This product complies with CE 73/23 & 93/68 (low voltage safety) and 89/336 (EMC) , and EMC
standards of Australia and New Zealand (C-Tick) , and the following UPS product standards:
*IEC62040-1-1-General and safety requirements for use in operator access area
*IEC/EN62040-2 EMC requirements CLASS C3
*IEC62040-3 Performance requirements and test methods
警告
危险
WARNING- High earth leakage current
Earth connection is critical before connecting the input supply (include both utility supply and battery).
This equipment must be earthed in accordance with local electrical authority codes of practice.
Earth leakage current exceeds 3.5 mA and is less than 1000 mA.
Transient and steady-state earth leakage currents, which may occur when starting the equipment,
should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers ( RCCBs) must be selected insensitive to DC unidirectional pulses
( class A ) and transient current pulses ( RCCBs).
Note it that the earth leakage currents of the load will also flow across RCCB or RCD.
警告
危险
Components that can be maintained by user
All the equipment maintenance and servicing procedures involving internal access need special tools
and should be carried out only by trained personnel. The components that can only be accessed by
opening the protective cover with tools cannot be maintained by user.
This UPS full complies with “IEC62040-1-1-General and safety requirements for use in operator
access area. UPS dangerous voltages are present within the battery box. However, the risk of
contact with these high voltages is minimized for non-service personnel. Since the component with
dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of
touching high voltage component is minimized. No risk exists to any personnel when operating the
equipment in the normal manner, following the recommended operating procedures in this manual.
警告
危险
Battery Voltage Higher Than 400Vdc
All the battery maintenance and servicing procedures involving internal access need special tools or
keys and should be carried out only by trained personnel.
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED
WITH THIS EQUIPMENT. WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL
VOLTAGE WILL EXCEED 400Vdc AND IS POTENTIALLY LETHAL.
Battery manufacturers supply details of the necessary precautions to be observed when working on,
or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all
times. Particular attention should be paid to the recommendations concerning local environmental
conditions and the provision of protective clothing, first aid and fire-fighting facilities.
Safety Precautions
This manual is about the installation and operation of MD Series modular UPS (Hereinafter referred
to as UPS).
Please carefully read this manual prior to installation.
The UPS must be debugged and maintained by the engineer commissioned by the manufacturer or
the agent. Otherwise, human safety may be endangered and the damage of UPS shall not belong to the
warranty scope.
Appendix A Guidebook to Ordering and Selection of MU System ........................................................ 52
Chapter 1 Installation
警告
危险
Warning-Installation can only be done by authorized engineers
1. Do not apply electrical power to the UPS equipment before the approval of commissioning
engineer.
2. The UPS should be installed by a qualified engineer in accordance with the information contained
in this chapter.
警告
危险
Note: 3-Phase 4-Wire Input Power is required
The standard UPS can be connected to TN, TT and IT AC distribution system (IEC60364-3) of
3-phase 5-wire
警告
危险
WARNING: battery hazards
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED
WITH THIS EQUIPMENT. When connecting the battery, the battery terminal voltage will exceed
400Vdc and is potentially lethal.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Remove rings, watches and all metal objects.
Only use tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a
container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately
with water.
Chapter 1 Installation
This chapter introduces the installation of MD series UPS (hereby referred to as UPS), including
initial checking, sitting, positioning, cabling and installation drawings.
1.1 Introduction
This chapter introduces the relevant requirements for positioning and cabling of the UPS.
As each site has its requirements, this chapter provides step-by-step installation instructions, which
acts as a guide to the general procedures and practices that should be observed by the installing
engineer.
1.2 Initial Checking
Perform the following checking operations prior to the UPS installation.
1. Visually examine if there is any damage inside and outside the UPS rack and battery equipment
due to the transportation. Report any such damage to the shipper immediately.
2. Verify the product label and confirm the correctness of the equipment. The equipment label is
attached on the back of front door. The UPS model, capacity and main parameters are marked on
the label.
4
Chapter 1 Installation
1.3 Positioning
1.3.1 Distribution Room
The UPS is designed for indoor installation, which shall be located in a clean environment with
adequate ventilation to keep the environmental temperature within the required specification. The UPS
uses forced convection cooling by internal fans. Cooling air enters the module through ventilation grills
located at the front part of the cabinet and exhausted through grills located in the rear part of the cabinet.
Please do not block the ventilation holes.
If necessary, a system of extractor fans should be installed to aid cooling-air flow. An air filter should
be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain
airflow.
