This documentand theproduct andtechnology towhich itpertains are distributed underlicenses restricting their use,copying, distribution,and
decompilation. Nopart ofsuch productor technology,or ofthis document,may bereproduced inany formby anymeans withoutprior written
authorization ofOracle and/orits affiliatesand FujitsuLimited, andtheir applicablelicensors, ifany. Thefurnishings ofthis documentto youdoes not
give youany rightsor licenses,express orimplied, withrespect to the product ortechnology towhich itpertains, andthis documentdoes notcontain or
represent any commitment of any kind on the part of Oracle or Fujitsu Limited, or any affiliateof eitherof them.
This documentand theproduct andtechnology describedin thisdocument mayincorporate third-party intellectual property copyrighted byand/or
licensed fromthe suppliersto Oracleand/or itsaffiliates and Fujitsu Limited, including software andfont technology.
This distributionmay includematerials developedby thirdparties.
Parts ofthe product may bederived from BerkeleyBSD systems,licensed fromthe University of California. UNIXis aregistered trademark inthe U.S.and
in othercountries, exclusivelylicensed throughX/Open Company,Ltd.
Oracle andJava areregisteredtrademarks ofOracle and/orits affiliates.Fujitsu andthe Fujitsulogo are registered trademarks of Fujitsu Limited.
All SPARC trademarksareused underlicense andare registered trademarksof SPARC International,Inc. inthe U.S.and other countries. Products bearing
SPARC trademarks are based uponarchitectures developed by Oracle and/or its affiliates.SPARC64is atrademark ofSPARC International, Inc., used
under licenseby FujitsuMicroelectronics, Inc. and Fujitsu Limited. Other names may be trademarks of their respectiveowners.
United StatesGovernment Rights- Commercialuse. U.S.Government usersare subject to the standardgovernment userlicense agreementsof Oracle
and/or itsaffiliates andFujitsu Limitedand theapplicable provisions of theFAR and itssupplements.
Disclaimer: Theonly warrantiesgranted byOracle andFujitsu Limited,and/or anyaffiliate ofeither ofthem inconnection withthis documentor any
product ortechnology describedherein are thoseexpressly setforth inthe licenseagreement pursuant to which the product ortechnology isprovided.
EXCEPT ASEXPRESSLY SET FORTH IN SUCHAGREEMENT, ORACLE ORFUJITSU LIMITED,AND/OR THEIRAFFILIATESMAKE NO
REPRESENTATIONS ORWARRANTIES OF ANYKIND (EXPRESSOR IMPLIED)REGARDING SUCHPRODUCT ORTECHNOLOGY ORTHIS
DOCUMENT,WHICH AREALL PROVIDEDAS IS,AND ALLEXPRESS ORIMPLIED CONDITIONS,REPRESENTATIONS ANDWARRANTIES,
INCLUDING WITHOUTLIMITATION ANYIMPLIED WARRANTY OFMERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSEOR NONINFRINGEMENT,ARE DISCLAIMED,EXCEPT TO THE EXTENTTHATSUCH DISCLAIMERSARE HELDTO BE LEGALLY INVALID. Unless
otherwise expresslyset forthin suchagreement, to the extent allowed by applicable law,in noevent shallOracle orFujitsu Limited,and/or anyof their
affiliates haveany liabilityto anythird party under any legal theory for any loss of revenuesor profits,loss ofuse ordata, orbusiness interruptions,or for
any indirect,special, incidentalor consequentialdamages, evenif advisedof thepossibility ofsuch damages.
DOCUMENTATION ISPROVIDED “ASIS” ANDALL EXPRESSOR IMPLIEDCONDITIONS, REPRESENTATIONSAND WARRANTIES,
INCLUDING ANYIMPLIED WARRANTY OFMERCHANTABILITY,FITNESS FORA PARTICULAR PURPOSEOR NON-INFRINGEMENT, ARE
DISCLAIMED, EXCEPTTO THEEXTENT THAT SUCHDISCLAIMERS AREHELD TO BE LEGALLY INVALID.
technologies décritsdans cedocument. Demême, cesproduits, technologieset cedocument sontprotégés par des lois sur le copyright, des brevets,
d’autres loissur lapropriété intellectuelle et des traités internationaux.
Ce document,le produitet lestechnologies afférents sont exclusivement distribués avec des licences qui en restreignentl’utilisation, lacopie, la
distribution etla décompilation.Aucune partiede ceproduit, deces technologiesou dece documentne peutêtre reproduite sousquelque formeque ce
soit, parquelque moyenque cesoit, sansl’autorisation écritepréalable d’Oracleet/ou sessociétés affiliéeset deFujitsu Limited,et deleurs éventuels
bailleurs delicence. Cedocument, bienqu’il vousait étéfourni, nevous confèreaucun droit et aucunelicence, expresses ou tacites,concernant leproduit
ou latechnologie auxquelsil serapporte. Parailleurs, ilne contientni nereprésente aucunengagement, dequelque typeque cesoit, dela partd’Oracle ou
de FujitsuLimited, oudes sociétésaffiliées del’une oul’autre entité.
Ce document,ainsi queles produitset technologiesqu’il décrit,peuvent inclure des droits de propriété intellectuelle departies tiercesprotégés par
copyright et/oucédés souslicence pardes fournisseursà Oracleet/ou sessociétés affiliéeset FujitsuLimited, ycompris deslogiciels etdes technologies
relatives auxpolices decaractères.
Cette distributionpeut comprendre des composantsdéveloppés pardes partiestierces.
Des partiesde ceproduit peuventêtre dérivées des systèmes Berkeley BSD, distribués sous licence par l’Université de Californie. UNIX est une marque
Fujitsu Limited.
Toutes les marques SPARC sont utiliséessous licenceet sontdes marques déposées deSPARC International, Inc.,aux États-Uniset dansd’autrespays. Les
produits portantla marque SPARC reposent sur des architectures développéespar Oracleet/ou sessociétés affiliées. SPARC64 est unemarque de SPARC
International, Inc.,utilisée souslicence parFujitsu Microelectronics, Inc. etFujitsu Limited.Tout autre nom mentionné peut correspondreà desmarques
appartenant àd’autres propriétaires.
United StatesGovernment Rights- Commercialuse. U.S. Governmentusers aresubject tothe standard government userlicense agreements of Oracle
and/or itsaffiliates andFujitsu Limitedand theapplicable provisions of theFAR and itssupplements.
Avis de non-responsabilité : les seulesgaranties octroyéespar Oracleet FujitsuLimited et/outoute sociétéaffiliée de l’une ou l’autreentité enrapport
avec cedocument outout produitou toutetechnologie décritsdans lesprésentes correspondent aux garantiesexpressément stipulées dans le contrat de
licence régissantle produitou latechnologie fournis.SAUF MENTIONCONTRAIRE EXPRESSÉMENTSTIPULÉE DANSCE CONTRAT,ORACLE OU
FUJITSU LIMITEDET LESSOCIÉTÉS AFFILIÉESÀ L’UNE OUL’AUTREENTITÉ REJETTENTTOUTE REPRÉSENTATIONOU TOUTE GARANTIE,
QUELLE QU’ENSOIT LANATURE(EXPRESSE OUIMPLICITE) CONCERNANTCE PRODUIT, CETTETECHNOLOGIE OUCE DOCUMENT,
LESQUELS SONTFOURNIS ENL’ÉTAT. ENOUTRE, TOUTESLES CONDITIONS,REPRÉSENTATIONS ETGARANTIES EXPRESSESOU TACITES, Y
COMPRIS NOTAMMENT TOUTEGARANTIE IMPLICITERELATIVEÀ LAQUALITÉ MARCHANDE,À L’APTITUDE ÀUNE UTILISATION
PARTICULIÈRE OUÀ L’ABSENCE DE CONTREFAÇON,SONT EXCLUES,DANS LAMESURE AUTORISÉEPAR LA LOIAPPLICABLE. Saufmention
contraire expressément stipulée dansce contrat,dans lamesure autorisée par la loi applicable, en aucun cas Oracle ou Fujitsu Limited et/ou l’une ou
l’autre deleurs sociétésaffiliées ne sauraient être tenuesresponsables enversune quelconquepartie tierce, sous quelquethéorie juridiqueque cesoit, de
tout manqueà gagnerou deperte deprofit, deproblèmes d’utilisation ou de perte de données, ou d’interruptionsd’activités, oude toutdommage
indirect, spécial,secondaire ou consécutif, même si ces entités ont été préalablement informées d’une telle éventualité.
LA DOCUMENTATIONEST FOURNIE« EN L’ÉTAT » ETTOUTE AUTRE CONDITION, DÉCLARATIONET GARANTIE,EXPRESSE OUTACITE,EST
FORMELLEMENT EXCLUE,DANS LAMESURE AUTORISÉEPAR LA LOI EN VIGUEUR, Y COMPRIS NOTAMMENT TOUTE GARANTIE
IMPLICITE RELATIVE ÀLA QUALITÉMARCHANDE, ÀL’APTITUDEÀ UNEUTILISATIONPARTICULIÈRE OUÀ L’ABSENCE DE
CONTREFAÇON.
