Orion MUA II User Manual

Page 1
FACTORY CONTROLS SYSTEM
MUA II Controller
Technical Guide
Page 2
Table Of Contents
Controller Overview ......................................................................................................................................... 3
Features ..................................................................................................................................................................................... 3
Controller Inputs and Outputs ......................................................................................................................... 5
General....................................................................................................................................................................................... 5
Controller Installation & Wiring ....................................................................................................................... 6
General....................................................................................................................................................................................... 6
Controller Mounting .................................................................................................................................................................... 6
MUA Controller Relay Outputs.................................................................................................................................................... 6
Expansion Board Relay Outputs................................................................................................................................................ 6
Important Wiring Considerations .............................................................................................................................................. 6
Expansion Board Installation & Wiring ........................................................................................................... 7
Jumper Settings ......................................................................................................................................................................... 7
Wiring Considerations ............................................................................................................................................................... 8
Wiring Details ................................................................................................................................................... 9
Space Temperature Sensor ....................................................................................................................................................... 9
Outside Air Temperature Sensor ............................................................................................................................................. 10
Remote Occupied Contact ....................................................................................................................................................... 10
Outside Air Humidity Sensor.....................................................................................................................................................11
Space Humidity Sensor ............................................................................................................................................................11
Fan Proof Of Flow Switch ..........................................................................................................................................................11
Start-up & Commissioning ............................................................................................................................ 12
Controller Addressing .............................................................................................................................................................. 12
Power Wiring ............................................................................................................................................................................ 12
Initialization:.............................................................................................................................................................................. 13
Programming The Controller ................................................................................................................................................... 13
Sequence Of Operations ............................................................................................................................... 14
MUA Operation Overview .......................................................................................................................................................... 14
MUA Modes............................................................................................................................................................................... 14
Initialization............................................................................................................................................................................... 16
MUA II Configuration & Setup ................................................................................................................................................... 16
Scheduling ............................................................................................................................................................................... 17
Force Modes or Overrides....................................................................................................... ................................................. 17
Internal Trend Logging ............................................................................................................................................................. 18
Troubleshooting ............................................................................................................................................. 18
Using LED’s To Verify Operation .............................................................................................................................................. 18
Appendix ........................................................................................................................................................ 20
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1 100 PH: (816) 505-1100 · F AX: (816) 505-1 101 · E-mail: mail@wattmaster .com Visit our web site at www.orioncontrols.com Form: AO-MUAII-TGD-01A Copyright 2002 WattMaster Controls, Inc. AAON is a registered trademark of AAON, Inc., Tulsa, OK. WattMaster Controls, Inc. assumes no responsibility for errors, or omissions. This document is subject to change without notice.
Page 3
Controller Overview
Technical Guide
Features
The MUA II Controller Board is designed with 5 usable analog inputs, and 5 relay outputs. The controllers input and output capabilities can be expanded by use of either 2 slot or 4 slot expansion boards that plug into the MUA II Controller by means of a modular cable. The MUA II Controller is designed for used with Makeup Air HVAC units. Features
include the following:
Up to 8 Stages of Cooling (4 on board, 4 more with expansion board)
Up to 8 Stages of Heating (4 on board, 4 more with expansion board)
External Modulating Heat
Fan Proving Interlock
Supply Air Setpoint Reset From Temperature Input
Dewpoint Setpoint Reset From Humidity Input
Accepts Remote Occupied Signal
De-Humidification Capable
7 Day, 2 Event per Day Scheduler Built In
14 Day Holiday Scheduler Built In
Internal Trend Logging
Direct Connection With MODGAS II And REHEAT II
Controllers
Most makeup air control configurations can be configured with the standard MUA II Controller. If the application requires more outputs, optional relay expansion boards are available from the factory to provide for additional relay outputs as required. These expansion boards are installed on eithMUA II Controller board via a modular cable connection.
The available expansion board configurations allow for up to 16 additional binary (relay) outputs. The various expansion boards connect to the expansion board base. Jumpers must be set according to the board type installed. Up to 4 Relay Output Expansion Boards can be
installed on the expansion base board connected to the controller.
.20 Dia. Typ. of 4
7.3”
C21
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7 PWR
LD8 LED1
LD9 LED2
R1
U7
RV1 VREFADJ
INPUTS
+VDC
AIN1
AIN2 AIN3
AIN4
AIN5
GND GND AOUT1
AOUT2
AIN7 GND
PJ1
TB3
PRESSURE SENSOR
CX1
RN1
1
U5
RS-485
COMM
1
RN3
P1
+VREF
5.11V
TESTPOINT
EWDOG
RN5
C10
C12
C17
R26
EXPANSION
6.2“
U3
CX2
U2
U1
RAM
HH
U6
C1
R28
ADD
ADDRESS
1
2 4
PU1
8
D6
16
PU2
32
D7
TOKEN
PU3
NETWORK
D8 PU4
SW1 D9 PU5
D11 PU7
D14
D15
C20
PJ2
X2
0-1
0-5
VDC
VDC
JP1
U13
R15
C14
R19
CX13
U15
C15
R22
R24
R25
CX15
PJ3
EPROM
TUC-5RPLUS
YS101816REV. 2
U10
C11
U14
D17
CX3
(1MEG)
CX6
C2
C3
CX10
CX12
U12
CX14
D18
C18
T' STAT
D1
CX4
U4
RLY1
D2
RLY2
D3
PAL
1
RLY3
D4
RN2
RLY4
D5
X1
RLY5
1
RN4
U9
C7
D10
R7
L1
D13
D12 R13
SC1
D19
C19
VR1
VR2
CX8
R10
D16
COM1-3
COM4-5
R6
R11
R27
V6
C9
R1 R2 R3
R4
R5
U8
V1
V2
V3
V4
V5
U11
C13
C16
TB4
GND
POWER
24VAC
TB2
6.6”
6.7”
Figure 1: MUA II Controller Dimensions
MUA II Controller 3
Page 4
Technical Guide
Controller Overview
2.12
TB2
TB1
C6
GND
24VAC-IN
PWR
LD1
R14
D3
VR2
VR3
4.73
VR4
VR5
VR6
R13
MC
7824CT
CX3
MC
7805ACT
MC
7812CT
MC
7824CT
MC
7824CT
2 Slot Expansion
Base Board
C1
C2 C3
C4 C5
4.24
GND
+24VDC-OUT
YS101780
4.00
4.00
0.28
TB2
TB1
GND
+24VDC-OUT
GND
24VAC-IN
PJ2
PJ1
R11
R9
D2D1 R8 R7
P1
U1
P82B715P
CX1
JP1
R1
R2 R3
U2
P2 JP2
LM358N
CX2
VR1
R10
R4
2 SLOT MODULAR I/O
R5 R6
R12
5.96
5.40
C8
VR2
VR3
VR4
VR5
VR6
9.52
VR7
VR8
LD1
PWR
R20
D3
7824CT
7805ACT
7812CT
7824CT
7824CT
7824CT
7824CT
4 SLOTMODULAR I/O BD.
YS101782
PJ2
PJ1
R17
R19
CX3
R15
D1 D2
C1
R13 R14
P1
U1
P82B715P
C2
C3
C4
C5
C6
C7
CX1
JP1
R1 R2 R3
U2
P2
LM358N
CX2
JP2
R5R4 R6
P3
JP3
R9R8R7
P4
VR1
R16
JP4
R10 R11 R12
R18
8.29
8.96
0.28
Figure 2: Expansion Base Boards Dimensions
V4
4RLY IO BD.
