Oracle Sun SPARC Enterprise T5140, Sun SPARC Enterprise T5240 Installation Manual

Page 1
Sun SPARC Enterprise T5140 and T5240 Servers
Installation Guide
Part No. 820-3315-14 December 2010, Revision A
Page 2
Copyright © 2008, 2010 ,Oracle and/orits affiliates.All rightsreserved. FUJITSU LIMITEDprovided technicalinput andreview on portions of this material. Oracle and/orits affiliatesand FujitsuLimited eachown orcontrol intellectual propertyrights relatingto products and technologydescribed inthis
This documentand theproduct andtechnology towhich itpertains are distributed underlicenses restricting their use,copying, distribution,and decompilation. Nopart ofsuch productor technology,or ofthis document,may bereproduced inany formby anymeans withoutprior written authorization ofOracle and/orits affiliatesand FujitsuLimited, andtheir applicablelicensors, ifany. Thefurnishings ofthis documentto youdoes not give youany rightsor licenses,express orimplied, withrespect to the product ortechnology towhich itpertains, andthis documentdoes notcontain or represent any commitment of any kind on the part of Oracle or Fujitsu Limited, or any affiliateof eitherof them.
This documentand theproduct andtechnology describedin thisdocument mayincorporate third-party intellectual property copyrighted byand/or licensed fromthe suppliersto Oracleand/or itsaffiliates and Fujitsu Limited, including software andfont technology.
Per theterms ofthe GPLor LGPL,a copyof thesource codegoverned bythe GPLor LGPL,as applicable,is availableupon request by theEnd User. Please contact Oracleand/or itsaffiliates orFujitsu Limited.
This distributionmay includematerials developedby thirdparties. Parts ofthe product may bederived from BerkeleyBSD systems,licensed fromthe University of California. UNIXis aregistered trademark inthe U.S.and
in othercountries, exclusivelylicensed throughX/Open Company,Ltd. Oracle andJava areregisteredtrademarks ofOracle and/orits affiliates.Fujitsu andthe Fujitsulogo are registered trademarks of Fujitsu Limited. All SPARC trademarksareused underlicense andare registered trademarksof SPARC International,Inc. inthe U.S.and other countries. Products bearing
SPARC trademarks are based uponarchitectures developed by Oracle and/or its affiliates.SPARC64is atrademark ofSPARC International, Inc., used under licenseby FujitsuMicroelectronics, Inc. and Fujitsu Limited. Other names may be trademarks of their respectiveowners.
United StatesGovernment Rights- Commercialuse. U.S.Government usersare subject to the standardgovernment userlicense agreementsof Oracle and/or itsaffiliates andFujitsu Limitedand theapplicable provisions of theFAR and itssupplements.
Disclaimer: Theonly warrantiesgranted byOracle andFujitsu Limited,and/or anyaffiliate ofeither ofthem inconnection withthis documentor any product ortechnology describedherein are thoseexpressly setforth inthe licenseagreement pursuant to which the product ortechnology isprovided. EXCEPT ASEXPRESSLY SET FORTH IN SUCHAGREEMENT, ORACLE ORFUJITSU LIMITED,AND/OR THEIRAFFILIATESMAKE NO REPRESENTATIONS ORWARRANTIES OF ANYKIND (EXPRESSOR IMPLIED)REGARDING SUCHPRODUCT ORTECHNOLOGY ORTHIS DOCUMENT,WHICH AREALL PROVIDEDAS IS,AND ALLEXPRESS ORIMPLIED CONDITIONS,REPRESENTATIONS ANDWARRANTIES, INCLUDING WITHOUTLIMITATION ANYIMPLIED WARRANTY OFMERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSEOR NON­INFRINGEMENT,ARE DISCLAIMED,EXCEPT TO THE EXTENTTHATSUCH DISCLAIMERSARE HELDTO BE LEGALLY INVALID. Unless otherwise expresslyset forthin suchagreement, to the extent allowed by applicable law,in noevent shallOracle orFujitsu Limited,and/or anyof their affiliates haveany liabilityto anythird party under any legal theory for any loss of revenuesor profits,loss ofuse ordata, orbusiness interruptions,or for any indirect,special, incidentalor consequentialdamages, evenif advisedof thepossibility ofsuch damages.
DOCUMENTATION ISPROVIDED “ASIS” ANDALL EXPRESSOR IMPLIEDCONDITIONS, REPRESENTATIONSAND WARRANTIES, INCLUDING ANYIMPLIED WARRANTY OFMERCHANTABILITY,FITNESS FORA PARTICULAR PURPOSEOR NON-INFRINGEMENT, ARE DISCLAIMED, EXCEPTTO THEEXTENT THAT SUCHDISCLAIMERS AREHELD TO BE LEGALLY INVALID.
Page 3
Copyright ©2008, 2010,Oracle et/ouses sociétésaffiliées. Tous droits réservés. FUJITSU LIMITEDa fourniet vérifiédes donnéestechniques decertaines partiesde cecomposant. Oracle et/ouses sociétésaffiliées etFujitsu Limiteddétiennent etcontrôlent chacunedes droits de propriété intellectuelle relatifs aux produitset
technologies décritsdans cedocument. Demême, cesproduits, technologieset cedocument sontprotégés par des lois sur le copyright, des brevets, d’autres loissur lapropriété intellectuelle et des traités internationaux.
Ce document,le produitet lestechnologies afférents sont exclusivement distribués avec des licences qui en restreignentl’utilisation, lacopie, la distribution etla décompilation.Aucune partiede ceproduit, deces technologiesou dece documentne peutêtre reproduite sousquelque formeque ce soit, parquelque moyenque cesoit, sansl’autorisation écritepréalable d’Oracleet/ou sessociétés affiliéeset deFujitsu Limited,et deleurs éventuels bailleurs delicence. Cedocument, bienqu’il vousait étéfourni, nevous confèreaucun droit et aucunelicence, expresses ou tacites,concernant leproduit ou latechnologie auxquelsil serapporte. Parailleurs, ilne contientni nereprésente aucunengagement, dequelque typeque cesoit, dela partd’Oracle ou de FujitsuLimited, oudes sociétésaffiliées del’une oul’autre entité.
Ce document,ainsi queles produitset technologiesqu’il décrit,peuvent inclure des droits de propriété intellectuelle departies tiercesprotégés par copyright et/oucédés souslicence pardes fournisseursà Oracleet/ou sessociétés affiliéeset FujitsuLimited, ycompris deslogiciels etdes technologies relatives auxpolices decaractères.
Conformément auxconditions dela licenceGPL ouLGPL, unecopie ducode sourcerégi parla licenceGPL ouLGPL, selonle cas,est disponiblesur demande parl’Utilisateur final.Veuillez contacter Oracle et/ou ses sociétés affiliées ouFujitsu Limited.
Cette distributionpeut comprendre des composantsdéveloppés pardes partiestierces. Des partiesde ceproduit peuventêtre dérivées des systèmes Berkeley BSD, distribués sous licence par l’Université de Californie. UNIX est une marque
déposée auxÉtats-Unis etdans d’autrespays, distribuéeexclusivement souslicence parX/Open Company, Ltd. Oracle etJava sontdes marquesdéposées d’OracleCorporation et/oude sessociétés affiliées. Fujitsu etle logoFujitsu sontdes marques déposées de
Fujitsu Limited. Toutes les marques SPARC sont utiliséessous licenceet sontdes marques déposées deSPARC International, Inc.,aux États-Uniset dansd’autrespays. Les
produits portantla marque SPARC reposent sur des architectures développéespar Oracleet/ou sessociétés affiliées. SPARC64 est unemarque de SPARC International, Inc.,utilisée souslicence parFujitsu Microelectronics, Inc. etFujitsu Limited.Tout autre nom mentionné peut correspondreà desmarques appartenant àd’autres propriétaires.
United StatesGovernment Rights- Commercialuse. U.S. Governmentusers aresubject tothe standard government userlicense agreements of Oracle and/or itsaffiliates andFujitsu Limitedand theapplicable provisions of theFAR and itssupplements.
Avis de non-responsabilité : les seulesgaranties octroyéespar Oracleet FujitsuLimited et/outoute sociétéaffiliée de l’une ou l’autreentité enrapport avec cedocument outout produitou toutetechnologie décritsdans lesprésentes correspondent aux garantiesexpressément stipulées dans le contrat de licence régissantle produitou latechnologie fournis.SAUF MENTIONCONTRAIRE EXPRESSÉMENTSTIPULÉE DANSCE CONTRAT,ORACLE OU FUJITSU LIMITEDET LESSOCIÉTÉS AFFILIÉESÀ L’UNE OUL’AUTREENTITÉ REJETTENTTOUTE REPRÉSENTATIONOU TOUTE GARANTIE, QUELLE QU’ENSOIT LANATURE(EXPRESSE OUIMPLICITE) CONCERNANTCE PRODUIT, CETTETECHNOLOGIE OUCE DOCUMENT, LESQUELS SONTFOURNIS ENL’ÉTAT. ENOUTRE, TOUTESLES CONDITIONS,REPRÉSENTATIONS ETGARANTIES EXPRESSESOU TACITES, Y COMPRIS NOTAMMENT TOUTEGARANTIE IMPLICITERELATIVEÀ LAQUALITÉ MARCHANDE,À L’APTITUDE ÀUNE UTILISATION PARTICULIÈRE OUÀ L’ABSENCE DE CONTREFAÇON,SONT EXCLUES,DANS LAMESURE AUTORISÉEPAR LA LOIAPPLICABLE. Saufmention contraire expressément stipulée dansce contrat,dans lamesure autorisée par la loi applicable, en aucun cas Oracle ou Fujitsu Limited et/ou l’une ou l’autre deleurs sociétésaffiliées ne sauraient être tenuesresponsables enversune quelconquepartie tierce, sous quelquethéorie juridiqueque cesoit, de tout manqueà gagnerou deperte deprofit, deproblèmes d’utilisation ou de perte de données, ou d’interruptionsd’activités, oude toutdommage indirect, spécial,secondaire ou consécutif, même si ces entités ont été préalablement informées d’une telle éventualité.
LA DOCUMENTATIONEST FOURNIE« EN L’ÉTAT » ETTOUTE AUTRE CONDITION, DÉCLARATIONET GARANTIE,EXPRESSE OUTACITE,EST FORMELLEMENT EXCLUE,DANS LAMESURE AUTORISÉEPAR LA LOI EN VIGUEUR, Y COMPRIS NOTAMMENT TOUTE GARANTIE IMPLICITE RELATIVE ÀLA QUALITÉMARCHANDE, ÀL’APTITUDEÀ UNEUTILISATIONPARTICULIÈRE OUÀ L’ABSENCE DE CONTREFAÇON.
