These operating instructions are for ORIFLOW model RHINO air leakage tester.
Take pride in knowing that you have purchased the best air leakage tester on the
market. It is no secret that Oriflow manufactures the highest quality testers, and has
unparalleled customer service and technical support.
The orifice plates available for your duct leakage tester are constructed from lasercut 3.2 mm stainless steel and do not require recalibration for 10 years. Note the
authority having jurisdiction may override this requirement, and if so, Oriflow has very
reasonable rates for calibrating orifice plates manufactured by Oriflow.
Safety Precautions
Before operating your tester, read the following safety precautions:
DO NOT operate the tester in the rain,
DO NOT operate the tester while it is near or in water,
DO NOT operate the tester with a damaged electrical cord or plug,
DO NOT remove the inlet safety screen,
DO NOT touch the blower wheel when the unit is plugged in,
DO NOT look into the discharge end of the tester when the unit is plugged in,
DO NOT use the tester as a ladder or step stool,
DO NOT allow children near the tester,
DO use an extension cord of the proper gauge (see Table 2),
DO use the proper voltage and line frequency listed on the motor nameplate,
DO lock the caster when the tester is positioned horizontally,
DO use the tester on level ground,
DO secure the tester when transporting it,
DO wear proper hearing protection, safety glasses and work gloves,
DO seek assistance when lifting the tester (e.g., loading onto truck, going up
Cap off all ends of system using clear plastic and duct tape or sheetmetal duct end
caps. Make sure you test the part of the duct system that leakage testing is required.
Usually, this is from the system fan up to, but not including, the VAV boxes (terminal
units). Refer to the engineer's specifications and all applicable codes and test
standards.
Power Requirements
Do you have an adequate power supply for your tester (see Table 1)?
If you need an extension cord, is it the proper gauge? See Table 2 below for
extension cord requirements.
Table 2 – Required Extension Cord Wire Gauge
Rhino Model
Flow
Control
Option
VFD 230 1
Slide Gate 230 3
VFD 230 3
Slide Gate 380 3
VFD 380 3
Slide Gate 460 3
VFD 460 3
Flex-Duct Length
Voltage Phase
Cord Length
Extension
(meters)
3 to 15 10
15 to 30 10
3 to 15 14
15 to 30 14
3 to 15 14
15 to 30 14
3 to 15 14
15 to 30 14
3 to 15 14
15 to 30 14
3 to 15 14
15 to 30 14
3 to 15 14
15 to 30 14
Gauge
Wire
Make sure you have enough flexible-duct with your tester for the job. Each tester
includes 3.8 m, which is enough for most applications. Extra lengths of flexible-duct
are available at www.oriflow.com/products.
Determining Maximum Allowable Leakage
To determine the maximum allowable leakage for the project, use ORIFLOW’s free online programs to make these calculations (www.oriflow.com/programs).
Calculations are done for either of the two typical specifications: percentage of
system flow, or leakage class. If the specification uses leakage class, you will need
to calculate the total duct system surface area. Oriflow has a free Adobe form
available to our customers that will calculate duct surface area given the duct shape,
dimensions and length.
After determining the allowable leakage at the system test pressure, refer to the
following tables for the capacities of each orifice plate available for the RHINO model
tester. Make sure you have an orifice plate that can measure the maximum allowable
leakage. The proper plate is the one where the maximum allowable leakage falls
between the minimum and maximum leakage at the system static pressure. For
example, if you are testing a system at 2500 Pa pressure and the maximum
allowable leakage is 283 L/s, you will need a 125 mm orifice plate since the 125 mm
plate can be used for up to 380 L/s of leakage (see Table 7).
It is a good idea to have the next larger orifice plate size since it is common for duct
systems to leak more than the maximum allowable. Smaller diameter plates are use
when leakage is relatively low.
Table 3 – Tester Capacities using the 25 mmOrifice Plate
The orifice plate that was determined from the previous section should now be
installed with the serial number facing upwards, so the corresponding calibration
certificate may be referenced after installation. Refer to Figures 1 through 4.
Figure 1 – Install Orifice Plate and then Rotate Clockwise
Figure 2 – Rotate Orifice Plate Clockwise until it Locks in Place
Install Orifice Plate and Upper Tube Section (continued)
After the orifice plate is locked in place, place the upper tube section over the
bolt/wing nut set, rotate clockwise, and tighten wing nuts (Figures 3 and 4).