K4
YS101790
4.00
K3
K4
OMRON
24VDC
G5L-114P-PS
OMRON
24VDC
G5L-114P-PS
K3
RN1
1.67
UL 5A250VAC
CONTACT:
UL 5A250VAC
CONTACT:
K2
OMRON
24VDC
G5L-114P-PS
OMRON
24VDC
G5L-114P-PS
K1
2.12
4 Slot Expansion
Base Board
TB1
V1
UL 5A250VAC
CONTACT:
K1
UL 5A250VAC
CONTACT:
K2
4.24
4.24
Figure 3: Relay Expansion Board Dimensions
4
U3
CX3
PCF8574P
74HC04N
U2
CX2
AN
ID
U1
ULN2803A/
PHILIPS
TL
HA
CX1
P1
MUA II Controller
Page 5
Technical Guide
RS-485 Communications Loop Connection
RS-485 Communications Driver Chip
Comm LED
Power LED
Diagnostic Blink Code LED
Pull-up Resistors For Analog Inputs
Analog Input And Output Terminal Block
Pressure Sensor
(AIN6 Modular Connection)
Not Used
Modular Service Tool - Mini Din Connector
C21
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7 PWR
LD8
LED1
LD9
LED2
R1
U7
RV1 VREF ADJ
INPUTS
+VDC
AIN1
AIN2 AIN3
AIN4
AIN5
GND GND AOUT1
AOUT2
AIN7 GND
PJ1
TB3
PRESSURE
SENSOR
Typical Pin 1 Indicator
CX1
RN1
1
U1
U5
RS-485
COMM
1
RN3
P1
+VREF
5.11V
TEST POINT
EWDOG
RN5
C10
C12
D15
C17
C20
R26
EXPANSION
Mounting Hole
EPROM
RAM
Chip
Chip
ADD
1
2 4
8 16 32 TOKEN NETWORK
VDC
JP1
PJ3
X2
R15
C14
R19
C15
R22
R24
R25
U3
EPROM
TUC-5R PLUS
YS101816 REV.2
C2
CX10
U10
C11
U12
CX14
U14
D17
T'STAT
(1 MEG)
C3
CX3
CX4
U4
PAL
1
RN2
CX6
X1
1
RN4
U9
C7
D10
CX12
D12
R13
SC1
D19
D18
C19
C18
VR1
CX2
U2
RAM
HH
U6
C1
R28
ADDRESS
PU1 D6 PU2
D7 PU3
D8 PU4
SW1 D9 PU5
D11 PU7
0-1
0-5
VDC
D14
U13
CX13
U15
CX15
PJ2
PAL Chip
D1
RLY1
D2
RLY2
D3
V1
V2
V3
COM1-3
R1 R2
RLY3
D4
R3
R4
R5
RLY4
RLY5
R7
COM4-5
D5
CX8
L1
R10
D13
D16
TB2
V4
V5
U8
R6
C9
R11
U11
C13
C16
TB4
GND
R27
V6
POWER
24VAC
VR2
Typ o f 4
Mounting Backplate
Relay Output Terminal Block
Address Switch
EEPROM
24 VAC Power Input
Expansion Board (Modular Connection)
Figure 4: MUA II Controller Component Locations
Controller Inputs and Outputs
General
The following inputs and outputs are available on the MUA II controller and/or the relay expansion boards that can be added to the main control­ler board expansion port. For component locations of the inputs on the MUA II Controller see Figure 4. For wiring of inputs and outputs see Figure 5 and 6.
MUA II Controller Analog Inputs:
Input #1: Reset Temperature Sensor
A space temperature sensor can be connected here and used for modu­lation of the Supply Air Setpoint. At a specified Space Temperature Setpoint the Supply Air Setpoint will be reset towards the Maximum Supply Air Temperature Setpoint
VAV/CAV Controller
Not Used
Real Time Clock Chip
Input #2: Supply Air Temperature
The Supply Air Temperature sensor is connected to this input. This sensor is used to control heating and cooling staging.
Input #3: Remote Occupied Contact
This input can be configured to monitor a contact closure from another building automation system, that indicates that the equipment should be operating in the occupied mode. If the remote occupied signal is being monitored, you must program all the internal schedules to be zero for both the start and stop times on every day of the week.
5
Page 6
Technical Guide
Controller Inputs and Outputs
Input #4 - Outdoor Air Temperature
The Outdoor Air Temperature Sensor is connected to this input. The Outdoor Air Temperature Sensor is used to initiate the heating, cooling and vent modes of operation. It is also used in combination with the outdoor air humidity to calculate the Dewpoint Temperature.
Input #5 - Outdoor Air Humidity
This input is used for an Outdoor Air Humidity sensor that, combined with the outdoor air temperature, is used to calculate a Dewpoint Tem­perature for the purpose of dehumidification.
Input #6 - Not Used
Input #7 - Fan Proof of Flow Switch or Reset Humidity Sensor
A Proof of Flow Switch that provides a contact closure whenever the fan is moving air, can be monitored on this input. If this contact opens while the fan is on, all heating and cooling is suspended. This is an optional item. If a switch is installed, the user must configure the MUA II to utilize the signal. If this option is not configured the unit will default to reset humidity input. An indoor Humidity Sensor can be installed on this input instead of the Proof of Flow Switch. This extra Humidity Sensor is used to provide for reset of the Dewpoint setpoint
Relay Outputs
Relay #1 - Fan (Enable)
This is a non-configurable output.
Relay #2 - #5 Configurable Relays
These relays are located on the MUA Controller. Configuration order and options are the same as for relays #6 -#21 as outlined in the informa­tion for these relays that follows.
Relay #6 – #21 Configurable Relays
These relays are available by using Relay Expansion boards connected to the MUA II controller. Relays can be configured in any order but we recommend that they be configured in the following order:
1. Heating (aux. heating) stages
2. Cooling (compressor) stages
3. Gas Reheat Control for De-Humidification
4. External Heat Enable
You can have up to 8 stages of Heating (aux. heating) and 8 stages of Cooling (compressors) as well as individual relays assigned to options 3 and 4 above.
Analog Output
AOUT1
The MUA II controller has 1 Analog Output available. The usable out­put is located at terminal AOUT1and is used for controlling an external heating device. Voltage ranges for this output are user configurable for either a 0-10 VDC or 2-10 VDC signal.
Controller Installation & Wiring
General
Correct wiring of the MUA II controller is the most important factor in the overall success of the controller installation process. In general most MUA II controllers are factory installed and wired at the AAON factory. It is also possible to purchase these controllers directly from W attMaster Controls for installation in the field. Some of the following information pertains to field wiring and may not apply to your installa­tion since it was pre-wired at the factory. However, in the unlikely event that troubleshooting of the controller is required, it is a good idea to be familiar with the system wiring, no matter if it was factory or field wired.
Controller Mounting
When the controller is to be field mounted, it is important to mount the controller in a location that is free from extreme high or low tempera­tures, moisture dust and dirt. It is recommended that it be installed in the HV AC unit control panel. If this is not practical, it should be mounted in a separate control enclosure that is weathertight. Be careful not to damage the electronic components when mounting the controller. Re­move the controller from its backplate. Mark the control enclosure base using the backplate as a template. Drill pilot holes in the enclosure base and secure the backplate to it using sheet metal screws. Do not allow metal shavings to fall onto the circuit board. Reattach the controller to the backplate.
Important Wiring Considerations
Please carefully read and apply the following information when wiring the MUA II controller. See Figure 5 for MUA II controller wiring diagram.
