE TRANSFORMER USED FOR THE POWER/COMM BOARD!
Line Voltage
24VAC
24VAC Transformer (By Others) Size For Total Load Of Devices Connected To Board
25
F1
4 Amp Slow Blow Fuse
4A
Power/ Cable To Power/Comm
Comm Other Distribution Board, System Manager, MiniLink Or Other VAV/Zone Controllers On Local Loop
Power/Comm Cable Power/Comm Distribution Board, System Manager, MiniLink Or Other VAV/Zone Controller On Local Loop. If This Is The First
Power/Comm Board On The Local Loop,
Connection Is Not Required.
TB2
VAC
24
LD1
POWER
V1
D1
P1
From Other
Polling Device
Connect To VAV/CAV Controller If This Is First Power/Comm Board On Local Loop - Otherwise No Connection Is Required.
Local Loop RS-485
9600 Baud
All Comm Loop Wiring Is
Straight Thru
TtoT
C1
P5
RtoR
SHLD to SHLD
Local Loop RS-485
9600 Baud
COMMPIN
TB1
P2
SHLD
T
R
POWER& COMM
DIST.BOARD
YS101856
REV.0
R1
P4
P3
OUT
POWER& COMM
Polling Device
Figure 5: Typical Power/Comm Board Wiring
YS101830PREV. 2PMODULARPSYSTEM MANAGER
U1
74HC259
CX2
U2
R3
R1
R4
PCB80C552-5-16WPP442860=2/5 PDfD9722V7Y
C1
X1
C2
U7
PAL
U8
CX7
CX11
U11
CX12
V62C518256L-70P
U12
R2
EWDOG
CX4
U3
R3
PHILIPS
24C128
U4
PHILIPS
CX5
CX6
R9
D3
C3
8583
X2
U6
RN1
74HC573
P1
CX8
P2
SC1
EPROM
VAR1
RAM
CX13
U13
75176
RS-485P COMM
R14
Power/Commr Cables To Power/Comm Board, MiniLink Polling Device Or VAV/Zone Controllers On Local Loop.
DSPY1
U3
CX3
D1
R5
82B715
R6
D2
PJ1
COMMOUT
R11
R12
U9
9936
COMMIN
D6
MC34064A
R13
470uF50v
C7
470uF50v
All Modular Power/Comm
Cables Are To Be WattMaster Part Number PCC-xx Or PCCE-xx Cables.
Distribution
RV1
R7
R10
D5
D4
L1
CX10
C4
74HC923
C5
U10
CX9
1000uF10v
C6
C8
1000uF10v
CX14
P3
74HC540
U14
Modular System Manager Back of Front Cover
YS101830PREV. 2PMODULARPSYSTEM MANAGER
U1
74HC259
CX2
U2
R3
R1
R4
PCB80C552-5-16WPP442860=2/5PDfD9722V7Y
C1
X1
C2
U7
PAL
U8
CX7
CX11
U11
CX12
V62C518256L-70P
U12
Note: If Desired A Power/Comm Board As
Used With The Networked System Can Be Installed And Wired Instead Of Using The Pigtail Cable Wiring Shown Below. See The Networked System Wiring Diagram For Details.
Use Supplied Modular
Cable With Stripped Ends
For Connection To Terminal
Block And Transformer
WHITE (T) DRAIN WIRE (SHLD) BLACK (R)
RED (24 VAC) BROWN (GND) GREEN (GND)
R2
EWDOG
CX4
U3
R3
PHILIPS
24C128
U4
PHILIPS
CX5
CX6
R9
D3
C3
8583
X2
U6
RN1
CX8
74HC573
SC1
EPROM
RAM
CX13
75176
RS-485P COMM
R14
DSPY1
U3
CX3
D1
R5
82B715
R6
D2
PJ1
COMMOUT
P1
P2
VAR1
U13
D5
R11
R12
L1
U9
C4
9936
COMMIN
D6
MC34064A
R13
CX9
1000uF10v
470uF50v
C8
C7
1000uF10v
470uF50v
RV1
R7
R10
D4
CX10
74HC923
C5
U10
C6
P3
74HC540
CX14
U14
Modular System Manager Back of Front Cover
T SHLD
R
Controller Board
Figure 4: Modular System Manager - Networked
Operator Interfaces
Class 2 Transformer
Rated For 6 VA Minimum
Figure 6: Modular System Manager - Stand Alone
5
Technical Guide
General Programming Information
Operator Interfaces Comparison
In order to configure and program the Orion System controllers you must have a central operators interface or a personal computer with the Prism computer front end software installed. Two different central op­erators interfaces are available for programming of the Orion Controls System. Y ou may use either the Modular Service Tool and/or the Modu- lar System Manager to access the status and setpoints of any control­ler on your communications loop.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
Modular Service Tool
13
2
MINUS
PREV
6
9
-
4
708
DEC
5
UP
ENTER
DOWN
NEXT
CLEAR
2
5
6
9
MINUS
-
PREV
ESC
13
4
708
DEC
System Manager
UP
NEXT
DOWN
ENTER
CLEAR
ESC
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
The Modular Service Tool or the System Manager allow the user to view any temperature or output condition and change any setpoint to fine tune the operations of the total system. All keypad operations are simple and straightforward, utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
The System Manager display screens and the Modular Service Tool display screens are very similar. For most setpoints and modes the only difference between using the Service T ool and the System Manager is a few differences in the function of the keypads. The Modular Service Tool has 2 extra function keys (“Configuration” and “Balance-Test”) that are not available on the System Manager. Where a dif ference in the keypad input or the screens displayed exists between the two operators interfaces, both screens or keypads will be shown. See the chart below for a list of the keypad descriptions and functions.