Page 4
Contents
Preface x
Preparing for Installation 1
Server Overview 1
Server Handling Precautions 3
Input Power Information and Precautions 3
Tools and Equipment Needed 4
Optional Component Installation 5
ESD Precautions 6
Installation Overview 6
Prepare for Installation 8
Install the Hardware 8
Configure the Service Processor 9
Configure the Host Software 10
Cabling Notes for Both Servers 10
Port, Connector, and LED Locations for Both Servers 12
Slide Rail Assembly Notes for Both Servers 15
Cable Management Notes for Both Servers 18
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 19
Installing the Servers in a Rack 19
Install the Slide Rail Assemblies 20
Insert and Lock the Server in the Rack 26
vi
Page 5
Installing the Cable Management Arm for Both Servers 28
Install the Cable Management Arm 28
Verify the Operation of the Slide Rails and the CMA 32
Connecting the Server Cables for Both Servers 34
Connect the Service Processor Serial Management Port 35
Connect the Service Processor Network Management Port 36
Connect the Ethernet Network Cables 37
AC Power Cable Notes 38
Managing Cables With the CMA 39
Secure the Server Cables in the CMA 39
Dismounting the Servers 40
Powering On the System 41
Powering On the System for the First Time 41
ILOM System Console 42
ILOM Service Processor 42
Power On the System for the First Time 43
Enable the Service Processor Network Management Port 47
Logging Into the Service Processor 49
Log Into the Service Processor Using the Serial Management Port 49
Configure the Service Processor Network Management Port 50
Log Into the Service Processor Using the Network Management Port
53
Using the Service Processor for Common Operations 54
Perform a Normal System Initialization 54
Examine the System for Faults 56
Devices in the OpenBoot Device Tree 58
Booting the Solaris Operating System 59
Boot the Solaris Operating System 59
vii Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 6
Avoid Booting the Solaris Operating System at Startup 60
Reset the System 60
Power Cycle the System 61
Verifying System Functionality 62
Updating the Firmware 63
flashupdate command 63
Update the Firmware 64
Selecting a Boot Device 67
Boot Device Selection Overview 67
Select a Boot Device 68
Installing the Servers With the Express Rail Rackmounting Kit 69
Slide Rail Assembly Notes for the Express Rail Rackmounting Kit 69
Install the Slide Rail Assemblies 72
Insert and Lock the Server in the Rack 77
Dismounting the Server 79
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise
T5140 Server 81
Requirements for Servers With DC Input Power 81
DC Supply and Ground Conductor Requirements 82
Overcurrent Protection Requirements 83
Assembling and Installing the DC Input Power Cables 83
Assemble the DC Input Power Cable 83
Install the Strain Relief Housings 89
Connect the DC Input Power Cords to the Server 91
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise
T5240 Server 93
Requirements for Servers With DC Input Power 93
Contents viii
Page 7
DC Supply and Ground Conductor Requirements 94
Overcurrent Protection Requirements 95
Assembling and Installing the DC Input Power Cables 95
Assemble the DC Input Power Cables 95
Connect the DC Input Power Cords to the Server 99
Index 101
ix Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 8
Preface
This installation guide provides instructions and information to help you install the Sun SPARC Enterprise T5140 and T5240 servers from Oracle. The installation instructions assume that you are a system administrator experienced with the Oracle Solaris Operating System.
“UNIX Commands” on page x
“Shell Prompts” on page xi
“Related Documentation” on page xi
“Documentation, Support, and Training” on page xii
“Documentation Feedback” on page xii
UNIX Commands
This document might not contain information on basic UNIX commands and procedures such as shutting down the system, booting the system, and configuring devices. Refer to the following for this information:
Software documentation that you received with your system
Solaris Operating System documentation, which is at
(http://docs.sun.com)
x
Page 9
Shell Prompts
Shell Prompt
C shell machine-name%
C shell superuser machine-name#
Bourne shell and Korn shell $
Bourne shell and Korn shell superuser #
Related Documentation
The documents listed as online are available at:
(http://docs.sun.com/app/docs/prod/sparc.t5140)
(http://docs.sun.com/app/docs/prod/sparc.t5240)
Application Title Part Number Format Location
Product Notes Sun SPARC Enterprise T5140 and T5240 Servers
Product Notes
Getting Started Sun SPARC Enterprise T5140 Server Getting Started
Guide
Getting Started Sun SPARC Enterprise T5140 Server Getting Started
Guide (DC)
Getting Started Sun SPARC Enterprise T5240 Server Getting Started
Guide
Getting Started Sun SPARC Enterprise T5240 Server Getting Started
Guide (DC)
Planning Sun SPARC Enterprise T5140 and T5240 Servers Site
Planning Guide
Installation Sun SPARC Enterprise T5140 and T5240 Servers
Installation Guide
Administration Sun SPARC Enterprise T5140 and T5240 Servers
Administration Guide
820-3312 PDF Online
820-3875 Printed Shipswith
system
820-5840 Printed Shipswith
system
820-3521 Printed Shipswith
system
820-5841 Printed Shipswith
system
820-3314 PDF
HTML
820-3315 PDF
HTML
820-3316 PDF
HTML
Online
Online
Online
xi Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 10
Application Title Part Number Format Location
Service Sun SPARC Enterprise T5140 and T5240 Servers
Service Manual
Safety Sun SPARC Enterprise T5140 and T5240 Servers
Safety and Compliance Guide
Remote Management
Oracle Integrated Lights Out Manager (ILOM) 3.0 Supplement for Sun SPARC Enterprise T5140 and T5240 Servers
Documentation, Support, and Training
Additional resources are available at:
Documentation (http://www.sun.com/documentation)
Support (http://www.sun.com/support)
Training (http://www.sun.com/training)
820-3318 PDF
HTML
820-3319 PDF Online
820-6684 PDF
HTML
Online
Online
Documentation Feedback
Submit comments about this document by clicking the Feedback[+] link at
(http://docs.sun.com).
Please include the title and part number of your document with your feedback:
Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide, part number 820-3315-14.
Preface xii
Page 11
xiii Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 12
Preparing for Installation
This chapter provides background information about the installation procedures for both servers. This chapter contains these topics:
“Server Overview” on page 1
“Server Handling Precautions” on page 3
“Input Power Information and Precautions” on page 3
“Tools and Equipment Needed” on page 4
“Optional Component Installation” on page 5
“ESD Precautions” on page 6
“Installation Overview” on page 6
“Prepare for Installation” on page 8
“Install the Hardware” on page 8
“Configure the Service Processor” on page 9
“Configure the Host Software” on page 10
“Cabling Notes for Both Servers” on page 10
“Port, Connector, and LED Locations for Both Servers” on page 12
“Slide Rail Assembly Notes for Both Servers” on page 15
“Cable Management Notes for Both Servers” on page 18
Server Overview
The Sun SPARC Enterprise T5140 server from Oracle is a 1 rack unit (1U) server. Oracle’s Sun SPARC Enterprise T5240 server is a 2 rack unit (2U) server.
1
Page 13
FIGURE: Sun SPARC Enterprise T5240 Server
FIGURE: Sun SPARC Enterprise T5140 Server
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
2 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 14
Server Handling Precautions
Caution – Deploy the antitilt bar on the equipment rack before beginning an
installation.
Caution – The Sun SPARC Enterprise T5240 server weighs approximately 46 lb (20.7
kg). Two people are required to lift and mount this 2U server into a rack enclosure when using the procedures in this document.
Caution – When completing a two-person procedure, always communicate your
intentions clearly before, during, and after each step to minimize confusion.
Related Information
“Input Power Information and Precautions” on page 3
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
Input Power Information and Precautions
The Sun SPARC Enterprise T5140 and T5240 servers are available in the following input power configurations:
Two redundant, hot-swappable AC power supplies
Preparing for Installation 3
Page 15
Two redundant, DC power supplies
Note – Safety agency requirements prohibit manufacturers from changing a product
from AC input to DC input or from DC input to AC input after the product has been removed from the agency approved manufacturing site.
Note – The DC version of the server must be installed in a restricted-access location.
According to the intent of the National Electrical Code, a restricted-access location is an area intended for qualified or trained personnel only and has access controlled by a locking mechanism, such as a key lock or an access card system.
When each power supply is connected to a separate power source, the server continues to operating under the following fault conditions:
A power source failure that removes input power from one of the power supplies.
Failure of one of the power supplies.
Service actions which require removal of one of the power supplies.
Refer to the Sun SPARC Enterprise T5140 and T5240 Servers Site Planning Guide for input power specifications.
Note – Input AC/DC power cables: To avoid missing initialization messages, do not
attach power cables to the power supplies until you have finished connecting the data cables, and have connected the server to a serial terminal or a terminal emulator (PC or workstation). The server goes into Standby mode and the ILOM service processor initializes as soon as the input power cables are connected to the power source.
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Site Planning Guide
Tools and Equipment Needed
To install the system, you must have the following tools:
No. 2 Phillips screwdriver
No. 1 Phillips screwdriver
4 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 16
ESD mat and grounding strap
In addition, you must provide a system console device, such as one of the following:
ASCII terminal
Workstation
Terminal server
Patch panel connected to a terminal server
Related Information
“Optional Component Installation” on page 5
Optional Component Installation
The standard components of the server are installed at the factory. However, if you ordered options such as additional memory or PCI cards, these will be shipped separately. If possible, install these components prior to installing the server in a rack.
If you ordered any options that are not factory-installed, see the Sun SPARC Enterprise T5140 and T5240 Servers Service Manual for installation instructions.
Note – The list of optional components can be updated without notice. See the
product web pages for the most current list of components supported in the server.
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
Preparing for Installation 5
Page 17
ESD Precautions
Electronic equipment is susceptible to damage by static electricity. Use a grounded antistatic wriststrap, footstrap, or equivalent safety equipment to prevent electrostatic damage (ESD) when you install or service the servers.
Caution – To protect electronic components from electrostatic damage, which can
permanently disable the system or require repair by service technicians, place components on an antistatic surface, such as an antistatic discharge mat, an antistatic bag, or a disposable antistatic mat. Wear an antistatic grounding strap connected to a metal surface on the chassis when you work on system components.
Related Information
“Installation Overview” on page 6
Installation Overview
This installation guide provides procedures that are to be performed in the following order.
6 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 18
FIGURE: Installation Overview
Figure Legend
1 Preparing for installation
2 Installing the hardware
3 Configuring the service processor
4 Configuring the host software
Preparing for Installation 7
Page 19
Prepare for Installation
1. Verify that you have received all of the components that ship with your server.
2. Gather configuration information for your system. See your system administrator for specific details, including these parameters:
Netmask
IP address for the service processor
Gateway IP address
3. Install any optional components shipped with your system.
If you have purchased other optional components such as additional memory, install them prior to mounting the server in a rack.
Related Information
“Optional Component Installation” on page 5
Install the Hardware
1. Mount the server into a rack or cabinet. See “Installing the Servers in a Rack” on
page 19 for both the 1U and 2U servers. Or, if you ordered the express rail
rackmounting kit, which has the same rack rail assemblies for both servers, see
“Installing the Servers With the Express Rail Rackmounting Kit” on page 69.