1. All 24 VAC wiring must be connected so that all ground wires remain common. Failure to follow this procedure can result in damage to the controller and connected devices.
2. All wiring is to be in accordance with local and national electrical codes and specifications.
3. Minimum wire size for 24 VAC wiring should be 18 gauge.
4. Minimum wire size for all sensors should be 24 gauge. Some sensors require 2 conductor wire and some require 3 conductor.
5. Be sure that all wiring connections are properly inserted and tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals which could potentially cause a short circuit.
6
MUA II Controller
Page 7
Technical Guide
6. When communication wiring is to be used to interconnect controllers together or to connect to other communication devices, all wiring must be minimum 18 gauge, 2 conductor, twisted pair with shield.
Connect To Next Controller And/Or
MiniLink PD On Local Loop For Stand Alone Applications Connect To System Manager
C21
CX1
RN1
All Comm Loop Wiring Is
Straight Thru
TtoT
RtoR
SHLD to SHLD
Analog Inputs
See Individual Sensor
Wiring Diagrams For
Detailed Sensor Wiring
0-10 VDC
0r 2-10 VDC
Connect To
External Heat
Device If Used
Local Loop RS-485
9600 Baud
+ _
1
T
SHLD
R
COMM
LD7 PWR
LED1
LD9 LED2
U7
+VDC
AIN1
AIN2 AIN3
AIN4
AIN5
GND GND AOUT1
AOUT2
AIN7 GND
PJ1
CX5
RV1 VREFADJ
U1
U5
RS-485
COMM
1
RN3
P1
+VREF
5.11V
TESTPOINT
EWDOG
RN5
C10
C12
C17
C20
R26
EXPANSION
HH
C1
R28
ADDRESS
PU1 D6 PU2
D7 PU3
D8 PU4
D9 PU5
D11 PU7
D14
U13
D15
PJ2
TB1
COMM
LD6
LD8
R1
INPUTS
TB3
PRESSURE SENSOR
Note: All Temperature Sensors Must Be Thermistor Type III Which Provide 10K Ohms Resistance @77 Deg. F
Figure 5: MUA II Controller Wiring
MUA II Controller
U3
CX2
U2
EPROM
RAM
TUC-5RPLUS
(1MEG)
YS101816REV. 2
U6
CX6
C2
PHILIPS
ADD
SW1
0-5
0-1
VDC
VDC
CX13
U15
CX15
1 2 4 8
16 32 TOKEN NETWORK
JP1
PJ3
C3
CX10
U10
CX12
C11
X2
R15
U12
CX14
C14
R19
U14
C15
R22
R24
R25
D18
D17
C18
T' STAT
Connect To Expansion Board Base (When Used)
7. Before applying power to the MUA II controller, be sure to recheck all wiring connections and terminations
thoroughly.
CX3
X1
D1
CX4
U4
RLY1
D2
RLY2
D3
PAL
1
RLY3
D4
RN2
RLY4
D5
RLY5
1
RN4
U9
C7
D10
R7
L1
D13
D12 R13
SC1
D19
C19
7824CT
M
VR1
VR2
R10
CX8
D16
COM1-3
COM4-5
R11
R27
V1
V2
R1 R2 R3
R4
R5
U8
NE5090NPB3192 0PS
R6
C9
9936
U11
MC34064A
C13
C16
GND
V6
POWER
24VAC
V3
TB2
V4
V5
TB4
R - 24VAC
G - Fan ON/OFF Only
Relay Output Dry Contacts R2 Thru R5 May Be User Configured For The Following:
1 - Heating (Aux. Heating)Stages 2 - Cooling (Compressor) Stages 3 - Gas Reheat Control For Dehumidification 4 - External Heat Enable
Note: Up To 16 More Relays Are Available By Adding Relay Expansion Boards. All Expansion Board Relay Outputs Are User Configurable As Listed Above.
GND
24VAC
Required VA For
Transformer = 8VA
Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers.
Line Voltage
Expansion Board Installation & Wiring
Jumper Settings
The expansion boards are connected to the MUA II Controller with a modular cable. Up to 2 Expansion Base Boards can be populated with expansion boards to provide additional inputs and outputs. The expan-
4 Relay Output Expansion Board
K1
V1
Relay Outputs - 6 Through 21
N.O. Contact #6 - Configurable N.O. Contact #7 - Configurable
N.O. Contact #8 - Configurable
N.O. Contact #9 - Configurable
Common
TB1
V4
4RLY IO BD.
UL 5A250VAC
CONTACT: 24VDC G5L-114P-PS
OMRON
UL 5A250VAC
CONTACT: 24VDC G5L-114P-PS
OMRON
K4
YS101790
Relays 6-9 Relays 10-13
Figure 6: Expansion Board Jumper Settings
VAV/CAV Controller
sion boards can be placed on the expansion base board in any order, however, the jumpers on the Expansion Base Board must be set cor­rectly for proper operation. See Figure 6 for correct jumper settings and jumper locations.
K2
UL 5A250VAC CONTACT:
K1
24VDC
G5L-114P-PS
OMRON
K2
UL 5A250VAC CONTACT: 24VDC
G5L-114P-PS
K3
RN1
OMRON
K3
K4
Relays 14-17 Relays 18-21
CX1
P1
ULN2803A/
PHILIPS
TL HA AN ID
U1
CX2
74HC04N
U2
PCF8574P
Address Jumpers
Jumpers Under Expansion Board To Be Set As Shown
7
Page 8
Technical Guide
Expansion Board Installation & Wiring
Wiring Considerations
The expansion base boards must be connected to 24 VAC as shown in the wiring diagram below. As noted below, the power requirement for a
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC.
Failure to observe polarity will result in damage to one or more of the boards. Expansion
Boards must be wired in such a way that power to both the expansion boards and the
controller are always powered together. Loss of power to the expansion board will cause the
controller to become inoperative until power is restored to the expansion board.
Relay Output #6 - Configurable (N.O. Dry Contact) Relay Output #7 - Configurable (N.O. Dry Contact)
Relay Output #8 - Configurable (N.O. Dry Contact)
Relay Output #9 - Configurable (N.O. Dry Contact)
Common
two slot base board is 10 VA. A four slot base board requires 20 VA. Be sure that the transformer used for powering the base boards meets these minimums. See Figure 7 for complete wiring details.
WARNING!!
24VAC
POWER
INPUT
Connect to
MUA
Controller Board
24VAC
GND
4RLY IO BD.
YS101790
Relay Output #10 - Configurable (N.O. Dry Contact) Relay Output #11 - Configurable (N.O. Dry Contact)
Relay Output #12 - Configurable (N.O. Dry Contact)
Relay Output #13 - Configurable (N.O. Dry Contact)
Relay Output #14 - Configurable (N.O. Dry Contact) Relay Output #15 - Configurable (N.O. Dry Contact)
Relay Output #16 - Configurable (N.O. Dry Contact)
Relay Output #17 - Configurable (N.O. Dry Contact)
Relay Output #18 - Configurable (N.O. Dry Contact) Relay Output #19 - Configurable (N.O. Dry Contact)
Relay Output #20 - Configurable (N.O. Dry Contact)
Relay Output #21 - Configurable (N.O. Dry Contact)
Figure 7: Expansion Board Wiring
Common
Common
Common
4RLY IO BD.
4RLY IO BD.
4RLY IO BD.
