Oriflow Panther User Manual

Operating Instructions for
Panther
Duct Leakage Tester
© Copyright 2015 ORIFLOW LLC
Table of Contents
Introduction
Introduction ……………………………………….…….. 2
Safety Precautions
Safety Precautions ………………………………….…. 2
Prior to Testing
System Preparation …………………….………………. 4 Power Requirements …………………………………... 3 Extension Cord Requirements ………………………... 3 Flex-Duct Length ………………………………………... 3 Determining Maximum Allowable Leakage ….……... 4 Determining Which Orifice Plate to Use ……………... 4 - 5
Duct Leakage Test Setup and Procedure
Install Orifice Plate ……………………………………... 6 Connect Flexible Duct to Orifice Tube ……………….. 7 Connect Flexible Duct to Duct System ………………. 7 System Test Pressure Connection …………………… 8 Duct Leakage Test Setup (SUPPLY) ………………… 9 Duct Leakage Test Setup (RETURN/EXHAUST) ….. 10 Zeroing Pressure Gauges ……………………………… 11 - 12 Avoiding Over Pressurization ………………………… 12 Obtaining System Test Pressure ……………………… 12 - 13 Determining Leakage Rate……………………………… 13 - 14
Troubleshooting
Zero reading on “DUCT SYSTEM” gauge ………….... 15
Zero reading on “ORIFICE TUBE” gauge …………….. 16 Can’t obtain system test pressure ……………………… 17
“ORIFICE TUBE” gauge reading maxed out………...... 17
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Introduction
These operating instructions are for ORIFLOW model PANTHER air leakage testers.
Take pride in knowing that you have purchased the best air leakage tester on the market. It is no secret that Oriflow manufactures the highest quality testers, and has unparalleled customer service and technical support.
The orifice plates available for your duct leakage tester are constructed from laser­cut 0.125-inch stainless steel and do not require recalibration for 10 years. Note the authority having jurisdiction may override this requirement, and if so, Oriflow has very reasonable rates for calibrating orifice plates manufactured by Oriflow.
Safety Precautions
Before operating your tester, read the following safety precautions:
DO NOT operate the tester in the rain,
DO NOT operate the tester while it is near or in water,
DO NOT operate the tester with a damaged electrical cord or plug,
DO NOT remove the inlet safety screen,
DO NOT touch the blower wheel when the unit is plugged in,
DO NOT look into the discharge end of the tester when the unit is plugged in,
DO NOT use the tester as a ladder or step stool,
DO NOT allow children near the tester,
DO use an extension cord of the proper gauge (see Table 2),
DO use the proper voltage and line frequency listed on the motor nameplate,
DO lock the caster when the tester is positioned horizontally,
DO use the tester on level ground,
DO secure the tester when transporting it,
DO wear proper hearing protection, safety glasses and work gloves,
DO seek assistance when lifting the tester (e.g., loading onto truck, going up
or down stairs).
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Prior to Testing
System Preparation Cap off all ends of system using clear plastic and duct tape or sheetmetal duct end caps. Make sure you test the part of the duct system that leakage testing is required. Usually, this is from the system fan up to, but not including, the VAV boxes (terminal units). Refer to the engineer's specifications and all applicable codes and test standards.
Power Requirements
Do you have an adequate power supply for your tester (see Table 1)?
Table 1 – Tester Amp Draw
Tester Model
Panther
* - The only flow control option for the Panther is the inlet slide gate. If a speed controller is desired, consider the Rhino model.
Voltage
115 Inlet Slide Gate 31
230 Inlet Slide Gate 16
Flow Control
Option*
Full Load
Amps
Extension Cord Requirements
If you need an extension cord, is it the proper gauge? See Table 2 below for
extension cord requirements.
Table 2 – Required Extension Cord Wire Gauge
Tester Model Voltage
115
Panther
230 up to 100 12
Extension Cord Length
(feet)
up to 50 8
51 to 100 6
Wire Gauge
Flex-Duct Length Make sure you have enough flexible-duct with your tester for the job. Each tester includes 12.5 feet, which is enough for most applications. Extra lengths of flexible­duct are available at www.oriflow.com/Products
.
