Oriflow Lynx, Cobra User Manual

Operating Instructions for
Cobra and Lynx
Duct Leakage Testers
© Copyright 2018 ORIFLOW LLC
Links to Online Help
(QR Code)
Video – Commercial Duct Leakage
Testing
Online Max Leakage Calculator
(SMACNA Leakage Class)
Online Technical Library
Online Max Leakage Calculator
(% Allowable)
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
1
Table of Contents
Introduction
Introduction ……………………………………….………………………….…………… 3
Safety Precautions
Safety Precautions ………… READ FIRST! ……….….……………….……………… 3
Prior to Testing
Are You Using the Correct Tester? …………………………………….…...…………. 4 System Preparation …………………….……………….…………….……...….……… 4
Power Requirements …………………………………....…………….……...….……… 4
Extension Cord Requirements ………………………....…………….……...…………. 5
Flex-Duct Length ………………………………………...…………………….……...…. 5 Determining Maximum Allowable Leakage ….………..……………...…….….……… 5 FREE Oriflow duct test summary form (SMACNA or DW/143) ………….….………. 5
Determining Which Orifice Plate to Use ……………....……………..……..…………. 6 - 7
Duct Leakage Test Setup and Procedure
Install Orifice Plate and Upper Tube Section ……………………………..………..…. 8 - 9
Connect Flex-Duct to Orifice Tube ………………........…………….……...….……… 9
Connect Flex-Duct and Static Pressure Tap to Duct System ………….……………. 10 - 11 Duct Leakage Test Setup (SUPPLY) ………………….……………..……..…………. 12 Duct Leakage Test Setup (RETURN/EXHAUST) …………………..……..…………. 13 Zeroing Pressure Gauges ……………………………………………..……..…………. 14 Avoiding Over-Pressurization …………………………..……………...…….…………. 15 Obtaining System Test Pressure ……………………………………...…….…………. 15 - 16 Determining Leakage Rate……………………………………………..….….…………. 16 - 17
Troubleshooting
Can’t obtain system test pressure (DUCT PRESSURE TOO LOW) …………….…. 18 Can’t obtain system test pressure (DUCT PRESSURE TOO HIGH) …….……….… 19
Zero reading on ORIFICE PLATE gauge ……………..…………………........……….. 19
ORIFICE PLATE gauge reading maxed out ………......……………...….…....………. 20
GFCI/GFI trips …………………………………………………………………………….. 20
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
2
Introduction
These operating instructions are for ORIFLOW models COBRA and LYNX air leakage testers. Take pride in knowing that you have purchased the best air leakage tester on the market. It is no secret that Oriflow manufactures the highest quality testers, and has unparalleled customer service and technical support.
The orifice plates available for your duct leakage tester are constructed from laser-cut 0.063-inch stainless steel and do not require recalibration for 5 years. Note the authority having jurisdiction may override this requirement, and if so, Oriflow has reasonable rates for re-calibrating orifice plates manufactured by Oriflow.
Safety Precautions
Before operating your tester, read the following safety precautions:
DO NOT operate the tester in the rain, DO NOT operate the tester while it is near or in water, DO NOT operate the tester with a damaged electrical cord or plug, DO NOT remove the inlet safety screen, DO NOT touch the blower wheel when the unit is plugged in, DO NOT look into the discharge end of the tester when the unit is plugged in, DO NOT use the tester as a ladder or step stool, DO NOT allow children near the tester, DO use an extension cord of the proper gauge (see Table 2), DO use the proper voltage and line frequency listed on the motor nameplate, DO lock the caster when the tester is positioned horizontally, DO use the tester on level ground, DO secure the tester when transporting it, DO wear proper hearing protection, safety glasses and work gloves, DO seek assistance when lifting the tester (e.g., loading onto truck, going up or down stairs).
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
3
Prior to Testing
Are you Using the Correct Tester? See Table 1 for the maximum capacity for each duct tester when using the largest orifice plate.
Table 1 – Duct Leakage Tester Capacities
MaximumLeakageCapacity(cfm)*
Model
0.10 1 2 4 6 7 8 9 10 12 14 16
Lynx
Cobra
Panther
Rhino
* Using the largest sized orifice available for the model listed.
570 cfm 680 cfm
1400
cfm
1700
cfm
550 cfm 650 cfm
1350
cfm
1630
cfm
540 cfm 645 cfm
1320
cfm
1550
cfm
455 cfm 600 cfm
1210
cfm
1420
cfm
SystemTestPressure(in.wg.)