YS101790
YS101790
YS101790
8
MUA II Controller
Page 9
Wiring Details
Technical Guide
Space Temperature Sensor
A Space Temperature Sensor is used with the MUA II controller to provide for Supply Air Temperature Reset. At a specified Space Tem­perature Setpoint the Supply Air Setpoint will be reset towards the
Space Temperature Sensor
TMP
GND
Figure 8: Space Temperature Sensor Wiring
Supply Air Temperature Sensor
The Supply Air Temperature Sensor should be mounted in the unit discharge plenum or in the supply air duct.
The Supply Air Temperature Sensors are 10K Type III thermistor sen­sors.
For systems that are only using the MUA II controller and are not supplied with The MODGAS II or MHGRV II controllers, the Supply Air Temperature Sensor must be wired as shown in the illustration below for proper operation of the controller. See Figure 9 for detailed sensor wiring. The exception to this is when the MODGAS II and/or the MHGR V II controllers are also being used on the HVAC unit the MUA II controller is installed on. See the Caution note regarding this configuartion that follows.
Maximum Supply Air Temperature Setpoint. For more information on the operation of this sequence see the Sequence Of Operation section of this manual. This sensor is a 10K Type III thermistor sensor. See Fig- ure 8 for complete sensor wiring details.
INPUTS
+VDC AIN1
AIN2 AIN3 AIN4 AIN5 GND
GND
AOUT1 AOUT2 AIN7
GND
MUA II Unit Controller Board
Caution: If your HVAC unit is supplied with the
MODGAS II controller with or without an MHGRV II controller, the Supply Air T emperature Sensor must always be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGR V II controller, the SupplyAir Temperature Sensor must be connected to the MHGRV II controller, not the MUA II controller. If you have either of these controllers on your HVAC unit and connect the Supply Air Temperature Sensor to the MUA II controller, your controls will not function correctly.
See the MODGAS II and/or the MHGRV II Technical Guide(s) for Supply Air Temperature Sensor wiring terminations and information.
Supply
Air Temperature
Sensor
Mount In MUA
Unit Supply
Air Duct
Figure 9: Supply Air Temperature Sensor Wiring
VAV/CAV Controller
INPUTS
+VDC AIN1
AIN2 AIN3 AIN4 AIN5 GND GND
AOUT1
AOUT2 AIN7 GND
MUA II Controller Board
9
Page 10
Technical Guide
Wiring Details
Outside Air Temperature Sensor
The Outside Air Sensor must be wired as shown in the illustration be­low for proper operation. The Outside Air T emperature Sensor is a 10K Type III thermistor sensor. The sensor should be mounted in the up­right position as shown, in an area that is protected from the elements and direct sunlight. Be sure to make the wiring splices inside of the Outside Air T emperature Sensor weathertight enclosure. See Figure 10 for detailed wiring.
Outdoor
Air Temperature
Sensor
Make Splice Connections Inside Sensor Enclosure As Shown. Seal All Conduit Fittings With Silicone Sealant.
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
Caution: Be sure to mount the Outside Air Sensor in an
area that is not exposed to direct sunlight. A shaded area under the eve of the building or under the HV AC unit rainhood is normally a good location. If sensor is not located as specified, erroneous outside air temperature readings will result. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide raintight seal. W ater can damage sensor!
INPUTS
+VDC AIN1
AIN2 AIN3 AIN4 AIN5 GND
GND AOUT1 AOUT2
AIN7
GND
Figure 10: Outside Air Temperature Sensor Wiring
Remote Occupied Contact
A Remote Occupied contact closure supplied from another Building Automation System device can be used to enable Occupied and Unoccu-
Remote Occupied
Contact
(Relay By Others)
pied modes on the MUA II controller. This relay contact must be a dry contact and be wired as shown below. See Figur e 11 below for detailed wiring .
INPUTS
+VDC AIN1
AIN2 AIN3 AIN4 AIN5 GND GND
AOUT1
AOUT2 AIN7 GND
MUA II Controller Board
Figure 11: Remote Occupied Contact Wiring
10
MUA II Controller
Page 11
Technical Guide
GND
INPUTS
GND
AOUT1 AOUT2
GND
+VDC AIN1
AIN2 AIN3 AIN4 AIN5
AIN7
MUA II Controller Board
Fan Proof Of Flow
Switch
Outside Air Humidity Sensor
If you want to install a humidity sensor onto the MUA II controller, it is important that you follow these instructions. There are 2 terminals labeled “H+” and “H-”. T erminal “H+” will connect to the connection labeled “+VDC” on the analog input block. See Figure 12. Terminal “H-” connects to the connection labeled “AIN 5” on the analog input block. Also the resistor labeled “PU5” needs to be removed. Lastly, a
Outdoor
Air Humidity
Sensor - 4-20mA
H+(T1)
H-(T4)
Seal All Conduit Fittings With Silicone Sealant.
250 Ohm
Resistor
(Shipped With Sensor)
To be Installed Between
AIN5 and GND
If YouAre Using The Standard Factory Supplied Humidity Sensor, It Has Terminals Labeled “H+ (T1)” And “H- (T4)”. Terminal “H+ (T1)” Is The Voltage Input And Should Be Connected To The Terminal Labeled +VDC On The VAV/CAV Controller. Terminal “H- (T4)” Is The 4-20 Ma Output Signal And Should Be Connected To The Terminal Labeled AIN 5 On The VAV/CAV Controller. Should Be Connected Between AIN 5 AndA Ground Terminal On The VAV/CAV Controller. Factory Is Used, Refer To The Wiring Instructions Shipped With The Sensor.
A Factory Supplied 250 Ohm Resistor
If A Sensor Other Than The One Supplied By The
supplied 250 Ohm, 1/4 W att, 1% resistor needs to be installed between “AIN 5” and “GND”. See Figure 12 for detailed wiring.
Warning: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe the correct polarity will result in damage to the Humidity Sensor or controller.
The Pull-up Resistor (PU5)
INPUTS
+VDC AIN1 AIN2 AIN3 AIN4 AIN5 GND
GND AOUT1 AOUT2
AIN7
GND
MUA II Controller Board
Must Be Removed When Using A 4-20ma Device
Figure 12: Humidity Sensor Wiring
Space Humidity Sensor
A Space Humidity Sensor or a Fan Proof Of Flow Switch can be con­nected to AIN7 on the MUA II controller. Shown below is the Space Humidity Sensor wiring.
If YouAre Using The Standard Factory Supplied Humidity Sensor, It Has Terminals Labeled “+ (T1)”And - (T2)”. Terminal + (T1)” Is The Voltage Input And Should Be Connected To The Terminal Labeled +VDC On The MUA II Controller. Terminal “- (T2)” Is The 4-20 Ma Output Signal And Should Be Connected ToThe Terminal Labeled AIN7 On The MUA II Controller. Between AIN 7 AndA Ground Terminal On The MUAII Controller. Sensor Other Than The One Supplied By The Factory Is Used, Refer To The Wiring Instructions Shipped With The Sensor.
Figure 13: Space Humidity Sensor Wiring
VAV/CAV Controller
A Factory Supplied 250 Ohm Resistor Should Be Connected
+ (T1)
- (T2)
250 Ohm
Resistor
(Shipped With Sensor)
To be Installed Between
AIN7 and GND
The Pull-up Resistor (PU7) Must Be Removed When Using A 4-20ma Device
If A
INPUTS
+VDC AIN1 AIN2 AIN3 AIN4 AIN5 GND GND
AOUT1
AOUT2 AIN7 GND
MUA II Controller Board
Fan Proof Of Flow Switch
If a Fan Proof Of Flow Switch is required then obviously the Space Humidity Sensor option is not available. By the same token if a Space Humidity Sensor is required then the Fan Proof Of Flow Switch option is not available. See Fan Proof Of Flow Switch wiring below.