Keypad
Description
ESC
ENTER
Clear
Minus
DEC
⇑ ⇓
System Manager Modular Service Tool
Used to exit from screens or from data entry. Use this s creen to return to the main menu from any screen in the system
This key is used to close a
data entry field and
advance to the next item
or screen
If a data entry mistake is
made, press this key to
clear the data entry field
and start over
If the a setpo i nt with a
negative value is required,
press this key for the
minus sign
Press this key when
entering data that requires
a decim al po int
Ste p s the user to the nex t
controller on the loop on
interconnected or
networked systems
Steps the user backward or
forward th rou gh the
screens
Key Function
Same function as
System Manager but
also turns off the
power to the Se rvic e
Tool when on the
main menu screen
Same function as
System M an age r
Same function as
System M an age r
Same function as
System M an age r
Same function as
System M an age r
Same function as
System M an age r
Same function as
System M an age r
6
Modular System Manager
Operator Interfaces
Modular System Manager
System Manager Initialization Screens
When the System Manager is powered up, the first screen displays the current version of the software installed in your System Manager and whether your system is configured for Network or Stand-Alone opera­tion. The System Manager will try to detect the type of installation you have by scanning the communications loop. See the screens below. If it is configured for Stand-Alone operation, only the HVAC unit controller that the System Manger is connected to is available for programming. On a Networked System, all controllers on the communications loop are available for programming by entering their loop address (ID). If an Interconnected System is connected to the System Manager all control­lers that are connected to the communication loop are available for pro­gramming.
Initializing System Manager vX.XX Wattmaster Controls Network Mode
Technical Guide
1) Set Time & Date
2) Communications
->) Next Menu ESC) Exit Menu
Press the “2” key on the keypad to enter the communications screen.
THIS ACTION REQUIRES PASSCODE CLEARANCE Enter Passcode: xxxx
Enter the seven digit passcode “2337377” to access the next screen. These seven digits spell the word “ADDRESS” on your telephone key­pad if you forget what they are. Once on the screen shown below, use the keypad to enter the correct mode for your installation. The screen will now show “Stand Alone System” or “Multiple MGRS” or “Net­work System” depending on what you selected.
System Manager vX.XX Monday Operations 09/09/99 04:26 PM Outdoor Air 87°F
The screen above will appear a few seconds later. If this is a Stand Alone system, the outdoor air temperature will not be shown on the display. If you believe your system is incorrectly configured, please fol­low the instructions that follow. If your system is configured correctly proceed to the Menu Screens section of this manual.
Configuring The System Manager For Network Or Stand-Alone Operation
The System Manager can operate as a Stand Alone interface with the HVAC unit controller and does not require any other communications devices to read or reset any available values. T o verify if it is currently configured for Stand Alone operation, cycle power to the System Man­ager and monitor the LCD initialization screen. If it is configured for Stand Alone you will see the words “Stand Alone Mode” on the bottom line of the display. If you are using this System Manager on a communi­cations loop and have installed a MiniLink or CommLink II communi­cations interface, then you need to operate in Network Mode and the bottom line should display the words “Network Mode”.
If your display indicates a different mode than the one you need, press the “Enter” key and the following screen will appear.
0) Stand Alone 1-60) Multiple MGRS
63) Network System Enter Mode Of Op:.xx
Once you have the correct mode displayed, press the ENTER key. The following screen will appear to telling you that you have changed the system mode. Press any key on the keyboard to exit this screen.
You Have Changed The System Mode Press Any Key To Continue
Modular Service Tool
The Modular Service Tool is very similar to the System Manager in its operations as stated previously . Two exceptions to this are that the Ser­vice Tool unlike the System Manager does not check the system to de­termine whether it should be in Network or Stand Alone Mode and it does not have any passcoding capability.
After connecting the Service Tool to the controller with the supplied cable, press the “On” key. The following screen will appear.
Service Tool vX.XX Monday Operations 09/09/02 04:26 PM Stand Alone Mode
Operator Interfaces
7
Technical Guide
General Programming Information
Configuring The Modular Service Tool For Network Or Stand-Alone Operation
As with the System Manager described previously, you must determine if the mode displayed is correct for your system. If it is configured for Stand Alone you will see the words “Stand Alone Mode” on the bottom line of the display. This is the factory default setting. If you are using this tool on a system or controller that does not have a CommLink or MiniLink installed, then this is the correct setting and you can proceed to desired screen by pressing the menu key or any function key. If you are using this Service Tool on a communications loop with and have installed a MiniLink or CommLink II communications interface, then you need to operate in network mode and the bottom line should dis­play the words “Network Mode”.
If your display indicates a different mode than the one you need, press the "Enter" key and the following screen will appear.
1) Set Time & Date
2) Communications
3) Energy Saving ESC) Exit Menu
1) Set Time & Date
2) Communications
3) Energy Saving ESC) Exit Menu
When this screen appears press the “3” key to access the Energy Saving screen. The following screen will appear.
Energy Saving Automatic Power Down Minutes: xx Press ESC to Exit
Enter the number of minutes you want the Service Tool to stay active before it automatically powers down. To cancel the automatic power down enter “99”. After you have entered this number between 1 and 99 minutes, press “ESC” to exit as the screen instructs you.