290 cfm 465 cfm
1065
cfm
1330
cfm
160 cfm 405 cfm 970 cfm
1255
cfm
350 cfm 875 cfm
1185
cfm
250 cfm 875 cfm
1185
cfm
615 cfm
1035
cfm
270 cfm 895 cfm
660 cfm
480 cfm
System Preparation Cap off all ends of system using clear plastic and duct tape or sheetmetal duct end caps. Make sure
you test the part of the duct system that leakage testing is required. Usually, this is from the system fan up to, but not including, the VAV boxes (terminal units). Refer to the engineer's specifications and all applicable codes and test standards.
Power Requirements Do you have an adequate power supply for your tester (see Table 2)?
Table 2 – Tester Amp Draw
Tester Model Voltage
Lynx 115 Slide Gate 12.7 Cobra 115 Slide Gate 12.8 Cobra 115 VFD 14.0 Cobra 230 Slide Gate 6.4 Cobra 230 VFD 8.0
Flow Control
Option
Full Load
Amps
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
4
Extension Cord Requirements If you need an extension cord, is it the proper gauge? See Table 3 below for extension cord
requirements.
Table 3 – Required Extension Cord Wire Gauge
Tester Model
Lynx or Cobra Slide Gate 115
Cobra Slide Gate 230
Cobra VFD 115
Cobra VFD 230
Flow Control
Option
Voltage
Extension Cord
Length (feet)
10 to 50 14
50 to 100 12
10 to 50 14
50 to 100 14
10 to 50 14
50 to 100 12
10 to 50 14
50 to 100 14
Wire Gauge
Flex-Duct Length Make sure you have enough flexible-duct with your tester for the job. Each tester
includes 12.5 feet, which is enough for most applications. Extra lengths of flexible-duct are available at www.oriflow.com/products.
Determining Maximum Allowable Leakage To determine the maximum allowable leakage for the project, use ORIFLOW’s free
online programs to make these calculations (www.oriflow.com/programs). In the U.S., calculations are done for either of the two typical specifications:
1. Percentage of system flow, or
2. SMACNA Leakage Class.
In Europe, Australia and other countries outside of the U.S., the following DW/143 specification is commonly used:
1. Pressure Classification (Class A, B, C or D)
If the specification uses SMACNA Leakage Class or Pressure Classification, you will need to calculate the total duct system surface area.
Oriflow has a FREE Adobe test summary sheet that will calculate duct surface area, leakage, leakage factor, allowable leakage, and Pass/Fail criteria. You can find these test summary sheets at (www.oriflow.com/freeform). It’s an excellent tool that can be printed out or emailed to a customer or engineer for submittal.
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
5
Determining Which Orifice Plate to Use After determining the allowable leakage at the system test pressure, refer to the following tables for the
capacities of each orifice plate available for the Cobra and Lynx model testers. The proper plate is the one where the specified allowable leakage falls between the minimum and maximum leakage at the system static pressure.
For example, if you are testing a system at 4 in.wg. pressure and the maximum allowable leakage is 350 cfm, you will need a 3-inch orifice plate if using the Cobra tester (see Table 6) or a 4-inch plate if using the Lynx tester (Table 7).
Table 4 – Tester Capacities using the 1-inch Orifice Plate*
System Static
Pressure
(in.wg.)
* If you need to measure lower flow rates, contact us about the ‘low-flow’ orifice plate. ** Recommended minimum based on 0.40 in.w g. across orifice plate.
Table 5 – Tester Capacities using the 2-inch Orifice Plate
System Static
Pressure
(in.wg.)
** Recommended minimum based on 0.40 in.wg. across orifice plate.
0.10 1 2 3 4 5 6 7 8 9
0.10 1 2 3 4 5 6 7 8 9
Minimum
Leakage**
Minimum
Leakage**
(cfm)
9 47 37 9 44 34 9 42 32 9 39 27 9 36 23 9 32 17 9 29 15 9 24 6 9 19 -­9 12 --
(cfm)
34 180 160 34 170 150 34 165 135 34 155 120 34 140 105 34 125 85 34 115 65 34 95 25 34 75 -­34 45 --
COBRA Tester
Maximum
Leakage
(cfm)
COBRA Tester
Maximum
Leakage
(cfm)
LYNX Tester
Maximum
Leakage
(cfm)
LYNX Tester
Maximum
Leakage
(cfm)
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
6
Determining Which Orifice Plate to Use (continued)
Table 6 – Tester Capacities using the 3-inch Orifice Plate
System Static
Pressure
(in.wg.)