Figure 14: Fan Proof Of Flow Switch Wiring
11
Page 12
Technical Guide
Start-up & Commissioning
In order to have a trouble free start-up it is important to follow a few simple procedures. Before applying power for the first time it is very important to correctly address the controller and run through a few simple checks.
Controller Addressing
All MUA II controllers are equipped with address switches. If the MUA II controller is to operate as a stand alone system (not connected to any other controllers) the controller address switch should be set for address 1. When using the Modular Service T ool or System Manager to program and configure the MUA II controller you would enter this address to communicate with the controller. When the system is to be connected to other HVAC unit controllers on a communication loop, each controllers address switch must be set with a unique address be­tween 1 and 59. See Figure 15 for address switch setting information. For detailed information regarding communication wiring and connec­tion for interconnected and networked systems, please see the Orion System Installation & Troubleshooting Guide.
Power Wiring
One of the most important checks to make before powering up the system for the first time, is to confirm proper voltage and transformer sizing for the controller. Each MUA II controller requires 10 VA of power delivered to it at 24 VAC. Each 2 slot expansion board requires 5
V A at 24 VAC and each 4 slot expansion board requires 10 V A at 24 VAC. Y ou may use separate transformers for each device (preferred) or power several devices from a common transformer. If several devices are to be powered from a single transformer correct polarity must be followed.
Warning: Observe Polarity! All boards must be wired with
GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Boards must be wired in sucha way that power to both the expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the controller to become inoperative until power is restored to the expansion board.
Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confirm that all sensors required for your system are mounted in the appropriate lo­cation and wired into the correct terminals on the MUA II controller . Be sure any expansion boards connected to the MUA II controller are also correctly wired just as you did for the MUA II controller.
After all the above wiring checks are complete, apply power to the MUA II controller and all expansion boards connected to it.
This Switch Should Be In The OFF Position As Shown
ADDRESS ADD
Address Switch Shown Is
Set For Address 1
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 59
INPUTS
+VDC
AIN1
AIN2 AIN3
AIN4
AIN5
GND
AOUT1
AOUT2
GND
TB3
PRESSURE SENSOR
ADDRESS ADD
Controller Address Switch
The Address For Each Controller
RN5
C10
GND
C12
AIN7
C17
PJ1
Address Switch Shown Is
ADDRESS
PU1 D6 PU2
D7 PU3
D8 PU4
D9 PU5
D11 PU7
D14
U13
D15
C20
R26
PJ2
1 2 4
8 16 32 TOKEN NETWORK
Set For Address 13
SW1
0-5
VDC
CX13
U15
CX15
EXPANSION
ADDRESS ADD
ADD
1
2
4
8 16
32
TOKEN
NETWORK
X2
0-1
VDC
JP1
C14
C15
PJ3
Note:
The Power To The Controller Must Be Removed And Reconnected After Changing The Address Switch Settings
Caution
Disconnect All Communication Loop Wiring From The Controller Before Removing Power From The Controller. Reconnect Power And Then Reconnect Communication Loop Wiring.
CX10
U10
C11
R15
U12
CX14
R19
U14
R22
R24
R25
D17
C7
D10
R7
CX12
D18
C18
L1
D12
R13
SC1
D19
C19
VR1
VR2
R6
C9
R10
D13
R11
U11
C13
C16
TB4
GND
R27
D16
V6
POWER
24VAC
Figure 15: MUA II Controller Address Switch Setting
12
MUA II Controller
Page 13
Technical Guide
Initialization:
Upon applying power to the MUA II controller the following should occur:
On system powerup a 30 second start-up delay is performed where all default setpoints are initialized, LED’s are initialized and all outputs are turned off.
When power is first applied, LED2 is turned off for 5 seconds. At this time the LED will “blink” to indicate the setting of the address switch and then extinguish for another 5 seconds. The LED will now “blink” for a 30 second start-up delay to protect the fan and other components from short cycling during intermittent power conditions. If all inputs are operating correctly it will blink once every ten seconds.
The PWR LED should glow continuously. If this is a stand alone or interconnected system, The COMM LED should also glow continu­ously after its initial start-up routine. If this is a networked system, The COMM LED should flicker approximately once every second to indi­cate communications are occurring. If the LEDs are behaving as indi­cated, proceed to the next step. If the LEDs fail to light or do not behave as indicated, please proceed to the troubleshooting section of this manual to diagnose and correct the problem before proceeding with the start-up process.
Programming The Controller
The next step is programming the controller for your specific require­ments. In order to configure and program the MUA II controller you must have a central operators interface or a personal computer with the Prism computer front end software installed. Two different central op­erators interfaces are available for programming of the MUA II control­ler. You may use either the Modular Service Tool or the Modular Sys- tem Manager to access the status and setpoints of any controller on your communications loop. See the Modular Service T ool and System Man­ager Programming guide for MUA II controller programming. If you are going to use a personal computer and the Prism computer front end software, please see the Orion Prism Programming Manual. No matter which operators interface you use, it is recommended that you proceed with the programming and setup of the controller in the order that follows:
1.) Configure The Controller For Your Application
2.) Program The Controller Setpoints.
3.) Program The Controller Operation Schedules.
4.) Set The Controller Current Time And Date.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
UP
PREV
DOWN
ESC
ENTER
13
4
708
DEC
NEXT
CLEAR
2
5
6
9
MINUS
-
5.) Review Controller Status Screens T o Verify System Operation And Correct Controller Configuration
System Manager
STATUS
SETPOINTS
NEXT
SCHEDULES
OVERRIDES
ALARMS
13
2
MINUS
-
PREV
6
9
4
708
DEC
5
UP
DOWN
ENTER
CLEAR
ESC
Figure 16: Operators Interfaces
VAV/CAV Controller
13
Page 14
Technical Guide
Sequence Of Operations
MUA Operation Overview
The MUA controller is designed to control an HVAC unit to provide fresh air of neutral temperature (and humidity if required) into a building that has a net air loss caused by air being exhausted from the building. The MUA controlled HVAC unit can have heating, cooling and/or dehu­midification capabilities. Heating and cooling sequences are controlled based on outside air temperature. Whenever the outside air temperature is outside of the heating or cooling setpoints, the appropriate heating or cooling staging will be initiated to bring the supply air temperature within the required range and maintain it at that condition.
The outside air humidity and temperature in the form of a dewpoint temperature setpoint control the MUA controller dehumidification se­quence. Since dewpoint temperature by definition is the temperature at which water vapor condenses from the air mixture, it is good indicator of when dehumidification is required. The controller uses the outside air humidity sensor in conjunction with an outside air temperature sensor to calculate the dewpoint temperature of the outside air. If the outside air dewpoint exceeds the dewpoint setpoint with respect to the outside air temperature, the dehumidification sequence will be initiated to bring the supply air dewpoint temperature within the required range and maintain it at that condition.
MUA Modes
This controller has a total of 6 modes of operation that behave differ­ently. These are divided into 1 unoccupied mode and 5 occupied modes. The operation of each of these modes is explained on the following pages.
Figure 18 illustrates the Temperature Protect Modes which are deter­mined by the Supply Air Temperature.
Cool
Cool Setpoint
=
Dehumidification
Heat Setpoint
=
(OAT)
Outdoor Air Temperature
Vent
Heat
Cool Setpoint
Heat Setpoint
Dewpoint Temperature
Supply Setpoint + Cool Deadband
Dewpoint Setpoint
Supply Setpoint - Heat Deadband
Figure 17: Operational Modes
Unoccupied
In this mode the controller will shut off the cooling, the heating and the blower.
