Opto 22 AD5, AD5T, AD8, AD8T, AD17T Data Sheet

...
Standard Thermocouple Modules
Features
Features
Rugged Packaging
Rugged Packaging
4000 Vrms Transient Isolation
4000 Vrms Transient Isolation
12-bit Resolution
12-bit Resolution
Factory Calibrated, No User Adjustments
Factory Calibrated, No User Adjustments
Operating Temperature: 0 to 70 °C
Operating Temperature: 0 to 70 °C
"T" Models Offer Channel-to-Channel Isolation
"T" Models Offer Channel-to-Channel Isolation
Description
Description
The thermocouple analog modules provide a single channel
The thermocouple analog modules provide a single channel of optically isolated temperature-to-digital conversion. The
of optically isolated temperature-to-digital conversion. The modules offer wide nominal input and special over/under
modules offer wide nominal input and special over/under range capabilities. The 'T' module also includes 4000 Vrms
range capabilities. The 'T' module also includes 4000 Vrms transient channel-to-channel isolation which eliminates any
transient channel-to-channel isolation which eliminates any ground loop problems. Modules plug into a Classic standard
ground loop problems. Modules plug into a Classic standard analog I/O rack and are secured by a captive screw.
analog I/O rack and are secured by a captive screw.
Standard Thermocouple Modules
Part Numbers
Part Description
AD5 J Thermocouple Input AD5T J Thermocouple Input, Isolated AD8 K Thermocouple Input AD8T K Thermocouple Input, Isolated AD17T R Thermocouple Input, Isolated AD18T T Thermocouple Input, Isolated AD19T E Thermocouple Input, Isolated
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
PAG E
1
DATA SHEET
Standard Thermocouple Modules
Specifications
AD5 AD5T AD8 AD8T
Thermocouple Type J J K K Nominal Tempera-
ture Range °C
Nominal Tempera­ture Range °F
Over/Under Range Capability °C
Over/Under Range Capability °F
Average Resolution
Accuracy* ± 3 °C (0 to 700 °C) ± 3 °C (0 to 700 °C) ± 3 °C (-100 to 924 °C) ± 3 °C (-100 to 924 °C) Repeatability ± 1 °C ± 1 °C ± 1 °C ± 1 °C
Power Requirements
*Accuracy may be improved by the use of "Set Offset" and "Set Gain" commands in the OPTOMUX command set.
0° to 700° 0° to 700° -100° to 924° -100° to 924°
32° to 1292° 32° to 1292° -148° to 1695° -148° to 1695°
-20° to 1200° -20° to 1200° -125° to 1250° -125° to 1250°
- 4° to 2192° - 4° to 2192° -193° to 2282° -193° to 2282°
0.18 °C (0 to 700 °C)
0.36 °C (700 to 1200 °C)
17 mA at +15 (+/- 0.25) VDC 12 mA at -15 (+/- 0.25) VDC
0.18 °C (0 to 700 °C)
0.36 °C (700 to 1200 °C)
35 mA at +15 (+/- 0.25) VDC 35 mA at -15 (+/- 0.25) VDC
± 0.25 °C
(-100 to 924 °C)
± 0.5 °C
(924 to 1250 °C)
17 mA at +15 (+/- 0.25) VDC 12 mA at -15 (+/- 0.25) VDC
± 0.25 °C
(-100 to 924 °C)
± 0.5 °C
(924 to 1250 °C)
35 mA at +15 (+/- 0.25) VDC 35 mA at -15 (+/- 0.25) VDC
Standard Thermocouple Modules
DATA SHEET
Form 439-111026
PAG E
2
© 2011 Opto 22. All rights reserved. Dimensions and specifications are subject to chang e. Brand or product names used herein are trademarks or register ed trademarks of their respective companies or organizations.