Orion GPC-XP User Manual

LED B LI NK CO DES
LED NAME
STATUS1
STATUS2
NORMAL OPERATION 0 1
SCHEDULE OVERRIDE 0 2
JUMPER 1
JUMPER 2
SETTING
ON
ON
USE ON-BOARD COMMLINK
OFF
OFF
USE EXTERNAL COMMLINK
www.wattmaster.com
GPC-XP Controller
Technical Guide
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
www.wattmaster.com
OE338-23-GPC-XP
GPC-XP CONTROLLER
AI1 =
AI2 = BI2 = AO2 =
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
AI7 = BI7 =
AI8 = BI8 =
ANALOG
INPUT
JUMPERS
4-20mA
0-5V
0-10V
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
VDC
OUTPUTS
+ 24 VDC + 5 VDC GND
BI1 = AO1 =
THERM
NOTES:
1.) ANALOG INPUT JUMPER SETTINGS MUST BE SET FOR YOUR SPECIFIC INPUT DEVICE REQUIREMENT.
2.) IT IS RECOMMENDED THATYOU WRITE THE DESCRIPTION OF THE INPUT,AND/OR OUTPUTS YOU ARE CONNECTING TOTHE CONTROLLER IN THE BOXES PROVIDED ABOVE USING A PERMANENTMARKER (SHARPIE ) FOR FUTURE REFERENCE.
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED OR THE CONTROLLER WILL BE DAMAGED
GND
USB
E-BUS
PORT
+ 24 VAC
PORT
RELAY CONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY4
COMMON
RELAY5
RELAY6
RELAY7
RELAY8
COMMON
®
WattMaster Label
#LB102095
Rev.: 1C
Table of Contents
OVERVIEW ................................................................................................................................................. 3
Features ........................................................................................................................................................... 3
Step-By-Step Guide ......................................................................................................................................... 4
SECTION 1: GPC-XP WIRING & SETUP ................................................................................................... 5
Environmental Requirements ........................................................................................................................... 5
Mounting .......................................................................................................................................................... 5
Power Supply ................................................................................................................................................... 5
GPC-XP Controller Dimensions ....................................................................................................................... 5
GPC-XP Wiring ................................................................................................................................................ 6
Communication Settings .................................................................................................................................. 7
Addressing and Baud Rate Settings ................................................................................................................ 8
SECTION 2: INSTALLING PRISM 2........................................................................................................... 9
SECTION 3: GPC-XP NAVIGATION AND STATUS ................................................................................... 10
SECTION 4: CONFIGURING ANALOG INPUTS ....................................................................................... 12
SECTION 5: CONFIGURING BINARY INPUTS ........................................................................................ 17
SECTION 6: CONFIGURING RELAYS...................................................................................................... 20
SECTION 7: CONFIGURING ANALOG OUTPUTS ................................................................................... 28
SECTION 8: OUTDOOR STATUS & AVC STATUS ................................................................................... 34
SECTION 9: SETTING SCHEDULES ....................................................................................................... 35
SECTION 10: CONFIGURING ALARMS .................................................................................................. 39
SECTION 11: MISCELLANEOUS SETTINGS .......................................................................................... 40
SECTION 12: SAVING AND RESTORING SETPOINTS ............................................................................ 44
SECTION 13: TREND LOGGING AND PRINTING .................................................................................... 45
APPENDIX A: HELP SCREENS AND SAMPLE STATUS REPORT ............................................................ 48
APPENDIX B: USB DRIVER INSTALLATION ........................................................................................... 52
INDEX ...................................................................................................................................................... 54
2
www.wattmaster.com
WattMaster Controls, Inc. 8500 NW River Park Drive · Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.wattmaster.com
WattMaster Controls, Inc. assumes no responsibility for errors or omissions. This document is subject to change without notice. Form: WM-GPCXP-TGD-01E Copyright May 2015 WattMaster Controls, Inc.
GPC-XP Controller Technical Guide
Overview
GPC-XP Controller
Overview
The GPC-XP Controller ( OE338-23-GPC-XP) is used for controlling equipment or processes that cannot be controlled using a standard HVAC controller.
The GPC-XP provides the fl exibility to control, schedule and/or monitor equipment such as unit heaters, exhaust fans, motorized dampers, pumps, and other mechanical equipment. It can also be used for simple boiler, chiller, or refrigeration applications as well as to provide lead/lag start function.
The GPC-XP has an on-board CommLink that provides for stand­alone programming and monitoring via a direct USB connection to a computer running Prism 2 software. If used on a networked system that has an external CommLink, this on-board CommLink would not be used. Alternatively, the System Manager Touch Screen II for GPC-XP (OE392-10-GPCXP) can be used to
force modes, and set schedules.
The GPC-XP has (8) confi gurable analog inputs which will ac- cept signals from thermistor temperature sensors or from 4-20mA, 0-5VDC, or 0-10VDC transmitters. The inputs are set for the desired scaling by means of a jumper bar. Custom formulas created by available math functions and operators can be used in conjunction with the analog inputs to create a calculated value to be used and displayed for a specifi c analog input. An additional modular input is available for WattMaster communicating sensors.
view status, perform
Features
The GPC-XP Controller provides the following:
 8 con gurable analog inputs
 8 wet contact binary inputs con gured for normally open
or normally closed operation
 8 relay outputs for on/off control
 4 analog outputs for proportional or PID control signals
 E-BUS port for communicating sensors
 8 separate 2 events per day schedules which can be
assigned to any input or output for operational control or alarm recognition based on time of day
 Schedules can be confi gured to broadcast to other
WattMaster HVAC equipment installed on the same communications loop as the GPC-XP
 Can be confi gured using a computer with Prism 2
software installed
 The System Manager Touch Screen II for GPC-XP (sold
separately) can be used to view status, perform force modes, and set schedules.
The GPC-XP has (8) wet contact binary inputs that can be confi g- ured for either normally open or normally closed operation. Also available are (8) relay outputs for on/off control and (4) analog outputs (0-10VDC) for modulating control. Highest/lowest/average (H/L/A) of the analog input values can be used in the GPC-XP logic or broadcast to other controllers on the control system loop. These H/L/A values are referred to in this technical guide as AVC (Analog Value Comparison) values.