Note – In the rest of this guide, the term rack means either an open rack or a closed
cabinet.
2. Connect the server to a serial terminal or a terminal emulator (PC or workstation) to display system messages. See “Powering On the System for the
First Time” on page 41.
8 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 20
Tip – The serial terminal or a terminal emulator should be connected before you
connect the power cables. As soon as AC power is connected to the system, the service processor immediately powers on and runs diagnostics. Diagnostic test failures will be printed on the serial terminal. For more information, refer to the
Integrated Lights Out Manager Supplement for Sun SPARC Enterprise T5140 and T5240 Servers.
3. Connect the data cables to the server, but do not connect the AC power cable
yet. See “Connecting the Server Cables for Both Servers” on page 34.
4. Connect the AC power cable to the server and examine the display for any error
messages. See “Powering On the System for the First Time” on page 41.
Caution – There is a potential for electric shock if the server and related equipment
are not properly grounded.
Note – The service processor runs on the 3.3V standby voltage. As soon as AC
power is connected to the system, the service processor immediately powers on, runs diagnostics, and initializes the ILOM firmware.
Related Information
“Powering On the System for the First Time” on page 41
Configure the Service Processor
1. After the service processor boots, access the ILOM command-line interface
(CLI) through the serial management port. See “Log Into the Service Processor
Using the Serial Management Port” on page 49.
2. Configure the service processor network addresses. See “Configure the Service
Processor Network Management Port” on page 50.
Note – The service processor network management port is not operational until you
configure network settings for the service processor (through the service processor serial management port).
Preparing for Installation 9
Page 21
3. Commit the changes to the service processor network parameters. See Step 3 in
“Power On the System for the First Time” on page 43.
4. Power on the server from a keyboard using the ILOM software. See “Examine
the System for Faults” on page 55.
Related Information
“Configure the Host Software” on page 10
Configure the Host Software
1. Configure the Solaris OS. See “Booting the Solaris Operating System” on page 58.
The Solaris OS is preinstalled on the servers. When you power on, you are automatically guided through the Solaris OS configuration procedure.
2. Install any required patches to the server.
Refer to the Sun SPARC Enterprise T5140 and T5240 Servers Product Notes for a list of required patches.
3. Load additional software from the Solaris media kit (optional).
The Solaris media kit (sold separately) includes several CDs containing software to help you operate, configure, and administer your server. Refer to the documentation provided with the media kit for a complete listing of included software and detailed installation instructions.
Related Information
“Cabling Notes for Both Servers” on page 10
Sun SPARC Enterprise T5140 and T5240 Servers Product Notes
Cabling Notes for Both Servers
Minimum cable connections for the servers:
At least one system on-board Ethernet network connection (NET port)
Service processor serial management port (SER MGT port)
Service processor network management port (NET MGT port)
Power cables for the two system power supplies
10 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 22
Service processor management ports: There are two service processor
management ports for use with the ILOM service processor.
The service processor serial management port (labeled SER MGT) uses an RJ-45
cable and is always available. This port is the default connection to the ILOM service processor.
The service processor network management port (labeled NET MGT) is the
optional connection to the ILOM service processor. This port is not available until you configure network settings for the service processor (through the service processor serial management port). See “Enable the Service Processor
Network Management Port” on page 47.
The service processor network management port uses an RJ-45 cable for a
10/100 BASE-T connection. This port does not support connections to Gigabit networks. See the Sun SPARC Enterprise T5140 and T5240 Servers Overview for more information.
Ethernet ports are labeled NET0, NET1, NET2, and NET3. The Ethernet interfaces
operate at 10 Mbps, 100 Mbps, and 1000 Mbps. The table below shows the transfer rates for the Ethernet ports.
TABLE: Ethernet Connection Transfer Rates
Connection Type IEEE Terminology Transfer Rate
Ethernet 10BASE-T 10 Mbit/sec
Fast Ethernet 100BASE-TX 100 Mbits/sec
Gigabit Ethernet 1000BASE-T 1000 Mbit/sec
TTYA serial port: Use the DB-9 connector with a null modem cable for serial
devices. This port appears as ttya in Solaris OS and OpenBoot messages. This port is not connected to the service processor serial management port.
USB ports: USB ports support hot-plugging. You can connect and disconnect USB
cables and peripheral devices while the system is running, without affecting system operations.
You can only perform USB hot-plug operations while the OS is running. USB
hot-plug operations are not supported when the system ok prompt is displayed or before the system has completed booting.
You can connect up to 126 devices to each of the four USB controllers, for a total
of 504 USB devices per system.
AC power cables: Do not attach power cables to the power supplies until you have
finished connecting the data cables, and have connected the server to a serial terminal or a terminal emulator (PC or workstation). The server goes into Standby mode and the ILOM service processor initializes as soon as the AC power cables are connected to the power source. System messages might be lost after 60 seconds if the server is not connected to a terminal, PC, or workstation.
Preparing for Installation 11
Page 23
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
Sun SPARC Enterprise T5140 and T5240 Servers Overview Guide
Port, Connector, and LED Locations for Both Servers
See the figures below for the locations of the ports on the Sun SPARC Enterprise T5140 server.
FIGURE: Rear Panel Cable Connectors and LEDs on the Sun SPARC Enterprise T5140 Server
Figure Legend
1 Power supply 0 10 Gbit Enet port NET2
2 Power supply 1 11 Gbit Enet port NET3
3 Locator LED button 12 USB port 0
4 Service Required LED 13 USB port 1
5 PowerOKLED 14 TTYA serial port
6 Service processor serial management port 15 PCIe/XAUI slot 0
7 Service processor network management port 16 PCIe/XAUI slot 1
8 Gbit Enet port NET0 17 PCIe slot 2
9 Gbit Enet port NET1
USB ports 2 and 3 are located on the front panel.
12 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 24
FIGURE: Front Panel USB Ports on the Sun SPARC Enterprise T5140 Server
Figure Legend
1 System status indicators: Top to bottom: Locator LED button, Service
Required LED, Power OK LED, and Power button
2 Hard drive HDD0 6 USB port 2
3 Hard drive HDD1 7 USB port 3
4 Hard drive HDD2
5 Hard drive HDD3
See the figures below for the locations of the ports on the Sun SPARC Enterprise T5240 server.
FIGURE: Rear Panel Cable Connectors and LEDs on the Sun SPARC Enterprise T5240 Server
Figure Legend
1 Power supply 0 11 Gbit Enet port NET3
2 Power supply 1 12 USB port 0
3 Locator LED button 13 USB port 1
4 Service Required LED 14 TTYA serial port
5 PowerOKLED 15 PCIe slot 3
6 Service processor serial management port 16 PCIe or XAUI slot 0
7 Service processor network management port 17 PCIe slot 4
Preparing for Installation 13
Page 25
Figure Legend (Continued)
8 Gbit Enet port NET0 18 PCIe or XAUI slot 1
9 Gbit Enet port NET1 19 PCIe slot 5
10 Gbit Enet port NET2 20 PCIe slot 2
USB ports 2 and 3 are located on the front panel.
FIGURE: Front Panel USB Ports on the Sun SPARC Enterprise T5240 Server
Figure Legend
1 System status indicators: Top to bottom: Locator LED button,
7 Hard drive HDD5
Service Required LED, Power OK LED, and Power button
2 Hard drive HDD0 8 Hard drive HDD6
3 Hard drive HDD1 9 Hard drive HDD7
4 Hard drive HDD2 10 USB port 2
5 Hard drive HDD3 11 USB port 3
6 Hard drive HDD4
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide
Sun SPARC Enterprise T5140 and T5240 Servers Getting Started Guide (DC)
Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
14 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 26
Slide Rail Assembly Notes for Both Servers
The rackmounting kit has two slide rail assemblies. A slide rail assembly can be installed on either the right or left side of the rack.
Note – The slide rail assemblies are different for the T5140 and T5240 servers. The
removable mounting bracket of the Sun SPARC Enterprise T5140 rail slides 13 in. (33 cm) out of the slide rail, then locks in place. The removable mounting bracket of the Sun SPARC Enterprise T5240 rails slide 14 in. (35.5 cm) before locking.
Each slide rail assembly consists of a three-section slide rail and a removable mounting bracket.
FIGURE: Sections of the Slide Rail Assembly on the Sun SPARC Enterprise T5240 Server
Figure Legend
1 Mounting bracket 3 Middle section
2 Front section 4 Rear section
Preparing for Installation 15
Page 27
The front, middle, and rear sections form the slide rail. The middle and rear sections
have holes for mounting screws, and adjust to fit rack depths from 24 in. (61 cm) to 36.5 in. (93 cm). The front section can be extended to allow movement of the server out of the rack.
The removable mounting bracket slides 14 in. (35.5 cm) out of the slide rail, then
locks in place. If you unlock the mounting bracket at this point, it slides an additional 12 in. (30 cm) before separating from the slide rail. You can then mount the mounting bracket to the right or left side of the server chassis.
There are a total of five locks in a slide rail assembly. Four are on the mounting
bracket. One lock is on the front section of the slide rail. “Installing the Servers in
a Rack” on page 19 describes the uses of these locks.
16 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 28
FIGURE: Locating the Locks on the Slide Rail Assembly for the Sun SPARC Enterprise
T5240 Server
Preparing for Installation 17
Page 29
Related Information
“Cable Management Notes for Both Servers” on page 18
“Installing the Servers in a Rack” on page 19
Cable Management Notes for Both Servers
The same cable management arm (CMA) is included with the rackmounting kit for each server. The CMA clips onto the slide rails. Use the velcro straps to secure cabling to the CMA.
FIGURE: Cable Management Arm for Both Servers
Related Information
“Managing Cables With the CMA” on page 39
18 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 30
Installing the Sun SPARC Enterprise T5140 and T5240 Servers
This chapter provides instructions for installing the servers into an equipment rack.
Note – If your rackmounting kit came with its own instructions, use the instructions
in your rackmounting kit instead of the instructions in this chapter. After performing the server installation, proceed to “Powering On the System” on page 41 for first-time power on.
Note – References to left and right are from your viewpoint as you face either the
front or rear of the equipment.
This chapter contains the following sections:
“Installing the Servers in a Rack” on page 19
“Installing the Cable Management Arm for Both Servers” on page 28
“Connecting the Server Cables for Both Servers” on page 34
“Managing Cables With the CMA” on page 39
Installing the Servers in a Rack
Note – Ensure that you have all of the parts in the rackmounting kit before you
begin the installation of the server.
Each slide rail assembly consists of two parts, a slide rail and a removable mounting bracket. The slide rail attaches to the rack posts. The mounting bracket attaches to the server chassis.
19
Page 31
Note – The rackmounting kit is the same for both 1U and 2U servers. It contains two
slide rail assemblies, which can be installed on either the right or left side of the rack.