Unit Selection
Press the “2” key on the keypad to enter the communications screen.
0) Stand Alone
1) Network System
Enter Mode Of Op:.xx
As the screen indicates, press “0” or “1” keys to select the proper mode of operation. When you are finished press “Enter” to move back to the main menu screen.
You Have Changed The System Mode Press Any Key To Continue
Setting The Energy Saving Timer
The Modular Service Tool has a built in timer that can be programmed to shut the Service T ool off after a specified period of time if no buttons are pressed. This is a very useful feature if you are powering the Service Tool from the internal batteries. To access this setting from the main status screen press "Enter".
With both the Modular Service Tool and the Modular System Manager You must enter the ID (Address) of the controller you wish to program
Unit Selection Enter Unit ID# Selected ID#: xxxx
With the main menu screen displayed, press the function key associated with the operation (setpoints, configuration, etc.) you want to perform. The screen shown above will appear asking you to enter a unit I.D.# (controller address). Put in the ID# of the controller you wish to com­municate with then press the “ENTER” key.
If this is Network System (the system has a CommLink), the Unit ID is actually two separate numbers, combined into one value. The first part of the number contains the Loop Address at which the controller is located. The second part of the number contains the actual controller address. See Examples #1 & #2 below.
If this is a Stand Alone System (system without a CommLink) this will be a number between 1 and 59. It is recommended the address be set to
1. See example #3 below.
EXAMPLE #1
You would like to view the 3rd controller on the 5th loop. Enter “503” as the Unit ID.
8
Operator Interfaces
Technical Guide
EXAMPLE #2
Y ou would like to view the 12th controller on the 24th loop. Enter “2412” as the Unit ID
EXAMPLE #3
You would like to view the only controller on the loop. Enter 1 as the Unit ID. No loop number is required since there is only one loop.
Hit the “Enter” key after entering the unit ID. If you are using the Modular Service T ool you will be taken directly to the first screen for the opera­tion you are trying to program.
System Manager Passcodes
Anytime you enter a unit ID with the Modular System Manager you will be asked for a passcode. Passcodes are not required to view Status Screens. The screen below will appear if this action requires passcode clearance.
THIS ACTION REQUIRES PASSCODE CLEARANCE Enter Passcode: xxxx
The System Manager has two levels of user access. Level 1 users are limited to viewing or changing the Time and Date and Operating Sched­ules. Level 2 users have complete system access. Any status or setpoint field can be read or reset from the System Manager.
These two levels of passcodes are programmable by any Level 2 user. The default Level 1 passcode is “111 1” and the default Level 2 passcode is “2222.”
If you wish to change either Level 1 or Level 2 passcodes please see the instructions that follow.
From the main status screen press "Enter", The following screen will appear.
1) Set Time & Date
2) Communications
->) Next Menu ESC) Exit Menu
Press ">", to proceed to the next menu and the following screen will appear.
1) Change Passcodes
2) Loop Search <-) Prev. Menu ESC) Exit Menu
Press the “1” key on the keypad to enter the Change Passcode screen.
THIS ACTION REQUIRES PASSCODE CLEARANCE Enter Passcode: xxxx
Enter the default Level 2 passcode “2222” to access the next screen. You must use the Level 2 passcode to change passcodes. Level 1 passcodes will not allow changing passcodes!
Enter New Passcode
Level 1.....: xxxx
Level 2.....: xxxx
[Must Be 4 Digits]
Operator Interfaces
This screen allows you to enter new Level 1 or Level 2 passcodes. The actual digits in your passcodes are never displayed. An “X” is used as a place holder for each digit entered. Passcodes must always be four dig­its in length, so the usable range of numbers is 1000 to 9999.
Caution: If you change the Level 2 passcode and cannot
remember what it is, you will be locked out of your system!
9
Technical Guide
General Programming Information
Scheduling
The MUA II D controller scheduling screens are accessed by pressing the “Schedule” button on either the System Manager or the Modular Service T ool. Press the number button for the scheduling function you wish to view.
1)Schedule Overrides
2)Week Schedules
3)Holidays ESC) Exit Menu
Week Schedules
Event #1
MUA II Sched ID 59 Sunday Event #1 Start Time : xxxx Stop Time : xxxx
Event #2
Note: The second line displays which day of the week is cur-
rently being programmed. This automatically increments as you finish the Event #2 screen and continue to the next days Event #1 screen.
Caution: The controller ships with all schedules set to zero so
that the controller will not attempt to heat or cool before the user has configured his system.
Holiday Start/Stop Day Selection
MUA II Hldy ID 59 Holiday # 1 Start Mon/Day: xxxx [ July 4
MUA II Hldy ID 59 Holiday # 1 Stop Mon/Day: xxxx [ July 4
th
= 704 ]
th
= 704 ]
MUA II Sched ID 59 Sunday Event #2 Start Time : xxxx Stop Time : xxxx
If you are using the internal scheduling capability of the V AV/CA V con­troller, set the schedule hours and holiday periods from the menu shown above. You can also force the unit to operate continuously in occupied or unoccupied mode by selecting the Schedule Override menu item and entering the desired command.
If you are using an external contact closure to signal the occupied mode, you must access the Week Schedule screens and set all start and stop times to zero to prevent the internal schedule from bringing the equip­ment on when you don’t want it to operate.