Occupied
In the occupied cycle the unit has the following modes:
Cooling
Vent
Dehumidification
Heating
Temperature Protect Mode
The diagrams that follow depict the operational modes of the MUA II controller.
Figure 17 illustrates how the OAT (Outdoor Air Temperature) and the Dewpoint Temperature initiate the various normal operational modes.
0F°
Low SAT
Cutoff Limit
(SAT) Supply Air Temperature
High SAT
Cutoff Limit
150 F°
Figure 18: Temperature Protect Mode
Cool
This mode occurs when the controller reads an OAT one Cooling Deadband above the Supply Air Setpoint and a Dewpoint Tempera­ture below the Dewpoint Setpoint. The migration table for this mode
is shown below.
14
MUA II Controller
Page 15
Technical Guide
(SAT) Supply Air
Condition Mode
Dewpoint
Outside
Dewpoint Setpoint. OAT
drops below the
rises above the
Cool Setpoint
Dehu midification
Vent
During this mode the controller will maintain the SAT between a ± Cooling Deadband from the Supply Air Setpoint. This is achieved
by activating and deactivating the stages of cooling.
Temperature
Supply Setpoint
Staging Up
Cool Deadband
Cool Deadband
Staging Down
Time
Figure 19: Cool Mode Staging
Dehumidification Mode
This mode occurs when the controller reads a Dewpoint Temperature above the Dewpoint Setpoint. The migration table for this mode is shown below.
Condition Mode
OAT
falls below the
Dewpoint Temperatu re Dewpoint Setpoint
OAT
rises above the
Dewpoint Temperature
and
Dewpoint Setpoint
the
Dewpoint Temperatu re Dewpoint Setpoint
In this mode the controller will use the Outside Enthalpy to calculate the number of compressors needed to extract the moisture from the air. At the same time the Reheat Control will be active to avoid over cooling.
Reheat Control
The control can utilize a combination of different heating methods to reheat the supply air during dehumidification mode. The following is the order the control will try to reheat de supply air.
Heat Setpoint
falls below the
Cool Setpoint
falls below
falls below the
and
Heat
Cool
Vent
Vent Mode
This mode occurs when the controller reads an OAT between the Cool­ing and Heating Deadband from the Supply Air Setpoint, and a Dewpoint reading below the Dewpoint Setpoint. The migration table
for this mode is shown below.
Condition Mode
OAT
falls below the
OAT
rises above the
Dewpoint Temperature
Dewpoint Setpoint
the
During this mode the controller will shut off heating and cooling, but will allow the blower to continue its normal operation.
Heat Setpoint
Cool Setpoint
rises above
Heat Cool
Dehumidification
1.) Unit Hot Gas Reheat
Two kinds of Hot Gas Reheat are available with the MUA II controller, ON/OFF Hot Gas Reheat control and Modulating Hot Gas Reheat Control. Modulating Hot Gas Reheat control requires that the HVAC unit is equipped with the MHGRV II controller. If the MHGRV II board is detected, the MUA II board will send the Supply Temperature Setpoint to the MHGRV II controller in order to modulate the Hot Gas Reheat Valve to maintain the desired Supply Air Temperature. If the HVAC unit does not have the MHGRV II controller installed and is instead using an ON/OFF Hot Gas Reheat Valve for reheat control, the user must configure a relay to activate the ON/OFF Hot Gas Reheat Valve. The relay will cycle the ON/OFF Hot Gas Reheat Valve to maintain the supply air temperature between the Cooling and Heating Setpoints.
2.) Dehumidification Heat:
The user can elect to use the unit heating source to reheat the air during dehumidification or to supplement Hot Gas Reheat dehumidification control. If the HVAC unit is not equipped with Hot Gas Reheat or the Hot Gas Reheat is not able to bring the Supply Air Temperature to the desired setpoint, the MUA II controller will activate the heat source to maintain the Supply Air Temperature Setpoint. The heat source can be either internal or external to the HVAC unit.
VAV/CAV Controller
15
Page 16
Technical Guide
Heat
Deadband
(SAT) Supply Air
Sequence Of Operations
Heat
This mode occurs when the controller reads an OAT one Heating DeadBand below the Supply Air Setpoint and a Dewpoint T empera­ture below the Dewpoint Setpoint. The migration table for this mode
is shown below.
Condition Mode
OAT
rises above the
Dewpoint Temperature
Dewpoint Setpoint
the
Temperature
Supply Setpoint
Heat Setpoint
rises above
Vent Mode
Dehu midification
Heat Deadband
Time
Condition Mode
SAT rises above the High Cutoff Temperature
SAT drops below the Low Cutoff Temperature
After Temperature Protect is initiated and SAT rises 10°F abov e the Low
Cutoff Temperature
After Temperature Protect is initiated and SAT drops10°F below the High
Cutoff Temperature
Heating & Cooling
Disabled
Blower Operation
For 3 M inute s
Then Off
Return to Normal
Operation
Initialization
On system powerup a 30 second start-up delay is performed where all default setpoints are initialized, LED’s are initialized and all outputs are turned off.
When power is first applied, LED2 is turned off for 5 seconds. At this time the LED will “blink” to indicate the setting of the address switch and then extinguish for another 5 seconds. The LED will now “blink” for a 30 second start-up delay to protect the fan and other components from short cycling during intermittent power conditions.
MUA II Configuration & Setup
Figure 19: Heat Mode Staging
In this mode the unit will stage the Heating to deliver the Supply Air at the Supply Temperature Setpoint. If the MODGAS II is connected to the system, the MUA II board will send the Supply Temperature Setpoint to the MODGAS II in order to modulate to the desired Sup­ply Temperature. The MODGAS II will work as the first stage of Heating. This allows having the MODGAS II working together with standard ON/OFF heat stages. If External Heat is configured, it will cancel the internal heat call.
External Heating
This feature is designed to control an external Hot Water Valve or an SCR controller. Configuring a relay for External Heating Control enables this feature. This relay is activated any time the unit needs heat. The output follows a proportional control scheme and can be configured for a range of 0-10 VDC or 2-10 VDC. The External Heat relay is deacti­vated when the call for heat or reheat is canceled or the Supply Air
Temperature rises one Heating Deadband above the Supply Air T em­perature Setpoint.
Temperature Protect
This mode occurs when the SAT rises above the High Cutoff Tem- perature Setpoint or drops below the Low Cutoff Temperature Setpoint for a defined period of time. T o return to the normal mode, the SAT must drop 10° F below the High Cutoff Temperature Setpoint
or rise 10° F above the Low Cutoff T emperatur e Setpoint, depending on the situation. See the table that follows.
There are a few configuration selections available to the user, which can be used to tailor the software operation to match the mechanical equip­ment this controller is installed on.
Resets
Supply Temperature Reset from Space Temperature
This feature requires a Space T emperature Sensor connected to the con­troller. The reset is always upwards from the Supply Temp Setpoint to the Maximum Supply temp (Maximum Supply temp = Supply Temp Setpoint + Reset band). When the Space Temperature is at the
Min Temp Reset the desired Supply temp is the Supply Temp Setpoint. When the Space Temperature is at the Max Temp Reset the desired Supply temp is the Maximum Supply temp.