“Install the Slide Rail Assemblies” on page 20
“Insert and Lock the Server in the Rack” on page 26
Install the Slide Rail Assemblies
1. Pull both mounting brackets completely out of their respective slide rails.
a. Simultaneously press and hold the upper and lower lock buttons of the slide
rail lock.
FIGURE: Unlocking the Slide Rail Assembly (Either Server)
b. Pull the mounting bracket out until it locks in the extended position.
c. Slide the mounting bracket release button, then slide the mounting bracket
out of the slide rail.
20 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 32
FIGURE: Location of the Mounting Bracket Release Button (Either Server)
d. Press the metal lever (labeled Push) on the middle section of the sliding rail,
then push the middle section back into the rack.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 21
Page 33
FIGURE: Unlocking the Slide Rail Middle Section (Either Server)
2. Attach a mounting bracket to the right side of the chassis.
a. Position the mounting bracket against the chassis. Ensure that the slide rail
lock is at the front and the three keyed openings on the mounting bracket are aligned with the three locating pins on the side of the chassis.
22 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 34
FIGURE: Attaching a Mounting Bracket to the Chassis (Either Server)
b. Ensure that the heads of the locating pins protrude though the keyed
openings in the mounting bracket. Pull the mounting bracket toward the front of the chassis until the bracket locks into place with an audible click.
c. Verify that all locating pins are trapped in the keyed openings and that the
correct locating pin has engaged the mounting bracket lock.
3. Attach the second mounting bracket to the left side of the chassis.
4. Determine which rack hole numbers to use when attaching the slide rails to the rack posts.
If the server is two rack units high (2U), the slide rails occupy the lower half of the 2U space.
5. Determine which screws you will use to mount the slide rails.
If your rack has threaded mounting holes in the rack posts, determine whether
the threads are metric or standard. Select the appropriate screws from the package included in the mounting kit.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 23
Page 35
If your rack does not have threaded mounting holes, the mounting screws are
secured with a caged nut.
6. Attach a slide rail to the right front rack post.
a. Loosely attach the front of a slide rail to the right front rack post using two
screws.
Note – Do not tighten the screws yet.
FIGURE: Mounting a Slide Rail (Either Server)
b. Adjust the length of the slide rail by sliding the rear mounting flange to
reach the outside edge of the rear rack post.
c. Loosely attach the rear of the slide rail to the rear rack post with two screws.
7. Attach the second slide rail to the left rack posts in a similar manner.
Do not tighten the screws.
8. Use the slide rail spacing tool to adjust the distance between the slide rails.
24 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 36
a. At the front of the rack, plug the left side of the tool into slots at the end of
the left rail.
FIGURE: Using the Slide Rail Spacing Tool to Adjust the Distance Between the Slide Rails
(Either Server)
b. Insert the right side of the tool into the front end of the right rail.
c. Slide the end of the rail to the right or left as needed to allow the ends of the
tool to enter the ends of both rails.
The distance between the rails is now equal to the width of the server with mounting brackets.
d. Tighten the screws to lock the ends of the rails in place.
e. At the rear of the rack, repeat Step a through Step d for the rear ends of the
rails.
Related Information
“Insert and Lock the Server in the Rack” on page 26
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 25
Page 37
Insert and Lock the Server in the Rack
1. Deploy the antitilt bar, if the chassis or rack is so equipped.
Caution – The weight of the servers on extended slide rails can be enough to
overturn an equipment rack.
Caution – The 2U server weighs approximately 55 lb (25 kg). Two people are
required to lift and mount the server into a rack enclosure when using the procedures in this chapter.
2. Insert the ends of the mounting brackets into the sliding rails.
FIGURE: Mounting the Chassis on the Slide Rails (Either Server)
26 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 38
3. Slide the chassis into the rack.
Caution – Before continuing, verify that the server is securely mounted in the rack,
and that the slide rails are locked to the mounting brackets.
Related Information
“Installing the Cable Management Arm for Both Servers” on page 28
Installing the Cable Management Arm for Both Servers
The rackmounting kit for each server comes with the same cable management arm (CMA) assembly. The CMA installation and cable management procedures are the same for both servers.
Note – The CMA includes velcro straps to secure the cables inside the CMA. Do not
install the velcro straps until you install the CMA, connect the cables, and place the cabling inside the CMA as described in the following procedures.
“Install the Cable Management Arm” on page 28
“Verify the Operation of the Slide Rails and the CMA” on page 32
Install the Cable Management Arm
Caution – Support the CMA during this installation. Do not allow the assembly to
hang by its own weight until it is secured by all three attachment points.
1. Remove the tape from the CMA rail extension (on the left of the CMA) and remove the CMA rail extension.
2. Attach the CMA rail extension to rear left slide rail.
At the rear of the rack, plug the CMA rail extension into the end of the left sliding rail assembly. The tab at the front of the rail extension clicks into place. The right sides of the two CMA arms have hinged extensions. On the manufacturer’s instruction sheet, the smaller extension is called the CMA Connector for Inner
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 27
Page 39
Member. This extension attaches to the right mounting bracket. The larger extension is called the CMA Connector for Outer Member, and attaches to the right sliding rail.
FIGURE: Inserting the CMA Rail Extension Into the Rear of the Left Slide Rail (Either
Server)
3. Insert the smaller extension into the clip located at the end of the mounting bracket.
Slide the smaller extension into the square hole on the middle-in-width of the clip that is located at the end of the mounting bracket.
28 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 40
FIGURE: Mounting the Inner CMA Connector (Either Server)
4. Insert the larger extension into the end of the right sliding rail.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 29
Page 41
FIGURE: Attaching the Outer CMA Connector (Either Server)
5. Insert the hinged plastic connector at the left side of the CMA fully into the CMA rail extension.
The plastic tab on the CMA rail extension locks the hinged plastic connector in place.
30 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 42
FIGURE: Mounting the Left Side of the Slide Rail (Either Server)
Related Information
“Verify the Operation of the Slide Rails and the CMA” on page 32
Verify the Operation of the Slide Rails and the
CMA
Tip – Two people are needed for this procedure, one to move the server in and out
of the rack, and one to observe the cables and CMA.
1. For a free-standing rack, deploy the antitilt bar.
2. Unlock the slide lock button s at the right and left sides of the chassis.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 31
Page 43
3. Slowly pull the server out of the rack until the slide rails reach their stops.
FIGURE: Unlocking the Slide Rail Assembly (Either Server)
4. Inspect any attached cables for binding or kinks.
5. Verify that the CMA extends fully and does not bind in the slide rails.
6. Verify that the server extends fully and locks in the maintenance position.
The server should stop after approximately 15 inches (40 cm) of travel.
7. Pull both slide rail release buttons toward you simultaneously and slide the server back into the rack.
The server should slide smoothly into the rack without binding.
32 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 44
FIGURE: Rail Mounting Bracket Release Button (Either Server)
8. Verify that the CMA retracted without binding.
9. Adjust the cable straps and CMA as required to secure the cables.
Related Information
“Managing Cables With the CMA” on page 39
Connecting the Server Cables for Both Servers
To boot the server, you must connect and configure the network and serial ports. The procedures are given in the following sections.
The servers also have serial and USB ports available for connections to optional device.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 33
Page 45
Note – When you are finished connecting the cables to the server, ensure that the
server can slide smoothly in and out of the rack without binding or damaging the cables.
“Connect the Service Processor Serial Management Port” on page 35
“Connect the Service Processor Network Management Port” on page 36
“Connect the Ethernet Network Cables” on page 37
“AC Power Cable Notes” on page 38
Related Information
“Verify the Operation of the Slide Rails and the CMA” on page 32
Connect the Service Processor Serial
Management Port
The service processor serial management port is marked SER MGT. This port is the farthest left RJ-45 port on the rear panel.
Note – The cable and DB-9 RJ-45 adapters are for the host serial port, and not for the
server SER MGT port.
Use this port for server management. This port is needed to set up the service processor network management port, as detailed in “Enable the Service Processor
Network Management Port” on page 47.
34 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 46
Note – Use the service processor serial management port only for server
management. It is the default connection between the service processor and a terminal or a computer.
Caution – Do not attach a modem to this port.
Connect a Category 5 cable from the SER MGT serial management port to the
terminal device.
When connecting either a DB-9 or a DB-25 cable, use an adapter to perform the crossovers given for each connector.
Related Information
“Enable the Service Processor Network Management Port” on page 47
“Connect the Service Processor Network Management Port” on page 36
“Connect the Ethernet Network Cables” on page 37
Connect the Service Processor Network
Management Port
The service processor network management port is labeled NET MGT. This port is located just to the right of the serial management (SER MGT) port on the rear panel.
Note – If you have access to a DHCP server on the network, you can see the service
processor get an IP address because the DHCP client is enabled by default.
Note – The service processor network management port is configured by default to
retrieve network settings with Dynamic Host Configuration Protocol (DHCP) and allow connections using Solaris Secure Shell (SSH). You might need to modify these settings for your network. Instructions are given in “Configure the Service Processor
Network Management Port” on page 50.
Note – This port is not operational until you configure the network settings (through
the serial management port), as detailed in “Configure the Service Processor
Network Management Port” on page 50.
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 35
Page 47
Connect a Category 5 cable from the NET MGT network management port to
your network switch or hub.
FIGURE: Service Processor Network Management Port – Rear Panel
Related Information
“Connect the Service Processor Serial Management Port” on page 35
“Connect the Ethernet Network Cables” on page 37
Connect the Ethernet Network Cables
1. Connect a Category 5 cable from your network switch or hub to Ethernet Port 0 (NET0) on the rear of the chassis.
NET0 is the farthest left port in the 4-port network cluster.
2. Connect Category 5 cables from your network switch or hub to the remaining Ethernet ports (NET1, NET2, NET3), as needed.
36 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 48
FIGURE: Service Processor Ethernet Network Ports – Rear Panel
Related Information
“Connect the Service Processor Serial Management Port” on page 35
“Connect the Service Processor Network Management Port” on page 36
AC Power Cable Notes
Powering on the system for the first time requires special preparation and procedures. For example, if you have not prepared a display before connecting the AC power cable, system messages might be lost.
Caution – Finish the hardware procedures in this chapter, but do not attach the AC
power cable yet.
Caution – The server goes into Standby mode and the service processor initializes as
soon as the AC power cable is connected to the power source.
Related Information
“Powering On the System for the First Time” on page 41
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 37
Page 49
Managing Cables With the CMA
Managing the cables with the CMA is the same for both servers.
“Secure the Server Cables in the CMA” on page 39
“Dismounting the Servers” on page 40
Secure the Server Cables in the CMA
1. Once the server cables are connected and placed inside the CMA, open the velcro cable straps and wrap the straps around the CMA securing the cables inside the CMA.
FIGURE: Securing the Server Cables With the CMA and Velcro Straps (Either Server)
Caution – Verify the operation of the slide rails and CMA, and cable service loops.
