Opto 22 G4AD5, G4AD8, G4AD17, G4AD18, G4AD19 Data Sheet

...
I/O MODULES
ANALOG INPUT
G4
DAT A SHEET
Form 422-050809
Description
Thermocouple analog modules provide a single channel of transformer and optically- isolated temperature-to-digital conversion. The modules offer wide nominal input range and special over/under range capabilities. The modules also include complete electrical channel-to-channel isolation that eliminates troublesome ground loop problems. Modules plug into an Opto 22 Modular controller or an analog I/O brick and are secured by a captive screw. The field connections are made through four contacts to the terminal strip located on the brick base or Modular Controller I/O board.
NOTE: Any system using analog sensors and input modules should be calibrated annually for analog signals. To do so, use OptoControl commands “Calculate and Set Analog Offset” and “Calculate and Set Analog Gain.”
page 1/3
Part
Numbers
G4AD5 Type "J" Thermocouple Input
G4AD8 Type "K" Thermocouple Input
G4AD17 Type "R" Thermocouple Input
G4AD18 Type "T" Thermocouple Input
G4AD19 Type "E" Thermocouple Input
G4AD23 Type "S" Thermocouple Input
G4AD24 Type "B" Thermocouple Input
Description
Features
Rugged packaging
4000 Vrms Transient Isolation
True Differential (Floating) Inputs
12-bit Resolution
Factory-calibrated, no user adjustment necessary
Operating temperature 0° to 70° C
I/O MODULES
ANALOG INPUT
G4
DAT A SHEET
Form 422-050809
Specifications
Module Specification
G4AD5 G4AD8 G4AD17 G4AD18 G4AD19 G4AD23 G4AD24
Thermocouple Type J K R T E S B
Nominal Temperature Range °C 0° to 485° -100° to 460° 0° to 960° -200° to 224° -100° to 435° 0° to 1,034° 42° to 1,491.85°
Nominal Temperature Range °F 32° to 905° -148° to 860° 32° to 1,760° -328° to 435.2° -148° to 815° 32° to 1,893.2° 107.888° to 2,717.33°
Accuracy* ± 1° C ± 1° C ± 2.5° C ± 0.9° C ± 0.9° C ± 2.5° C ± 5° C
Over/Under Range Capability °C -32° to 1,200° -150° to 1,372° -50° to 1,768° -270° to 400° -155° to 1,000° -50° to 1,768° 42° to 1,820°
Over/Under Range Capability °F -25° to 2,192° -238° to 2,501° -58° to 3,214° -454° to 752° -247° to 1,832° -58° to 3,214° 107.9° to 3,308°
Over/Under Range Accuracy ± 2° C ± 2° C ± 5° C ± 1.8° C ± 1.8° C ± 2.5° C ± 5° C
* Accuracy figure requires use of gain and offset commands.
General Specification
Isolation (Transient) Input-to-output Input-to-analog supply
Cold Junction Compensated Yes
Open Thermocouple Detection Yes
Input Response Time 5% of scale change in 8.5 ms
Ambient Temperature Operating Storage
Resolution 12 bits
4,000 Vrms 4,000 Vrms
63% of scale change in 165 ms
0° to 70°C
-25° to 85°C
page 2/3