There are (8) separate two events per day schedules which can be assigned to any input or output for operational control or for alarm recognition based on time of day. These schedules can also be con­ gured to broadcast to other WattMaster controllers on the control system loop.
NOTE: The internal USB communication port of the GPC-
XP Controller uses a specialized driver (USB Driver CD-ROM included) that must be installed on your Windows PC before communication to the device can be established. To install the USB Driver, follow the
instructions in Appendix B on page 52.
 Can be operated Stand-Alone or connected to a
networked system
 On-board CommLink for Stand-Alone programming
using a USB connection to a computer running Prism 2 software
NOTE: The GPC-XP Controller contains no user-serviceable
parts. Contact qualifi ed technical personnel if your Controller is not operating correctly.
GPC-XP Controller Technical Guide
3
Overview
Step-By-Step Guide
Zone
Zone
Step-By-Step Guide
This guide will lead you through each step in confi guring your GPC- XP Controller. Below is a quick overview of each step.
Section 1: GPC-XP Wiring & Setup—This section explains
how to mount and wire your GPC-XP properly. It also explains how to set the address and baud rate for your particular system.
Section 2: Prism 2 Installation—This section explains how
to install Prism 2 software required to program your GPC-XP Con­troller. If you are not familiar with the Prism 2 software program, please refer to the Prism 2 T echnical Guide which can be downloaded from the Orion Controls website: www.orioncontrols.com.
Section 3: GPC-XP Personalization & Status—This sec-
tion explains how to individualize and access GPC-XP Controllers when more than one is installed and also provides and overview of the GPC-XP Controller Status Screen.
Section 4: Confi guring Analog Inputs—This section ex-
plains how to confi gure analog inputs, individualize analog input descriptions, and calibrate thermistor sensors, and override and clear other analog input values.
Section 5: Confi guring Binary Inputs—This section ex-
plains how to confi gure binary inputs, individualize binary input descriptions, and override binary inputs.
Section 6: Confi guring Relays—This section explains how
to confi gure relay outputs and individualize relay descriptions.
Section 7: Confi guring Analog Outputs—This section
explains how to confi gure analog outputs, individualize analog output descriptions, override voltages, and cancel overrides.
Section 8: Outdoor Status and AVC (Analog Value Comparison) Status
and view AVC and Outdoor Status setpoints.
Section 9: Setting Schedules—This section describes how
to confi gure daily and holiday schedules and perform schedule force modes.
Section 10: Confi guring Alarms—This section explains how
to confi gure and view alarms.
Section 11: Miscellaneous Settings—This section includes
miscellaneous settings for Week Schedule Broadcasts, AVC Inputs, AVC Setpoints, Rouge Sensor Limits, Reset Rogue Sensor, Outdoor Air Broadcasts, Trend Logging, and Daylight Savings.
Section 12: Saving and Copying Setpoints—This section
explains how to save GPC-XP setpoints to a fi le on your computer and how to restore GPC-XP setpoints once you have saved them to a fi le.
Section 13: Viewing and Printing Trend Logs—This
section explains how to view and print Trend Logs.
Appendix A—This appendix provides Help Screen information.
Appendix B—This appendix explains USB Driver Installation.
—This section explains how to confi gure
Index—The index provides page numbers for easy reference to
quickly fi nd the information you need.
4
GPC-XP Controller Technical Guide
Section 1: GPC-XP Wiring & Setup
Dimensions and Mounting
Environmental Requirements
The GPC-XP Controller needs to be installed in an environment that can maintain a temperature range between -30°F and 150°F and not exceed 90% RH levels (non-condensing).
Mounting
The GPC-XP Controller is housed in a plastic enclosure. It is de­signed to be mounted by using the 3 mounting holes in the enclosure base. It is important to mount the module in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the module.
See Figure 1 for Controller dimensions (in inches).
5.985.98
2.752.75
T-
SH
R+
BIN1
D6
BIN2
D7
BIN3
D8
BIN4
D9
BIN5
D10
BIN6
D11
BIN7
D12
BIN8
D13
COM
COM
COM
COM
0-5v
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
GND
GND
GND
GND
+24V
+5V
GND
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T” TO“T” “SHLD” TO “SHLD”
ON BOA COMMLI CONNEC
0-10v
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
R38
300
R41
300
R43
300
R47
300
300
300
300
R61R59R55R51
300
CUTTO ISOLATE
COMFROM GND
4-20mA
THERM
www.wattmaster.com
OE338-23-GPC-XP
GPC-XP CONTROLLER
RLY1 =
RLY2 =
RLY3 =
RLY4 =
AI1 =
AI2 = BI2 = AO2 =
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
AI7 = BI7 =
AI8 = BI8 =
ANALOG
INPUT
JUMPERS
4-20mA
0-10V
0-5V
THERM
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
VDC
OUTPUTS
+ 24 VDC + 5 VDC GND
RLY5 =
RLY6 =
RLY7 =
RLY8 =
BI1 = AO1 =
LED NAME STATUS1 STATU S2
NORMAL OP ERATION 0 1
SCHEDULE OVERRIDE 0 2
NOTES:
1.) ANALOG INPUTJUMPER SETTINGS MUST BE SET FOR YOUR SPECIFIC INPUT DEVICE REQUIREMENT.
2.) IT IS RECOMMENDED THATYOU WRITE THE DESCRIPTION OF THE INPUT,AND/OR OUTPUTS YOUARE CONNECTING TO THE CONTROLLER IN THE BOXES PROVIDEDABOVE USING APERMANENT MARKER (SHARPIE) FOR FUTURE REFERENCE.
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED OR THE CONTROLLER WILL BE DAMAGED
GND
+24VAC
8.388.38
0.290.29
7.837.83
BINARY INPUTS
ANALOG INPUTS
VDC
OUTPUTS
LOOPCOMM
TB1
TB3
TB7
TB8
Power Supply
The GPC-XP Controller requires a 24 VAC power connection with a minimum rating of 8 VA.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to observe polarity could result in damage to the boards.