Page 4
Contents
Prefacex
Preparing for Installation1
Server Overview1
Server Handling Precautions3
Input Power Information and Precautions3
Tools and Equipment Needed4
Optional Component Installation5
ESD Precautions6
Installation Overview6
▼Prepare for Installation8
▼Install the Hardware8
▼Configure the Service Processor9
▼Configure the Host Software10
Cabling Notes for Both Servers10
Port, Connector, and LED Locations for Both Servers12
Slide Rail Assembly Notes for Both Servers15
Cable Management Notes for Both Servers18
Installing the Sun SPARC Enterprise T5140 and T5240 Servers19
Installing the Servers in a Rack19
▼Install the Slide Rail Assemblies20
▼Insert and Lock the Server in the Rack26
vi
Page 5
Installing the Cable Management Arm for Both Servers28
▼Install the Cable Management Arm28
▼Verify the Operation of the Slide Rails and the CMA32
Connecting the Server Cables for Both Servers34
▼Connect the Service Processor Serial Management Port35
▼Connect the Service Processor Network Management Port36
▼Connect the Ethernet Network Cables37
AC Power Cable Notes38
Managing Cables With the CMA39
▼Secure the Server Cables in the CMA39
Dismounting the Servers40
Powering On the System41
Powering On the System for the First Time41
ILOM System Console42
ILOM Service Processor42
▼Power On the System for the First Time43
Enable the Service Processor Network Management Port47
Logging Into the Service Processor49
▼Log Into the Service Processor Using the Serial Management Port49
▼Configure the Service Processor Network Management Port50
▼Log Into the Service Processor Using the Network Management Port
53
Using the Service Processor for Common Operations54
▼Perform a Normal System Initialization54
▼Examine the System for Faults56
Devices in the OpenBoot Device Tree58
Booting the Solaris Operating System59
▼Boot the Solaris Operating System59
viiSun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 6
▼Avoid Booting the Solaris Operating System at Startup60
▼Reset the System60
▼Power Cycle the System61
Verifying System Functionality62
Updating the Firmware63
flashupdate command63
▼Update the Firmware64
Selecting a Boot Device67
Boot Device Selection Overview67
▼Select a Boot Device68
Installing the Servers With the Express Rail Rackmounting Kit69
Slide Rail Assembly Notes for the Express Rail Rackmounting Kit69
▼Install the Slide Rail Assemblies72
▼Insert and Lock the Server in the Rack77
Dismounting the Server79
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise
T5140 Server81
Requirements for Servers With DC Input Power81
DC Supply and Ground Conductor Requirements82
Overcurrent Protection Requirements83
Assembling and Installing the DC Input Power Cables83
▼Assemble the DC Input Power Cable83
▼Install the Strain Relief Housings89
▼Connect the DC Input Power Cords to the Server91
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise
T5240 Server93
Requirements for Servers With DC Input Power93
Contentsviii
Page 7
DC Supply and Ground Conductor Requirements94
Overcurrent Protection Requirements95
Assembling and Installing the DC Input Power Cables95
▼Assemble the DC Input Power Cables95
▼Connect the DC Input Power Cords to the Server99
Index101
ixSun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 8
Preface
This installation guide provides instructions and information to help you install the
Sun SPARC Enterprise T5140 and T5240 servers from Oracle. The installation
instructions assume that you are a system administrator experienced with the Oracle
Solaris Operating System.
■ “UNIX Commands” on page x
■ “Shell Prompts” on page xi
■ “Related Documentation” on page xi
■ “Documentation, Support, and Training” on page xii
■ “Documentation Feedback” on page xii
UNIX Commands
This document might not contain information on basic UNIX commands and
procedures such as shutting down the system, booting the system, and configuring
devices. Refer to the following for this information:
■ Software documentation that you received with your system
■ Solaris Operating System documentation, which is at
(http://docs.sun.com)
x
Page 9
Shell Prompts
ShellPrompt
C shellmachine-name%
C shell superusermachine-name#
Bourne shell and Korn shell$
Bourne shell and Korn shell superuser#
Related Documentation
The documents listed as online are available at:
(http://docs.sun.com/app/docs/prod/sparc.t5140)
(http://docs.sun.com/app/docs/prod/sparc.t5240)
ApplicationTitlePart NumberFormatLocation
Product NotesSun SPARC Enterprise T5140 and T5240 Servers
Product Notes
Getting StartedSun SPARC Enterprise T5140 Server Getting Started
Guide
Getting StartedSun SPARC Enterprise T5140 Server Getting Started
Guide (DC)
Getting StartedSun SPARC Enterprise T5240 Server Getting Started
Guide
Getting StartedSun SPARC Enterprise T5240 Server Getting Started
Guide (DC)
PlanningSun SPARC Enterprise T5140 and T5240 Servers Site
Planning Guide
InstallationSun SPARC Enterprise T5140 and T5240 Servers
Installation Guide
AdministrationSun SPARC Enterprise T5140 and T5240 Servers
Administration Guide
820-3312PDFOnline
820-3875PrintedShipswith
system
820-5840PrintedShipswith
system
820-3521PrintedShipswith
system
820-5841PrintedShipswith
system
820-3314PDF
HTML
820-3315PDF
HTML
820-3316PDF
HTML
Online
Online
Online
xiSun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 10
ApplicationTitlePart NumberFormatLocation
ServiceSun SPARC Enterprise T5140 and T5240 Servers
Service Manual
SafetySun SPARC Enterprise T5140 and T5240 Servers
Safety and Compliance Guide
Remote
Management
Oracle Integrated Lights Out Manager (ILOM) 3.0
Supplement for Sun SPARC Enterprise T5140 and
T5240 Servers
Submit comments about this document by clicking the Feedback[+] link at
(http://docs.sun.com).
Please include the title and part number of your document with your feedback:
Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide, part number
820-3315-14.
Prefacexii
Page 11
xiiiSun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 12
Preparing for Installation
This chapter provides background information about the installation procedures for
both servers. This chapter contains these topics:
■ “Server Overview” on page 1
■ “Server Handling Precautions” on page 3
■ “Input Power Information and Precautions” on page 3
■ “Tools and Equipment Needed” on page 4
■ “Optional Component Installation” on page 5
■ “ESD Precautions” on page 6
■ “Installation Overview” on page 6
■ “Prepare for Installation” on page 8
■ “Install the Hardware” on page 8
■ “Configure the Service Processor” on page 9
■ “Configure the Host Software” on page 10
■ “Cabling Notes for Both Servers” on page 10
■ “Port, Connector, and LED Locations for Both Servers” on page 12
■ “Slide Rail Assembly Notes for Both Servers” on page 15
■ “Cable Management Notes for Both Servers” on page 18
Server Overview
The Sun SPARC Enterprise T5140 server from Oracle is a 1 rack unit (1U) server.
Oracle’s Sun SPARC Enterprise T5240 server is a 2 rack unit (2U) server.
1
Page 13
FIGURE:Sun SPARC Enterprise T5240 Server
FIGURE:Sun SPARC Enterprise T5140 Server
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
2Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 14
Server Handling Precautions
Caution – Deploy the antitilt bar on the equipment rack before beginning an
installation.
Caution – The Sun SPARC Enterprise T5240 server weighs approximately 46 lb (20.7
kg). Two people are required to lift and mount this 2U server into a rack enclosure
when using the procedures in this document.
Caution – When completing a two-person procedure, always communicate your
intentions clearly before, during, and after each step to minimize confusion.
Related Information
■ “Input Power Information and Precautions” on page 3
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
Input Power Information and
Precautions
The Sun SPARC Enterprise T5140 and T5240 servers are available in the following
input power configurations:
■ Two redundant, hot-swappable AC power supplies
Preparing for Installation3
Page 15
■ Two redundant, DC power supplies
Note – Safety agency requirements prohibit manufacturers from changing a product
from AC input to DC input or from DC input to AC input after the product has been
removed from the agency approved manufacturing site.
Note – The DC version of the server must be installed in a restricted-access location.
According to the intent of the National Electrical Code, a restricted-access location is
an area intended for qualified or trained personnel only and has access controlled by
a locking mechanism, such as a key lock or an access card system.
When each power supply is connected to a separate power source, the server
continues to operating under the following fault conditions:
■ A power source failure that removes input power from one of the power supplies.
■ Failure of one of the power supplies.
■ Service actions which require removal of one of the power supplies.
Refer to the Sun SPARC Enterprise T5140 and T5240 Servers Site Planning Guide for
input power specifications.
Note – Input AC/DC power cables: To avoid missing initialization messages, do not
attach power cables to the power supplies until you have finished connecting the
data cables, and have connected the server to a serial terminal or a terminal emulator
(PC or workstation). The server goes into Standby mode and the ILOM service
processor initializes as soon as the input power cables are connected to the power
source.
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Site Planning Guide
Tools and Equipment Needed
To install the system, you must have the following tools:
■ No. 2 Phillips screwdriver
■ No. 1 Phillips screwdriver
4Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 16
■ ESD mat and grounding strap
In addition, you must provide a system console device, such as one of the following:
■ ASCII terminal
■ Workstation
■ Terminal server
■ Patch panel connected to a terminal server
Related Information
■ “Optional Component Installation” on page 5
Optional Component Installation
The standard components of the server are installed at the factory. However, if you
ordered options such as additional memory or PCI cards, these will be shipped
separately. If possible, install these components prior to installing the server in a
rack.
If you ordered any options that are not factory-installed, see the Sun SPARCEnterprise T5140 and T5240 Servers Service Manual for installation instructions.
Note – The list of optional components can be updated without notice. See the
product web pages for the most current list of components supported in the server.
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
■ Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
Preparing for Installation5
Page 17
ESD Precautions
Electronic equipment is susceptible to damage by static electricity. Use a grounded
antistatic wriststrap, footstrap, or equivalent safety equipment to prevent
electrostatic damage (ESD) when you install or service the servers.
Caution – To protect electronic components from electrostatic damage, which can
permanently disable the system or require repair by service technicians, place
components on an antistatic surface, such as an antistatic discharge mat, an antistatic
bag, or a disposable antistatic mat. Wear an antistatic grounding strap connected to a
metal surface on the chassis when you work on system components.
Related Information
■ “Installation Overview” on page 6
Installation Overview
This installation guide provides procedures that are to be performed in the following
order.
6Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 18
FIGURE:Installation Overview
Figure Legend
1Preparing for installation
2Installing the hardware
3Configuring the service processor
4Configuring the host software
Preparing for Installation7
Page 19
▼Prepare for Installation
1. Verify that you have received all of the components that ship with your server.
2. Gather configuration information for your system. See your system
administrator for specific details, including these parameters:
■ Netmask
■ IP address for the service processor
■ Gateway IP address
3. Install any optional components shipped with your system.
If you have purchased other optional components such as additional memory,
install them prior to mounting the server in a rack.
Related Information
■ “Optional Component Installation” on page 5
▼Install the Hardware
1. Mount the server into a rack or cabinet. See “Installing the Servers in a Rack” on
page 19 for both the 1U and 2U servers. Or, if you ordered the express rail
rackmounting kit, which has the same rack rail assemblies for both servers, see
“Installing the Servers With the Express Rail Rackmounting Kit” on page 69.
Note – In the rest of this guide, the term rack means either an open rack or a closed
cabinet.
2. Connect the server to a serial terminal or a terminal emulator (PC or
workstation) to display system messages. See “Powering On the System for the
First Time” on page 41.
8Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 20
Tip – The serial terminal or a terminal emulator should be connected before you
connect the power cables. As soon as AC power is connected to the system, the
service processor immediately powers on and runs diagnostics. Diagnostic test
failures will be printed on the serial terminal. For more information, refer to the
Integrated Lights Out Manager Supplement for Sun SPARC Enterprise T5140 and T5240
Servers.
3. Connect the data cables to the server, but do not connect the AC power cable
yet. See “Connecting the Server Cables for Both Servers” on page 34.
4. Connect the AC power cable to the server and examine the display for any error
messages. See “Powering On the System for the First Time” on page 41.
Caution – There is a potential for electric shock if the server and related equipment
are not properly grounded.
Note – The service processor runs on the 3.3V standby voltage. As soon as AC
power is connected to the system, the service processor immediately powers on, runs
diagnostics, and initializes the ILOM firmware.
Related Information
■ “Powering On the System for the First Time” on page 41
▼Configure the Service Processor
1. After the service processor boots, access the ILOM command-line interface
(CLI) through the serial management port. See “Log Into the Service Processor
Using the Serial Management Port” on page 49.
2. Configure the service processor network addresses. See “Configure the Service
Processor Network Management Port” on page 50.
Note – The service processor network management port is not operational until you
configure network settings for the service processor (through the service processor
serial management port).
Preparing for Installation9
Page 21
3. Commit the changes to the service processor network parameters. See Step 3 in
“Power On the System for the First Time” on page 43.
4. Power on the server from a keyboard using the ILOM software. See “Examine
the System for Faults” on page 55.
Related Information
■ “Configure the Host Software” on page 10
▼Configure the Host Software
1. Configure the Solaris OS. See “Booting the Solaris Operating System” on page 58.
The Solaris OS is preinstalled on the servers. When you power on, you are
automatically guided through the Solaris OS configuration procedure.
2. Install any required patches to the server.
Refer to the Sun SPARC Enterprise T5140 and T5240 Servers Product Notes for a list
of required patches.
3. Load additional software from the Solaris media kit (optional).
The Solaris media kit (sold separately) includes several CDs containing software
to help you operate, configure, and administer your server. Refer to the
documentation provided with the media kit for a complete listing of included
software and detailed installation instructions.
Related Information
■ “Cabling Notes for Both Servers” on page 10
■ Sun SPARC Enterprise T5140 and T5240 Servers Product Notes
Cabling Notes for Both Servers
■ Minimum cable connections for the servers:
■ At least one system on-board Ethernet network connection (NET port)
■ Service processor serial management port (SER MGT port)
■ Service processor network management port (NET MGT port)
■ Power cables for the two system power supplies
10Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 22
■ Service processor management ports: There are two service processor
management ports for use with the ILOM service processor.
■ The service processor serial management port (labeled SER MGT) uses an RJ-45
cable and is always available. This port is the default connection to the ILOM
service processor.
■ The service processor network management port (labeled NET MGT) is the
optional connection to the ILOM service processor. This port is not available
until you configure network settings for the service processor (through the
service processor serial management port). See “Enable the Service Processor
Network Management Port” on page 47.
■ The service processor network management port uses an RJ-45 cable for a
10/100 BASE-T connection. This port does not support connections to Gigabit
networks. See the Sun SPARC Enterprise T5140 and T5240 Servers Overview for
more information.
■ Ethernet ports are labeled NET0, NET1, NET2, and NET3. The Ethernet interfaces
operate at 10 Mbps, 100 Mbps, and 1000 Mbps. The table below shows the transfer
rates for the Ethernet ports.
TABLE:Ethernet Connection Transfer Rates
Connection TypeIEEE TerminologyTransfer Rate
Ethernet10BASE-T10 Mbit/sec
Fast Ethernet100BASE-TX100 Mbits/sec
Gigabit Ethernet1000BASE-T1000 Mbit/sec
■ TTYA serial port: Use the DB-9 connector with a null modem cable for serial
devices. This port appears as ttya in Solaris OS and OpenBoot messages. This
port is not connected to the service processor serial management port.
■ USB ports: USB ports support hot-plugging. You can connect and disconnect USB
cables and peripheral devices while the system is running, without affecting
system operations.
■ You can only perform USB hot-plug operations while the OS is running. USB
hot-plug operations are not supported when the system ok prompt is displayed
or before the system has completed booting.
■ You can connect up to 126 devices to each of the four USB controllers, for a total
of 504 USB devices per system.
■ AC power cables: Do not attach power cables to the power supplies until you have
finished connecting the data cables, and have connected the server to a serial
terminal or a terminal emulator (PC or workstation). The server goes into Standby
mode and the ILOM service processor initializes as soon as the AC power cables
are connected to the power source. System messages might be lost after 60 seconds
if the server is not connected to a terminal, PC, or workstation.
Preparing for Installation11
Page 23
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
■ Sun SPARC Enterprise T5140 and T5240 Servers Overview Guide
Port, Connector, and LED Locations for
Both Servers
See the figures below for the locations of the ports on the Sun SPARC Enterprise
T5140 server.
FIGURE:Rear Panel Cable Connectors and LEDs on the Sun SPARC Enterprise T5140 Server
Figure Legend
1Power supply 010 Gbit Enet port NET2
2Power supply 111 Gbit Enet port NET3
3Locator LED button12 USB port 0
4Service Required LED13 USB port 1
5PowerOKLED14 TTYA serial port
6Service processor serial management port15 PCIe/XAUI slot 0
FIGURE:Front Panel USB Ports on the Sun SPARC Enterprise T5240 Server
Figure Legend
1System status indicators: Top to bottom: Locator LED button,
7Hard drive HDD5
Service Required LED, Power OK LED, and Power button
2Hard drive HDD08Hard drive HDD6
3Hard drive HDD19Hard drive HDD7
4Hard drive HDD210USB port 2
5Hard drive HDD311USB port 3
6Hard drive HDD4
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
■ Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
■ Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
14Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 26
Slide Rail Assembly Notes for Both
Servers
The rackmounting kit has two slide rail assemblies. A slide rail assembly can be
installed on either the right or left side of the rack.
Note – The slide rail assemblies are different for the T5140 and T5240 servers. The
removable mounting bracket of the Sun SPARC Enterprise T5140 rail slides 13 in. (33
cm) out of the slide rail, then locks in place. The removable mounting bracket of the
Sun SPARC Enterprise T5240 rails slide 14 in. (35.5 cm) before locking.
Each slide rail assembly consists of a three-section slide rail and a removable
mounting bracket.
FIGURE:Sections of the Slide Rail Assembly on the Sun SPARC Enterprise T5240 Server
Figure Legend
1Mounting bracket3Middle section
2Front section4Rear section
Preparing for Installation15
Page 27
■ The front, middle, and rear sections form the slide rail. The middle and rear sections
have holes for mounting screws, and adjust to fit rack depths from 24 in. (61 cm)
to 36.5 in. (93 cm). The front section can be extended to allow movement of the
server out of the rack.
■ The removable mounting bracket slides 14 in. (35.5 cm) out of the slide rail, then
locks in place. If you unlock the mounting bracket at this point, it slides an
additional 12 in. (30 cm) before separating from the slide rail. You can then mount
the mounting bracket to the right or left side of the server chassis.
■ There are a total of five locks in a slide rail assembly. Four are on the mounting
bracket. One lock is on the front section of the slide rail. “Installing the Servers in
a Rack” on page 19 describes the uses of these locks.
16Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 28
FIGURE:Locating the Locks on the Slide Rail Assembly for the Sun SPARC Enterprise
T5240 Server
Preparing for Installation17
Page 29
Related Information
■ “Cable Management Notes for Both Servers” on page 18
■ “Installing the Servers in a Rack” on page 19
Cable Management Notes for Both
Servers
The same cable management arm (CMA) is included with the rackmounting kit for
each server. The CMA clips onto the slide rails. Use the velcro straps to secure
cabling to the CMA.
FIGURE:Cable Management Arm for Both Servers
Related Information
■ “Managing Cables With the CMA” on page 39
18Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 30
Installing the Sun SPARC Enterprise
T5140 and T5240 Servers
This chapter provides instructions for installing the servers into an equipment rack.
Note – If your rackmounting kit came with its own instructions, use the instructions
in your rackmounting kit instead of the instructions in this chapter. After performing
the server installation, proceed to “Powering On the System” on page 41 for
first-time power on.
Note – References to left and right are from your viewpoint as you face either the
front or rear of the equipment.
This chapter contains the following sections:
■ “Installing the Servers in a Rack” on page 19
■ “Installing the Cable Management Arm for Both Servers” on page 28
■ “Connecting the Server Cables for Both Servers” on page 34
■ “Managing Cables With the CMA” on page 39
Installing the Servers in a Rack
Note – Ensure that you have all of the parts in the rackmounting kit before you
begin the installation of the server.
Each slide rail assembly consists of two parts, a slide rail and a removable mounting
bracket. The slide rail attaches to the rack posts. The mounting bracket attaches to the
server chassis.
19
Page 31
Note – The rackmounting kit is the same for both 1U and 2U servers. It contains two
slide rail assemblies, which can be installed on either the right or left side of the rack.
■ “Install the Slide Rail Assemblies” on page 20
■ “Insert and Lock the Server in the Rack” on page 26
▼ Install the Slide Rail Assemblies
1. Pull both mounting brackets completely out of their respective slide rails.
a. Simultaneously press and hold the upper and lower lock buttons of the slide
rail lock.
FIGURE:Unlocking the Slide Rail Assembly (Either Server)
b. Pull the mounting bracket out until it locks in the extended position.
c. Slide the mounting bracket release button, then slide the mounting bracket
out of the slide rail.
20Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 32
FIGURE:Location of the Mounting Bracket Release Button (Either Server)
d. Press the metal lever (labeled Push) on the middle section of the sliding rail,
then push the middle section back into the rack.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers21
Page 33
FIGURE:Unlocking the Slide Rail Middle Section (Either Server)
2. Attach a mounting bracket to the right side of the chassis.
a. Position the mounting bracket against the chassis. Ensure that the slide rail
lock is at the front and the three keyed openings on the mounting bracket are
aligned with the three locating pins on the side of the chassis.
22Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 34
FIGURE:Attaching a Mounting Bracket to the Chassis (Either Server)
b. Ensure that the heads of the locating pins protrude though the keyed
openings in the mounting bracket. Pull the mounting bracket toward the
front of the chassis until the bracket locks into place with an audible click.
c. Verify that all locating pins are trapped in the keyed openings and that the
correct locating pin has engaged the mounting bracket lock.
3. Attach the second mounting bracket to the left side of the chassis.
4. Determine which rack hole numbers to use when attaching the slide rails to the
rack posts.
If the server is two rack units high (2U), the slide rails occupy the lower half of the
2U space.
5. Determine which screws you will use to mount the slide rails.
■ If your rack has threaded mounting holes in the rack posts, determine whether
the threads are metric or standard. Select the appropriate screws from the
package included in the mounting kit.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers23
Page 35
■ If your rack does not have threaded mounting holes, the mounting screws are
secured with a caged nut.
6. Attach a slide rail to the right front rack post.
a. Loosely attach the front of a slide rail to the right front rack post using two
screws.
Note – Do not tighten the screws yet.
FIGURE:Mounting a Slide Rail (Either Server)
b. Adjust the length of the slide rail by sliding the rear mounting flange to
reach the outside edge of the rear rack post.
c. Loosely attach the rear of the slide rail to the rear rack post with two screws.
7. Attach the second slide rail to the left rack posts in a similar manner.
Do not tighten the screws.
8. Use the slide rail spacing tool to adjust the distance between the slide rails.
24Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 36
a. At the front of the rack, plug the left side of the tool into slots at the end of
the left rail.
FIGURE:Using the Slide Rail Spacing Tool to Adjust the Distance Between the Slide Rails
(Either Server)
b. Insert the right side of the tool into the front end of the right rail.
c. Slide the end of the rail to the right or left as needed to allow the ends of the
tool to enter the ends of both rails.
The distance between the rails is now equal to the width of the server with
mounting brackets.
d. Tighten the screws to lock the ends of the rails in place.
e. At the rear of the rack, repeat Step a through Step d for the rear ends of the
rails.
Related Information
■ “Insert and Lock the Server in the Rack” on page 26
Installing the Sun SPARC Enterprise T5140 and T5240 Servers25
Page 37
▼ Insert and Lock the Server in the Rack
1. Deploy the antitilt bar, if the chassis or rack is so equipped.
Caution – The weight of the servers on extended slide rails can be enough to
overturn an equipment rack.
Caution – The 2U server weighs approximately 55 lb (25 kg). Two people are
required to lift and mount the server into a rack enclosure when using the
procedures in this chapter.
2. Insert the ends of the mounting brackets into the sliding rails.
FIGURE:Mounting the Chassis on the Slide Rails (Either Server)
26Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 38
3. Slide the chassis into the rack.
Caution – Before continuing, verify that the server is securely mounted in the rack,
and that the slide rails are locked to the mounting brackets.
Related Information
■ “Installing the Cable Management Arm for Both Servers” on page 28
Installing the Cable Management Arm
for Both Servers
The rackmounting kit for each server comes with the same cable management arm
(CMA) assembly. The CMA installation and cable management procedures are the
same for both servers.
Note – The CMA includes velcro straps to secure the cables inside the CMA. Do not
install the velcro straps until you install the CMA, connect the cables, and place the
cabling inside the CMA as described in the following procedures.
■ “Install the Cable Management Arm” on page 28
■ “Verify the Operation of the Slide Rails and the CMA” on page 32
▼ Install the Cable Management Arm
Caution – Support the CMA during this installation. Do not allow the assembly to
hang by its own weight until it is secured by all three attachment points.
1. Remove the tape from the CMA rail extension (on the left of the CMA) and
remove the CMA rail extension.
2. Attach the CMA rail extension to rear left slide rail.
At the rear of the rack, plug the CMA rail extension into the end of the left sliding
rail assembly. The tab at the front of the rail extension clicks into place. The right
sides of the two CMA arms have hinged extensions. On the manufacturer’s
instruction sheet, the smaller extension is called the CMA Connector for Inner
Installing the Sun SPARC Enterprise T5140 and T5240 Servers27
Page 39
Member. This extension attaches to the right mounting bracket. The larger
extension is called the CMA Connector for Outer Member, and attaches to the
right sliding rail.
FIGURE:Inserting the CMA Rail Extension Into the Rear of the Left Slide Rail (Either
Server)
3. Insert the smaller extension into the clip located at the end of the mounting
bracket.
Slide the smaller extension into the square hole on the middle-in-width of the clip
that is located at the end of the mounting bracket.
28Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 40
FIGURE:Mounting the Inner CMA Connector (Either Server)
4. Insert the larger extension into the end of the right sliding rail.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers29
Page 41
FIGURE:Attaching the Outer CMA Connector (Either Server)
5. Insert the hinged plastic connector at the left side of the CMA fully into the
CMA rail extension.
The plastic tab on the CMA rail extension locks the hinged plastic connector in
place.
30Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 42
FIGURE:Mounting the Left Side of the Slide Rail (Either Server)
Related Information
■ “Verify the Operation of the Slide Rails and the CMA” on page 32
▼ Verify the Operation of the Slide Rails and the
CMA
Tip – Two people are needed for this procedure, one to move the server in and out
of the rack, and one to observe the cables and CMA.
1. For a free-standing rack, deploy the antitilt bar.
2. Unlock the slide lock button s at the right and left sides of the chassis.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers31
Page 43
3. Slowly pull the server out of the rack until the slide rails reach their stops.
FIGURE:Unlocking the Slide Rail Assembly (Either Server)
4. Inspect any attached cables for binding or kinks.
5. Verify that the CMA extends fully and does not bind in the slide rails.
6. Verify that the server extends fully and locks in the maintenance position.
The server should stop after approximately 15 inches (40 cm) of travel.
7. Pull both slide rail release buttons toward you simultaneously and slide the
server back into the rack.
The server should slide smoothly into the rack without binding.
32Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
9. Adjust the cable straps and CMA as required to secure the cables.
Related Information
■ “Managing Cables With the CMA” on page 39
Connecting the Server Cables for Both
Servers
To boot the server, you must connect and configure the network and serial ports. The
procedures are given in the following sections.
The servers also have serial and USB ports available for connections to optional
device.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers33
Page 45
Note – When you are finished connecting the cables to the server, ensure that the
server can slide smoothly in and out of the rack without binding or damaging the
cables.
■ “Connect the Service Processor Serial Management Port” on page 35
■ “Connect the Service Processor Network Management Port” on page 36
■ “Connect the Ethernet Network Cables” on page 37
■ “AC Power Cable Notes” on page 38
Related Information
■ “Verify the Operation of the Slide Rails and the CMA” on page 32
▼ Connect the Service Processor Serial
Management Port
The service processor serial management port is marked SER MGT. This port is the
farthest left RJ-45 port on the rear panel.
Note – The cable and DB-9 RJ-45 adapters are for the host serial port, and not for the
server SER MGT port.
Use this port for server management. This port is needed to set up the service
processor network management port, as detailed in “Enable the Service Processor
Network Management Port” on page 47.
34Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 46
Note – Use the service processor serial management port only for server
management. It is the default connection between the service processor and a
terminal or a computer.
Caution – Do not attach a modem to this port.
● Connect a Category 5 cable from the SER MGT serial management port to the
terminal device.
When connecting either a DB-9 or a DB-25 cable, use an adapter to perform the
crossovers given for each connector.
Related Information
■ “Enable the Service Processor Network Management Port” on page 47
■ “Connect the Service Processor Network Management Port” on page 36
■ “Connect the Ethernet Network Cables” on page 37
▼ Connect the Service Processor Network
Management Port
The service processor network management port is labeled NET MGT. This port is
located just to the right of the serial management (SER MGT) port on the rear panel.
Note – If you have access to a DHCP server on the network, you can see the service
processor get an IP address because the DHCP client is enabled by default.
Note – The service processor network management port is configured by default to
retrieve network settings with Dynamic Host Configuration Protocol (DHCP) and
allow connections using Solaris Secure Shell (SSH). You might need to modify these
settings for your network. Instructions are given in “Configure the Service Processor
Network Management Port” on page 50.
Note – This port is not operational until you configure the network settings (through
the serial management port), as detailed in “Configure the Service Processor
Network Management Port” on page 50.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers35
Page 47
● Connect a Category 5 cable from the NET MGT network management port to
your network switch or hub.
FIGURE:Service Processor Network Management Port – Rear Panel
Related Information
■ “Connect the Service Processor Serial Management Port” on page 35
■ “Connect the Ethernet Network Cables” on page 37
▼ Connect the Ethernet Network Cables
1. Connect a Category 5 cable from your network switch or hub to Ethernet Port 0
(NET0) on the rear of the chassis.
NET0 is the farthest left port in the 4-port network cluster.
2. Connect Category 5 cables from your network switch or hub to the remaining
Ethernet ports (NET1, NET2, NET3), as needed.
36Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
■ “Connect the Service Processor Serial Management Port” on page 35
■ “Connect the Service Processor Network Management Port” on page 36
AC Power Cable Notes
Powering on the system for the first time requires special preparation and
procedures. For example, if you have not prepared a display before connecting the
AC power cable, system messages might be lost.
Caution – Finish the hardware procedures in this chapter, but do not attach the AC
power cable yet.
Caution – The server goes into Standby mode and the service processor initializes as
soon as the AC power cable is connected to the power source.
Related Information
■ “Powering On the System for the First Time” on page 41
Installing the Sun SPARC Enterprise T5140 and T5240 Servers37
Page 49
Managing Cables With the CMA
Managing the cables with the CMA is the same for both servers.
■ “Secure the Server Cables in the CMA” on page 39
■ “Dismounting the Servers” on page 40
▼ Secure the Server Cables in the CMA
1. Once the server cables are connected and placed inside the CMA, open the
velcro cable straps and wrap the straps around the CMA securing the cables
inside the CMA.
FIGURE:Securing the Server Cables With the CMA and Velcro Straps (Either Server)
Caution – Verify the operation of the slide rails and CMA, and cable service loops.
2. Perform the steps in the following procedure again before continuing: “Verify
the Operation of the Slide Rails and the CMA” on page 32.
38Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 50
Related Information
■ “Dismounting the Servers” on page 40
Dismounting the Servers
To install or replace internal parts in the server, you must first remove the server
from the rack.