The screens will step through the Start T ime and then the S top T ime for each day of the week. You can quit at any point in the process by press­ing the “Escape” key. There are two Start/Stop events available per day so the screen will show which event is being programmed. If you need only one event, leave Event #2 times to ZERO.
All times are in 24-hour military format, so 5:00 PM would be entered as 1700.
If both the Start and Stop T imes are ZERO, the schedule is in a continu­ous OFF mode. (Use for Remote Signal Contact)
The screens will step through the fourteen possible holidays, one pe­riod at a time. Line 2 shows which holiday is currently being pro­grammed. Since a holiday period can encompass more than one day, you need to program the day the holiday starts and the day the holiday ends. If your holiday only lasts one day simply set both the Start Day and the Stop Day to the same value. Remember to combine the month and day into a single four-digit value.
EXAMPLE: 704 = July 4th (Note : Leading zero not required) 1225 = December 25
th
Holiday Start/Stop Times
MUA II Hldy ID 59 Holiday Schedule Start Event #1: xxxx Stop Event #1: xxxx
MUA II Hldy ID 59 Holiday Schedule Start Event #2: xxxx Stop Event #2: xxxx
If both the Start and Stop Times are 2359, the schedule is in a continu­ous ON mode.
10
The fourteen holidays all use the same Start and Stop times which are entered on this screen and then next. It is entered in 24-hour military format, the same as a regular week schedule.
Operator Interfaces
Technical Guide
Normally the holidays will operate in an unoccupied mode or a reduced schedule mode. There are two start/stop events available on holidays to match the standard schedule number of events.
Schedule Override
Schedule Override Enter Override : x
[0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied or Unoccupied mode, select this menu item to activate the desired method. If a Schedule Override is active, all other methods of schedule control are ignored. (Push-Button, Internal or Remote)
As you can see on the last line of the display you enter a ‘1’ to run continuously in the Occupied Mode or a ‘2’ to run continuously in the Unoccupied Mode.
T o restore normal schedule operations, make sure a ‘0’ is entered here. This override remains in effect until canceled by the user and does not time-out like the Output Overrides do after 10 minutes of no communi­cations.
For the Service T ool, from the main screen press “Enter” and the fol- lowing screen will appear.
1) Set Time & Date
2) Communications
3) Energy Saving ESC) Exit Menu
Press 1 to enter the Set Time and Date Menu.
Programming Times
Although the times are displayed on the Main Screen in a standard 12­hour format, they are programmed using the 24-hour military format. If the VAV/CA V controller was configured to use its own Internal Sched­ules, the Occupied/Unoccupied modes are calculated on the basis of the current real time clock reading.
Program Time/Date Day (Sunday=0): x Enter Hr. (0-23): xx Enter Minutes : xx
Note: Do not use the Force OFF mode in place of setting all
the week schedules to ZERO if you are using a Remote Signal for your scheduling since the Override has pri­ority over the Remote Signal.
Setting Time & Date
Both the Modular Service Tool and Modular System Manager are equipped with a real time clock chip allowing it to maintain the cor­rect time. Once the correct time and date are entered, the information is broadcast globally to all controllers on the entire system. The Sys­tem Manager will also broadcast this information once every day at midnight to synchronize all the controllers on the system.
From the main System Manager screen press “Enter” and the follow­ing screen will appear.
1) Set Time & Date
2) Communications
->) Next Menu ESC) Exit Menu
Press 1 to enter the Set Time and Date Menu.
Day Enter the Day of the Week (0 to 6)
Sunday = 0
Hours (Hr) Enter Hours in 24-Hour Military Format
(1700 = 5:00 PM)
Minutes - Enter the Minutes
(0 to 59)
Programming Date
Program Time/Date Month (1-12): xx Day (1-31): xx Year (00-99): xx
Month Enter the Month (1 to 12) Day Enter the Day of the Month (1 to 31) Year Enter the current Year with two digits (00 to 99)
Space Sensor Overrides
When a space sensor with override option is used the System Manager or Modular Service Tool can determine and report any units which are currently operating in an override condition. This function requires that a polling device is installed on the loop where the controllers are lo­cated.
Operator Interfaces
T o access the Space Sensor Overrides screen, press the “Override” but­ton located on the System Manager or Modular Service Tool. A screen will appear asking you to enter a unit ID. Enter an ID for any active
11
Technical Guide
General Programming Information
controller on the system and press "Enter". The following screen will appear.
Overrides Screen
SEARCHING!
After the System Manager or Modular Service T ool completes its search, it will list the first unit on the system that is currently in the override mode. Press the previous or next button to scroll through all units that are in the Override Mode.
Overrides Screen Loop = 1 Unit = 59 Override Unit
Alarm Search
The System Manager or the Modular Service T ool can be used to search for all active alarms on the system. From either of the operators inter­faces press the “Alarm” key. The Unit Selection screen below will be displayed. Enter the Unit ID of any unit on the system and press “En­ter”.
The following screen will appear. The operators interface will search for any active alarms on the entire system.
Alarm Screen
SEARCHING!
After the System Manager or Modular Service T ool completes it’s search, it will list the first unit on the system that currently has an active alarm. Press “Enter” to scroll through all the alarms on that particular unit. T o move to the next unit or back to the previous unit use the “Prev” or “Next” arrows to move between units with alarms.
Alarm Search Screen Loop = 1 Unit = 59 Space Sensor Failure
T o clear any alarms that are found you must fix the problem indicated in the alarm. Once the problem is fixed, the alarm will clear from the screen the next time the unit is polled.