1.49
YS102432 REV 3
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
COMMON
RLY1
RLY2
RLY3
RLY4
COMMON
SERIAL #
1002
R74
U17
AOUT1-2
.1uF
C36
1002
R97
U19
AOUT3-4
.1uF
C46
GND
STATUS1
STATUS2
EBUS
POWER
.1uF
ADDRESS
1002
1002
1002
1002
1002
1002
1002
1002
SW1
TB2
RELAY
OUTPUTS
TB4
ANALOG OUTPUTS
AOUT1
AOUT2
AOUT3
AOUT4
GND
GND
TB6
1002
R21
1002
R109
1002
R16
1002
R14
C21
ADD
1 2 4
8 16 32
LOOP
BAUD
1
2
C14
.01uF
LED BLINK C ODES
USB
E-BUS
PORT
PORT
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY4
COMMON
RELAY5
RELAY6
RELAY7
RELAY8
COMMON
®
WattMaster Label
#LB102095
Rev.: 1C
0.700.70
Figure 1: GPC-XP Dimensions
GPC-XP Controller Technical Guide
4.104.10
0.980.98
5
Section 1: GPC-XP Wiring & Setup
Installation & Wiring
Important Wiring Considerations
Please read carefully and apply the following information when wiring the GPC-XP Controller:
1. To operate the GPC-XP Controller, you must connect power to the 24 VAC input terminal block.
All Communication Loop Wiring Is
Straight Through
T To T, R To R, SHLD To SHLD
Local Loop RS-485
Connect To Next Device
On The Local Loop
CommLink Jumpers
Both On = Use On Board CommLink
Both Off - Use External CommLink
Binary Inputs BIN1Through BIN8 Configured for The Following:
1. Not Used
2. Normally Closed Operation
3. Normally Open Operation
4. Read Global Binary
5. Push-Button Override
6. Follow Relay
Analog Inputs AI1Through AI8 Configured For the Following:
1. Thermistor 10K Ohm Type III
Temperature Sensors (Fahrenheit)
2. Thermistor 10K Ohm Type III
Temperature Sensors (Celsius)
3. 4 - 20mA User Scaled
4. 0 - 5 vdc User Scaled
5. Wall Sensor Slide Offset
6. Read Global Analog Broadcast from
another Controller
7. Communicating Temperature Sensor
8. Communicating Humidity Sensor
9. Communicating Carbon Dioxide
Jumpers - Typical
Jumpers Must Be Set
Correctly For The Type Of
Input You Require.
9600 Baud
BINARY INPUTS
ANALOG INPUTS
VDC
OUTPUTS
5 VDC & 24VDC
Power For
Sensors
LOOPCOMM
T-
SH
R+
TB1
COM
COM
COM
COM
TB3
GND
GND
GND
GND
TB7
+24V
+5V
GND
TB8
BIN1
D6
BIN2
D7
BIN3
D8
BIN4
D9
BIN5
D10
BIN6
D11
BIN7
D12
BIN8
D13
0-5v
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
OE338-23-GPC-XP
GPC-XP Controller
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T”TO “T” “SHLD” TO “SHLD”
www.wattmaster.com
OE338-23-GPC-XP
GPC-XP CONTROLLER
300
300
300
300
RLY1 =
RLY2 =
300
RLY3 =
300
RLY4 =
300
300
AI1 =
AI2 = BI2 = AO2 =
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
AI7 = BI7 =
THERM
AI8 = BI8 =
ANALOG
INPUT
JUMPERS
4-20mA
0-10V
0-5V
THERM
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
VDC
OUTPUTS
+ 24VDC + 5VDC
GND
GND
24 VAC
GND
0-10v
ON BOA COMMLI CONNEC
COMFROM GND
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
R38
R41
R43
R47
R61R59R55R51
CUTTO ISOLATE
4-20mA
2. Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confi rm that all sensors required for your system are mounted in the appropriate location and wired into the correct
terminals. See Figure 2 below for wiring.
24VAC Power For Relay Outputs
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY4
COMMON
RELAY5
LED BLINK CODES
USB
E-BUS
PORT
PORT
RELAY6
RELAY7
RELAY8
COMMON
WattMaster Label
®
#LB102095
Rev.: 1C
RLY5 =
RLY6 =
RLY7 =
RLY8 =
BI1 = AO1 =
LED NAME STATU S1 STATUS2
NORMAL OPERATI ON 0 1
SCHEDULE OVERRIDE 0 2
NOTES:
1.)ANALOG INPUT JUMPER SETTINGS MUST BE SET FOR YOUR SPECIFIC INPUTDEVICE REQUIREMENT.
2.) IT IS RECOMMENDED THATYOU WRITE THE DESCRIPTION OF THE INPUT,AND/OR OUTPUTS YOUARE CONNECTING TO THE CONTROLLER IN THE BOXES PROVIDEDABOVE USINGA PERMANENT MARKER (SHARPIE) FOR FUTURE REFERENCE.
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED OR THE CONTROLLER WILL BE DAMAGED
+24VAC
YS102432 REV 3
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
COMMON
RLY1
RLY2
RLY3
RLY4
COMMON
SERIAL #
1002
R74 U17
AOUT1-2
.1uF
C36
R97
1002
U19
AOUT3-4
.1uF
C46
GND
STATUS1
STATUS2
EBUS
POWER
.1uF
ADDRESS
1002
1002
1002
1002
1002
1002
1002
1002
SW1
TB2
RELAY
OUTPUTS
TB4
ANALOG OUTPUTS
AOUT1
AOUT2
AOUT3
AOUT4
GND
GND
TB6
1002
R21
1002
R109
1002
R16
1002
R14
C21
ADD
1 2 4
8 16 32
LOOP
BAUD
1
2
C14
.01uF
8 Relay Outputs Are Available For On/Off Control Of Equipment Configured For the Following:
1. Not Configured
2. On Above / Off Below
3. On Above / On Below
4. Off Above / On Below
5. Off Above / Off Below
6. Follow Active Binary Input
7. Follow Inactive Binary Input
8. Follow Relay Output
9. Follow Schedule
10. Ventilation Control
11. Lead Relay for Lead/Lag Control
12. Lag Relay for Lead/Lag Control
Analog Outputs AOUT1 through AOUT4 Provide (4) 0-10 VDC Outputs Configured For The Following:
1. Not Configured
2. Direct Acting Floating Point
3. Reverse Acting Floating Point
4. Direct Acting PID
5. Reverse Acting PID
ADDRESS Dipswitch
is Used for Setting
the Address and
Baud Rate.