Related Information
■ “Secure the Server Cables in the CMA” on page 39
■ Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
Installing the Sun SPARC Enterprise T5140 and T5240 Servers39
Page 51
40Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 52
Powering On the System
This chapter includes instructions for booting the servers and for enabling the service
processor network management port.
This chapter contains the following topics:
■ “Powering On the System for the First Time” on page 41
■ “Enable the Service Processor Network Management Port” on page 47
■ “Logging Into the Service Processor” on page 49
■ “Using the Service Processor for Common Operations” on page 54
■ “Booting the Solaris Operating System” on page 58
■ “Verifying System Functionality” on page 62
Powering On the System for the First
Time
This section provides an overview and instructions for powering on your system the
first time.
■ “ILOM System Console” on page 42
■ “ILOM Service Processor” on page 42
■ “Power On the System for the First Time” on page 43
Related Information
■ “Enable the Service Processor Network Management Port” on page 47
■ “Verifying System Functionality” on page 62
41
Page 53
ILOM System Console
When you power on the system, the boot process begins under the control of the
Integrated Lights Out Manager (ILOM) system console. The system console displays
status and error messages generated by firmware-based tests during system startup.
Note – To see these status and error messages, connect a terminal or terminal
emulator to the serial management port (SER MGT). For a basic procedure to connect
a terminal or terminal emulator, see “Power On the System for the First Time” on
page 43.
For a more detailed discussion on configuring the system console and connecting
terminals, refer to the Sun SPARC Enterprise T5140 and T5240 Servers AdministrationGuide.
Related Information
■ “ILOM Service Processor” on page 42
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
ILOM Service Processor
After the system console finishes its low-level system diagnostics, the ILOM service
processor initializes and runs a higher level of diagnostics. When you access the
ILOM service processor using a device connected to the serial management port, you
see the output of the ILOM diagnostics.
By default, the service processor configures the network management port
automatically, retrieving network configuration settings using the Dynamic Host
Configuration Protocol (DHCP) and allowing connections using Secure Shell (SSH).
Note – If you are unable to use DHCP on your network, you must connect to the
ILOM service processor using the serial management port to configure the network
management port for your network.
Related Information
■ “Power On the System for the First Time” on page 43
■ “Configure the Service Processor Network Management Port” on page 50
42Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 54
▼ Power On the System for the First Time
1. Confirm that you have completed all of the preparations for installation.
See the instructions in “Preparing for Installation” on page 1.
2. Confirm that you have completed the installation of the server in its rack.
See the instructions in “Installing the Servers in a Rack” on page 19.
3. Connect a terminal or a terminal emulator (PC or workstation) to the service
processor serial management port (FIGURE: Server Connections on page 44).
Configure the terminal or terminal emulator with these settings:
■ 9600 baud
■ 8 bits
■ No parity
■ 1 Stop bit
■ No handshake
A null modem configuration is needed, meaning the transmit and receive signals
are reversed (crossed over) for DTE to DTE communications. You can use the
supplied RJ-45 crossover adapters with a standard RJ-45 cable to achieve the null
modem configuration.
Note – When you power on the server for the first time and you do not have a
terminal or terminal emulator (PC or workstation) connected to the service processor
serial management port, you will not see system messages.
4. (Optional) Connect an Ethernet cable between the server’s NET MGT port and
the network to which future connections to the SP and host will be made.
After the initial configuration of the system using the SP SER MGT port,
communication with the SP and host is usually performed through this Ethernet
interface.
Powering On the System43
Page 55
FIGURE:Server Connections
Figure Legend
1Power cables5RJ-45 to DB-25 crossover adapter
2Ethernet cables6RJ-45 to DB-9 crossover adapter
3Service processor to ethernet7Terminal device
4NET MGT to network (optional)
5. Connect an Ethernet cable between one of the server’s NET ports and the
network to which the server will communicate.
6. Determine the input power installation instructions you need, based on the
model or your server (AC or DC input power):
■ AC input power models–Continue to the next step.
■ DC input power models–See “Assembling and Installing DC Power Cables for
the Sun SPARC Enterprise T5140 Server” on page 81.
7. Plug the power cords into the power supplies and into a power source.
44Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 56
Note – Only one power connection is required for operation. Use two power
connections for redundancy.
The service processor runs on the 3.3V standby voltage. As soon as AC power is
connected to the system, the service processor powers on, runs diagnostics, and
initializes the ILOM firmware.
After a few minutes, the SP login prompt appears on the terminal device. The host
is not initialized or powered on yet.
8. At the terminal device, log in to the SP as root with a password of changeme.
After a brief delay, the SP prompt is displayed (->). At this point, there are many
commands you can perform using the Integrated Lights Out Manager interface.
Additional SP information, such as how to change the password and how to set
up the SP network parameters is available in the online documentation set.
9. Power on the server and redirect the host output to display on the serial
terminal device:
-> start /SYS
Are you sure you want to start /SYS (y/n)? y
-> start /SP/console
Are you sure you want to start /SP/CONSOLE (y/n)? y
Serial console started. To stop, type #.
. . .
After you start the SP console, the server initialization takes approximately 20
minutes to complete.
Powering On the System45
Page 57
10. When prompted, follow the onscreen instructions for configuring the Solaris
Operating System on your host and enter the following configuration
information.
You will be prompted to confirm the configuration several times, enabling
confirmation and changes. If you are not sure how to respond to a particular
value, you can accept the default, and make future changes when the Solaris OS is
running.
ParameterDescription
LanguageSelect a number from the displayed language list.
LocaleSelect a number from the displayed locale list.
Terminal TypeSelect a terminal type that corresponds with your terminal device.
Network?Select Yes.
Multiple Network
Interfaces
DHCP?Select Yes or No according to your network environment.
Host NameEnter the host name for the server.
IP AddressEnter the IP address for this Ethernet interface.
Subnet?Select Yes or No according to your network environment.
Subnet Netmask(If subnet was Yes) Enter the netmask for the subnet for your network
IPv6?Specify whether or not to use IPv6. If you are not sure, select No to configure the
Security PolicySelect either standard UNIX security (No) or Kerberos Security (Yes). If you are not
ConfirmReview the onscreen information and change it if needed. Otherwise, continue.
Name ServiceSelect the name service according to your network environment.
NFSv4 Domain NameSelect the type of domain name configuration according to your environment. If
Select the network interfaces that you plan to configure. If you are not sure, select
the first one in the list.
environment.
Ethernet interface for IPv4.
sure, select No.
Note–If you select a name service other than None, you will be prompted for
additional name service configuration information.
you are not sure, select Use the NFSv4 domain derived by the system.
Time Zone (Continent)Select your continent.
Time Zone (Country or
Region)
46Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Select your country or region.
Page 58
Time ZoneSelect the time zone.
Date and TimeAccept the default date and time or change the values.
root PasswordEnter the root password twice. This password is for the superuser account for the
Solaris OS on this server. This password is not the SP password.
11. Log in to the server and explore its capabilities.
There are many commands you can use to verify the functionality of the system.
The following list describes a few of them:
■ showrev – Displays the hostname and system architecture information. Use
the -a option with this command to see the patches that are installed.
■ psrinfo – Displays information about the number and status of the processors
and cores in the host.
■ prtdiag – Displays system configuration and diagnostic information.
Review the Solaris OS man pages and documentation for more details.
Related Information
■ “Enable the Service Processor Network Management Port” on page 47
■ Solaris Documentation
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide.
Enable the Service Processor Network
Management Port
The service processor network management port is not operational unless your
network employs DHCP, in which case the configuration in automatic. If your
network uses DHCP, you can run this command to view your server’s network
configuration information:
If your network does not use DHCP, the network management port is not operational
until you configure network settings for the service processor. Configure the service
processor in this order:
1. After the service processor boots, access the ILOM CLI through the serial
management port. See “Log Into the Service Processor Using the Serial
Management Port” on page 49.
2. Configure the service processor. See “Configure the Service Processor Network
Management Port” on page 50.
3. Commit the changes to the service processor parameters. See Step 3 in “Configure
the Service Processor Network Management Port” on page 50.
You can now use the network management port at any time to access the service
processor.
Related Information
■ “Logging Into the Service Processor” on page 49
48Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 60
Logging Into the Service Processor
If you are powering on the system for the first time after installation, use the service
processor serial port to power on the system and run POST. See “Log Into the Service
Processor Using the Serial Management Port” on page 49.
If the network management port has already been configured, you can use it instead
of the serial management port.
This section contains the following topics:
■ “Log Into the Service Processor Using the Serial Management Port” on page 49
■ “Configure the Service Processor Network Management Port” on page 50
■ “Log Into the Service Processor Using the Network Management Port” on page 53
▼ Log Into the Service Processor Using the Serial
Management Port
After the service processor boots, access the ILOM CLI to configure and manage the
system. The ILOM CLI prompt (->) is displayed at the first time the service processor
is booted. The default configuration provides an ILOM CLI root user account. The
default root password is changeme. Change the password using the service
processor ILOM CLI password command.
1. If this is the first time the system has been powered on, use the password
command to change the root password.
Copyright 2007 Sun Microsystems, Inc. All rights reserved.
Use is subject to license terms.
...
Federal Acquisitions: Commercial Software -- Government Users
Subject to Standard License Terms and Conditions.
...
Warning: password is set to factory default.
Powering On the System49
Page 61
-> set /SP/users/root password
Enter new password: ********
Enter new password again: ********
->
Note – After the root password has been set, on subsequent reboots, the ILOM CLI
login prompt is displayed.
2. Enter root for the login name followed by your password.
...
hostname login: root
Password: password (nothing displayed)
Waiting for daemons to initialize...
Daemons ready
Integrated Lights Out Manager
Version 3.0.0.0
Copyright 2009 Sun Microsystems, Inc. All rights reserved.
Use is subject to license terms.
->
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
▼ Configure the Service Processor Network
Management Port
Note – If your network allows the use of DHCP, this configuration is performed
automatically the first time you boot the system.
Use this procedure only when:
■ You are unable to use DHCP on your network.
■ You need to modify the ILOM service processor network management port
settings.
50Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 62
In this procedure, you connect to the ILOM service processor using the serial
management port to manually reconfigure the network management port.