Unit Selection Enter Unit ID# Selected ID#: xxxx
12
Operator Interfaces
Programming The MUA II D Controller
Technical Guide
Configuration
In order to correctly setup the MUA II D controller you must first con­figure several parameters in regard to the type of HV AC unit and system you have installed. Most of these values and operating parameters are only set once, at the initial system setup and are never changed.
System Manager Instructions
From any menu screen press the “Setpoint” key. The unit selection screen will appear requesting that you enter the unit ID number. Enter the cor ­rect unit ID number of the MUA II D controller you want to configure and hit the “Enter” key. You will see the screen shown below.
1)Change Setpoint
2)Configure Unit
3)Damper Force ESC) Exit Menu
Press “2” on the keypad to enter Configuration Screen #1.
Modular Service Tool Instructions
From any menu screen press the “Configuration” key. The unit selec­tion screen will appear requesting that you enter the unit ID number. Enter the correct unit ID number of the MUA II D controller you want to configure and hit the “Enter” key. You will then see unit configura­tion screen #1.
Configuration Screen #1
MUA II Cnfg IDxxxx Proof Of Flow Switch Installed: NO (0=No 1=Yes)
If you need proof of airflow before allowing any heating or cooling stages to operate, install a differential pressure switch with a contact closure that is connected to analog input #7 and select this option. If this option is not selected, the air handler assumes there is adequate airflow anytime the fan is running and ignores this signal defaulting input #7 to space humidity.
Configuration Screen #2
temperatures for control of the HVAC unit, the setting should be set to 0=No. If you have an Outside Air Humidity Sensor installed and wish to use dewpoint calculations for unit control, select 1=Y es. If you have a sensor installed and do not select 1=Yes, the sensor readings will be ignored.
Configuration Screen #3
MUA II Cnfg IDxxxx Heat In Dehumidify Installed : Yes (0=No 1=Yes)
If you need to allow heat during dehumidification, select this option. If this option is not selected, the controller assumes that only reheat will be allowed during dehumidification mode.
Configuration Screen #4
MUA II Cnfg IDxxxx Is External Heat Reverse Actn: Yes Use Left/Right Arrow
If you need the modulation of the external heat to be reverse acting, select this option. If this option is not selected, the controller assumes the modulation will be direct acting.
Configuration Screen #5
MUA II Cnfg IDxxxx If External Heat Output Range.: 0 (0=2-10V 1=0-10V)
If you have an external heat device to be controlled by the MUA II D controller, you can select between the voltage ranges that will be used to control the device. The available options are 2-10 VDC and 0-10 VDC.
Configuration Screen #6
MUA II Cnfg IDxxxx OA Humidity Sensor Installed: NO (0=No 1=Yes)
This configuration screen allows the user to indicate whether an Out­side Air Humidity Sensor is to be installed and used to calculate dewpoint settings. If you either don’t have an Outside Air Humidity Sensor installed or have one installed but wish to use only drybulb
Operator Interfaces
MUA II Cnfg IDxxxx Broadcast Outside Temperature:_NO (0=No 1=Yes)
If you have other unit controllers on the system, you can elect to broad­cast the Outside Air Temperature to these units by selecting 1=Yes on this screen. If you don’t have other controllers or they have their own Outside Air Temperature Sensors, select 0=No on this screen.
13
Technical Guide
Programming The MUA II D Controller
Configuration Screen #7
MUA II Cnfg IDxxxx Broadcast Humidity Reading :_NO [0=No 1=Yes]
If you have other unit controllers on the system, you can elect to broad­cast the Outside Humidity to these units by selecting 1=Yes on this screen. If you don’t have other controllers or they have their own Out­side Humidity Sensors, select 0=No on this screen.
Configuration Screen #8- #27
MUA II Cnfg IDxxxx Stage Configurations Rly #xx: Not Used Select Using ‘0’ Key
The first relay on the controller is always reserved for the Supply Fan. The remaining four relays on the main board and the additional 16 re­lays on the expansion relay modules can be configured by pressing the left or right arrow key to change the relay to the desired configuration.
Press “1” on the keypad to enter the first unit setpoint screen.
Modular Service Tool Instructions
From any menu screen press the “Setpoint” key. The unit selection screen will appear requesting that you enter the unit ID number. Enter the cor ­rect unit ID number of the MUA II D controller you want to change setpoints and press the “Enter” key. You will then see setpoint screen #1.
Setpoint Screen #1
MUA II Spts IDxxxx Supply Air Temp
Setpoint.....: xxx°F
The Supply Air Setpoint is the desired temperature to be delivered by the MUA II D at any time during the occupied mode of operation
Description Minimum De fault Maximum
Supply Air Temp Setpoint 50° F 70° F 90° F
Setpoint Screen #2
Possible Relay Descriptions:
Not Used HeatStage CoolStage Gas Reheat External Heat
The MUA II D controller does not require whether you start configur­ing your heating or cooling stages first nor does it require that you uti­lize consecutive relays until all heating or cooling stages have been defined. This method allows the greatest flexibility in the field, but it requires close attention to the wiring of the heating and cooling stages to prevent incorrect and possibly harmful operation. The controller as­sumes that there will only be one relay configured for Hot Gas Reheat and one relay for External Heat Enable, although it doesn’t prevent multiple relays from being selected.