Line Voltage
Warning:
24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controller
NOTES:
1.)24 VAC Must Be Connected So That All Ground Wires Remain Common.
2.)All Wiring To Be In Accordance With Local And National Electrical Codes and Specifications.
3.)All Communication Wiring To Be 18 Ga. Minimum, 2 Conductor Twisted Pair With Shield. Belden #82760 Or Equivalent.
4.)It Is Recommended That The Address Switch Is Set Before Installation.
Figure 2: GPC-XP Controller Wiring Diagram
6
24 VAC
Transformer
8 VA
Minimum
EBC E-BUS Cable
Connect to
Communicating Sensor
USB Cable
Connect to Computer with
Prism II Software Installed For
Stand-Alone Programming
GPC-XP Controller Technical Guide
Section 1: GPC-XP Wiring & Setup
Communication Settings
Before Applying Power
In order to have a trouble free start-up, it is important to follow a few simple procedures. Before applying power for the fi rst time, it is very important to correctly address the controller and run through a few simple checks.
Communication Settings
Stand Alone Operation
The GPC-XP has an on-board CommLink that is used during Stand­Alone Operation. When confi gured for Stand-Alone operation, a computer running Prism 2 software can be connected directly to the USB port located at the bottom of the GPC-XP for programming and monitoring. In order to operate in Stand-Alone Mode, two things need to be set. First, both CommLink Jumpers found on the
upper left hand side of the board need to be set to ON. See Figure
Caution:
Disconnect All Communication Loop Wiring From The Controller Before Removing Power From The Controller. Reconnect Power And Then Reconnect Communication Loop Wiring.
3 below for details. Second, the Baud Rate determined by setting
ADDRESS Dipswitches 7 and 8 needs to be set to OFF/ON. See
Figure 4, page 8 for details.
NOTE: If using the Internal CommLink, you must set up
the USB drivers. See Appendix B, page 52.
Network Operation
The GPC-XP can be confi gured for connection to a networked system that has an external CommLink. In this case, the on-board CommLink would not be used. For this confi guration, two things need to be set. First, both CommLink Jumpers found on the upper left found on the
upper left hand side of the board need to be set to OFF. See Figure 3 below for details. Second, the Baud Rate determined by setting
ADDRESS Dipswitches 7 and 8 needs to be set to OFF/OFF if us­ing a CommLink IV and to OFF/ON if using a CommLink 5. See
Figure 4, page 8 for details.
Note:
The Power To The Controller Must Be Removed And Reconnected After Changing The Address Switch Settings In Order For Any Changes To Take Effect.
ON-BOARD COMMLINK SETTING
Jumper 1
ON
OFF
Jumper 2
ON
OFF
Both Jumpers ON
Use On-Board CommLink
Use External CommLink
Setting
ON BOARD COMMLINK CONNECT
Both Jumpers OFF
ON BOARD COMMLINK CONNECT
BINARY INPUTS
ANALOG
INPUTS
VDC
OUTPUTS
LOOPCOMM
T-
SH
R+
TB1
COM
COM
COM
COM
TB3
GND
GND
GND
GND
TB7
+24V
+5V
GND
TB8
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T”TO “T” “SHLD” TO “SHLD”
ON BOA COMMLI CONNEC
R38
BIN1
300
D6
R41
BIN2
300
D7
R43
300
BIN3
R47
D8
300
BIN4
RLY1 =
D9
BIN5
300
RLY2 =
D10
300
BIN6
RLY3 =
D11
300
BIN7
RLY4 =
R61R59R55R51
D12
300
BIN8
AI1 =
D13
AI2 = BI2 = AO2 =
CUTTO ISOLATE
COMFROM GND
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
4-20mA
THERM
0-10v
AI7 = BI7 =
0-5v
AI8 = BI8 =
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
ANALOG
AI1
INPUT
JUMPERS
AI2
0-5V
AI1
AI3
AI2
AI3
AI4
AI4
AI5
AI5
AI6
AI6
AI7
AI8
AI7
VDC
OUTPUTS
AI8
+ 24 VDC + 5 VDC GND
GPC-XP Controller
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
www.wattmaster.com
OE338-23-GPC-XP
GPC-XP CONTROLLER
RLY5 =
RLY6 =
RLY7 =
RLY8 =
BI1 = AO1 =
LED NAME STATUS1 STATU S2
NORMAL OP ERATION 0 1
SCHEDULE OVERRIDE 0 2
4-20mA
0-10V
THERM
NOTES:
1.)ANALOG INPUT JUMPER SETTINGS MUST BE SET FOR YOUR SPECIFIC INPUTDEVICE REQUIREMENT.
2.) IT IS RECOMMENDED THATYOU WRITE THE DESCRIPTION OF THE INPUT,AND/OR OUTPUTS YOUARE CONNECTING TO THE CONTROLLER IN THE BOXES PROVIDEDABOVE USINGA PERMANENT MARKER (SHARPIE) FOR FUTURE REFERENCE.
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED OR THE CONTROLLER WILL BE DAMAGED
GND
+24VAC
LED BLINK CO D ES
USB
E-BUS
PORT
PORT
COMMON
COMMON
RELAY1
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY7
RELAY8
WattMaster Label
®
#LB102095
Rev.: 1C
YS102432 REV 3
WATTMASTER CONTROLS
RLY1
RLY2
RLY3
RLY4
COMMON
RLY1
RLY2
RLY3
RLY4
COMMON
SERIAL #
1002
R74 U17
AOUT1-2
.1uF
C36
R97
1002
U19
AOUT3-4
.1uF
C46
GND
.1uF
ADDRESS
1002
1002
1002
1002
1002
1002
1002
1002
SW1
MADE IN USA
AOUT1
AOUT2
AOUT3
AOUT4
GND
GND
STATUS1
STATUS2
EBUS
POWER
C21
R109
TB2
RELAY
OUTPUTS
TB4
ANALOG OUTPUTS
TB6
R21
R16 R14
1002
1002
1002
1002
ADD
1 2 4
8 16 32
LOOP
BAUD
1 2
C14
.01uF
Figure 3: GPC-XP Controller Address Switch Setting
GPC-XP Controller Technical Guide
7
Section 1: GPC-XP Wiring & Setup
Addressing and Baud Rate Settings
Zone
Zone
Controller Addressing and Baud Rate
The GPC-XP Controller is equipped with address switches. When using Prism 2 to program and confi gure the GPC-XP Controller, you would enter this address to communicate with the controller. When the system is to be connected to other HVAC unit controllers on a communication loop, each controller’s address switch must be set with a unique address between 1 and 59.