2. Perform the steps in the following procedure again before continuing: “Verify
the Operation of the Slide Rails and the CMA” on page 32.
38 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 50
Related Information
“Dismounting the Servers” on page 40
Dismounting the Servers
To install or replace internal parts in the server, you must first remove the server from the rack.
Related Information
“Secure the Server Cables in the CMA” on page 39
Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
Installing the Sun SPARC Enterprise T5140 and T5240 Servers 39
Page 51
40 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 52
Powering On the System
This chapter includes instructions for booting the servers and for enabling the service processor network management port.
This chapter contains the following topics:
“Powering On the System for the First Time” on page 41
“Enable the Service Processor Network Management Port” on page 47
“Logging Into the Service Processor” on page 49
“Using the Service Processor for Common Operations” on page 54
“Booting the Solaris Operating System” on page 58
“Verifying System Functionality” on page 62
Powering On the System for the First Time
This section provides an overview and instructions for powering on your system the first time.
“ILOM System Console” on page 42
“ILOM Service Processor” on page 42
“Power On the System for the First Time” on page 43
Related Information
“Enable the Service Processor Network Management Port” on page 47
“Verifying System Functionality” on page 62
41
Page 53
ILOM System Console
When you power on the system, the boot process begins under the control of the Integrated Lights Out Manager (ILOM) system console. The system console displays status and error messages generated by firmware-based tests during system startup.
Note – To see these status and error messages, connect a terminal or terminal
emulator to the serial management port (SER MGT). For a basic procedure to connect a terminal or terminal emulator, see “Power On the System for the First Time” on
page 43.
For a more detailed discussion on configuring the system console and connecting terminals, refer to the Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide.
Related Information
“ILOM Service Processor” on page 42
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
ILOM Service Processor
After the system console finishes its low-level system diagnostics, the ILOM service processor initializes and runs a higher level of diagnostics. When you access the ILOM service processor using a device connected to the serial management port, you see the output of the ILOM diagnostics.
By default, the service processor configures the network management port automatically, retrieving network configuration settings using the Dynamic Host Configuration Protocol (DHCP) and allowing connections using Secure Shell (SSH).
Note – If you are unable to use DHCP on your network, you must connect to the
ILOM service processor using the serial management port to configure the network management port for your network.
Related Information
“Power On the System for the First Time” on page 43
“Configure the Service Processor Network Management Port” on page 50
42 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 54
Power On the System for the First Time
1. Confirm that you have completed all of the preparations for installation.
See the instructions in “Preparing for Installation” on page 1.
2. Confirm that you have completed the installation of the server in its rack.
See the instructions in “Installing the Servers in a Rack” on page 19.
3. Connect a terminal or a terminal emulator (PC or workstation) to the service
processor serial management port (FIGURE: Server Connections on page 44).
Configure the terminal or terminal emulator with these settings:
9600 baud
8 bits
No parity
1 Stop bit
No handshake
A null modem configuration is needed, meaning the transmit and receive signals are reversed (crossed over) for DTE to DTE communications. You can use the supplied RJ-45 crossover adapters with a standard RJ-45 cable to achieve the null modem configuration.
Note – When you power on the server for the first time and you do not have a
terminal or terminal emulator (PC or workstation) connected to the service processor serial management port, you will not see system messages.
4. (Optional) Connect an Ethernet cable between the server’s NET MGT port and the network to which future connections to the SP and host will be made.
After the initial configuration of the system using the SP SER MGT port, communication with the SP and host is usually performed through this Ethernet interface.
Powering On the System 43
Page 55
FIGURE: Server Connections
Figure Legend
1 Power cables 5 RJ-45 to DB-25 crossover adapter
2 Ethernet cables 6 RJ-45 to DB-9 crossover adapter
3 Service processor to ethernet 7 Terminal device
4 NET MGT to network (optional)
5. Connect an Ethernet cable between one of the server’s NET ports and the network to which the server will communicate.
6. Determine the input power installation instructions you need, based on the model or your server (AC or DC input power):
AC input power models–Continue to the next step.
DC input power models–See “Assembling and Installing DC Power Cables for
the Sun SPARC Enterprise T5140 Server” on page 81.
7. Plug the power cords into the power supplies and into a power source.
44 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 56
Note – Only one power connection is required for operation. Use two power
connections for redundancy.
The service processor runs on the 3.3V standby voltage. As soon as AC power is connected to the system, the service processor powers on, runs diagnostics, and initializes the ILOM firmware.
After a few minutes, the SP login prompt appears on the terminal device. The host is not initialized or powered on yet.
8. At the terminal device, log in to the SP as root with a password of changeme.
XXXXXXXXXXXXXXXX login: root Password: changeme . . .
->
After a brief delay, the SP prompt is displayed (->). At this point, there are many commands you can perform using the Integrated Lights Out Manager interface.
Additional SP information, such as how to change the password and how to set up the SP network parameters is available in the online documentation set.
9. Power on the server and redirect the host output to display on the serial terminal device:
-> start /SYS Are you sure you want to start /SYS (y/n)? y
-> start /SP/console Are you sure you want to start /SP/CONSOLE (y/n)? y Serial console started. To stop, type #. . . .
After you start the SP console, the server initialization takes approximately 20 minutes to complete.
Powering On the System 45
Page 57
10. When prompted, follow the onscreen instructions for configuring the Solaris Operating System on your host and enter the following configuration information.
You will be prompted to confirm the configuration several times, enabling confirmation and changes. If you are not sure how to respond to a particular value, you can accept the default, and make future changes when the Solaris OS is running.
Parameter Description
Language Select a number from the displayed language list.
Locale Select a number from the displayed locale list.
Terminal Type Select a terminal type that corresponds with your terminal device.
Network? Select Yes.
Multiple Network Interfaces
DHCP? Select Yes or No according to your network environment.
Host Name Enter the host name for the server.
IP Address Enter the IP address for this Ethernet interface.
Subnet? Select Yes or No according to your network environment.
Subnet Netmask (If subnet was Yes) Enter the netmask for the subnet for your network
IPv6? Specify whether or not to use IPv6. If you are not sure, select No to configure the
Security Policy Select either standard UNIX security (No) or Kerberos Security (Yes). If you are not
Confirm Review the onscreen information and change it if needed. Otherwise, continue.
Name Service Select the name service according to your network environment.
NFSv4 Domain Name Select the type of domain name configuration according to your environment. If
Select the network interfaces that you plan to configure. If you are not sure, select the first one in the list.
environment.
Ethernet interface for IPv4.
sure, select No.
Note–If you select a name service other than None, you will be prompted for additional name service configuration information.
you are not sure, select Use the NFSv4 domain derived by the system.
Time Zone (Continent) Select your continent.
Time Zone (Country or Region)
46 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Select your country or region.
Page 58
Time Zone Select the time zone.
Date and Time Accept the default date and time or change the values.
root Password Enter the root password twice. This password is for the superuser account for the
Solaris OS on this server. This password is not the SP password.
11. Log in to the server and explore its capabilities.
There are many commands you can use to verify the functionality of the system. The following list describes a few of them:
showrev – Displays the hostname and system architecture information. Use
the -a option with this command to see the patches that are installed.
psrinfo – Displays information about the number and status of the processors
and cores in the host.
prtdiag – Displays system configuration and diagnostic information.
Review the Solaris OS man pages and documentation for more details.
Related Information
“Enable the Service Processor Network Management Port” on page 47
Solaris Documentation
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide.
Enable the Service Processor Network Management Port
The service processor network management port is not operational unless your network employs DHCP, in which case the configuration in automatic. If your network uses DHCP, you can run this command to view your server’s network configuration information:
-> show /SP/network
For example,
-> show /SP/network
/SP/network Targets:
Powering On the System 47
Page 59
Properties: commitpending = (Cannot show property) dhcp_server_ip = 10.8.31.5 ipaddress = 10.8.31.188 ipdiscovery = dhcp ipgateway = 10.8.31.248 ipnetmask = 255.255.252.0 macaddress = 00:14:4F:7E:83:4F pendingipaddress = 10.8.31.188 pendingipdiscovery = dhcp pendingipgateway = 10.8.31.248 pendingipnetmask = 255.255.252.0 state = enabled
Commands: cd set show
If your network does not use DHCP, the network management port is not operational until you configure network settings for the service processor. Configure the service processor in this order:
1. After the service processor boots, access the ILOM CLI through the serial management port. See “Log Into the Service Processor Using the Serial
Management Port” on page 49.
2. Configure the service processor. See “Configure the Service Processor Network
Management Port” on page 50.
3. Commit the changes to the service processor parameters. See Step 3 in “Configure
the Service Processor Network Management Port” on page 50.
You can now use the network management port at any time to access the service processor.
Related Information
“Logging Into the Service Processor” on page 49
48 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 60
Logging Into the Service Processor
If you are powering on the system for the first time after installation, use the service processor serial port to power on the system and run POST. See “Log Into the Service
Processor Using the Serial Management Port” on page 49.
If the network management port has already been configured, you can use it instead of the serial management port.
This section contains the following topics:
“Log Into the Service Processor Using the Serial Management Port” on page 49
“Configure the Service Processor Network Management Port” on page 50
“Log Into the Service Processor Using the Network Management Port” on page 53
Log Into the Service Processor Using the Serial
Management Port
After the service processor boots, access the ILOM CLI to configure and manage the system. The ILOM CLI prompt (->) is displayed at the first time the service processor is booted. The default configuration provides an ILOM CLI root user account. The default root password is changeme. Change the password using the service processor ILOM CLI password command.
1. If this is the first time the system has been powered on, use the password command to change the root password.
... Starting OpenBSD Secure Shell server: sshd. Starting Servicetags listener: stlistener. Starting FRU update program: frutool.
hostname login: root Password: changeme
Copyright 2007 Sun Microsystems, Inc. All rights reserved. Use is subject to license terms. ... Federal Acquisitions: Commercial Software -- Government Users Subject to Standard License Terms and Conditions. ...
Warning: password is set to factory default.
Powering On the System 49
Page 61
-> set /SP/users/root password
Enter new password: ******** Enter new password again: ********
->
Note – After the root password has been set, on subsequent reboots, the ILOM CLI
login prompt is displayed.
2. Enter root for the login name followed by your password.
... hostname login: root Password: password (nothing displayed) Waiting for daemons to initialize...
Daemons ready
Integrated Lights Out Manager
Version 3.0.0.0
Copyright 2009 Sun Microsystems, Inc. All rights reserved. Use is subject to license terms.
->
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Configure the Service Processor Network
Management Port
Note – If your network allows the use of DHCP, this configuration is performed
automatically the first time you boot the system.
Use this procedure only when:
You are unable to use DHCP on your network.
You need to modify the ILOM service processor network management port
settings.
50 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 62
In this procedure, you connect to the ILOM service processor using the serial management port to manually reconfigure the network management port.