Setpoints
System Manager Instructions
From any menu screen press the “Setpoint” key. The unit selection screen will appear requesting that you enter the unit ID number. Enter the cor ­rect unit ID number of the MUA II D controller you want to change setpoints for and hit the “Enter” key. You will see the screen shown below.
MUA II Spts IDxxxx Staging Deadbands
Cooling....: xxx°F
Heating....: xxx°F
The Cooling Deadband added to the Supply Air Setpoint gives the Cooling Mode Setpoint. When the Outside Air T emperature rises above this setpoint, the MUA II D will go to Cooling Mode. The Heating Deadband subtracted to the Supply Air Setpoint gives the Heating Mode Setpoint. When the Outside Air Temperature drops below this
setpoint, the MUA II D will go to Heating Mode.
Description Minimum Default Maximum
Cooling Deadband 2° F 5° F 20° F
Hea ting D ead ban d 2° F 5° F 20° F
Setpoint Screen #3
MUA II Spts IDxxxx Unoccupied Deadbands
Cooling....: xxx°F
Heating....: xxx°F
14
1)Change Setpoint
2)Configure Unit
3)Damper Force ESC) Exit Menu
The Uncoccupied Cooling Deadband added to the Supply Air Setpoint gives the Unoccupied Cooling Mode Setpoint. When the Space Air
Temperature rises above this setpoint, the MUA II D will go to Unoc­cupied Cooling Mode. The Unoccupied Heating Deadband subtracted
Operator Interfaces
Technical Guide
from the Supply Air Setpoint gives the Unoccupied Heating Mode Setpoint. When the Space Air T emperature drops below this setpoint,
the MUA II D will go to Unoccupied Heating Mode.
If the default setpoint of 30° F is used it will cancel the corresponding unoccupied cooling or unoccupied heating mode.
Descriptio n Minimum Default Maximum
Unoccupied Cooling
Deadband
Unoccupied Heating
Deadband
Cooling
Deadband
Setpoint Heatling
Deadband
Setpoint
30° F 30° F
30° F 30° F
Setpoint Screen #4
MUA II Spts IDxxxx Systems With Re-heat Dewpoint Control Setpoint...: xxx°F
The systems capable of dehumidification will enter this mode of opera­tion when the Outside Air Dewpoint rises above the Dewpoint Setpoint.
Description Minimum Default Maximum
Dewpoint Setpoint 40° F 55° F 80° F
Setpoint Screen #5
Setpoint Screen #6
MUA II Spts IDxxxx Heat Delay During Dehumidifcation Will Occur..: xxxMin
If heating during dehumidification is configured, this is the amount of time the heating call will be delayed after the dehumidification is acti­vated.
Description Minimum Default Maximum
Heat Delay 0 Min 2 Min 10 Min
Setpoint Screen #7
MUA II Spts IDxxxx Alarm Limits Hi SAT Limit.: xxx°F Lo SAT Limit.: xxx°F
If the Supply Air Temperature ever rises above the Hi SAT Limit or drops below the Lo SAT Limit for a user defined period of time, an alarm is generated.
Description Minimum Default Maximum
Hi SA T Limit 50° F 150° F 150 ° F Lo SAT Limit 0° F 0° F 70° F
MUA II Spts IDxxxx Enthalpy Staging
Deadband....: xxxBTU
Hysterisis..: x.xBTU
The Enthalpy Deadband if the amount Enthalpy in the Outside Air needed to activate an extra stage of cooling. The Enthalpy Hysterisis is use to avoid unnecessary cycling of the cooling stages when the Out- side Enthalpy is close to the setpoint.
Description Minimum Default Maximum
Enthalpy Deadband 3 BTU 5 BTU 20 BTU Entha lpy Hysterisis 0.5 BT U 1 BTU 2.5 BTU
Setpoint Screen #8
MUA II Spts IDxxxx Supply Air Alarms If Out Of Range For xxx Minutes
This is the amount of time the Supply Air Temperature must be outside either the Hi or Lo SAT Limit setpoint before it generates an alarm.
Description Minimum Default Maximum
Min utes 0 Min 30 Min 300 M in
Operator Interfaces
15
Technical Guide
Programming The MUA II D Controller
Setpoint Screen #9
MUA II Spts IDxxxx Set Sat Temp Reset SPC= xxx Spt= xxx SPC= xxx Rst= xxx
A Type III Thermistor Sensor connected to AIN 1 can be used to reset the Supply Air Temperature. This screen allows the user to set the tem­perature that the reset will begin at and the new reset Supply Air Tem­perature range.
Description Minimum Default Maximum
Minim um Range 40° F 0° F 100° F
Maxim um R a nge 40° F 0° F 100° F
Reset SAT S pt SAT Spt Spt + 50° F
Setpoint Screen #10
MUA II Spts IDxxxx Set Dewpoint Reset HUM= xxx Spt= xxx HUM= xxx Rst= xxx
An Indoor Humidity Sensor connected to AIN7 can be used to reset the Dewpoint Setpoint. This screen allows the user to set the relative hu­midity percentage that the reset will begin at, and the new reset Dewpoint Setpoint percentage range.
Description Minimum Default Maximum
Minimum Range 0% 0% 100%
Maximum Range 0% 0% 100%
Reset 35° F 55° F Dewpoint Spt
MUA II Spts IDxxxx Heating Stage Delays Staging Up : xx Min Staging Down: xx Min
MUA II Spts IDxxxx Heating Stage Delays Min Run Time: xx Min Min Off Time: xx Min
Both the Heating Stages and the DX Cooling Stages utilize S taging Up and Down delay periods between stages and Minimum Run T imes and Off Times.