GPC-XP Controller
BINARY INPUTS
ANALOG INPUTS
VDC
OUTPUTS
LOOPCOMM
T-
SH
R+
TB1
COM
COM
COM
COM
TB3
GND
GND
GND
GND
TB7
+24V
+5V
GND
TB8
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T”TO “T” “SHLD” TO “SHLD”
ON BOA COMMLI CONNEC
R38
BIN1
300
D6
R41
BIN2
300
D7
R43
300
BIN3
R47
D8
300
RLY1 =
BIN4
D9
RLY2 =
BIN5
300
D10
RLY3 =
300
BIN6
D11
300
RLY4 =
BIN7
R61R59R55R51
D12
300
AI1 =
BIN8
D13
AI2 = BI2 = AO2 =
CUTTO ISOLATE
COMFROM GND
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
4-20mA
AI7 = BI7 =
THERM
0-10v
0-5v
AI8 = BI8 =
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
ANALOG
INPUT
AI1
JUMPERS
AI2
0-5V
AI1
AI3
AI2
AI3
AI4
AI4
AI5
AI5
AI6
AI7
AI6
AI8
AI7
VDC
OUTPUTS
AI8
+ 24VDC + 5VDC GND
www.wattmaster.com
OE338-23-GPC-XP
GPC-XP CONTROLLER
RLY5 =
RLY6 =
RLY7 =
RLY8 =
BI1 = AO1 =
LED BLINK CODES
LED NAME STATUS1 STATUS2
NORMAL OPERATI ON 0 1
SCHEDULE O VERRIDE 0 2
4-20mA
0-10V
THERM
NOTES:
1.)ANALOG INPUT JUMPER SETTINGS MUST BE SET FOR YOUR SPECIFIC INPUTDEVICE REQUIREMENT.
2.) IT IS RECOMMENDED THATYOU WRITE THE DESCRIPTION OF THE INPUT,AND/OR OUTPUTS YOUARE CONNECTING TO THE CONTROLLER IN THE BOXES PROVIDEDABOVE USINGA PERMANENT MARKER (SHARPIE) FOR FUTURE REFERENCE.
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED OR THE CONTROLLER WILL BE DAMAGED
GND
USB
PORT
+24VAC
E-BUS PORT
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY4
COMMON
RELAY5
RELAY6
RELAY7
RELAY8
COMMON
WattMaster Label
#LB102095
Rev.: 1C
YS102432 REV 3
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
COMMON
TB2
RELAY
OUTPUTS
TB4
RLY1
RLY2
RLY3
RLY4
COMMON
SERIAL #
ANALOG OUTPUTS
1002
R74 U17
AOUT1
AOUT1-2
AOUT2
.1uF
AOUT3
C36
R97
1002
AOUT4
U19
AOUT3-4
GND
GND
.1uF
C46
TB6
GND
STATUS1
STATUS2
EBUS
1002
1002
1002
1002
1002
1002
1002
1002
SW1
POWER
.1uF
C21
ADDRESS
1002
R21
1002
R109
1002
R16
1002
R14
ADD
1 2 4
8 16 32
LOOP
BAUD
1 2
C14
.01uF
®
Address 1 @ 9600 Baud
Address switches 7 and 8 are used for the baud rate selection. See
Figure 4
below for address switch and baud rate setting information.
Caution:
Disconnect All Communication Loop Wiring From The Controller Before Removing Power From The Controller. Reconnect Power And Then Reconnect Communication Loop Wiring.
Note:
The Power To The Controller Must Be Removed And Reconnected After Changing The Address Switch Settings In Order For Any Changes To Take Effect.
BAUD RATE SELECTION
Baud
9600
57600
Switch 7 Switch 8
OFF
OFF
OFF
ON
Communication Setting
CommLink IV
CommLink 5 & Stand Alone
Address 5 @ 57,600 Baud
ADD
1 2 4 8 16
32 Baud 0 Baud 1
ADD
1 2 4 8
16
32 Baud 0 Baud 1
Figure 4: GPC-XP Controller Address Switch Setting
8
ADD
Address Switch Shown Is
Set For Address 1
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 59
GPC-XP Controller Technical Guide
ADD
Controller Address Switch
Address Switch Shown Is
Set For Address 13
Section 2: Installing Prism 2
Initialization, Prism 2 Software, and SMTS II for GPC-XP
Initialization
On system power up, there is an approximately 30-second startup delay where all default setpoints are initialized, LED’s are initialized, and all outputs are turned off.
When power is fi rst applied, the STATUS1 LED will fl ash intermit- tently for about 10 seconds. After a short pause, STATUS1 LED and STATUS2 LED will fl ash out the controller address. STATUS1 LED will fl ash to represent the tens position. STATUS2 LED will ash to represent the ones position. After the controller address is complete, there will be a short pause while the initialization process is completed. There will be no controller operation or communica­tions during initialization. After initialization, STATUS2 LED will continuously fl ash the status code—(1) blink indicates Normal Operation; (2) blinks indicates a Push-Button Schedule Override is in effect.
Example of a controller address of 25:
STATUS1 LED will fl ash 2 times. STATUS2 LED will fl ash 5 times.
Prism 2 Software
The next step is programming the controller for your specifi c re- quirements. Initial programming of the GPC-XP must fi rst be done
with a personal computer using our Prism 2 software.
gives you access to the status, confi guration, and setpoint screens of the GPC-XP Controller. The software is distributed on CD or can
be downloaded for free from our website: www.wattmaster.com/ techsupport. Prism 2 does not require any license agreement and may be freely copied and distributed. See Figure 5 below.