** Recommended minimum based on 0.40 in.wg. across orifice plate.
Table 7 – Tester Capacities using the 4-inch Orifice Plate
System Static
Pressure
(in.wg.)
** Recommended minimum based on 0.40 in.wg. across orifice plate.
0.10
1 2 3 4 5 6 7 8 9
0.10
1 2 3 4 5 6 7 8 9
Minimum
Leakage**
(cfm)
82 440 375 82 420 355 82 410 340 82 390 320 82 375 285 82 340 230 82 290 170 82 245 55 82 195 -­82 130 --
Minimum
Leakage**
(cfm)
175 680 570 175 650 550 175 645 540 175 630 510 175 600 455 175 545 365 175 465 290 175 405 160 175 350 -­175 250 --
COBRA Tester
Maximum
Leakage
(cfm)
COBRA Tester
Maximum
Leakage
(cfm)
LYNX Tester
Maximum
Leakage
(cfm)
LYNX Tester
Maximum
Leakage
(cfm)
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
7
Duct Leakage Test Setup and Procedure
Install Orifice Plate and Upper Tube Section The orifice plate that was determined from the previous section should now be installed with the serial
number facing upwards so the corresponding calibration certificate may be referenced after installation. Refer to Figures 1 through 4.
Figure 1 – Install Orifice Plate and then Rotate Clockwise
Figure 2 – Rotate Orifice Plate Clockwise until it Locks in Place
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
8
Install Orifice Plate and Upper Tube Section (continued) After the orifice plate is locked in place, place the upper tube section over the bolt/wing nut set, rotate
clockwise, and tighten wing nuts (Figures 3 and 4).
Figure 3 – Install Upper Tube Section and Rotate Clockwise
Figure 4 – Tighten Wing Nuts after Rotation
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
9
Connect Flex-Duct to Orifice Tube See Figure 5 below for securing the 5-inch end of the flexible duct to the orifice tube. Slide the flexible
duct so that it overlaps the orifice tube 2 to 3 inches, and tighten clamp using a 5/16-inch nut driver.
Figure 5 – Installing Flex-Duct on Tube
Connect Flex-Duct and Static Pressure Tap to Duct System Refer to Figures 6 and 7. Connect the 6-inch end of the flex-duct to the duct system. Find a convenient
location in the duct system where the tester has easy access. Make sure the connection is a sturdy, sealed tight connection. You don’t want to create a leaky connection thereby adding to the system leakage.
To monitor the system static pressure, you need to drill a 5/16-inch diameter hole for the grey plastic static pressure tap to measure system static pressure (Figure 7).
If the static pressure tap is missing, locate the hole at least 3 feet away from flex-duct connection, and insert the pressure tubing from the DUCT SYSTEM gauge so that 6 to 12 inches of tubing is inside the duct system. Using putty or duct tape, seal the connection. See Figure 8.
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
10
Connect Flex-Duct and Static Pressure Tap to Duct System (continued)
Figure 6 – Connection to Duct System
Figure 7 – Connection to Duct System using Static Pressure Tap
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
11
Duct Leakage Test Setup (SUPPLY) See Figure 8 for the test setup for SUPPLY duct system testing (positive pressure testing). On the
backside of the DUCT SYSTEM pressure gauge, move the pressure tubing to the pressure port labeled SUPPLY SYSTEM.
Figure 8 – Duct Leakage Test Setup for a SUPPLY System
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
12
Duct Leakage Test Setup (RETURN/EXHAUST) Refer to Figure 9 for the test setup required to measure air leakage of a RETURN/EXHAUST system
(negative pressure testing). On the backside of the DUCT SYSTEM pressure gauge, move the pressure tubing to the pressure port labeled RETURN SYSTEM.
Connect the 6-inch end of the flex-duct to the inlet of the blower so that air from the system is drawn into the blower. You will determine the leakage of the system since the air drawn from the blower is discharged through the orifice plate which you are measuring.
Figure 9 – Duct Leakage Test Setup for a RETURN/EXHAUST System
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
13
Zeroing Pressure Gauges Before you turn on the tester, make sure both gauges have been zeroed.
Zeroing Analog Gauges Using a small slotted screwdriver, turn the zero-adjustment screw on the gauge until the needle
is aligned with the zero reading. Turning the screw clockwise increases the pressure reading; turning it counterclockwise decreases the reading. See Figure 10.