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Determining Maximum Allowable Leakage
To determine the maximum allowable leakage for the project, use ORIFLOW’s free online programs to make these calculations (www.oriflow.com/Technical).
Calculations are done for either of the two typical specifications: percentage of system flow, or leakage class. If the specification uses leakage class, you will need to calculate the total duct system surface area. Oriflow has a free Adobe form available to our customers that will calculate duct surface area given the duct shape, dimensions and length.
Determining Which Orifice Plate to Use
After determining the allowable leakage at the system test pressure, refer to the
following tables for the capacities of each orifice plate available for the PANTHER
model tester. Make sure you have an orifice plate that can measure the maximum allowable leakage. The proper plate is the one where the maximum allowable leakage falls between the minimum and maximum leakage at the system static pressure. For example, if you are testing a system at 4 in.wg. pressure and the maximum allowable leakage is 600 cfm, you will need a 4-inch orifice since the 4­inch plate can test up to 740 cfm at a test pressure of 4 in.wg.
It is a good idea to have the next larger orifice plate size since it is common for duct systems to leak more than the maximum allowable. Smaller diameter plates are use when leakage is relatively low.
Table 3 – Tester Capacity using the 1-inch Orifice Plate
System Static
Pressure
(in.wg.)
2 4 6
8 5 30 10 12
Minimum
Flow Rate*
(cfm)
5 45 5 40 5 35
5 25 5 15
Table 4 – Tester Capacity using the 2-inch Orifice Plate
System Static
Pressure
(in.wg.)
2
4
6
8 25 130 10 12
Minimum
Flow Rate*
(cfm)
25 190 25 170 25 150
25 100 25 55
PANTHER Tester
Maximum
Flow Rate (cfm)
PANTHER Tester
Maximum
Flow Rate (cfm)
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Determining Which Orifice Plate to Use (continued)
Table 5 – Tester Capacity using the 3-inch Orifice Plate
System Static
Pressure
(in.wg.)
Minimum
Flow Rate*
(cfm)
PANTHER Tester
Maximum
Flow Rate (cfm)
2 50 390
4
6
8 50 265 10 12
50 350 50 310
50 205 50 120
Table 6 – Tester Capacity using the 4-inch Orifice Plate
System Static
Pressure
(in.wg.)
2
4
6
8 105 550 10 12
Minimum
Flow Rate*
(cfm)
105 820 105 740 105 655
105 425 105 245
PANTHER Tester
Flow Rate (cfm)
Maximum
Table 7 – Tester Capacity using the 5-inch Orifice Plate
System Static
Pressure
(in.wg.)
Minimum
Flow Rate*
(cfm)
PANTHER Tester
Maximum
Flow Rate (cfm)
2 190 1320
4
6
8 190 875 10 12
190 1210 190 1065
190 615 190 270
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Install Orifice Plate The orifice plate that was determined from the previous section should now be installed. Install the orifice plate with the serial number facing upwards so the corresponding calibration certificate may be referenced after installation. Refer to
Figures 1 through 3.
Figure 1 – Installing Orifice Plate Figure 2 – Installing Top Tube Section
Figure 3 – Bolting Flange (hand tighten snuggly)
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Connect Flexible Duct to Orifice Tube See the figures below for securing one end of the flexible duct to the orifice tube.
Note that the worm-gear clamp should be slid over the flex-duct before connecting it
to the orifice tube. Slide the flexible duct so that it overlaps the orifice tube1 to 2 inches, and tighten clamp using a 5/16-inch nut driver.
Figure 4 – Installing Flex-Duct on Tube Figure 5 – Tightening Clamp
Connect Flex-Duct to Duct System Find a convenient location in the duct system where the tester has easy access. Make sure that the connection where you connect the flexible duct is a sturdy, sealed tight connection. You don’t want to create a leaky connection where the tester is supplying air into the system.
Figure 6 – Connection to Duct System
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
System Test Pressure Connection So that you can monitor the system static pressure, you need to drill a hole at least 3 feet away from the flex-duct connection. Drill a 5/16-inch diameter hole and insert the pressure tubing from the “DUCT SYSTEM” gauge so that 6 to 12 inches of tubing is inside the duct system. Using putty or duct tape, seal the connection. If your pressure tubing has a plastic static pressure tap at the end of the pressure tubing,
insert the tap in the hole and seal it to the duct wall using duct tape. See Figure 4
below.