For more information, please see the Prism 2 Technical Guide to familiarize yourself with the program.
System Requirements
To use Prism 2 you must have a computer that meets or exceeds the following requirements:
Operating System
Microsoft
Windows
NOTE: Prism 2 is not intended for a server/client
environment.
®
Windows® 2000/ Windows® Vista,
®
7, or Windows® 8
Prism 2 software
* NOTE: The GPC-XP has a built-in CommLink that can
be utilized in Stand-Alone Mode. See page 7 for setting up Stand-Alone a nd Network operations. In Network Mode,
you must have a CommLink IV or CommLink 5 installed in order to communicate between your computer and the sys­tem. If remote communication is required, a WattMaster IP-
Module (Ether net) must also be installed in the CommLink.
System Manager Touc h Screen II for GPC-XP
The OE392-10-GPCXP System Manager TS II (Touch Screen) for the GPC-XP provides a direct, graphic-enhanced, menu-driven link to enable you to view the status, perform force modes, and set
schedules for your GPC-XP Controller. See Figure 5 below. For more information, please see the System Manager TS II for GPC- XP Technical Guide.
Support Information
WattMaster Controls provides Prism 2 installation and confi guration support. Call (866) 918-1100 for free, direct telephone support or (816) 505-1100 to talk to a Technical Support Representative. Sup­port for all telephone services is available Monday through Friday, 7:00 AM to 5:00 PM central standard time.
NOTE: WattMaster Controls Technical Support can-
not troubleshoot internal PC and/or Windows®-based operating system problems.
NOTE: WattMaster Controls Technical Support can-
not troubleshoot fi rewalls, r oute rs, a nd/o r p robl ems on a customer’s internal or external network. An IT professional may need to be consulted.
Operator
Interfaces
Minimum Hardware
Windows
®
compatible computer
Pentium 2 GHz Processor (Pentium 4 2 GHz or
greater,
Recommended)
1 GB RAM or greater)
120 MB hard drive space
XVGA (1024 x 768) adapter and monitor
(1280 x 1024, Recommended)
Network card for TCP/IP connection when IP
Module is used
CommLink*
GPC-XP Controller Technical Guide
System Manager TS II
for GPC-XP
Computer & CommLink
with Prism 2 Software Installed
Figure 5: GPC-XP Operator Interfaces
9
Section 3: GPC-XP Navigation & Status
Unit Selection
Selecting and Naming GPC-XP Controllers
Selecting GPC-XP Controllers
NOTE: See the Prism 2 Technical Guide for instructions on
setting up the job site and doing a search for units.
From the Prism 2 Main Screen, click on the GPC-XP Controller address in the Unit Selection Window. In this example, it is address
18. See Figure 6 below.
Selected Name Dialog Box
Figure 6: Prism 2 Main Screen GPC-XP Controller Selection
Naming GPC-XP Controllers
If you have more than one GPC-XP Controller, you can rename it
in the Selected Name Dialog Box. See Figure 7 below. Many users
name their GPC-XP Controller according to the application that it performs.
Figure 7: Naming the GPC-XP Controller
10
GPC-XP Controller Technical Guide
Section 3: GPC-XP Navigation & Status
GPC-XP Controller Status Screen
GPC-XP Controller Status Screen
Figure 8 below depicts the GPC-XP Controller Status Screen when
you fi rst access it with the Prism 2 program before any data has been entered.
The screen is divided into separate windows as follows: Analog
Inputs Window, Binary Inputs Window, Relays Window, Analog Outputs Window, Outdoor Status Window, AVC Status Window, Schedule Status Window, and Alarms.
The GPC-XP Controller Status Screen Toolbar also gives you the options to access the Miscellaneous Setpoints Screen, Save and Restore Setpoints, View and Print Trend Logs, and Print a Status Report for the current day.
The GPC-XP Controller Status Screen provides real-time live up- dates of the current operating conditions and is used to access the various setpoint and confi guration options.
No control takes place until the you confi gure the operation of the GPC-XP Controller..
Once you confi gure your inputs, outputs, and operating schedules, everything you need to monitor your GPC-XP is found on this GPC- XP Controller Status Screen.
The rest of this technical guide explains each component on this screen and provides detailed instructions for confi guring the data.
The following is a list of topics and their page numbers:
Analog Inputs Window, page 12 Binary Inputs Window, page 17 Relays Window, page 20 Analog Outputs Window, page 28 Outdoor Status Window, page 34 AVC Status Window, page 34 Schedule Status Window, page 35 Confi guring Alarms, page 39
Figure 8: GPC-XP Controller Status Screen
GPC-XP Controller Technical Guide
11
Section 4: Confi guring Analog Inputs
Components and Navigation
Analog Inputs
The Analog Inputs Window is located in the upper left-hand side of the GPC-XP Controller Status Scr een (Figure 8, page 11). There are 8 Analog Inputs. See Figure 9 below for the Analog Inputs Window component summary and the pages that follow for details.
Right or Left-click on any of the Analog Input name elds to access the description entry box to add or change the name of the Analog Input.
Left-Click in the data entry fi eld to confi gure the Analog Input.
Right-Click on these fi elds to access the Calibration, Override, and Clear Override.
The bell will light up to indicate that an alarm is on.
The Light bulb will light up when the Input is in the Occupied Mode.
Figure 9: Analog Input Window Components and Navigation
Renaming Analog Inputs
To give an Analog Input a new name, click on the blue highlighted Analog Input # fi eld and the Analog Input Data Entry Dialog Box
will open. See Figure 10 below. Once you have typed in a new description, press
characters is 17.
<ENTER> to save. The maximum number of
Figure 10: Analog Input Data Entry Dialog Box
12
GPC-XP Controller Technical Guide
Section 4: Confi guring Analog Inputs
Confi guring Analog Inputs
Left-click in the data entry fi eld in the Analog Inputs Window to open the Analog Input Con guration Window (Figure 11 below).