Note – For more information on configuring ILOM, refer to the Integrated Lights Out
Manager Supplement for Sun SPARC Enterprise T5140 and T5240 Servers.
Set these network parameters according to the specific details of your network
configuration:
■ /SP/network state – Specifies whether the service processor is on the network
or not
■ /SP/network pendingipaddress – IP address of the service processor
■ /SP/network pendingipgateway – IP address of the gateway for the subnet
■ /SP/network pendingipnetmask – Netmask for the service processor subnet
■ /SP/network pendingipdiscovery - Specifies whether the service processor
uses DHCP or static IP address assignment
■ /SP/network commitpending - Commits the service processor to use the
pending settings
Configure these parameters with the set command. The usage is as follows:
set target property=value where /SP/network is the target and
pendingipaddress=xxx.xxx.xxx.xxx, for example, is the property=value.
1. Configure the service processor using information from your network
administrator.
Your choices are:
■ dhcp - Set up the network connection with a dynamically created IP
configuration.
■ static - Set up the network connection with a static IP configuration.
a. If you choose to use a dynamically created IP address (use DHCP to retrieve
the network setting), set pendingipdiscovery to dhcp.
-> set /SP/network pendingipdiscovery=dhcp
Set 'pendingipdiscovery' to 'dhcp'
b. If you choose to configure a static IP configuration, set the parameters
pendingipdiscovery, pendingipaddress, pendingipgateway, and
pendingipnetmask as follows.
i. Set the service processor to accept a static IP address.
-> set /SP/network pendingipdiscovery=static
Set 'pendingipdiscovery' to 'static'
Powering On the System51
Page 63
ii. Set the IP address for the service processor.
-> set /SP/network pendingipaddress=service-processor-IPaddr
Set 'pendingipaddress' to 'service-processor-IPaddr'
iii. Set the IP address for the service processor gateway.
-> set /SP/network pendingipgateway=gateway-IPaddr
Set 'pendingipgateway' to 'gateway-IPaddr'
iv. Set the netmask for the service processor.
-> set /SP/network pendingipnetmask=255.255.255.0
Set 'pendingipnetmask' to '255.255.255.0'
This example uses 255.255.255.0 to set the netmask. Your network
environment subnet might require a different netmask. Use a netmask number
most appropriate to your environment.
2. Use the show /SP/network command to verify that the parameters were set
correctly.
For example:
-> show /SP/network
/SP/network
Targets:
Properties:
commitpending = (Cannot show property)
dhcp_server_ip = xxx.xxx.xxx.xxx
ipaddress = xxx.xxx.xxx.xxx
ipdiscovery = dhcp
ipgateway = xxx.xxx.xxx.xxx
ipnetmask = 255.255.252.0
macaddress = 00:14:4F:3F:8C:AF
pendingipaddress = xxx.xxx.xxx.xxx
pendingipdiscovery = static
pendingipgateway = xxx.xxx.xxx.xxx
pendingipnetmask = 255.255.255.0
state = enabled
Commands:
cd
set
show
->
52Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 64
Note – After setting the configuration parameters, you must enter the set
/SP/network commitpending=true command for the new values to take affect.
3. Commit the changes to the service processor network parameters.
-> set /SP/network commitpending=true
Set 'commitpending' to 'true'
Note – You can type the show /SP/network command again (after performing the
set /SP/network commitpending=true command) to verify that the
parameters have been updated.
Related Information
■ “Configure the Service Processor Network Management Port” on page 50
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
▼ Log Into the Service Processor Using the
Network Management Port
Note – You must configure the service processor parameters shown in “Configure
the Service Processor Network Management Port” on page 50 before you can use the
network management port.
● Open an SSH session and connect to the service processor by specifying its
network address.
% ssh root@xx.xxx.xx.x
...
Are you sure you want to continue connecting (yes/no)? yes
...
Password: password (nothing displayed)
Waiting for daemons to initialize...
Daemons ready
Integrated Lights Out Manager
Version 3.0.0.0
Powering On the System53
Page 65
Copyright 2009 Sun Microsystems, Inc. All rights reserved.
Use is subject to license terms.
->
Related Information
■ “Perform a Normal System Initialization” on page 54
Using the Service Processor for Common
Operations
The following topics are described in this section:
■ “Perform a Normal System Initialization” on page 54
■ “Examine the System for Faults” on page 55
■ “Devices in the OpenBoot Device Tree” on page 57
▼ Perform a Normal System Initialization
1. Type the start /SYS command.
-> start /SYS
Are you sure you want to start /SYS (y/n)? y
Starting /SYS
2. To monitor the power on sequence, type the start /SP/console command.
You will see an ILOM CLI alert message on the system console. This message
indicates that the system has reset.
-> start /SP/console
Are you sure you want to start /SP/console (y/n)? y
Serial console started. To stop, type #.
The CPU and memory controllers initialize, and eventually OpenBoot initializes.
After a number of system console messages, the ok prompt appears, or the system
will boot into the Solaris OS.
54Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 66
Note – System behavior (such as whether the system halts at the ok prompt or boots
to the Solaris OS) depends on how the auto-boot variable is set. See the Sun SPARC
Enterprise T5140 and T5240 Servers Administration Guide for more information.
The following example output is a small section of the complete output.
0:1:0>
0:1:0>SPARC-Enterprise[TM] T5140/T5240 POST 4.27.x.
2007/12/11 18:55
...
0:1:0>Network Interface Unit Tests....Done
0:1:0>Functional CPU Tests....Done
0:1:0>Extended Memory Tests....Done
2007-12-14 16:45:28.800 0:1:0>INFO:
2007-12-14 16:45:28.806 0:1:0> POST Passed all devices.
2007-12-14 16:45:28.816 0:1:0>POST: Return to VBSC.
2007-12-14 16:45:28.824 0:1:0>Master set ACK for vbsc runpost
command and spin...
SPARC Enterprise T5240, No Keyboard
Copyright 2007 Sun Microsystems, Inc. All rights reserved.
OpenBoot 4.27.x, 3968 MB memory available, Serial #74409918.
Ethernet address 0:14:4f:6f:67:be, Host ID: 846f67be.
{0} ok
Related Information
■ “Examine the System for Faults” on page 55
■ Integrated Lights Out Manager (ILOM) Supplement for SPARC Enterprise T5140 and
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
▼ Examine the System for Faults
1. Perform the following steps to verify that there are no faults:
Powering On the System55
Page 67
a. Set the virtual keyswitch to diag mode so that POST will run in Service
mode.
-> set /SYS keyswitch_state=diag
Set ’keyswitch_state’ to ’diag’
b. To initiate the power on sequence, type the start /SYS command.
You will see an ILOM CLI alert message on the system console. This message
indicates that the system has reset.
-> start /SYS
Are you sure you want to start /SYS (y/n)? y
Starting /SYS
->
c. Switch to the system console to view POST output.
-> start /SP/console
Are you sure you want to start /SP/console (y/n)? y
Serial console started. To stop, type #.
.
.
.
Watch the POST output for possible fault messages. The following output is a
sign that POST did not detect any faults. The message indicating successful
passage of POST is indicated in bold.
.
.
.
2007-12-14 16:34:53.385 0:1:0>INFO:
2007-12-14 16:34:53.391 0:1:0>POST Passed all devices.
2007-12-14 16:34:53.399 0:1:0>POST: Return to VBSC.
2007-12-14 16:34:53.406 0:1:0>Master set ACK for vbsc runpost
command and spin.
...
SPARC Enterprise T5240, No Keyboard
Copyright 2007 Sun Microsystems, Inc. All rights reserved.
OpenBoot 4.27.x, 3968 MB memory available, Serial #74409918.
Ethernet address 0:14:4f:6f:67:be, Host ID: 846f67be.
{8} ok
56Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 68
2. Type the console escape sequence (by default #. (Hash-Period)) to return to the
ILOM prompt.
3. Check the POST execution result with the following command:
-> show /SP/faultmgmt -level all
Note – Depending on the configuration of ILOM, POST variables, and whether
POST detected faults or not, the server might boot, or the system might remain at the
ok prompt. If the system is at the ok prompt, type boot.
4. Use the set /SYS keyswitch_state=normal command to return the virtual
keyswitch to Normal mode (default) so that the system can power on and start
the boot process.
-> set /SYS keyswitch_state=normal
Set ’keyswitch_state’ to ’normal’
Related Information
■ Integrated Lights Out Manager (ILOM) Documentation
■ Integrated Lights Out Manager Supplement for SPARC Enterprise T5140 and T5240
Servers
■ Integrated Lights Out Manager (ILOM) 3.0 Supplement for SPARC Enterprise T5140
and T5240 Servers
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Devices in the OpenBoot Device Tree
To understand the various devices and their path names as represented in the
OpenBoot device tree, refer to the tables below.
TABLE:Disk Slot Numbers, Logical Device Names, and Physical Device Names
■ “Booting the Solaris Operating System” on page 58
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Booting the Solaris Operating System
The Solaris OS is preinstalled on the servers on the disk in slot 0. The Solaris OS is
not configured (that is, the sys-unconfig command was run in the factory). If you
boot the system from this disk, you will be prompted to configure the Solaris OS for
your environment.
■ “Boot the Solaris Operating System” on page 59
■ “Avoid Booting the Solaris Operating System at Startup” on page 59
■ “Reset the System” on page 60
■ “Power Cycle the System” on page 60
58Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 70
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
▼ Boot the Solaris Operating System
1. At the ok prompt, boot from the disk that contains the Solaris OS.
If you need to determine which disk to boot from, type the show-disks
command at the ok prompt to see the path to the configured disks, similar to the
following:
ok show-disks
a) /pci@0/pci@0/pci@2/scsi@0/disk
b) /pci@0/pci@0/pci@1/pci@0/pci@1/pci@0/usb@0,2/storage@2/disk
q) NO SELECTION Enter Selection, q to quit: q
ok
2. Type the boot command at the ok prompt.
Use the value from Step 1 to construct the boot command. You must append the
target to the disk path.
In the following example, the server is booted from disk 0 (zero) on a Sun SPARC
Enterprise T5140 server.
ok boot disk0
Boot device: /pci@0/pci@0/pci@2/scsi@0/disk@0 File and args:
SunOS Release 5.10 Version Generic_127127-03 64-bit
Copyright 1983-2007 Sun Microsystems, Inc. All rights reserved.