Figure 3 – Install Upper Tube Section and Rotate Clockwise
Find a convenient location in the duct system where the tester has easy access.
Make sure that the connection where you connect the flexible duct is a sturdy, sealed
tight connection. You don’t want to create a leaky connection where the tester is
supplying air into the system.
So that you can monitor the system static pressure, you need to drill a hole at least 1
meter away from the flex-duct connection. Drill a 8 mm diameter hole and insert the
pressure tubing from the “DUCT SYSTEM” gauge so that 150 to 300 mm of tubing is
inside the duct system. Using putty or duct tape, seal the connection. If your
pressure tubing has a plastic static pressure tap at the end of the pressure tubing,
insert the tap in the hole and seal it to the duct wall using duct tape. See Figure 8
below.
Figure 8 - Static Pressure Tubing Connection
See Figure 9 showing the test setup for SUPPLY system testing. Refer to Figure 10
for the test setup required to measure air leakage of a RETURN/EXHAUST system.
Note you will need an inlet transition to attach to the blower inlet when performing a
return/exhaust test. The dimensions of the transition required depends on whether
you have a Rhino model with an inlet slide gate or VFD for flow control. See Figure 11 and 12 for inlet transition dimensions required.
DUCT SYSTEM pressure tubing
inserted into duct system
Before you run the tester, make sure both gauges have been zeroed.
Zeroing Analog Gauges
Using a very small screwdriver, turn the zero-adjustment screw on the gauge
until the needle is aligned with the zero reading. Turning the screw clockwise
increases the pressure reading; turning it counterclockwise, decreases the
reading. See Figure 13.
Figure 13 – Zeroing Analog Gauges
(zero BOTH gauges before testing)
Zeroing Digital Gauges
Use the following steps to zero each digital gauge:
1. Press MENU button once.
2. Press
3. Press
4. Press
5. Press
6. Press MENU button two times to get back to the pressure reading.
7. Pressure should be reading zero or within +/- 5 Pa If not, repeat
steps.
E button once to go into auto-zero mode
E button again and AUTO will be blinking on screen
E button a third time to complete the zeroing process.
15
Page 17
Avoid Over-Pressurization
Prior to starting the blower, shut the inlet slide gate on models without the speed
controller option. For models with the VFD speed controller, rotate the speed control
knob completely counter-clockwise.
Figure 14 – Avoid Over-Pressurizing by Minimizing Air Delivery upon Startup
Obtaining System Test Pressure
Turn the blower on and slowly open the inlet slide gate for models without the
speed control option. If your tester has the VFD speed controller, rotate speed
control knob slowly clockwise to obtain system test pressure.
Regardless of tester model used, pay attention to the “DUCT SYSTEM” gauge while
increasing airflow. When you have reached the required system static pressure,
tighten the set-screw on the inlet damper (or STOP rotating speed control knob).
Figure 16 – Duct System Gauge Reading (analog on left, digital on right)
Determining the Leakage Rate
Now that you have obtained the system test pressure, note the pressure reading of
the ORIFICE PLATE gauge (Figure 17). Refer to your calibration certificate to
determine the leakage rate that corresponds to the gauge reading. An example of a
calibration certificate is shown in Figure 18; it is for informational purposes only and
used in the example shown on the next page. Always refer to the calibration
certificate(s) that came with your calibrated orifice plate(s).
Figure 17 –ORIFICE PLATE Gauge Reading (analog on left, digital on right)
where the value of “7.206” is a constant and will be specific to the orifice
plate used (every plate has its own value; yours will be different).
Using a calculator, take the square root of the gauge reading first, and then
multiply by the constant for your orifice plate (for this example, the constant
is "7.206"). The exact leakage is 7.206 x (square root of 725) = 194.0 L/s.
Oriflow has FREE Adobe forms available that will calculate the leakage, leakage
factor, allowable leakage, Pass/Fail criteria and duct surface area among other
variables (www.oriflow.com/freeform).
Troubleshooting
Zero reading on “DUCT SYSTEM” gauge
If the gauge reading is zero, refer to the table below to fix this problem. Perform
troubleshooting steps in the order shown in the Table 9 below.