Analog Input Confi guration Screen
Figure 11: Analog Input Confi guration Window
The following confi gurations are available for each Analog Input:
Not Used
Thermistor Fahrenheit Temperature: 10K Ohm Type III
Scaled for Fahrenheit. Set jumper to the appropriate setting
(Figure 2, page 6.)
Thermistor Celsius Temperature: 10K Ohm Type III
Scaled for Celsius. Set jumper to the appropriate setting
(Figure 2, page 6.)
4 - 20mA User Scaled: 4-20mA User-Scaled Sensor
0 - 5vdc or 0-10 vdc User Scaled: Select this option
if using a 0-5vdc or 10vdc scaled sensor. Set jumper associated with this input to the appropriate 0-5v or 0-10v
setting (Figure 2, page 6.)
Wall Sensor Slide Offset: If using a WattMaster
thermistor space sensor with the slide adjust, this would be the input confi guration for the AUX connection from that sensor.
Read Global Analog – Channel: See Figure 110, page
48 for an explanation of Analog Globals. Left or right click
on the Question mark beside Global Analog Help to access information about the Global Broadcasts and to view pre­defi ned channels.
Communicating Temperature Sensor: If using a
WattMaster Communicating Temperature Sensor with a modular cable, confi gure this input to read the appropriate Communicating Sensor Address. Enter an address from 1-8 in the < Communicating Sensor Address> fi eld and
press <ENTER>. If using a combination Temperature and Humidity Communicating Sensor, confi gure one input to read the temperature and another input to read the humidity, both using the same Communicating Sensor address.*
Communicating Humidity Sensor: If using a
combination Temperature and Humidity Communicating Sensor with a modular cable, confi gure one input to read the temperature and another input to read the humidity, both using the same Communicating Sensor address. Enter an address from 1-8 in the <Communicating Sensor
Address>
Communicating Carbon Dioxide Sensor: If using a
WattMaster Communicating CO2 Sensor with a modular cable, confi gure this input to read the appropriate Comm- unicating Sensor Address. Enter an address from 1-8 in the <Communicating Sensor Address> fi eld and press
<ENTER>.*
Communicating Combination Outdoor Air Temperature and Humidity Sensor:
unicating Combination Outdoor Air Temperature and Humidity Sensor, confi gure one input to read the temperature and another input to read the humidity. For each input, enter
<25> as the Communicating Sensor Address. Only one of
these sensors can be used on a GPC-XP.
*NOTE: See the appropriate E-BUS Digital Room Sensor or
fi eld and press <ENTER>.*
If using a WattMaster Comm-
E-BUS Digital CO information on how to address the communicating sensors.
Sensor Technical Guides for
2
GPC-XP Controller Technical Guide
13
Section 4: Confi guring Analog Inputs
Sensor Reading, Scaling, and Override Duration
Sensor Reading Appendix
Figure 12: Sensor Reading Appendix Field
Select from the drop down list in the <Sensor Reading Appen-
fi eld (Figure 12 below) to give the sensor reading a qualifi er.
dix>
For User De ned, type in your own quali er in the < User Defi ned
Appendix>
eld.
User Defi ned: Enter your own in the
User Defi ned Appendix fi eld
°F: Fahrenheit
°C: Celsius
PPM: Parts Per Million
PSI: Pound per Square Inch
“WG: Inches of Water Gauge
Ft.: Feet
RPM: Revolutions per Minute
Internal Schedule Used for Night Setbacks and Overrides
If this input is reading a temperature sensor which will be using Night Setbacks or Unoccupied Overrides, select the applicable schedule.
See Figure 14 below. Actual Schedules are set in the Schedules Window. See instructions on page 35 for setting Schedules.
Figure 14: Schedule for Night Setbacks and Overrides
RH%: Humidity Percentage
%: Percentage
VDC: Volts D.C.
BTU: British Thermal Unit
CFM: Cubic Feet per Minute
HR: Hours
MIN: Minutes
GPM: Gallons per Minute
Sensor Scaling
All readings are user-scalable according to the number of digits
to the right of the decimal point. See Figure 13 and values and
examples below.
X 1 65°F
X 10 65.5°F
X 100 65.54°F
X 1000 65.543°F
Figure 13: Sensor Scaling Field
Override Duration
When setting an Override Duration, you must fi rst select the schedule in the <Internal Schedule Used for Night Setbacks & Over-
rides>
Sensor or a Communicating Temperature Sensor is used, an Over­ride Duration can be entered. When the Override Button is pushed on one of these sensors during the scheduled Unoccupied Mode, the schedule will be overridden back into the Occupied Mode. The Override Duration determines the amount of time the schedule will remain in Override Occupied Mode.
eld. When either a WattMaster Thermistor Temperature
Type a value between .1 Hours and 24 Hours and press <ENTER> to save.
Figure 15: Override Duration Field
NOTE: If using a Thermistor Sensor, the Override can be
cancelled by pressing the override button for 3 to 10 seconds. If using a Communicating Sensor with an Override button, pressing the button while in Override operation will cancel the Override.
14
GPC-XP Controller Technical Guide
Section 4: Confi guring Analog Inputs
Reading Average, Broadcast, and Scaling
Number of Readings to Average
This function has the capability of averaging up to 25 sensor read­ings before it displays a new value on the GPC-XP Controller Status
Screen. Sensor values are read once per second.
Type the number of readings from this sensor you want to aver-
age in the
<ENTER> to save. See Figure 16. Valid entries are from 1-25.
If you want the input sensor to only show its most current reading, enter <1>.
<Number of Readings to Average> fi eld and press
Figure 16: Number of Readings to Average Field
Send Global Analog
The reading of this sensor can also be “broadcast” to other controllers
on the communications loop. See Figure 17 below. The following
options are available: No Broadcast, Send to Local Loop, or Send to ALL Loops.
User Scaling
The User Scaling Box allows you to set a Maximum and Minimum Reading for the specifi c 4-20 mA or 0-5 vdc sensor you are using. See Figur e 19 below. T ype in the values and press
Figure 19: User Scaling Box
User Entered Formula
The User Entered Formula fi eld allows you to create a custom math function (formula) associated with the Analog Input of the screen you are on. The product of this formula will then be displayed as the value of that Analog Input, just as if it were the reading of a sensor connected to the input. This value can then be used in the control logic of a Relay Output or an Analog Output or it can be used in a AVC Highest/Lowest/Average calculation.