Note – For more information on configuring ILOM, refer to the Integrated Lights Out
Manager Supplement for Sun SPARC Enterprise T5140 and T5240 Servers.
Set these network parameters according to the specific details of your network configuration:
/SP/network state – Specifies whether the service processor is on the network
or not
/SP/network pendingipaddress – IP address of the service processor
/SP/network pendingipgateway – IP address of the gateway for the subnet
/SP/network pendingipnetmask – Netmask for the service processor subnet
/SP/network pendingipdiscovery - Specifies whether the service processor
uses DHCP or static IP address assignment
/SP/network commitpending - Commits the service processor to use the
pending settings
Configure these parameters with the set command. The usage is as follows:
set target property=value where /SP/network is the target and pendingipaddress=xxx.xxx.xxx.xxx, for example, is the property=value.
1. Configure the service processor using information from your network administrator.
Your choices are:
dhcp - Set up the network connection with a dynamically created IP
configuration.
static - Set up the network connection with a static IP configuration.
a. If you choose to use a dynamically created IP address (use DHCP to retrieve
the network setting), set pendingipdiscovery to dhcp.
-> set /SP/network pendingipdiscovery=dhcp Set 'pendingipdiscovery' to 'dhcp'
b. If you choose to configure a static IP configuration, set the parameters
pendingipdiscovery, pendingipaddress, pendingipgateway, and pendingipnetmask as follows.
i. Set the service processor to accept a static IP address.
-> set /SP/network pendingipdiscovery=static Set 'pendingipdiscovery' to 'static'
Powering On the System 51
Page 63
ii. Set the IP address for the service processor.
-> set /SP/network pendingipaddress=service-processor-IPaddr Set 'pendingipaddress' to 'service-processor-IPaddr'
iii. Set the IP address for the service processor gateway.
-> set /SP/network pendingipgateway=gateway-IPaddr
Set 'pendingipgateway' to 'gateway-IPaddr'
iv. Set the netmask for the service processor.
-> set /SP/network pendingipnetmask=255.255.255.0
Set 'pendingipnetmask' to '255.255.255.0'
This example uses 255.255.255.0 to set the netmask. Your network environment subnet might require a different netmask. Use a netmask number most appropriate to your environment.
2. Use the show /SP/network command to verify that the parameters were set correctly.
For example:
-> show /SP/network /SP/network Targets: Properties: commitpending = (Cannot show property) dhcp_server_ip = xxx.xxx.xxx.xxx ipaddress = xxx.xxx.xxx.xxx ipdiscovery = dhcp ipgateway = xxx.xxx.xxx.xxx ipnetmask = 255.255.252.0 macaddress = 00:14:4F:3F:8C:AF pendingipaddress = xxx.xxx.xxx.xxx pendingipdiscovery = static pendingipgateway = xxx.xxx.xxx.xxx pendingipnetmask = 255.255.255.0 state = enabled Commands: cd set show
->
52 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 64
Note – After setting the configuration parameters, you must enter the set
/SP/network commitpending=true command for the new values to take affect.
3. Commit the changes to the service processor network parameters.
-> set /SP/network commitpending=true
Set 'commitpending' to 'true'
Note – You can type the show /SP/network command again (after performing the
set /SP/network commitpending=true command) to verify that the
parameters have been updated.
Related Information
“Configure the Service Processor Network Management Port” on page 50
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Log Into the Service Processor Using the
Network Management Port
Note – You must configure the service processor parameters shown in “Configure
the Service Processor Network Management Port” on page 50 before you can use the
network management port.
Open an SSH session and connect to the service processor by specifying its
network address.
% ssh root@xx.xxx.xx.x ... Are you sure you want to continue connecting (yes/no)? yes ... Password: password (nothing displayed) Waiting for daemons to initialize...
Daemons ready
Integrated Lights Out Manager
Version 3.0.0.0
Powering On the System 53
Page 65
Copyright 2009 Sun Microsystems, Inc. All rights reserved. Use is subject to license terms.
->
Related Information
“Perform a Normal System Initialization” on page 54
Using the Service Processor for Common Operations
The following topics are described in this section:
“Perform a Normal System Initialization” on page 54
“Examine the System for Faults” on page 55
“Devices in the OpenBoot Device Tree” on page 57
Perform a Normal System Initialization
1. Type the start /SYS command.
-> start /SYS
Are you sure you want to start /SYS (y/n)? y Starting /SYS
2. To monitor the power on sequence, type the start /SP/console command.
You will see an ILOM CLI alert message on the system console. This message indicates that the system has reset.
-> start /SP/console
Are you sure you want to start /SP/console (y/n)? y Serial console started. To stop, type #.
The CPU and memory controllers initialize, and eventually OpenBoot initializes. After a number of system console messages, the ok prompt appears, or the system will boot into the Solaris OS.
54 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 66
Note – System behavior (such as whether the system halts at the ok prompt or boots
to the Solaris OS) depends on how the auto-boot variable is set. See the Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide for more information.
The following example output is a small section of the complete output.
0:1:0> 0:1:0>SPARC-Enterprise[TM] T5140/T5240 POST 4.27.x. 2007/12/11 18:55
...
0:1:0>Network Interface Unit Tests....Done
0:1:0>Functional CPU Tests....Done
0:1:0>Extended Memory Tests....Done
2007-12-14 16:45:28.800 0:1:0>INFO: 2007-12-14 16:45:28.806 0:1:0> POST Passed all devices. 2007-12-14 16:45:28.816 0:1:0>POST: Return to VBSC. 2007-12-14 16:45:28.824 0:1:0>Master set ACK for vbsc runpost command and spin...
SPARC Enterprise T5240, No Keyboard Copyright 2007 Sun Microsystems, Inc. All rights reserved. OpenBoot 4.27.x, 3968 MB memory available, Serial #74409918. Ethernet address 0:14:4f:6f:67:be, Host ID: 846f67be.
{0} ok
Related Information
“Examine the System for Faults” on page 55
Integrated Lights Out Manager (ILOM) Supplement for SPARC Enterprise T5140 and
T5240 Servers
Integrated Lights Out Manager (ILOM)
Documentation (http://docs.sun.com/app/docs/prod/int.lights.mgr
)
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Examine the System for Faults
1. Perform the following steps to verify that there are no faults:
Powering On the System 55
Page 67
a. Set the virtual keyswitch to diag mode so that POST will run in Service
mode.
-> set /SYS keyswitch_state=diag Set ’keyswitch_state’ to ’diag’
b. To initiate the power on sequence, type the start /SYS command.
You will see an ILOM CLI alert message on the system console. This message indicates that the system has reset.
-> start /SYS
Are you sure you want to start /SYS (y/n)? y Starting /SYS
->
c. Switch to the system console to view POST output.
-> start /SP/console Are you sure you want to start /SP/console (y/n)? y Serial console started. To stop, type #. . . .
Watch the POST output for possible fault messages. The following output is a sign that POST did not detect any faults. The message indicating successful passage of POST is indicated in bold.
. . . 2007-12-14 16:34:53.385 0:1:0>INFO: 2007-12-14 16:34:53.391 0:1:0> POST Passed all devices. 2007-12-14 16:34:53.399 0:1:0>POST: Return to VBSC. 2007-12-14 16:34:53.406 0:1:0>Master set ACK for vbsc runpost command and spin. ... SPARC Enterprise T5240, No Keyboard Copyright 2007 Sun Microsystems, Inc. All rights reserved. OpenBoot 4.27.x, 3968 MB memory available, Serial #74409918. Ethernet address 0:14:4f:6f:67:be, Host ID: 846f67be.
{8} ok
56 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 68
2. Type the console escape sequence (by default #. (Hash-Period)) to return to the ILOM prompt.
3. Check the POST execution result with the following command:
-> show /SP/faultmgmt -level all
Note – Depending on the configuration of ILOM, POST variables, and whether
POST detected faults or not, the server might boot, or the system might remain at the ok prompt. If the system is at the ok prompt, type boot.
4. Use the set /SYS keyswitch_state=normal command to return the virtual keyswitch to Normal mode (default) so that the system can power on and start the boot process.
-> set /SYS keyswitch_state=normal Set ’keyswitch_state’ to ’normal’
Related Information
Integrated Lights Out Manager (ILOM) Documentation
Integrated Lights Out Manager Supplement for SPARC Enterprise T5140 and T5240
Servers
Integrated Lights Out Manager (ILOM) 3.0 Supplement for SPARC Enterprise T5140
and T5240 Servers
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Devices in the OpenBoot Device Tree
To understand the various devices and their path names as represented in the OpenBoot device tree, refer to the tables below.
TABLE: Disk Slot Numbers, Logical Device Names, and Physical Device Names
Disk Slot Number Logical Device Name
Slot 0 c1t0d0 /devices/pci@0/pci@0/pci@2/scsi@0/sd@0,0
Slot 1 c1t1d0 /devices/pci@0/pci@0/pci@2/scsi@0/sd@1,0
Slot 2 c1t2d0 /devices/pci@0/pci@0/pci@2/scsi@0/sd@2,0
Slot 3 c1t3d0 /devices/pci@0/pci@0/pci@2/scsi@0/sd@3,0
* The logical device names might appear differently on your system, depending on the number and type of add-on disk controllers in-
stalled.
*
Physical Device Name
Powering On the System 57
Page 69
TABLE: Device Identifiers and Devices
Device Identifiers Devices
/SYS/MB/CMPcpu_number/Pstrand_number CMP (0-1) CPU strand (0-63)
/SYS/MB/CMPn/RISERn/PCIEslot_number CMP (0-1) Riser (0-1) PCIe slot
(0-5)
/SYS/MB/CMPn/RISERn/XAUIcard_number CMP (0-1) Riser (0-1) XAUI card
(0-1)
/SYS/MB/NETnetwork_number Network interfaces (0-3)
/SYS/MB/PCIE PCIe root complex
/SYS/MB/USBnumber USB ports (0-1, located on rear
of chassis)
/SYS/MB/CMPn/L2_BANKnumber CMP (0-1) Bank (0-7)
/SYS/DVD DVD
/SYS/USBBD/USBnumber USB ports (2-3, located on front
of chassis)
/SYS/TTYA DB9 Serial Port
/SYS/MB/CMPn/MRn/BR/branch_number/CHchannel_number/Ddimm_number CMP (0-1) Riser (0-1) Branch
(0-1) Channel (0-1) DIMM (0-3)
Related Information
“Booting the Solaris Operating System” on page 58
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Booting the Solaris Operating System
The Solaris OS is preinstalled on the servers on the disk in slot 0. The Solaris OS is not configured (that is, the sys-unconfig command was run in the factory). If you boot the system from this disk, you will be prompted to configure the Solaris OS for your environment.