Outside Dewpoint Reset from Space Humidity
This feature requires a Space Humidity Sensor connected to the control­ler on analog input AIN7. When this option is used the Fan Proof Of Flow Switch option is not available as it also connects to analog input AIN7. The reset is always downwards from the Outside Dewpoint Setpoint to the Minimum Outside Dewpoint (Minimum Outside Dewpoint = Outside Dewpoint Setpoint - Reset Band). When the Space Humidity is at the Space Hum Min Reset the desired Outside Dewpoint is the Minimum Outside Dewpoint. When the Space Humidity is at the Space Hum Max Reset the desired Outside Dewpoint is the Out- side Dewpoint Setpoint.
16
MUA II Controller
Page 17
Sequence Of Operations
Technical Guide
Other Control Options
Fan Proof Of Flow Switch
The MUA II controller can monitor a Fan Proof of Flow Switch contact closure on analog input #7. When this option is used the Outside Dewpoint Reset from Space Humidity option is not available as it also connects to analog input #7. Anytime the fan is running this contact must be closed. If the contact does not close or remain closed no heating or cooling outputs can activate or remain active. If this option is se­lected, the loss of this signal can generate an alarm so that the user knows there is a problem that needs to be corrected. There is a built-in five second filter provided to prevent intermittent contact “bounce” from affecting the operation. This option is not available
Remote Occupied Contact
If you have a separate source that will provide a dry contact closure to indicate the occupied mode, you can monitor this contact closure in place of a humidity sensor on analog input #3.
Outside Air Temperature Broadcast
If you have several Air Handlers on a job-site and they are connected together via the RS-485 communications loop, you can select this op­tion and configure the controller to broadcast Outside Air Temperature to all controllers on the network, instead of installing a Outside Air Temperature sensor on every unit. This saves the user from having to install duplicate sensors on every air handler.
Outside Air Humidity Broadcast
If you have several Air Handlers on a job-site and they are connected together via the RS-485 communications loop, you can select this op­tion and configure the controller to broadcast Outside Air Humidity to all controllers on the network, instead of installing a Outside Air Humid­ity sensor on every unit. This saves the user from having to install duplicate sensors on every air handler.
Relay Configuration
Output Relay Configuration
Relays #2 thru 21 can be configured for the type of function that matches the MUA II controller options. The relays can be configured for any of the following: Heating (aux. Heating) Stages, Cooling (compressor) Stages, Gas Reheat Control for De-Humidification and External Heat Enable for control of external heating devices.
the feature of viewing the current time the MUA II Controller is using, you must install a Personal Computer and the PRISM computer front end software.
Alarm Detection and Reporting
The MUA II controller continuously performs self diagnostics during normal operations to determine if any operating failures have occurred. These failures can be reported to the user in several ways, depending on the type of system and options installed by the user.
If a Modular Service Tool or System Manager is connected, the alarms will be reported on the Status Screens. If the Prism computer graphic front end is installed, the alarms will be reported on the main screen of the program and logged to disk. If neither remote communication op­tion is installed, the user can check for alarms by viewing LED2 on the MUA II controller board. If everything is operating normally, the LED will blink once every 10 seconds. If there is a problem detected, the LED will flash a specific number of times every 10 seconds to indicate what the problem is. These flashes or “blink codes” are described below in order of priority. The highest priority condition must be corrected be­fore any lower conditions can be observed and corrected. One blink is the lowest priority and indicates no alarms. Five blinks is the highest priority.
If the RemoteLink (modem) is installed, any alarm condition can ini­tiate a callout to a pager to alert someone to the alarm condition. See the Prism computer front end program operations manual for further infor­mation on this topic.
LED Blinks This
Number Of Times
1
Blink Code
Descripti on
Normal Operations. No
Alarm Conditions
2 Sensor Failure
(OAT, OAH and SAT) 3 Mechanical Failure 4 Fan Proving Alarm 5 Unit In Force Mode
Scheduling
The MUA II controller has an internal battery backed up Real Time Clock (RTC) that allows the controller to keep the time and allows for scheduling.
The MUA II controller has an internal 7 day schedule with 2 start-stop events per day. Y ou can also have 1 holiday schedule with 2 start-stop events. This holiday schedule can be used for 14 different holiday periods.
One thing to be noted is that you cannot view the current time when you are viewing the MUA II controller with the Modular Service T ool or the System Manager. You can however change the time on the MUA II controller through the Modular Service T ool or the System Manager . If there is any doubt on the current time, re-enter the time and date and it will change the controller to match what you have entered. If you want
VAV/CAV Controller
T able 2: Diagnostic Blink Codes
Force Modes or Overrides
The MUA II Controller relay outputs can be user overridden if the Modular Service Tool or the PRISM graphical front-end program is available. The modes of operation for the relays are:
0 = Auto (Normal Operation) 1 = Forced ON 2 = Forced OFF
The analog outputs are forced if the user specifies a value between 0.0 and 10.0 VDC. T o cancel the force mode, enter a value less than zero (-
1.0 VDC).
17
Page 18
Technical Guide
Sequence Of Operations
When the analog outputs are forced, the display on the Modular Service Tool or front-end can be interpreted as the actual voltage. During normal operation, the display indicates the percentage signal applied based on the user defined voltage limits. For example, if the user defines a 2.0 VDC to 10.0 VDC range, then 50% would be 6.0 VDC instead of the 5.0 VDC applied when the range is 0.0 VDC to 10.0 VDC.
As mentioned, force modes can only be activated with an attached re­mote communications device described previously. Furthermore, the override condition can only remain in effect as long as the remote device is connected and communicating with the unit. That means that you cannot set an override condition and then “walk away” from the equip­ment with the override still active. The loss of communications or the removal of the remote interface will automatically terminate the override within 10 minutes. This is to protect the equipment and to prevent an override condition from remaining active indefinitely resulting in ineffi­cient operation of the equipment.
Caution: No equipment protection is available during the
force mode of operation. That means you could start a compressor without running the fan or create other conditions that WILL damage the HVAC equipment. WattMaster Controls, Inc. assumes no responsibility or liability for the misuse of these user overrides that cause damage to the HVAC equipment!
front-end program. If you don’t have the Remote Communications op­tion with a front-end program, you do not have access to these logs.
There are 120 log positions available. Once the last ( 120th ) position has been recorded, the log jumps back to the first position and begins overwriting the old data. This means the user is required to retrieve the logs at an interval that is shorter than the duration of the last 120 logs. Shown below are some log intervals and the duration of 120 logs.
1 Minute Interval = 2 Hour Duration 15 Minute Interval = 30 Hour Duration 30 Minute Interval = 60 Hour Duration 60 Minute Interval = 120 Hour Duration
The fixed items in the log are listed below:
Date Time Supply Air Temperature Outside Air Temperature Supply Air Setpoint Outdoor Air Humidity Dewpoint Setpoint Onboard Relay Status ( BIT Pattern ) Expansion Board Relay Status ( BIT Pattern ) External Heat (% Of Max Heat )
Internal Trend Logging
The MUA II Controller continuously maintains an Internal Trend Log, which records a fixed set of values at an interval programmed by the user. These values can be retrieved only with the PRISM graphical
Troubleshooting
Using LED’s To Verify Operation
The MUA II controller is equipped with LEDs that can be used as very powerful troubleshooting tools. Their are four LEDs on the MUA II controller board. Three of these LEDs are used in troubleshooting. See Figure 18 for the LED locations. The LEDs and their uses are as fol­lows:
“COMM”
This LED will light up to indicate system communications.
“PWR”
This LED will light up to indicate that 24 VAC power has been applied to the controller.
“LED1”
This LED is not used for this controller application.
“LED2”
This is the diagnostic blink code LED. It will light up and blink out diagnostic codes.
PWR LED Operations
These items and values are explained in greater detail in the PRISM manual.