The formula can utilize the value(s) of any of the Analog Inputs, the Analog Outputs, the calculated AVC Highest/Lowest/Average values of several sensors, as well as other values listed in the Formula Help Window accessed by clicking on the question mark next to Formula Help in the User Scaling Box.
<ENTER> to save.
Figure 17: Send Global Analog Box
If you select < Send to Local Loop> or < Send to ALL Loops>, you must also type a channel in the and press for broadcast use. There are 31 available channels, but channels 1 to 14 are pre-defi ned for specifi c uses. See Figure 110, page 48 in the Appendix for the list of predefi ned channels that appear in the
Global Analog Help Screen.
Left or right click on the Question mark beside Global Analog Help
to access information about the Global Broadcasts and to view pre-
defi ned channels. See Figure 18 below.
<ENTER> to save. You must select from channel 15 to 31
< Analog Broadcast Channel> eld
Figure 18: Accessing Global Analog Help
To use this function you must click the <Enable User Entered
Formula> check box and then type the formula in the text box and
press <ENTER> to save.
Left or right click on the Question mark beside Formula Help to
access information about accepted formula formats.
To view the Formula Help Screen which contains some examples,
see the Formula Help section on page 49.
A maximum of 60 characters is allowed in the formula, so refrain from using spaces between characters and operators as they will use up needed space for the actual formula.
If you enter a formula incorrectly or create an invalid math function, such as dividing by zero, the Analog Input Window will display the word ERROR for that input so that you know something needs to be corrected in your formula.
GPC-XP Controller Technical Guide
15
Section 4: Confi guring Analog Inputs
Alarms, Calibration, and Overrides
Wall Sensor
If the sensor has been confi gured as a Wall Sensor Slide Offset, and you are using a WattMaster OE212, OE213, or Digital Space Temperature Sensor with the slide offset function, type the amount of the desired offset in < Maximum Slide Offset Effect> fi eld and
press <ENTER> to save. See Figure 20 below.
The value you enter is the amount of offset that will be applied to the Space Temperature Setpoint when the slider is all the way up or all the way down. At the center slide position, the Offset will have no effect on the current Space Temperature Setpoints.
Figure 20: Maximum Slide Offset
Alarm Confi guration
High and Low Alarm Limits can be programmed if the job-site requires out of range values to notify service personnel. The alarm limits can be increased at night by the amount of the Unoccupied Limit Spread. The Alarm Delay Period is the amount of time the sensor must be outside the limits before an alarm is generated. This prevents false alarms if the reading temporally exceeds the limit but then recovers and stays within the limits the remainder of the time. Type in a value and press <ENTER>. In order for the alarms to function, the <Alarming Enabled> check box must be checked.
See Figure 21 below.
Calibrate, Override, and Clear Sensor Override
Once confi gured, all thermistor sensors can be calibrated and all readings can be overridden to specifi c values.
Right-click in the data entry fi eld in the Analog Inputs Window to open the Calibrate, Override, and Clear Sensor Override Pop-Up Menu shown in Figure 22 below and select the desired function.
Figure 22: Calibrate and Override Sensor
If you select Calibrate Sensor or Override Reading, the data entry
window as shown by Figure 23 below will open. Left-click in the yel- low text fi eld, type in the desired value, and press
Figure 23: Data Entry Field
<ENTER> to save.
Figure 21: Alarm Confi guration
16
Calibrate Sensor: Type a positive or negative offset that
will be applied to the current reading and press <ENTER> to save.
Override Reading: Type a value that will override the
actual sensor reading and press <ENTER> to save.
Clear Sensor Override: Select to clear a sensor override
that was entered.
GPC-XP Controller Technical Guide
Section 5: Confi guring Binary Inputs
Binary Inputs
The Binary Inputs Window is located in the upper center of the GPC-XP Controller Status Screen (Figure 8, page 11). There are 8
Binary Inputs. See Figure 24 below for the Binary Inputs Window
component details.
Components and Navigation
Right or Left-click on any of the Binary Input name elds to access the description entry box to add or change the name of the Binary Input.
Left-click on the Status box to confi gure the Binary Input.
Right-click to override the Binary Input.
The bell will light up to indicate that an alarm is on.
The Light bulb will light up when the Input is in the Occupied Mode.
Figure 24: Binary Input Window Components and Navigation
Renaming Binary Inputs
To give the Binary Input a new name, click on the blue highlighted Binary Input # fi eld and the Binary Input Data Entry Dialog Box will
open (Figure 25 below). Once you have typed in a new description (max 17 characters), press
<ENTER> to save.
Figure 25: Binary Input Data Entry Dialog Box
GPC-XP Controller Technical Guide
17
Section 5: Confi guring Binary Inputs
Binary Input Type
Confi guring Binary Inputs
Left-click on the “ON” or “OFF” button to the right of Binary Input #1 in the Binary Input Window (Figure 24, page 17) to open the Binary Input Con guration Window (Figure 26 below). Each Binary Input is separately confi gured, so 8 binary input combinations are possible in one controller.
Figure 26: Binary Input Confi guration Window
Binary Confi guration
The following confi gurations are available for each Binary Input:
Not Used
N/O Contact (Close for Active) - This normally open
(N/O) input will become active when 24 VAC is applied.
N/C Contact (Open for Active) - This normally closed
(N/C) input will become active when 24 VAC is removed.
18
Read Global Binary - This input will read the Global
Binary on the selected channel. Click on the Question Mark symbol for Help information. See Figure 111, page 48 in the Appendix for the Global Binary Help Screen.
Push-Button Override - If a discrete Push-Button
Override switch (not on a space sensor) is wired to this input, also select the Override Duration desired (up to 24 hours). An Override on Binary Input #1 would affect Schedule #1. An Override on Binary Input #2 would affect Schedule #2, etc.
Follow Relay - This input will be active when the selected
relay is ON.
GPC-XP Controller Technical Guide
Loading...
+ 42 hidden pages