“Boot the Solaris Operating System” on page 59
“Avoid Booting the Solaris Operating System at Startup” on page 59
“Reset the System” on page 60
“Power Cycle the System” on page 60
58 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 70
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Boot the Solaris Operating System
1. At the ok prompt, boot from the disk that contains the Solaris OS.
If you need to determine which disk to boot from, type the show-disks command at the ok prompt to see the path to the configured disks, similar to the following:
ok show-disks a) /pci@0/pci@0/pci@2/scsi@0/disk b) /pci@0/pci@0/pci@1/pci@0/pci@1/pci@0/usb@0,2/storage@2/disk q) NO SELECTION Enter Selection, q to quit: q ok
2. Type the boot command at the ok prompt.
Use the value from Step 1 to construct the boot command. You must append the target to the disk path.
In the following example, the server is booted from disk 0 (zero) on a Sun SPARC Enterprise T5140 server.
ok boot disk0
Boot device: /pci@0/pci@0/pci@2/scsi@0/disk@0 File and args: SunOS Release 5.10 Version Generic_127127-03 64-bit Copyright 1983-2007 Sun Microsystems, Inc. All rights reserved. Use is subject to license terms. Hostname: hostname NIS domain name is x.x.x.x
hostname console login:
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Avoid Booting the Solaris Operating System at
Startup
In hard drive HDD0, the Solaris OS is preinstalled.
Powering On the System 59
Page 71
If you do not want to start the preinstalled OS, set the Open Boot PROM
parameter auto-boot? to false. For example:
-> set /HOST/bootmode script="setenv auto-boot? false"
Related Information
“Reset the System” on page 60
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Reset the System
If it is necessary to reset the system, use the shutdown -g0 -i6 -y command.
# shutdown -g0 -i6 -y
It is not necessary to power the system off and on to simply reset the system.
Related Information
“Power Cycle the System” on page 60
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Power Cycle the System
If a simple reset does not clear a system problem, you can power the system off and on with this procedure.
1. Shut down the Solaris OS.
At the Solaris OS prompt, type the shutdown -g0 -i0 -y command. Then type h when prompted to halt the Solaris OS and to return to the ok prompt.
# shutdown -g0 -i0 -y # svc.startd: The system is coming down. Please wait. svc.startd: 91 system services are now being stopped. Jun 12 19:46:57 wgs40-58 syslogd: going down on signal 15 svc.startd: The system is down. syncing file systems... done Program terminated r)eboot, o)k prompt, h)alt?
60 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 72
2. Switch from the system console prompt to the service processor console prompt using the console escape sequence (by default, #. (Pound-Period)).
ok #.
->
3. Using the ILOM CLI, type the stop /SYS command to perform a graceful shutdown of the system.
-> stop /SYS
Are you sure you want to stop /SYS (y/n)? y Stopping /SYS
->
Note – To perform an immediate and ungraceful shutdown, use the stop -force
-script /SYS or stop -script /SYS commands. These commands stop
everything immediately. Ensure that all data is saved before entering these commands.
4. Type the start /SYS command.
-> start /SYS
Are you sure you want to start /SYS (y/n)? y Starting /SYS
->
Note – To force a power-on sequence, use the start -script /SYS command.
5. Reconnect to the system console with the start /SP/console command.
-> start /SP/console
Are you sure you want to start /SP/console (y/n)? y Serial console started. To stop, type #.
The systems displays various messages, followed by the ok prompt.
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide
Solaris Documentation
Powering On the System 61
Page 73
Verifying System Functionality
After powering on the system for the first time, you can use the Sun Validation Test Suite (SunVTS) software to verify the functionality and performance of any installed components, as well as its network connections.
Related Information
SunVTS Documentation
62 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 74
Updating the Firmware
This section provides instructions for updating SP firmware.
flashupdate command” on page 63
“Update the Firmware” on page 64
flashupdate command
The flashupdate command updates both the service processor firmware and the server firmware.
The flash image consists of the following components:
Service processor firmware
OpenBoot firmware
POST
Reset/config
Sequencer
Partition description
Related Information
“Update the Firmware” on page 64
63
Page 75
Update the Firmware
1. Ensure that the ILOM service processor network management port is configured.
This configuration is required to access the new flash image over the network. See
“Configure the Service Processor Network Management Port” on page 50.
2. Open an SSH session to connect to the service processor.
% ssh root@xx.xxx.xx.x ... Are you sure you want to continue connecting (yes/no)? yes ... Password: password (nothing is displayed) Waiting for daemons to initialize...
Daemons ready
Integrated Lights Out Manager
Version 2.0.4.x
Copyright 2008 Sun Microsystems, Inc. All rights reserved. Use is subject to license terms.
->
3. Verify that the host is powered off.
If the host is not powered off, type the stop /SYS command.
-> stop /SYS
4. Verify that the keyswitch_state parameter is set to normal.
-> set /SYS keyswitch_state=normal
5. Type the load command.
The load command updates the service processor flash image and the host firmware. The load command requires the following information:
IP address of a TFTP server on the network that can access the flash image
64 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 76
Full path name to the flash image that the IP address can access
The command usage is as follows:
load [-script] -source tftp://xxx.xxx.xx.xx/pathname
where:
-script – Does not prompt for confirmation and acts as if yes was specified
-source – Specifies the IP address and full path name (URL) to the flash image
-> load -source tftp://xxx.xxx.xx.xx/pathname NOTE: A firmware upgrade will cause the server and ILOM to be reset. It is recommended that a clean shutdown of the server be done prior to the upgrade procedure. An upgrade takes about 6 minutes to complete. ILOM will enter a special mode to load new firmware. No other tasks can be performed in ILOM until the firmware upgrade is complete and ILOM is reset.
Are you sure you want to load the specified file (y/n)? y Do you want to preserve the configuration (y/n)? y
...............................................................
Firmware update is complete. ILOM will now be restarted with the new firmware. Update complete. Reset device to use new image.
->
After the flash image has been updated, the system will automatically reset. The service processor resets, runs diagnostics, and returns to the login prompt (on
the serial console), similar to the example below.
U-Boot 1.1.1 (May 23 2007 - 21:30:12) ... POST cpu PASSED POST ethernet PASSED Hit any key to stop autoboot: 0 ## Booting image at fe080000 ...
IP Protocols: ICMP, UDP, TCP, IGMP
Checking all file systems... fsck 1.37 (21-Mar-2005) Setting kernel variables ... ... done. Mounting local filesystems... Cleaning /tmp /var/run /var/lock.
Updating the Firmware 65
Page 77
Identifying DOC Device Type(G3/G4/H3) ... OK
Configuring network interfaces...Internet Systems Consortium DHCP Client V3.0.1 Copyright 2007 Internet Systems Consortium. All rights reserved. For info, please visit http://www.isc.org/products/DHCP
eth0: config: auto-negotiation on, 100FDX, 100HDX, 10FDX, 10HDX. Listening on LPF/eth0/00:14:4f:3f:8c:af Sending on LPF/eth0/00:14:4f:3f:8c:af Sending on Socket/fallback DHCPDISCOVER on eth0 to 255.255.255.255 port 67 interval 6 eth0: link up, 100 Mbps Full Duplex, auto-negotiation complete. DHCPDISCOVER on eth0 to 255.255.255.255 port 67 interval 15 Hostname: hostname. Starting portmap daemon: portmap. Initializing random number generator...done. INIT: Entering runlevel: 3 Starting system log daemon: syslogd and klogd. Starting periodic command scheduler: cron.
Starting IPMI Stack...... Done.
Starting OpenBSD Secure Shell server: sshd. Starting Servicetags listener: stlistener. Starting FRU update program: frutool.
hostname login:
Related Information
“Configure the Service Processor Network Management Port” on page 50
66 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 78
Selecting a Boot Device
This section provides instructions on selecting a boot device.
“Boot Device Selection Overview” on page 67
“Select a Boot Device” on page 68
Boot Device Selection Overview
The boot device is specified by the setting of an OpenBoot configuration variable called boot-device. The default setting of this variable is disk net. Because of this setting, the firmware first attempts to boot from the system hard drive, and if that fails, from the on-board NET0 Gigabit Ethernet interface.
This procedure assumes that you are familiar with the OpenBoot firmware and that you know how to enter the OpenBoot environment. For more information, see the Sun SPARC Enterprise T5140 and T5240 Servers Administration Guide.
Note – The serial management port on the ILOM card is preconfigured as the default
system console port. For more information, see the Sun SPARC Enterprise T5140 and T5240 Servers Overview.
If you want to boot from a network, you must connect the network interface to the network.
Related Information
“Select a Boot Device” on page 68
Sun SPARC Enterprise T5140 and T5240 Servers Overview
67
Page 79
Select a Boot Device
At the ok prompt, type:
ok setenv boot-device device-specifier
where the device-specifier is one of the following:
cdrom – Specifies the DVD drive
disk – Specifies the system boot disk (internal disk 0 by default)
disk0 – Specifies internal drive 0
disk1 – Specifies internal drive 1
disk2 – Specifies internal drive 2
disk3 – Specifies internal drive 3
net, net0, net1, net2, net3 – Specifies the network interfaces
full path name – Specifies the device or network interface by its full path name
Note – The Solaris OS modifies the boot-device variable to its full path name, not
the alias name. If you choose a nondefault boot-device variable, the Solaris OS specifies the full device path of the boot device.
Note – You can specify the name of the program to be booted as well as the way the
boot program operates. For more information, refer to the OpenBoot Command Reference Manual for your specific Solaris OS release.
If you want to specify a network interface other than an on-board Ethernet interface as the default boot device, you can determine the full path name of each interface by typing either of the following commands:
ok show-devs ok show-nets
The show-devs command lists the system devices and displays the full path name of each PCI device.
Related Information
OpenBoot Documentation
OpenBoot Command Reference Manual
68 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 80
Installing the Servers With the Express Rail Rackmounting Kit
This chapter provides instructions for installing the servers in an equipment rack with express (snap-in) rails.
“Slide Rail Assembly Notes for the Express Rail Rackmounting Kit” on page 69
“Install the Slide Rail Assemblies” on page 72
“Insert and Lock the Server in the Rack” on page 77
“Dismounting the Server” on page 79
Slide Rail Assembly Notes for the Express Rail Rackmounting Kit
The express rail rackmounting kit installs quickly, and does not require mounting screws or nuts. The kit and the installation procedures are the same for both the Sun SPARC Enterprise T5140 and T5240 servers.
Note – The illustrations used to support the procedure description show a 2U server
as an example.
Note – References to left and right are from your viewpoint as you face either the
front or the rear of the system.
Note – If your rackmounting kit came with its own instructions, use the instructions
in your rackmounting kit instead of the instructions in this section. After performing the server installation, proceed to “Powering On the System” on page 41 for first-time power on.
69
Page 81
The express rail rackmounting kit has two slide rail assemblies. A slide rail assembly can be installed on either the right or left side of the rack.
Each slide rail assembly consists of a three-section slide rail and a removable mounting bracket.