Use is subject to license terms.
Hostname: hostname
NIS domain name is x.x.x.x
hostname console login:
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
▼ Avoid Booting the Solaris Operating System at
Startup
In hard drive HDD0, the Solaris OS is preinstalled.
Powering On the System59
Page 71
● If you do not want to start the preinstalled OS, set the Open Boot PROM
parameter auto-boot? to false. For example:
-> set /HOST/bootmode script="setenv auto-boot? false"
Related Information
■ “Reset the System” on page 60
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
▼ Reset the System
● If it is necessary to reset the system, use the shutdown -g0 -i6 -y command.
# shutdown -g0 -i6 -y
It is not necessary to power the system off and on to simply reset the system.
Related Information
■ “Power Cycle the System” on page 60
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
▼ Power Cycle the System
If a simple reset does not clear a system problem, you can power the system off and
on with this procedure.
1. Shut down the Solaris OS.
At the Solaris OS prompt, type the shutdown -g0 -i0 -y command. Then type
h when prompted to halt the Solaris OS and to return to the ok prompt.
# shutdown -g0 -i0 -y
# svc.startd: The system is coming down. Please wait.
svc.startd: 91 system services are now being stopped.
Jun 12 19:46:57 wgs40-58 syslogd: going down on signal 15
svc.startd: The system is down.
syncing file systems... done
Program terminated
r)eboot, o)k prompt, h)alt?
60Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 72
2. Switch from the system console prompt to the service processor console prompt
using the console escape sequence (by default, #.
(Pound-Period)).
ok #.
->
3. Using the ILOM CLI, type the stop /SYS command to perform a graceful
shutdown of the system.
-> stop /SYS
Are you sure you want to stop /SYS (y/n)? y
Stopping /SYS
->
Note – To perform an immediate and ungraceful shutdown, use the stop -force
-script /SYS or stop -script /SYS commands. These commands stop
everything immediately. Ensure that all data is saved before entering these
commands.
4. Type the start /SYS command.
-> start /SYS
Are you sure you want to start /SYS (y/n)? y
Starting /SYS
->
Note – To force a power-on sequence, use the start -script /SYS command.
5. Reconnect to the system console with the start /SP/console command.
-> start /SP/console
Are you sure you want to start /SP/console (y/n)? y
Serial console started. To stop, type #.
The systems displays various messages, followed by the ok prompt.
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
■ Solaris Documentation
Powering On the System61
Page 73
Verifying System Functionality
After powering on the system for the first time, you can use the Sun Validation Test
Suite (SunVTS) software to verify the functionality and performance of any installed
components, as well as its network connections.
Related Information
■ SunVTS Documentation
62Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 74
Updating the Firmware
This section provides instructions for updating SP firmware.
■ “flashupdate command” on page 63
■ “Update the Firmware” on page 64
flashupdate command
The flashupdate command updates both the service processor firmware and the
server firmware.
The flash image consists of the following components:
■ Service processor firmware
■ OpenBoot firmware
■ POST
■ Reset/config
■ Sequencer
■ Partition description
Related Information
■ “Update the Firmware” on page 64
63
Page 75
▼Update the Firmware
1. Ensure that the ILOM service processor network management port is
configured.
This configuration is required to access the new flash image over the network. See
“Configure the Service Processor Network Management Port” on page 50.
2. Open an SSH session to connect to the service processor.
% ssh root@xx.xxx.xx.x
...
Are you sure you want to continue connecting (yes/no)? yes
...
Password: password (nothing is displayed)
Waiting for daemons to initialize...
Daemons ready
Integrated Lights Out Manager
Version 2.0.4.x
Copyright 2008 Sun Microsystems, Inc. All rights reserved.
Use is subject to license terms.
->
3. Verify that the host is powered off.
If the host is not powered off, type the stop /SYS command.
-> stop /SYS
4. Verify that the keyswitch_state parameter is set to normal.
-> set /SYS keyswitch_state=normal
5. Type the load command.
The load command updates the service processor flash image and the host
firmware. The load command requires the following information:
■ IP address of a TFTP server on the network that can access the flash image
64Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 76
■ Full path name to the flash image that the IP address can access
■ -script – Does not prompt for confirmation and acts as if yes was specified
■ -source – Specifies the IP address and full path name (URL) to the flash image
-> load -source tftp://xxx.xxx.xx.xx/pathname
NOTE: A firmware upgrade will cause the server and ILOM to
be reset. It is recommended that a clean shutdown of
the server be done prior to the upgrade procedure.
An upgrade takes about 6 minutes to complete. ILOM
will enter a special mode to load new firmware. No
other tasks can be performed in ILOM until the
firmware upgrade is complete and ILOM is reset.
Are you sure you want to load the specified file (y/n)? y
Do you want to preserve the configuration (y/n)? y
Firmware update is complete.
ILOM will now be restarted with the new firmware.
Update complete. Reset device to use new image.
->
After the flash image has been updated, the system will automatically reset.
The service processor resets, runs diagnostics, and returns to the login prompt (on
the serial console), similar to the example below.
U-Boot 1.1.1 (May 23 2007 - 21:30:12)
...
POST cpu PASSED
POST ethernet PASSED
Hit any key to stop autoboot: 0
## Booting image at fe080000 ...
IP Protocols: ICMP, UDP, TCP, IGMP
Checking all file systems...
fsck 1.37 (21-Mar-2005)
Setting kernel variables ...
... done.
Mounting local filesystems...
Cleaning /tmp /var/run /var/lock.
Updating the Firmware65
Page 77
Identifying DOC Device Type(G3/G4/H3) ...
OK
Configuring network interfaces...Internet Systems Consortium DHCP
Client V3.0.1
Copyright 2007 Internet Systems Consortium.
All rights reserved.
For info, please visit http://www.isc.org/products/DHCP
eth0: config: auto-negotiation on, 100FDX, 100HDX, 10FDX, 10HDX.
Listening on LPF/eth0/00:14:4f:3f:8c:af
Sending on LPF/eth0/00:14:4f:3f:8c:af
Sending on Socket/fallback
DHCPDISCOVER on eth0 to 255.255.255.255 port 67 interval 6
eth0: link up, 100 Mbps Full Duplex, auto-negotiation complete.
DHCPDISCOVER on eth0 to 255.255.255.255 port 67 interval 15
Hostname: hostname.
Starting portmap daemon: portmap.
Initializing random number generator...done.
INIT: Entering runlevel: 3
Starting system log daemon: syslogd and klogd.
Starting periodic command scheduler: cron.
■ “Configure the Service Processor Network Management Port” on page 50
66Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 78
Selecting a Boot Device
This section provides instructions on selecting a boot device.
■ “Boot Device Selection Overview” on page 67
■ “Select a Boot Device” on page 68
Boot Device Selection Overview
The boot device is specified by the setting of an OpenBoot configuration variable
called boot-device. The default setting of this variable is disk net. Because of this
setting, the firmware first attempts to boot from the system hard drive, and if that
fails, from the on-board NET0 Gigabit Ethernet interface.
This procedure assumes that you are familiar with the OpenBoot firmware and that
you know how to enter the OpenBoot environment. For more information, see the
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide.
Note – The serial management port on the ILOM card is preconfigured as the default
system console port. For more information, see the Sun SPARC Enterprise T5140 and
T5240 Servers Overview.
If you want to boot from a network, you must connect the network interface to the
network.
Related Information
■ “Select a Boot Device” on page 68
■ Sun SPARC Enterprise T5140 and T5240 Servers Overview
67
Page 79
▼Select a Boot Device
● At the ok prompt, type:
ok setenv boot-device device-specifier
where the device-specifier is one of the following:
■ cdrom – Specifies the DVD drive
■ disk – Specifies the system boot disk (internal disk 0 by default)
■ full path name – Specifies the device or network interface by its full path name
Note – The Solaris OS modifies the boot-device variable to its full path name, not
the alias name. If you choose a nondefault boot-device variable, the Solaris OS
specifies the full device path of the boot device.
Note – You can specify the name of the program to be booted as well as the way the
boot program operates. For more information, refer to the OpenBoot Command
Reference Manual for your specific Solaris OS release.
If you want to specify a network interface other than an on-board Ethernet
interface as the default boot device, you can determine the full path name of each
interface by typing either of the following commands:
ok show-devs
ok show-nets
The show-devs command lists the system devices and displays the full path
name of each PCI device.
Related Information
■ OpenBoot Documentation
■ OpenBoot Command Reference Manual
68Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 80
Installing the Servers With the
Express Rail Rackmounting Kit
This chapter provides instructions for installing the servers in an equipment rack
with express (snap-in) rails.
■ “Slide Rail Assembly Notes for the Express Rail Rackmounting Kit” on page 69
■ “Install the Slide Rail Assemblies” on page 72
■ “Insert and Lock the Server in the Rack” on page 77
■ “Dismounting the Server” on page 79
Slide Rail Assembly Notes for the
Express Rail Rackmounting Kit
The express rail rackmounting kit installs quickly, and does not require mounting
screws or nuts. The kit and the installation procedures are the same for both the Sun
SPARC Enterprise T5140 and T5240 servers.
Note – The illustrations used to support the procedure description show a 2U server
as an example.
Note – References to left and right are from your viewpoint as you face either the
front or the rear of the system.
Note – If your rackmounting kit came with its own instructions, use the instructions
in your rackmounting kit instead of the instructions in this section. After performing
the server installation, proceed to “Powering On the System” on page 41 for
first-time power on.
69
Page 81
The express rail rackmounting kit has two slide rail assemblies. A slide rail assembly
can be installed on either the right or left side of the rack.
Each slide rail assembly consists of a three-section slide rail and a removable
mounting bracket.
FIGURE:Sections of the Express Rail Slide Rail Assembly
Figure Legend
1Mounting bracket
2Front section
3Middle section
4Rear section
■ The front, middle, and rear sections form the slide rail. The middle and rear sections
have holes for mounting and adjust to fit rack depths from 24 in. (61 cm) to 36.5 in.
(93 cm). The front section can be extended to allow movement of the server out of
the rack.
■ The removable mounting bracket slides 14.5 in. (37 cm) out of the slide rail, then
locks in place. If you unlock the mounting bracket at this point, it slides an
additional 14.5 in. (37 cm) before separating from the slide rail. You can then
mount the mounting bracket to the right or left side of the server chassis.