Table 9 –Troubleshooting steps when “DUCT SYSTEM” gauge is zero
Step Scenario What to do
1
2
3
4
Inlet damper was left shut,
cutting off air to the system.
Pressure tubing connected
to gauge incorrectly
Plugged fitting or
malfunctioning gauge.
System is leaking
too much air.
Open inlet damper slowly.
Look at the P1 and P2 stickers that are located on the
orifice tube and gauges. Make sure tubing from P1 tap
matches the P1 tap on the “ORIFICE PLATE” gauge.
Gently blow through other end of pressure tubing from
“DUCT SYSTEM” gauge, and watch needle increase
pressure reading.
Check for these other sources of leakage:
Rectangular duct joints (check and seal corners),
Fire or smoke dampers,
Duct joints (pay particular attention to flex-duct
joints if they are part of the leak test),
VAV boxes (pay particular attention to parallel box
If the gauge reading is zero, refer to the table below to fix this problem. Perform
troubleshooting steps in the order shown in Table 10 below.
Table 10 –Troubleshooting steps when “ORIFICE PLATE” gauge is zero
Step Scenario What to do
1
2 Plugged pressure taps.
3
4
4
5 Malfunctioning gauge.
6 Not sure
Inlet damper was left shut,
cutting off air to the system.
Orifice plate too large for
application.
System is leaking very little
air.
Pressure tubing connected
incorrectly.
Open inlet damper slowly.
Remove pressure tubing from “ORIFICE PLATE” gauge,
and blow through each end to make sure the pressure taps
on the orifice tube are clear.
If you are using a 100 mm ID orifice plate, and the system
is leaking 20 L/s, you probably won’t even notice the gauge
needle moving. This can happen to other orifice plates too.
You need to use an orifice plate with a smaller bore
diameter so that a small amount of airflow/leakage will
result in a bigger pressure drop.
You’ll know if this is true if the fan inlet is almost shut. Not
likely unless system is small. Solution is to use a smaller
ID plate.
Look at the P1 and P2 stickers that are located on the
orifice tube and gauges. Make sure they match.
Remove the clear pressure tubing from the lower pressure
tap on the orifice tube and blow through the end of the
tubing. The needle should move in response. If not, the
gauge is faulty.
The best way to make sure that your tester is working
properly is to disconnect the flex duct from the system and
turn the blower on, and slowly open the inlet damper. If you
feel a lot of air coming out of the tube end, you should see
a pressure reading on the gauge “ORIFICE PLATE”.
This happens when the system is leaking too much air. Make sure all outlets are
sealed. Check corners of rectangular duct for excessive leakage. Inspect all duct
and fitting joints for leakage. Make sure you seal all suspect joints and allow to cure
24 to 48 hours. Always refer to duct sealant manufacturer’s instructions.
Check for these other sources of leakage:
Rectangular duct joints (check and seal corners),
Fire or smoke dampers,
Duct joints (pay particular attention to flex-duct joints if they are part of the
leak test),
VAV boxes (pay particular attention to parallel box back draft dampers),
Built-up air handlers,
Plenums,
Uncured duct sealant blow-thru (follow manufacturer instructions for cure
time),
Improperly sealed or un-sealed joints,
Hot water coils and electric heaters,
Open duct end that was supposed to be sealed/capped-off for the leak test.
A non-toxic smoke machine is an excellent tool for locating significant sources of
leakage. Call ORIFLOW at 727-400-4881 or online at www.oriflow.com for more
information.
“ORIFICE PLATE” gauge reading maxed out
Scenario 1: The system is leaking too much air. Make sure all outlets are
sealed. Check corners of rectangular duct for excessive leakage. Inspect all
duct and fitting joints for leakage. Make sure you seal all suspect joints and
allow curing time of 24 to 48 hours. Always refer to duct sealant
manufacturer’s instructions.
Scenario 2: The orifice plate bore could be too small, causing a high
pressure drop at low to moderate flows. You need an orifice plate with a
larger bore.
ORIFLOW LLC
www.oriflow.com
2125 Range Rd., Suite B
Clearwater, Florida 33765
727-400-4881 (phone) 8am to 5pm PST
877-420-7091 (fax)
sales@oriflow.com
engineering@oriflow.com