Figure 10 – Zeroing Analog Gauges
Zeroing Digital Gauges First, turn on both gauges by pressing the black (or red) button located on the backside of each
gauge. Use the following steps to zero each digital gauge:
1. Press MENU button once.
2. Press
3. Press
4. Press
5. Press
6. Press MENU button two times to get back to the pressure reading.
7. Pressure should be reading zero or within +/- 0.02 in.wg. If not, repeat steps.
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
arrow button until Adu shows on screen.
E button once to go into auto-zero mode E button again and AUTO will be blinking on screen E button a third time to complete the zeroing process.
14
Avoiding Over-Pressurization Prior to starting the blower, shut the inlet slide gate on models without the speed controller option. For
models with the VFD speed controller, press and hold the DOWN button
10.00 (the lowest speed setting). If powering up for the first time, the reading will already be at 10.00. See Figures 11.
Figure 11 – Avoid Over-Pressurizing by Minimizing Air Delivery upon Startup (inlet slide model on left, VFD speed control model on right)
Obtaining System Test Pressure Turn the blower on and slowly open the inlet slide gate if your tester has an inlet slide gate. If your
tester has the VFD speed controller, press the green RUN button, and then press the UP arrow button
until the readout shows
to increase fan speed. Pressing and holding the UP button will increase speed more quickly.
See Figures 12.
Figure 12 – Obtaining System Test Pressure (inlet slide model on left, VFD speed control model on right)
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
15
Obtaining System Test Pressure (continued) Regardless of tester model used, pay attention to the DUCT SYSTEM gauge while increasing airflow
(Figures 13). When you have reached the required system static pressure, tighten the set-screw on the inlet damper (or STOP pressing the UP arrow button
).
Figure 13 – Duct System Test Pressure (analog on left, digital on right)
Determining the Leakage Rate Now that you have obtained the system test pressure, note the pressure drop of the ORIFICE PLATE
gauge (Figures 14). Refer to your calibration certificate to determine the leakage rate that corresponds to the gauge reading. An example of a calibration certificate is shown in Figure 15; it is for informational purposes only and used in the example shown on the next page. Always refer to the calibration certificate(s) that came with your calibrated orifice plate(s).
Figure 14 – Orifice Plate Pressure Drop (analog on left, digital on right)
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
16
SAMPLE CALIBRATION CERTIFICATE
USE YOUR CERTIFICATE
Figure 15 – Example Calibration Certificate. Use the calibration certificate that came with your orifice plate
Example (refer to Figures 14 and 15) For an ORIFICE PLATE pressure drop (gauge reading) of 2.46 in.wg. (Figure 14), the leakage rate is
approximately 210 cfm using the calibration certificate shown in Figure 15. For an exact value, use the equation that comes with every calibration certificate. For the certificate
shown in Figure 15:
Leakage = 134.42 x ,
where the value of “134.42” is a constant and will be specific to the orifice plate used (every plate has its own value; yours will be different).
Using a calculator, take the square root of the ORIFICE PLATE gauge reading first, and then multiply by the constant for your orifice plate (for this example, the constant is "133.357"). The exact leakage is
134.42 x (square root of 2.46) = 210.8 cfm.
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
17
Troubleshooting
Can’t obtain system test pressure (DUCT PRESSURE TOO LOW)
This typically happens when the system is leaking too much air. Make sure all outlets are sealed. Check corners of rectangular duct for excessive leakage. Inspect all duct and fitting joints for leakage. Make sure you seal all suspect joints and allow to cure 24 to 48 hours. Always refer to duct sealant manufacturer’s instructions.
Perform troubleshooting steps in the order shown in the Table 7 below.
Table 7 –Troubleshooting steps when DUCT SYSTEM test pressure is too low
Step Scenario What to do
Allowable Leakage is
1
2
3
4
5 Malfunctioning gauge.
6
A non-toxic smoke machine is an excellent tool for locating significant sources of leakage. Call ORIFLOW at 727-400-4881 or to our website at www.oriflow.com for more information.
greater than capacity of
tester.
Inlet damper was left shut,
cutting off air to the system.
Pressure tubing connected
to gauge incorrectly
Plugged pressure port on
orifice tube
System is leaking
too much air.
Refer to page 4, “Are you using the correct tester.”
Open inlet damper slowly. Look at the P1 and P2 stickers that are located on the
orifice tube (airflow meter) and gauges. Make sure tubing from P1 tap is connected to the P1 tap on the ORIFICE PLATE gauge.