Both modes have their own set of staging and run delay times. The Heating timer screens look exactly the same as the cooling except they reference the Heating instead of Cooling.
See the Sequence of Operation Manual for information on how these delays and run times are used.
Description Minimum Default Maximum
Cooling Stage U p 3 Min 3 Min 15 Min
Cooling Stage Down 1 Min 1 Min 15 Min
Cooling Min R un T ime 5 M in 5 Min 15 Min
Cooling Min Off Time 3 Min 3 Min 15 Min
Heating Stage U p 3 Min 3 Min 15 Min
Heating Stage Down 1 Min 1 Min 15 Min
Heating Min Run Time 2 Min 2 Min 15 Min
Heating Min Off Time 1 Min 1 Min 15 Min
Setpoint Screen #11-14
MUA II Spts IDxxxx Cooling Stage Delays Staging Up : xx Min Staging Down: xx Min
MUA II Spts IDxxxx Cooling Stage Delays Min Run Time: xx Min Min Off Time: xx Min
16
Setpoint Screen #15
MUA II Spts IDxxxx External Mod Heat
DeadBand.....: xxx°F
The External Heat Pr oportional deadband is the range through which the external heating device will proportionally modulate.
Description Minimum Default Maximum
Proportional Band 1° F 5° F 30° F
Operator Interfaces
Technical Guide
Setpoint Screen #16
MUA II Spts IDxxxx Push-Button Override Duration : x.x Hr
If the Space T emperature sensor contains the optional push-button over­ride then this is the amount of time the unit will revert to occupied operation whenever the button is pressed during the unoccupied mode.
Description Minimum Default Maximum
Dura tion 0.0 Hr 2.0 Hr 8.0 Hr
Setpoint Screen #17
MUA II Spts IDxxxx Maximum Slide Offset Effect on Spt: x°F
If Space Temperature is used as the controlling sensor for the HVAC unit and it is supplied with the optional Setpoint Slide Adjust, this is the maximum amount the user can adjust the heating and cooling set­points up or down as the slide is moved from the center position to its full up or down position.
Description Minimum Default Maximum
Effect on Spt
F0° F10° F
0°
Setpoint Screen #18
MUA II Spts IDxxxx AHU Scheduled By Schedule Number: x 0=AHU 1-7=Scheduler
Setpoint Screen #19
MUA II Spts IDxxxx Fan Time Delay Before Activation Can Occur..:XXX Sec
This is the time delay that occurs before the fan is activated when the unit switches into the occupied mode from unoccupied mode.
Description Minimum Default Maximum
Fan Time Delay Before
1 Secon d 60 Seco nd 180 Se c on d
Activatio n Can O c cur
Setpoint Screen #20
MUA II Spts IDxxxx Sensor Calibration SAT: xx.x° xx.x OAT: xx.x° xx.x
The Thermistor Type III temperature sensors connected to the MUA II D controller can be calibrated using this screen. Enter a Positive value to increase a reading and a Negative value to decrease a reading.
Description Minimum Default Maximum
Supply Sensor - SAT -100.0° F 0.0° F +100.0° F Outdoor Sensor - OAT -100.0° F 0.0° F +100.0° F
° °
Setpoint Screen #21
MUA II Spts IDxxxx Sensor Calibration Reset Sensor SPC: xx.x° xx.x
°
Normally, the MUA II D controller will use its own internal time clock and week schedules to set the occupied mode of operation. If you have several air handlers you can connect an external scheduling device to the communications loop and program the air handler for the desired schedule to follow. If the MUA II D controller is using its internal sched­ule, enter a ‘0’ for the Schedule Number.
Description Minimum Default Maximum
Schedule Number 0 0 7
Operator Interfaces
If you are using a temperature sensor connected to analog input #1 on the MUA II D controller for resetting the Supply Air Temperature, the Thermistor Type III temperature sensor connected to the MUA II D controller can be calibrated using this screen. Enter a Positive value to increase a reading and a Negative value to decrease a reading.
Description Minimum Default Maximum
Rese t Sensor - R S T -100 .0° F 0.0° F +100.0° F
17
Technical Guide
Programming The MUA II D Controller
Status
The MUA II D controller status screens are accessed by pressing the “Status” button on either the System Manager or the Modular Service Tool. Following are the available status screens and a description of their functions.
