Flat Pak I/O Modules
Features
Industry-standard plug-in modules
4000 VAC optical isolation
Input modules handle both AC and DC inputs
AC output module has zero voltage turn-on, zero
current turn-off
UL and CSA recognized; RoHS lead-free; CE low voltage
and EMC
Flat Pak I/O Modules
Flat Pak I/O Modules
Description
Flat Pak I/O modules include AC and DC input and output
modules. All are industry-standard, plug-in modules with 4000
volts of optical isolation between the field side and the logic
side, and all are recognized by UL and CSA.
Because of their low profile, Flat Pak modules are ideal for
user-designed printed circuit boards where the standard
single-channel or Quad Pak modules do not provide an exact
fit.
AC/DC Input Modules
Flat Pak input modules handle either alternating current (AC)
or direct current (DC). These modules are used for sensing
ON/OFF voltage levels. All Flat Pak input modules are designed
with filtering on the input and a hysteresis amplifier for high
noise rejection and transient free “clean” switching. Each
module provides up to 4000 V of optical isolation between
field inputs and the logic side of the circuit.
Typical uses and applications include sensing the presence or
absence of voltage from sources such as:
Proximity switches
Limit switches
Selector switches
Push-button and toggle switches
Thermostats
Photoelectric switches
TTL-compatible devices
AC Output Module
The OAC5P Flat Pak output module is used for controlling or
switching AC loads. It is equivalent to a single-pole, singlethrow, normally open contact (FORM A, SPST-NO, Make). The
OAC5P features zero voltage turn-on and zero current turn-off.
Typical uses and applications for the OAC5P include switching
the following loads:
Relays
Solenoids and contactors
Motor starters
Heaters
Lamps or indicators
DC Output Module
The ODC5P Flat Pak output module is used for controlling or
switching DC loads. Typical uses and applications for the
ODC5P include switching the following loads:
DC relays
DC solenoids
DC motor starters
DC lamps or indicators
Part Numbers
Part Description
IAC5P Flat Pak input module, 90–140 VAC/VDC
IDC5P
OAC5P Flat Pak output module, 12–140 VAC
ODC5P Flat Pak output module, 5–60 VDC
Flat Pak input module, 10–32 VDC or
12–32 VAC
DATA SHEET
Form 1364-110914
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organ izations.
PAG E
1

Flat Pak I/O Modules
Specifications—AC/DC Input Modules
IAC5P IDC5P
Input Voltage Range 90–140 VAC or VDC 10–32 VDC or 12–32 VAC
Input Current at Maximum Line 11 mA 25 mA
Turn-on Time 20 ms 5 ms
Turn-off Time 20 ms 5 ms
Input Allowed for No Output 3 mA, 45 V 1 mA, 3 V
Logic Supply Voltage, Nominal 5 VDC 5 VDC
Logic Supply Voltage Range 4.5–6.0 VDC 4.5–6.0 VDC
Logic Supply Current at Nominal Logic Voltage 12 mA 12 mA
Input Resistance (R1 in Schematic Diagram) 14,000 Ohms 1500 Ohms
Control Resistance (Rc in Schematic Diagram 220 Ohms 220 Ohms
Optical Isolation, Input-to-output 4000 Vrms 4000 Vrms
Output Voltage Drop 0.4 V @ 50 mA 0.4 V @ 50 mA
Output Current 50 mA 50 mA
Output Leakage with No Input 100 µA maximum @ 30 VDC 100 µA maximum @ 30 VDC
Flat Pak I/O Modules
Operating Temperature –30 to 70 °C –30 to 70 °C
Agency Approvals
Warranty Lifetime Lifetime
UL (E58169), CSA (35852),
RoHS, CE
UL (E58169), CSA (35852),
RoHS, CE
DATA SHEET
PAG E
2
Form 1364-110914
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to chang e. Brand or product names used herein are trademarks or register ed trademarks of their respective companies or organizations.

Flat Pak I/O Modules
Specifications—AC and DC Output Modules
OAC5P ODC5P
Operating Voltage Range 12–140 VAC 5–60 VDC
Line Voltage, Nominal 120 VAC n/a
Current Rating
Off-state Leakage at Maximum Voltage 5 mA, rms 1 mA
Logic Voltage, Nominal 5 VDC 5 VDC
Logic Voltage Range (Vcc) 2.5–8 VDC 2.5–8 VDC
Logic Pickup Voltage 2.55 VDC 2.5 VDC
Logic Dropout Voltage 1 VDC 1 VDC
Logic Input Current at Normal Logic Voltage
(Iout in Schematic Diagram)
Control Resistance (Rc in Schematic Diagram) 220 Ohms 220 Ohms
One-second Surge n/a 5 A
One-cycle Surge 80 A peak n/a
Peak Repetitive Voltage 500 V n/a
Minimum Load Current 20 mA n/a
Operating Frequency 25–65 Hz n/a
Turn-on Time 1/2 cycle maximum, zero voltage 100 microseconds
Turn-off Time 1/2 cycle maximum, zero current 750 microseconds
DV/DT, Off-state 200 V/microsecond n/a
DV/DT, Commutating Snubbed for rated 0.5 power factor load n/a
Output Voltage Drop Maximum Peak 1.6 V 1.6 V
Operating Temperature –30 to 70 °C –30 to 70 °C
Agency Approvals UL (E58169), CSA (35852) UL (E58169), CSA (35852)
Warranty Lifetime Lifetime
3 A @ 45 °C ambient
2 A @ 70 °C ambient
12 mA 12 mA
3 A @ 45 °C ambient
2 A @ 70 °C ambient
Flat Pak I/O Modules
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organ izations.
Form 1364-110914
PAG E
3
DATA SHEET