■ There are six locks in a slide rail assembly. Four are on the mounting bracket. Two
locks are on the slide rail.
70Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 82
FIGURE:Locating the Locks on the Slide Rail Assembly for the Sun SPARC Enterprise
T5240 Server
Related Information
■ “Install the Slide Rail Assemblies” on page 72
■ “Insert and Lock the Server in the Rack” on page 77
Installing the Servers With the Express Rail Rackmounting Kit71
Page 83
▼Install the Slide Rail Assemblies
Note – Ensure that you have all of the parts in the rackmounting kit before you
begin the installation of the server.
The rackmounting kit contains two slide rail assemblies, which can be installed on
either the right or left side of the rack.
A slide rail assembly consists of two parts, a slide rail and a removable mounting
bracket. The slide rail attaches to the rack posts. The mounting bracket attaches to the
server chassis.
1. Pull both mounting brackets completely out of their respective slide rails.
a. Simultaneously press and hold the upper and lower lock buttons of the slide
rail lock.
FIGURE:Unlocking the Express Rail Slide Rail Assembly
b. Pull the mounting bracket out until it stops.
72Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 84
c. Slide the mounting bracket release button to the left; then slide the mounting
2. Attach a mounting bracket to the right side of the server chassis.
a. Position the mounting bracket against the chassis. Ensure that the slide rail
lock is at the front and the keyed openings on the mounting bracket are
aligned with the locating pins on the side of the chassis.
Installing the Servers With the Express Rail Rackmounting Kit73
Page 85
FIGURE:Attaching an Express Rail Mounting Bracket to the Chassis
b. Ensure that the heads of the four locating pins protrude through the keyed
openings in the mounting bracket. Slide the mounting bracket toward the
front of the chassis until the bracket locks into place with an audible click.
c. Verify that all four locating pins are trapped in the keyed openings and that
the third from the front locating pin has engaged the mounting bracket lock.
3. Attach the second mounting bracket to the left side of the server chassis.
4. Orient slide rails, ensuring that the ball bearing tracks (labeled FRONT) are
forward.
74Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 86
FIGURE:Express Rail Slide Rails Orientation for Installation
5. Extend the slide rails (outer section) to fit the rack and attach the slide rails to
the rack.
You hear an audible click when the rails securely attach to the rack.
Installing the Servers With the Express Rail Rackmounting Kit75
Page 87
FIGURE:Attaching Express Slide Rails to the Rack
Caution – Deploy the antitilt feature on the rack before continuing the installation.
Related Information
■ “Insert and Lock the Server in the Rack” on page 77
76Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 88
▼Insert and Lock the Server in the Rack
1. Deploy the antitilt feature, if the rack is so equipped.
Caution – The weight of the servers on extended slide rails can be enough to
overturn an equipment rack.
Caution – The 2U server weighs approximately 55 lb (25 kg). Two people are
required to lift and mount the server into a rack enclosure when using the
procedures in this chapter.
2. Insert the ends of the mounting brackets into the sliding rails.
3. Slide the server approximately halfway into the chassis.
FIGURE:Inserting Express Rail Mounting Brackets Into the Slide Rails
Installing the Servers With the Express Rail Rackmounting Kit77
Page 89
4. Slide the green release tab.
5. Push the server all the way into the rack until it locks into place.
FIGURE:Sliding the Express Rail Release Tab and Securing the Server in the Rack
Caution – Before continuing, verify that the server is securely mounted in the rack,
and that the slide rails are locked in the mounting brackets.
Dismounting the Server
Caution – To prevent damage to your server, do not move the rack while the server
is mounted.
78Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 90
To install or replace internal parts in the server, you must first remove the server
from the rack.
Related Information
■ Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
Installing the Servers With the Express Rail Rackmounting Kit79
Page 91
80Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 92
Assembling and Installing DC
Power Cables for the Sun SPARC
Enterprise T5140 Server
This section provides the following DC input power information for the Sun SPARC
Enterprise T5140 server:
■ “Requirements for Servers With DC Input Power” on page 81
■ “DC Supply and Ground Conductor Requirements” on page 82
■ “Overcurrent Protection Requirements” on page 83
■ “Assembling and Installing the DC Input Power Cables” on page 83
Related Information
■ “Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5240
Server” on page 93
Requirements for Servers With DC Input
Power
The following restrictions apply to the Sun SPARC Enterprise T5140 server with DC
input power:
■ The DC version of the server must be installed in a restricted-access location.
According to the intent of the National Electrical Code, a restricted-access location
is an area intended for qualified or trained personnel only and has access
controlled by a locking mechanism, such as a key lock or an access card system.
■ The server must not be directly connected to a centralized DC mains.
81
Page 93
Related Information
■ “DC Supply and Ground Conductor Requirements” on page 82
DC Supply and Ground Conductor
Requirements
The server must meet the following:
■ Suitable conductor material: Use copper conductors only
■ Power supply connections through the input connector: 12 AWG (between the
server and the source). There are three conductors:
■ -48V or -60V (negative terminal)
■ Chassis ground connection
■ -48V or -60V Return (positive terminal)
■ System ground conductor: 12 AWG (to be connected to the chassis)
■ Provide a Wago Type 721-103/037-000 mating connector for proper connection to
the DC connectors supplied with the server (Wago Type 721)
■ Branch circuit cable insulation color: According to applicable National Electrical
Codes
■ Grounding cable insulation color: Green/yellow
■ DC power source must meet TNV-2 requirements as defined by UL 60950-1 and
IEC 60950-1
Note – Depending on the DC power source, the -48V or -60V (negative terminal)
might be marked with a minus (-) symbol. The -48V or -60V Return (positive
terminal) might be marked with a positive (+) symbol.
When attaching DC cables, keep the following caution in mind:
Caution – You must restrict the connection of the server to the DC power source to
minimize the possibility that transient energy will appear on the main input to the
equipment. The DC battery power source must be in the same premises as the server.
The server cannot be in one building with the power source in another building.
82Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 94
Related Information
■ “Overcurrent Protection Requirements” on page 83
Overcurrent Protection Requirements
The following protections against excessive current loads must be satisfied before
servers that use DC input power can be installed:
■ Overcurrent protection devices must be provided as part of each equipment rack.
■ Circuit breakers must be located between the DC power source and the server. Use
one 20A fast-trip, double-pole, DC-rated circuit breaker for each power supply
unit.
Note – Overcurrent protection devices must meet applicable national and local
electrical safety codes and be approved for the intended application.
Related Information
■ “Assembling and Installing the DC Input Power Cables” on page 83
Assembling and Installing the DC Input
Power Cables
These topics explain how to assemble and install DC input power cables.
■ “Assemble the DC Input Power Cable” on page 83
■ “Install the Strain Relief Housings” on page 89
■ “Connect the DC Input Power Cords to the Server” on page 91
▼ Assemble the DC Input Power Cable
The following procedure describes how to assemble the DC input power cables for
Oracle’s Sun SPARC Enterprise T5140 server.
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server83
Page 95
Assemble one cable for each DC power supply in your server.
Before you begin the installation procedure, verify that the required conditions
described in the following table have been satisfied.
Prerequisite ConditionResponsible Party
Install a DC power source that meets the server’s input power
specifications.
Secure DC power cables that meet the server’s power cabling
specifications.
Attach the DC input plug to the DC input power cables. The input plug
is provided in the server’s shipping kit.
Customer
Customer
Customer
1. Turn off power from the DC power source using the circuit breakers.
Caution – Do not proceed with these instructions until you have turned off the
power from the DC power source through the circuit breakers.
2. Identify the parts that you will use to assemble the DC input power cables
For each cable, you need the items shown in. These items are provided in the
shipping kit that came with your server.
84Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 96
FIGURE:DC Connection Parts
Figure Legend
1Strain relief housing
2DC input plug
3Cage clamp operating lever
3. Locate the three wires coming from the DC power source that will be used in
the connection to your unit:
■ -48V or -60V (negative terminal)
■ Chassis ground
■ -48V or -60V Return (positive terminal)
Note – Depending on the DC power source, the -48V or -60V (negative terminal)
might be marked with a minus (-) symbol. The -48V or -60V Return (positive
terminal) might be marked with a positive (+) symbol.
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server85
Page 97
4. Strip 5/16 in. (8 mm) of insulation from each of the wires coming from the DC
power source.
Do not strip more than 5/16 in. (8 mm) from each wire. Doing so leaves
uninsulated wire exposed from the DC connector after the assembly is complete.
FIGURE:Stripping the Insulation From the Wire
Figure Legend
15/16 in. (8 mm)
5. Open the cage clamp for this section of the DC input plug by taking one of the
following actions:
■ Insert the tip of the cage clamp operating lever into the rectangular hole
directly above the hole in the DC input plug where you want to insert the first
wire. Press down on the cage clamp operating lever.
■ Insert a small slotted screwdriver into the rectangular hole directly above the
hole in the DC input plug where you want to insert the first wire, and push in
to open the cage clamp.
86Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 98
FIGURE:Opening the DC Input Plug Cage Clamp Using the Cage Clamp Operating
Lever
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server87
Page 99
FIGURE:Opening the Cage Clamp Using a Screwdriver
6. Feed the exposed section of the appropriate wire into the round hole in the DC
input plug.
FIGURE:Connector Wiring Assignments
Figure Legend
1Top of connector3From chassis ground (green/yellow)
2From -48V or -60V Return4From -48V or -60V
Note – If you need to remove a wire from the DC input plug, insert the cage clamp
operating lever or a small screwdriver as and pull the wire from the DC input plug.
7. Release the lever or remove the tool to secure the wire into the connector.
88Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 100
8. Repeat the procedures for the other two wires to complete the assembly of the
DC input power cable.
9. Repeat this procedure to create as many DC input power cables as you need for
your unit.
Related Information
■ “Install the Strain Relief Housings” on page 89
▼ Install the Strain Relief Housings
1. Insert the bottom portion of the strain relief housing into the notch on the DC
input plug until it snaps into place.
Ensure that the strain relief housing snaps into place on the DC input plug. You
cannot complete the assembly correctly if the strain relief housing is not snapped
into place.
FIGURE:Inserting the Bottom Portion of the Strain Relief Housing
2. Route the three wires coming from the DC power source through the opening at
the bottom end of the strain relief housing.
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server89