Remove pressure tubing from the P1 and P2 ports on the ORIFICE PLATE gauge. Blow through each tubing end. You should be able to blow air freely through both ports.
Attach pressure tubing to the port labeled “SUPPLY SYSTEM.” Gently blow through other end of pressure tubing. The pressure reading should increase.
Check for these other sources of leakage:
Rectangular duct joints (check and seal corners),  Fire or smoke dampers,  Duct joints (pay particular attention to flex-duct
joints if they are part of the leak test),
VAV boxes (pay particular attention to parallel box
back draft dampers),
Built-up air handlers,  Plenums,  Uncured duct sealant blow-thru (follow
manufacturer instructions for cure time),
Improperly sealed or un-sealed joints,  Hot water coils and electric heaters,  Open duct end that was supposed to be
sealed/capped-off for the leak test.
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
18
Can’t obtain system test pressure (DUCT PRESSURE TOO HIGH) This typically happens on small or tight systems when using a duct tester without the VFD speed
controller. Testers equipped with the inlet slide gate damper always run at about 3500 rpm and are so powerful, air pressure is generated even with the inlet damper completely shut.
Use a smaller orifice plate. If using the 1-inch plate, install the ½-inch plate which is used to
measure flow rates from 1 to 10 cfm.
Using duct tape, completely cover the upper orifice tube section, and then poke a hole in it with
a screwdriver or pen. Then install the flex-duct as usual. This will act as an outlet damper or restriction. Now you can use the inlet damper to regulate flow.
Zero reading on ORIFICE PLATE gauge
If the gauge reading is zero, refer to the table below to fix this problem. Perform troubleshooting steps in the order shown in Table 8 below.
Table 8 –Troubleshooting steps when ORIFICE PLATE gauge is zero
Step Scenario What to do
1
2 Plugged pressure taps.
3
4
4
5 Malfunctioning gauge.
6 Not sure
Inlet damper was left shut,
cutting off air to the system.
Orifice plate too large for
application.
System is leaking very little
air.
Pressure tubing connected
incorrectly.
Open inlet damper slowly. Remove pressure tubing from ORIFICE PLATE gauge, and
blow through each end to make sure the pressure taps on the orifice tube are clear.
If you are using a 4-inch ID orifice plate, and the system is leaking 40 cfm, you probably won’t even notice the gauge needle moving. This can happen to other orifice plates too. You need to purchase an orifice plate with a smaller bore diameter so that a small amount of airflow/leakage will result in a bigger pressure drop.
You’ll know if this is true if the fan inlet is almost shut. Not likely unless system is small. Fix is to use plate with smaller bore.
Look at the P1 and P2 stickers that are located on the orifice tube and the ORIFICE PLATE gauge. Make sure they match.
Remove the clear pressure tubing from the lower pressure tap on the orifice tube and blow through the end of the tubing. The needle should move in response. If not, the gauge is faulty.
The best way to make sure that your tester is working properly is to disconnect the flex duct from the system and turn the blower on, and slowly open the inlet damper. If you feel a lot of air coming out of the tube end, you should see a pressure reading on the gauge ORIFICE PLATE.
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 01/2018
19
ORIFICE PLATE gauge reading maxed out
Scenario 1: The system is leaking too much air. Make sure all outlets are sealed. Check
corners of rectangular duct for excessive leakage. Inspect all duct and fitting joints for leakage. Make sure you seal all suspect joints and allow curing time of 24 to 48 hours. Always refer to duct sealant manufacturer’s instructions.
Scenario 2: orifice plate bore could be too small, causing a high pressure drop at low to
moderate flows. Use the next larger sized orifice.
GFI/GFCI trips
We are aware of this happening only when using a Cobra duct leakage tester with the VFD, or variable speed drive option. We have found that in these cases, the supply wiring has ground wired to neutral, which can cause the GFI to activate when the VFD is operating.
Possible solutions: 1) utilize a correctly wired GFI outlet that has separate neutral and ground; 2) use a non-GFI outlet to power the tester; or 3) use a non-VFD model tester.
Operating Instructions for Cobra © Copyright 2018 and Lynx Duct Leakage Testers Rev: 11/2018
20
www.oriflow.com
ORIFLOW LLC
2125 Range Rd., Unit B
Clearwater, Florida 33765
Customer Service: 727-400-4881 Technical Support: 727-207-8973
sales@oriflow.com
© Copyright 2018 ORIFLOW LLC
Loading...