FIGURE: Sections of the Express Rail Slide Rail Assembly
Figure Legend
1 Mounting bracket
2 Front section
3 Middle section
4 Rear section
The front, middle, and rear sections form the slide rail. The middle and rear sections
have holes for mounting and adjust to fit rack depths from 24 in. (61 cm) to 36.5 in. (93 cm). The front section can be extended to allow movement of the server out of the rack.
The removable mounting bracket slides 14.5 in. (37 cm) out of the slide rail, then
locks in place. If you unlock the mounting bracket at this point, it slides an additional 14.5 in. (37 cm) before separating from the slide rail. You can then mount the mounting bracket to the right or left side of the server chassis.
There are six locks in a slide rail assembly. Four are on the mounting bracket. Two
locks are on the slide rail.
70 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 82
FIGURE: Locating the Locks on the Slide Rail Assembly for the Sun SPARC Enterprise
T5240 Server
Related Information
“Install the Slide Rail Assemblies” on page 72
“Insert and Lock the Server in the Rack” on page 77
Installing the Servers With the Express Rail Rackmounting Kit 71
Page 83
Install the Slide Rail Assemblies
Note – Ensure that you have all of the parts in the rackmounting kit before you
begin the installation of the server.
The rackmounting kit contains two slide rail assemblies, which can be installed on either the right or left side of the rack.
A slide rail assembly consists of two parts, a slide rail and a removable mounting bracket. The slide rail attaches to the rack posts. The mounting bracket attaches to the server chassis.
1. Pull both mounting brackets completely out of their respective slide rails.
a. Simultaneously press and hold the upper and lower lock buttons of the slide
rail lock.
FIGURE: Unlocking the Express Rail Slide Rail Assembly
b. Pull the mounting bracket out until it stops.
72 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 84
c. Slide the mounting bracket release button to the left; then slide the mounting
bracket completely out of the slide rail.
FIGURE: Express Rail Mounting Bracket Release Button
2. Attach a mounting bracket to the right side of the server chassis.
a. Position the mounting bracket against the chassis. Ensure that the slide rail
lock is at the front and the keyed openings on the mounting bracket are aligned with the locating pins on the side of the chassis.
Installing the Servers With the Express Rail Rackmounting Kit 73
Page 85
FIGURE: Attaching an Express Rail Mounting Bracket to the Chassis
b. Ensure that the heads of the four locating pins protrude through the keyed
openings in the mounting bracket. Slide the mounting bracket toward the front of the chassis until the bracket locks into place with an audible click.
c. Verify that all four locating pins are trapped in the keyed openings and that
the third from the front locating pin has engaged the mounting bracket lock.
3. Attach the second mounting bracket to the left side of the server chassis.
4. Orient slide rails, ensuring that the ball bearing tracks (labeled FRONT) are forward.
74 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 86
FIGURE: Express Rail Slide Rails Orientation for Installation
5. Extend the slide rails (outer section) to fit the rack and attach the slide rails to the rack.
You hear an audible click when the rails securely attach to the rack.
Installing the Servers With the Express Rail Rackmounting Kit 75
Page 87
FIGURE: Attaching Express Slide Rails to the Rack
Caution – Deploy the antitilt feature on the rack before continuing the installation.
Related Information
“Insert and Lock the Server in the Rack” on page 77
76 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 88
Insert and Lock the Server in the Rack
1. Deploy the antitilt feature, if the rack is so equipped.
Caution – The weight of the servers on extended slide rails can be enough to
overturn an equipment rack.
Caution – The 2U server weighs approximately 55 lb (25 kg). Two people are
required to lift and mount the server into a rack enclosure when using the procedures in this chapter.
2. Insert the ends of the mounting brackets into the sliding rails.
3. Slide the server approximately halfway into the chassis.
FIGURE: Inserting Express Rail Mounting Brackets Into the Slide Rails
Installing the Servers With the Express Rail Rackmounting Kit 77
Page 89
4. Slide the green release tab.
5. Push the server all the way into the rack until it locks into place.
FIGURE: Sliding the Express Rail Release Tab and Securing the Server in the Rack
Caution – Before continuing, verify that the server is securely mounted in the rack,
and that the slide rails are locked in the mounting brackets.
Dismounting the Server
Caution – To prevent damage to your server, do not move the rack while the server
is mounted.
78 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 90
To install or replace internal parts in the server, you must first remove the server from the rack.
Related Information
Sun SPARC Enterprise T5140 and T5240 Servers Service Manual
Installing the Servers With the Express Rail Rackmounting Kit 79
Page 91
80 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 92
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server
This section provides the following DC input power information for the Sun SPARC Enterprise T5140 server:
“Requirements for Servers With DC Input Power” on page 81
“DC Supply and Ground Conductor Requirements” on page 82
“Overcurrent Protection Requirements” on page 83
“Assembling and Installing the DC Input Power Cables” on page 83
Related Information
“Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5240
Server” on page 93
Requirements for Servers With DC Input Power
The following restrictions apply to the Sun SPARC Enterprise T5140 server with DC input power:
The DC version of the server must be installed in a restricted-access location.
According to the intent of the National Electrical Code, a restricted-access location is an area intended for qualified or trained personnel only and has access controlled by a locking mechanism, such as a key lock or an access card system.
The server must not be directly connected to a centralized DC mains.
81
Page 93
Related Information
“DC Supply and Ground Conductor Requirements” on page 82
DC Supply and Ground Conductor Requirements
The server must meet the following:
Suitable conductor material: Use copper conductors only
Power supply connections through the input connector: 12 AWG (between the
server and the source). There are three conductors:
-48V or -60V (negative terminal)
Chassis ground connection
-48V or -60V Return (positive terminal)
System ground conductor: 12 AWG (to be connected to the chassis)
Cable insulation rating: Minimum of 75˚C (167˚F), low smoke fume (LSF), flame
retardant
Provide a Wago Type 721-103/037-000 mating connector for proper connection to
the DC connectors supplied with the server (Wago Type 721)
Branch circuit cable insulation color: According to applicable National Electrical
Codes
Grounding cable insulation color: Green/yellow
DC power source must meet TNV-2 requirements as defined by UL 60950-1 and
IEC 60950-1
Note – Depending on the DC power source, the -48V or -60V (negative terminal)
might be marked with a minus (-) symbol. The -48V or -60V Return (positive terminal) might be marked with a positive (+) symbol.
When attaching DC cables, keep the following caution in mind:
Caution – You must restrict the connection of the server to the DC power source to
minimize the possibility that transient energy will appear on the main input to the equipment. The DC battery power source must be in the same premises as the server. The server cannot be in one building with the power source in another building.
82 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 94
Related Information
“Overcurrent Protection Requirements” on page 83
Overcurrent Protection Requirements
The following protections against excessive current loads must be satisfied before servers that use DC input power can be installed:
Overcurrent protection devices must be provided as part of each equipment rack.
Circuit breakers must be located between the DC power source and the server. Use
one 20A fast-trip, double-pole, DC-rated circuit breaker for each power supply unit.
Note – Overcurrent protection devices must meet applicable national and local
electrical safety codes and be approved for the intended application.
Related Information
“Assembling and Installing the DC Input Power Cables” on page 83
Assembling and Installing the DC Input Power Cables
These topics explain how to assemble and install DC input power cables.
“Assemble the DC Input Power Cable” on page 83
“Install the Strain Relief Housings” on page 89
“Connect the DC Input Power Cords to the Server” on page 91
Assemble the DC Input Power Cable
The following procedure describes how to assemble the DC input power cables for Oracle’s Sun SPARC Enterprise T5140 server.
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server 83
Page 95
Assemble one cable for each DC power supply in your server.
Before you begin the installation procedure, verify that the required conditions described in the following table have been satisfied.
Prerequisite Condition Responsible Party
Install a DC power source that meets the server’s input power specifications.
Secure DC power cables that meet the server’s power cabling specifications.
Attach the DC input plug to the DC input power cables. The input plug is provided in the server’s shipping kit.
Customer
Customer
Customer
1. Turn off power from the DC power source using the circuit breakers.
Caution – Do not proceed with these instructions until you have turned off the
power from the DC power source through the circuit breakers.
2. Identify the parts that you will use to assemble the DC input power cables
For each cable, you need the items shown in. These items are provided in the shipping kit that came with your server.
84 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 96
FIGURE: DC Connection Parts
Figure Legend
1 Strain relief housing
2 DC input plug
3 Cage clamp operating lever
3. Locate the three wires coming from the DC power source that will be used in the connection to your unit:
-48V or -60V (negative terminal)
Chassis ground
-48V or -60V Return (positive terminal)
Note – Depending on the DC power source, the -48V or -60V (negative terminal)
might be marked with a minus (-) symbol. The -48V or -60V Return (positive terminal) might be marked with a positive (+) symbol.
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server 85
Page 97
4. Strip 5/16 in. (8 mm) of insulation from each of the wires coming from the DC power source.
Do not strip more than 5/16 in. (8 mm) from each wire. Doing so leaves uninsulated wire exposed from the DC connector after the assembly is complete.
FIGURE: Stripping the Insulation From the Wire
Figure Legend
1 5/16 in. (8 mm)
5. Open the cage clamp for this section of the DC input plug by taking one of the following actions:
Insert the tip of the cage clamp operating lever into the rectangular hole
directly above the hole in the DC input plug where you want to insert the first wire. Press down on the cage clamp operating lever.
Insert a small slotted screwdriver into the rectangular hole directly above the
hole in the DC input plug where you want to insert the first wire, and push in to open the cage clamp.
86 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 98
FIGURE: Opening the DC Input Plug Cage Clamp Using the Cage Clamp Operating
Lever
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server 87
Page 99
FIGURE: Opening the Cage Clamp Using a Screwdriver
6. Feed the exposed section of the appropriate wire into the round hole in the DC input plug.
FIGURE: Connector Wiring Assignments
Figure Legend
1 Top of connector 3 From chassis ground (green/yellow)
2 From -48V or -60V Return 4 From -48V or -60V
Note – If you need to remove a wire from the DC input plug, insert the cage clamp
operating lever or a small screwdriver as and pull the wire from the DC input plug.
7. Release the lever or remove the tool to secure the wire into the connector.
88 Sun SPARC Enterprise T5140 and T5240 Servers Installation Guide • December 2010
Page 100
8. Repeat the procedures for the other two wires to complete the assembly of the DC input power cable.
9. Repeat this procedure to create as many DC input power cables as you need for your unit.
Related Information
“Install the Strain Relief Housings” on page 89
Install the Strain Relief Housings
1. Insert the bottom portion of the strain relief housing into the notch on the DC input plug until it snaps into place.
Ensure that the strain relief housing snaps into place on the DC input plug. You cannot complete the assembly correctly if the strain relief housing is not snapped into place.
FIGURE: Inserting the Bottom Portion of the Strain Relief Housing
2. Route the three wires coming from the DC power source through the opening at the bottom end of the strain relief housing.
Assembling and Installing DC Power Cables for the Sun SPARC Enterprise T5140 Server 89