Figure 7 - Static Pressure Tubing Connection
See Figure 8 showing the test setup for SUPPLY system testing. Refer to Figure 9
for the test setup required to measure air leakage of a RETURN/EXHAUST system.
DUCT SYSTEM pressure tubing inserted into duct system
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Figure 8 – Duct Leakage Test Setup for a SUPPLY System
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
Figure 9 – Duct Leakage Test Setup for a RETURN/EXHAUST System
Figure 9 – Duct Leakage Test Setup for a RETURN/EXHAUST System
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
10
Zeroing Pressure Gauges Before you run the tester, make sure both gauges have been zeroed.
Zeroing Analog Gauges Using a very small screwdriver, turn the zero-adjustment screw on the gauge until the needle is aligned with the zero reading. Turning the screw clockwise increases the pressure reading; turning it counterclockwise, decreases the
reading. See Figure 10.
Figure 10 – Zeroing Analog Gauges
(zero BOTH gauges before testing)
Zeroing Digital Gauges Use the following steps to zero each digital gauge:
1. Press MENU button once.
2. Press
3. Press
4. Press
5. Press
6. Press MENU button two times to get back to the pressure reading.
7. Pressure should be reading zero or within +/- 0.02 in.wg. If not, repeat steps.
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
arrow button until Adu shows on screen.
E button once to go into auto-zero mode E button again and AUTO will be blinking on screen E button a third time to complete the zeroing process.
11
Avoid Over Pressurization Prior to starting the blower, shut the inlet slide gate completely so that when the blower is turned on, it will not over pressurize the duct system.
Figure 12 – Avoid Over-Pressurizing by Minimizing Air Delivery upon Startup
Obtaining System Test Pressure
Turn the blower on and slowly open the inlet slide to obtain system test pressure.
Figure 13 – Obtaining System Test Pressure
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
12
Obtaining System Test Pressure (continued)
Regardless of tester model used, pay attention to the “DUCT SYSTEM” gauge while increasing airflow. When you have reached the required system static pressure, tighten the set-screw on the inlet damper (or stop rotating the speed control knob).
Figure 14 – Duct System Gauge Pressure Reading
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
13
Determining the Leakage Rate Now that you have obtained the system test pressure and have the inlet damper
locked in position, note the pressure reading of the ORIFICE TUBE gauge (Figure
15). Refer to your calibration certificate to determine the leakage rate that
corresponds to the gauge reading. An example of a calibration certificate is shown in
Figure 16; it is for informational purposes only and used in the example shown on the next page. Always refer to the calibration certificate that came with your
calibrated orifice plate.
Figure 15 –ORIFICE TUBE reading
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
14
SAMPLE CALIBRATION CERTIFICATE TABLE FOR EXAMPLE ONLY
USE YOUR CERTIFICATE
Figure 16 – Tables from a Sample Calibration Certificate. Every calibration chart has an equation located
below the table (not shown here)
Example (refer to Figure 16) For an ORIFICE TUBE gauge reading of 1.15 in.wg., the leakage rate
appears to be approximately 143 cfm. For an exact value, use the equation that comes with every calibration
certificate. For the example shown in Figure 16: Leakage = 133.6 x , where the value of “133.6” is a constant and will be specific to the orifice
plate used (every plate has its own value; yours will be different). Using a calculator, take the square root of the gauge reading first, and then
multiply by the constant for your orifice plate (for this example, the constant is "133.6"). The exact leakage is 133.6 x (square root of 1.15) = 143.3 cfm. In most cases, reporting the leakage as 143 cfm is acceptable.
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
15
Troubleshooting
Zero reading on “DUCT SYSTEM” gauge If the gauge reading is zero, refer to the table below to fix this problem. Perform
troubleshooting steps in the order shown in the Table 7 below.
Table 7 –Troubleshooting steps when “DUCT SYSTEM” gauge is zero
Step Scenario What to do
1
2
3
4
Inlet damper was left shut,
cutting off air to the system.
Pressure tubing connected
to gauge incorrectly
Plugged fitting or
malfunctioning gauge.
System is leaking
too much air.
Open inlet damper slowly.