Schematic—Input Modules
AC/DC Inputs (IAC5P and IDC5P)
Flat Pak I/O Modules
Flat Pak I/O Modules
DATA SHEET
PAG E
4
Form 1364-110914
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to chang e. Brand or product names used herein are trademarks or register ed trademarks of their respective companies or organizations.

Flat Pak I/O Modules
AC Output (OAC5P)
DC Output (ODC5P)
Schematics—Output Modules
Flat Pak I/O Modules
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organ izations.
DATA SHEET
Form 1364-110914
PAG E
5

Dimensional Drawing—All Flat Pak Modules
Flat Pak I/O Modules
Flat Pak I/O Modules
DATA SHEET
PAG E
6
Form 1364-110914
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to chang e. Brand or product names used herein are trademarks or register ed trademarks of their respective companies or organizations.

More About Opto 22
Products
Opto 22 develops and manufactures reliable, flexible, easy-touse hardware and software products for industrial automation,
energy management, remote monitoring, and data
acquisition applications.
OptoEMU Energy Management System
The easy-to-use OptoEMU Sensor monitors electrical energy
use in your facility and delivers detailed, real-time data you
can see and analyze. The Sensor can monitor energy data from
pulsing meters, electrical panels or subpanels, and equipment.
View energy data online using a software service or
incorporate the data into your control system for complete
energy management.
SNAP PAC System
Designed to simplify the typically
complex process of selecting and
applying an automation system, the
SNAP PAC System consists of four
integrated components:
SNAP PAC controllers
PAC Proj e ct
SNAP PAC brains
SNAP I/O
SNAP PAC Controllers
Programmable automation controllers (PACs) are
multifunctional, modular controllers based on open standards.
Opto 22 has been manufacturing PACs for over two decades.
The standalone SNAP PAC S-series and the rack-mounted
SNAP PAC R-series both handle a wide range of digital, analog,
and serial functions for data collection, remote monitoring,
process control, and discrete and hybrid manufacturing.
SNAP PACs are based on open Ethernet and Internet Protocol
(IP) standards, so you can build or extend a system easily,
without the expense and limitations of proprietary networks
and protocols.
PAC P roj e c t Softwa re Su i t e
Opto 22’s PAC Project Software Suite provides full-featured,
cost-effective control programming, HMI (human machine
interface) development and runtime, OPC server, and
database connectivity software for your SNAP PAC System.
Control programming includes both easy-to-learn flowcharts
and optional scripting. Commands are in plain English;
variables and I/O point names are fully descriptive.
PAC Project Basic offers control and HMI tools and is free for
download on our website, PAC Project
Professional, available for separate purchase, adds
™
Software Suite
™
OptoOPCServer, OptoDataLink, options for controller
redundancy or segmented networking, and support for legacy
Opto 22 serial
SNAP PAC Brains
While SNAP PAC controllers provide central control and data
distribution, SNAP PAC brains provide distributed intelligence
for I/O processing and communications. Brains offer analog,
digital, and serial functions, including thermocouple
linearization; PID loop control; and optional high-speed digital
counting (up to 20 kHz), quadrature counting, TPO, and pulse
generation and measurement.
SNAP I/O
I/O provides the local connection to sensors and equipment.
Opto 22 SNAP I/O offers 1 to 32 points of reliable I/O per
module, depending on the type of module and your needs.
Analog, digital, and serial modules are all mixed on the
same mounting rack and controlled by the same processor
(SNAP PAC brain or rack-mounted controller).
mistic
™
I/O units.
Quality
Founded in 1974, Opto 22 has established a
worldwide reputation for high-quality products. All
are made in the U.S.A. at our manufacturing
facility in Temecula, California. Because we do
no statistical testing and each part is tested
twice before leaving our factory, we can
guarantee most solid-state relays and optically
isolated I/O modules for life.
comprehensiv
staff of support engineers represents decades of training and
experience. Support is
Additional support is always available on our website: how-to
videos, OptoKnowledgeBase, self-training guide,
troubleshooting and user’s guides, and OptoForums.
In addition, hands-on training is available for free at our
or 951-695-3000, or visit our website at
e technical support for Opto 22 products. Our
contac
t Opto 22 headquarters at
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Form 1335-110907