When the MUA II controller is powered up the “PWR” LED should light up and stay on continuously. If it does not light up, check to be sure that you have 24 VAC connected to the board, that the wiring connections are tight and that they are wired for the correct polarity. The 24 VAC power must be connected so that all ground wires remain common. If after making all these checks the PWR LED does not light up, please contact WattMaster technical support for assistance.
COMM LED Operations
When power is applied to the controller The “COMM” LED will also light up. If this is a Stand Alone System (one controller only on the loop) or an Interconnected System (several MUA II controllers tied together without a CommLink) the COMM LED will glow continu­ously. The COMM LED will flicker when you are connected to the MUA II controller and you are entering setpoints with the Modular Service Tool or the System Manager. It will also flicker if this is a Networked System. If this is a Networked System (the system has a CommLink installed) the COMM LED should flicker rapidly indicating that the system is communicating. A “flicker” is defined as a brief mo­ment when the LED turns off then back on. It may be easier to see this “flicker” if you cup your hand around the LED.
18
MUA II Controller
Page 19
Technical Guide
If the COMM LED does not operate as indicated above, first check the address switch setting. Verify the address switch as outlined in LED (Diagnostic LED) Operations below. If the address switch setting is correct and the COMM LED still does not behave as indicated above, check to be sure the operators interface is connected correctly. The System Manager must be connected to a local communications loop either at the MUA II controller as shown in Figure 20 or to another controller on the same local communications loop. If you are using the Modular Service Tool, verify that it is plugged in securely to the DIN connection on the MUA II controller. See Figure 20 for DIN connec­tor location.
MUA II Controller Board
Communications Terminals System Manager Can Be Connected Here
(COMM) Communications
(PWR) Power
(LED1) Not Used
(LED2) Diagnostic
COMM
T
SHLD
R
COMM
PWR
LED1
LED2
DIN Connector For Modular Service Tool
Figure 20: LED & Interface Connection Locations
If the COMM LED still does not behave correctly, check the voltages at the communications terminal block. Be sure the board is powered up for this test. Unplug the communications terminal block from the board and check the DC voltage between T and SHLD and between R and SHLD.
Check the voltage with a digital multimeter set to DC volts. The voltage should be between 2.4 to 2.5 VDC between SHLD and either T or R. If your voltage is not in this range, you probably have a damaged driver chip that must be replaced. For driver chip replacement instructions, please see the Orion Controls System Installation & Troubleshooting Guide for more information or contact the factory for further assistance.
LED2 (Diagnostic LED) Operations
When power is first applied, LED2 is turned off for 5 seconds. At this time LED2 will “blink” to indicate the setting of the address switch and then extinguish for another 5 seconds. Verify that the address switch setting is correct by counting the number of blinks. If the address switch setting is not correct, remove the communication loop terminal plug from the controller and then the power terminal plug. Correctly set the address switch setting (See Figure 15) with the dip switches on the controller, reconnect the power connection and then the communication loop. Reapply power to the controller and observe the blink code to verify the address is set correctly.
Note: Power to the Controller being addressed must always
be cycled after changing address switch settings in or­der for the changes to take effect. Always unplug the communications terminal block before removing the power terminal block from the board. When finished reinstall the power terminal block first and then the communications terminal block.
If LED2 blinks the correct address, your board is addressed correctly. If it does not light up at all, the board is not operating correctly and could be defective.
If all of these tests are made and the controller still doesn’t operate, see the Orion Controls System Installation & Troubleshooting Guide for more information or contact the W attMaster T echnical Support T oll Free Number at 866-918-1100 for further assistance.
VAV/CAV Controller
19
Page 20
Technical Guide
Appendix
Sensor Checks
The following sensor voltage and resistance tables are provided to aid in checking sensors that appear to be operating incorrectly. Many sys­tem operating problems can be traced to incorrect sensor wiring. Be sure all sensors are wired per the wiring diagrams in this manual.
Temperature – Resistance – Voltage For Type III 10 K Ohm Thermistor Sensors
Temp
(ºF)
-10 93333 4.620 60 14681 3.042 86 8153 2.297
-5 80531 4.550 62 14014 2.985 88 7805 2.242
10 52500 4.297 68 12191 2.810 100 6047 1.927 15 45902 4.200 69 11906 2.780 105 5453 1.805 20 40147 4.095 70 11652 2.752 110 4923 1.687 25 35165 3.982 71 11379 2.722 115 4449 1.575 30 30805 3.862 72 11136 2.695 120 4030 1.469 35 27140 3.737 73 10878 2.665 125 3656 1.369 40 23874 3.605 74 10625 2.635 130 3317 1.274 45 21094 3.470 75 10398 2.607 135 3015 1.185 50 18655 3.330 76 10158 2.577 140 2743 1.101 52 17799 3.275 78 9711 2.520 145 2502 1.024 54 16956 3.217 80 9302 2.465 150 2288 0.952 56 16164 3.160 82 8893 2.407 58 15385 3.100 84 8514 2.352
Resistance
(Ohms)
0 69822 4.474 64 13382 2.927 90 7472 2.187 5 60552 4.390 66 12758 2.867 95 6716 2.055
Voltage @
Input (VDC)
Temp
(ºF)
Resistance
If the sensors still do not appear to be operating or reading correctly, check voltage and/or resistance to confirm that the sensor is operating correctly per the tables. Please follow the notes and instructions below each chart when checking sensors.
(Ohms)
Voltage @
Input (VDC)
Temp
(ºF)
Resistance
(Ohms)
Voltage @
Input (VDC)
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while discon­nected from the controllers (not powered).
Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-”(mi-
nus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
20
MUA II Controller
Page 21
Technical Guide
Percen
t
age
OE265 Relativ e H umidity Transmitters – H umidity vs. Voltage
Humidity
(RH)
0% 1.00 26% 2.04 52% 3.08 78% 4.12 2% 1.08 28% 2.12 54% 3.16 80% 4.20 4% 1.16 30% 2.20 56% 3.24 82% 4.28 6% 1.24 32% 2.28 58% 3.32 84% 4.36
8% 1.32 34% 2.36 60% 3.40 86% 4.44 10% 1.40 36% 2.44 62% 3.48 88% 4.52 12% 1.48 38% 2.52 64% 3.56 90% 4.60 14% 1.56 40% 2.60 66% 3.64 92% 4.68 16% 1.64 42% 2.68 68% 3.72 94% 4.76 18% 1.72 44% 2.76 70% 3.80 96% 4.84 20% 1.80 46% 2.84 72% 3.88 98% 4.92 22% 1.88 48% 2.92 74% 3.96 100% 5.00 24% 1.96 50% 3.00 76% 4.04
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
Humidity
Percentage
(RH)
Voltage
@
Input
(VDC)
OE265 Relative Humidity Sensors Testing Instructions:
Use the voltage column to check the Humidity Sensor while connected to a powered controller.
Read the voltage with meter set on DC volts. Place the “-” (minus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.” If
the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
VAV/CAV Controller
21
Page 22
Notes
Technical Guide
22
MUA II Controller
Page 23
Notes
Technical Guide
VAV/CAV Controller
23
Page 24
AAON, Inc.
Form: AO-MUAII-TGD-01A Printed in the USA November 2002 All rights reserved Copyright 2002
WattMaster Controls Inc.8500 NW River Park DriveParkville, Mo.64152 Phone (816) 505-1100 www.orioncontrols.com Fax (816) 505-1101
2425 So. Yukon Ave • Tulsa, OK 74107-2728
Ph: (918) 583-2266 • Fax: (918) 583-6094
AAON Part No. R08120
Loading...