Status Screen 1
MUA II vx.xx IDxxxx OCCUPIED Vent Mode Normal Operation
Line 2 Line displays one of the following:
Unoccupied Mode Remote Occupied Occupied Mode Override Mode Holiday Operations FORCED OCCUPIED FORCED UNOCCUPIED FORCED OUTPUT PUSH-BUTTON OVERRIDE
Line 3 Line displays one of the following:
Vent Mode Cooling Mode Heating Mode Dehumidification
Line 4 Line displays one of the following:
Normal Operation Fan Starting Delay
Status Screen 2
Status Screen 4
MUA II vx.xx IDxxxx Dewpoint...: xxx.x°F Dewpnt..Spt: xxx.x°F Outdoor.RH.: xxx.x%
Line 2 - Current Outside Air Dewpoint Line 3 - Current Dewpoint Setpoint Line 4 - Current Outside Humidity
Status Screen 5
MUA II vx.xx IDxxxx Enthalpy...: xx.xBTU Enthlpy Spt: xx.xBTU Enthalpy Db: xx.xBTU
Line 2 - Current Air Enthalpy Line 3 - Current Enthalpy Setpoint Line 4 - Current Enthalpy Deadband
Status Screen 6
MUA II vx.xx IDxxxx Space..Temp: xxx.x°F Reset...Hum: xxx.x%
MUA II vx.xx IDxxxx Supply Air: xxx.x°F Supply..Spt: xxx.x°F
Line 2 - Current Supply Air Temperature Line 3 - Current Supply Air Setpoint Line 4 - Blank Line
Status Screen 3
MUA II vx.xx IDxxxx Outdoor.Air: xxx.x°F Cooling.Spt: xxx.x°F Heating.Spt: xxx.x°F
Line 2 - Current Outdoor Air Temperature Line 3 - Current Cooling Mode Setpoint. Line 4 - Current Heating Mode Setpoint
18
Line 2 - Current Reset Temperature reading Line 3 - Current Reset Humidity reading Line 4 - Blank Line
Status Screen 7
MUA II vx.xx IDxxxx ModGas.Heat: xxx.x% Mod..Reheat: xxx.x% Extrnl Heat: xxx.x%
Line 2 - Current MODGAS II position Line 3 - Current REHEAT II position Line 4 - Current External Heat position
Operator Interfaces
Technical Guide
Status Screen 8-27
MUA II vx.xx IDxxxx Fan Relay : OFF Cool Stage1 : OFF Heat Stage1 : OFF
Line 2 - Current Supply Fan Relay Status
The letters FRC will appear before the colon if this relay is in a force mode.
Line 3 - Current Configurable Relay Status
Description of relay and what it is configured for and it’s current status. The letters FRC will indicate the relay is forced to its current condition.
Line 4 - Current Configurable Relay Status
Description of relay and what it is configured for and it’s current status. The letters FRC will indicate the relay is forced to its current condition.
Status Screen 28
MUA II vx.xx IDxxxx NO ALARMS
Scheduling
The MUA II D controller scheduling screens are accessed by pressing the “Schedule” button on either the System Manager or the Modular Service T ool. Press the number button for the scheduling function you wish to view. All Scheduling, Holiday Functions, Schedule Overrides, Time & Date Functions and Alarm Search Functions are identical to these functions as detailed in the scheduling portion of this manual. See pages 10 through 11 of this manual for complete information in regards to programming these functions for the MUA II D controller.
1)Schedule Overrides
2)Week Schedules
3)Holidays ESC) Exit Menu
Line 2 - Blank Line. Line 3 - NO ALARMS is displayed if none detected. If there are
one or more alarms active, the possible messages are shown below:
NO SUPPLY SENSOR BAD OUTDOOR AIR TEMP NO RELATIVE HUMIDITY FAN PROVING ALARM! LO SUPPLY AIR ALARM! HI SUPPLY AIR ALARM!
Line 4 - Blank Line.
Operator Interfaces
19
Technical Guide
Programming The MUA II D Controller
Outputs Force
Output Force settings are available for testing or troubleshooting the system. These Force settings can only be accessed and programmed from the Modular Service T ool, the System Manager does not allow for programming of this function.
Caution: The Output Force settings should only be applied by
qualified service personnel. Serious damage to the HVAC unit could result from improper use of these Outputs Force settings.
To access the Output Force settings simply press the “Balance-Test” key on the Modular Service Tool. You will then see the unit ID screen. Enter the unit ID of the MUA II D controller you wish to access and press "Enter". The Output Force settings are only available for the MUA II D controller.
Unit Does Not Support The Function Press Any Key To Continue
If you entered the unit ID of a MUA II D controller the following screen will be displayed.
AHU Fan Override Enter Override...: 0
[0=Auto 1=ON 2=OFF]
The first Outputs Force screen allows the AHU Fan Relay to be set for Auto, ON or OFF by entering a 0, 1 or 2 as desired. The default setting is 0=Auto. After completion of all troubleshooting or testing proce­dures all relays should be changed back to this setting. The 1=ON set­ting will force the relay to the ON (energized) position. The 2=OFF selection will force the relay to the OFF (de-energized) position.
The next screen displays the Relay Overrides for Relay 2. After press­ing the "Enter" key the next relay will be displayed. All 20 Relay Over ­ride screens (including the AHU fan relay) are available by pressing the "Enter" key after each setting is made.
Relay Overrides Relay 2 Override: 0
[0=Auto 1=ON 2=OFF]
After the screen for relay 20 is displayed, the first Analog Output Over­ride screen will be displayed.
Analog Output 1 Screen
1)Outputs Force
2)Dampers Force
Press the “1” key to access the Outputs Force screen.
Mod External Heat Analog Output #1 Override Volts: -1.0 [-1.0=Auto]
The default setting for normal operation is -1.0 volts. Voltages between 0 to 10.0 can be set for the Analog Output Override. Press “Enter” after making a setting change.
20
Operator Interfaces
Notes:
Technical Guide
Operator Interfaces
21
Notes:
Technical Guide
22
Operator Interfaces
Notes:
Technical Guide
Operator Interfaces
23
Form: OR-MUAIID-SMST-TGD-01C Printed in the USA December 2004 All rights reserved Copyright 2004
WattMaster Controls Inc. • 8500 NW River Park Drive Parkville, Mo. 64152 Phone (816) 505-1100 www.orioncontrols.com Fax (816) 505-1101
Loading...