Look at the P1 and P2 stickers that are located on the orifice tube and gauges. Make sure tubing from P1 tap matches the P1 tap on the “ORIFICE TUBE” gauge.
Gently blow through other end of pressure tubing from “DUCT SYSTEM” gauge, and watch needle increase pressure reading.
Check for these other sources of leakage:
Rectangular duct joints (check and seal corners),  Fire or smoke dampers,  Duct joints (pay particular attention to flex-duct
joints if they are part of the leak test),
VAV boxes (pay particular attention to parallel box
back draft dampers),
Built-up air handlers,  Plenums,  Uncured duct sealant blow-thru (follow
manufacturer instructions for cure time),
Improperly sealed or un-sealed joints,  Hot water coils and electric heaters,  Open duct end that was supposed to be
sealed/capped-off for the leak test.
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
16
Zero reading on “ORIFICE TUBE” gauge If the gauge reading is zero, refer to the table below to fix this problem. Perform
troubleshooting steps in the order shown in Table 8 below.
Table 8 –Troubleshooting steps when “ORIFICE TUBE” gauge is zero
Step Scenario What to do
1
2 Plugged pressure taps.
3
4
4
5 Malfunctioning gauge.
6 Not sure
Inlet damper was left shut,
cutting off air to the system.
Orifice plate too large for
application.
System is leaking very little
air.
Pressure tubing connected
incorrectly.
Open inlet damper slowly.
Remove pressure tubing from “ORIFICE TUBE” gauge, and blow through each end to make sure the pressure taps on the orifice tube are clear.
If you are using a 4-inch ID orifice plate, and the system is leaking 40 cfm, you probably won’t even notice the gauge needle moving. This can happen to other orifice plates too. You need to purchase an orifice plate with a smaller bore diameter so that a small amount of airflow/leakage will result in a bigger pressure drop.
You’ll know if this is true if the fan inlet is almost shut. Not likely unless system is small. Fix is to use plate with smaller bore.
Look at the P1 and P2 stickers that are located on the orifice tube and gauges. Make sure they match.
Remove the clear pressure tubing from the lower pressure tap on the orifice tube and blow through the end of the tubing. The needle should move in response. If not, the gauge is faulty.
The best way to make sure that your tester is working properly is to disconnect the flex duct from the system and turn the blower on, and slowly open the inlet damper. If you feel a lot of air coming out of the tube end, you should see a pressure reading on the gauge “ORIFICE TUBE”.
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
17
Can’t obtain system test pressure This happens when the system is leaking too much air. Make sure all outlets are sealed. Check corners of rectangular duct for excessive leakage. Inspect all duct and fitting joints for leakage. Make sure you seal all suspect joints and allow to cure 24 to 48 hours. Always refer to duct sealant manufacturer’s instructions.
Check for these other sources of leakage:
Rectangular duct joints (check and seal corners),  Fire or smoke dampers,  Duct joints (pay particular attention to flex-duct joints if they are part of the
leak test),
VAV boxes (pay particular attention to parallel box back draft dampers),  Built-up air handlers,  Plenums,  Uncured duct sealant blow-thru (follow manufacturer instructions for cure
time),
Improperly sealed or un-sealed joints,  Hot water coils and electric heaters,  Open duct end that was supposed to be sealed/capped-off for the leak test.
A non-toxic smoke machine is an excellent tool for locating significant sources of leakage. Call ORIFLOW at 727-400-4881 or online at www.oriflow.com information.
“ORIFICE TUBE” gauge reading maxed out
Scenario 1: The system is leaking too much air. Make sure all outlets are
sealed. Check corners of rectangular duct for excessive leakage. Inspect all duct and fitting joints for leakage. Make sure you seal all suspect joints and allow curing time of 24 to 48 hours. Always refer to duct sealant manufacturer’s instructions.
Scenario 2: orifice plate bore could be too small, causing a high pressure
drop at low to moderate flows. You need an orifice plate with a larger bore.
ORIFLOW LLC www.oriflow.com 2125 Range Rd., Unit B Clearwater, Florida 33765
727-400-4881 (phone) 8am to 5pm PST 877-420-7091 (fax) sales@oriflow.com engineering@oriflow.com
for more
© Copyright 2015 ORIFLOW LLC Rev: 06/2015-1
18
Loading...