Note: The UPS should be installed on a cement surface or other surface that is not
combustible.
1.3.2 Battery Room
The battery will generate some amount of hydrogen and oxygen at the end of charging, so the
fresh air volume of the battery installation environment must meet EN50272-2001 requirements. The
ambient temperature of the battery must be stable. Ambient temperature is a major factor in determining
the battery capacity and life. The nominal operating temperature of battery is 20°C. Operating above this
temperature will reduce the battery life, and operation below this temperature will reduce the battery
capacity. If the average operating temperature of battery is increased from 20ºC to 30ºC, then the
service life of the battery will be reduced by 50%. If the operating temperature of the battery is above
40ºC, then the battery service life will be decreased in exponent rate. In a normal installation, the battery
temperature is maintained between 15°C and 25°C. Keep batteries away from heat sources or air
outlets.
If external batteries are to be used, a battery protection device (a DC circuit breaker) must be
mounted as close as possible to the batteries, and the connecting cables should be as short as possible.
1.3.3 Storing
If the equipment is not installed immediately, it must be stored in a room so as to protect it against
excessive humidity and heat sources. The battery needs to be stored in dry and cool place with good
ventilation. The most suitable storage temperature is 20 ºC to 25ºC.
1.4 Disassembly, Initial Checking and Positioning
Check the packaging first upon the arrival of product to see if there is any damage; open the
packaging to check the equipment; report any such damage to the shipper immediately.
1.4.1 System Packaging:
Open the wooden case first, the open method is shown in fig 1-1:
5
Chapter 1 Installation
Fig 1-1 Open method
Firstly, open the top plate of the steel-edged wooden case with slotted awl and plier, followed by
sideboards. Be careful not to scratch the product. See fig 1-2.
Fig 1-2 Disassemble the case
Take out the foam after disassembling the sideboards of the case as shown in fig 1-3.
6
Chapter 1 Installation
Fig 1-3 Complete the disassembly
Tip: Dismantle the bolt that connects the cabinet and wooden pallet after disassembly, then lift the
cabinet to installation position. The dismantlement should be careful so as not to scratch the body.
Verify the product label and confirm the correctness of the equipment. The equipment label is
attached on the back of front door. The UPS model, capacity and main parameters are marked on the
label.
1.4.2 Module Packaging:
The open method is shown in fig 1-4:
The packing case should be placed horizontal and stable;
Fig 1-4 Open method
Cut the plastic packing belt and scotch tape to open the carton, see fig 1-5:
7
Chapter 1 Installation
Carton
Foamed package
Carton
Equipment
Top cover of foamed package
Foamed package
Fig 1-5 Open the carton
Open the foamed cover, the equipment with plastic package can be see as shown in fig 1-6:
At last, take out the equipment with plastic package, and dismantle the packaging materials.
Warm Tips: Please dispose the wasted materials in accordance with environmental
protection requirements after disassembly.
To prolong the service life, the place chosen for the UPS must guarantee:
Easy wiring
Sufficient space for operation
Fig 1-6 Open the foamed cover
8
Chapter 1 Installation
功率模块
旁路模块
开关单元
配电单元
Bypass module
Power module
Distribution
unit
Switch unit
Air sufficient enough to dispel heat produced by UPS
Against ambient corrosive gases
Against excessive humidity and heat sources
Against dust
With the current fire prevention requirements
The operating environment temperature is within 20℃~25℃. The batteries are at maximum
efficiency in this temperature range (for information about the battery storage and transportation as
well as the environment, please refer to table 6-2).
1.4.3 UPS Composition
UPS composition shall refer to fig 1-7; UPS configuration shall refer to table 1-1.
As UPS has no ventilation grills at either sides, no clearances are required for the sides.
To enable routine tightening of power terminations within the cabinet, it is recommended that
clearance around the front and back of the equipment should be sufficient to enable free passage of
personnel with the doors fully opened.
1.4.5 Front and Back Access
The component layout of the UPS supports front and back access for servicing, diagnosing and
repairing the UPS, thus reducing the space requirement for side access.
1.4.6 Final Positioning
When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS
will remain stationary and stable.
1.4.7 Power Module Installation
The installation position of power module and output distribution module are shown in fig 1-8. the
installation principle of these modules is to installed from bottom to top to prevent inclination of the
cabinet due to high center of gravity .
As is shown in fig 1-8, the installation procedure of power module is as follows:
10
Chapter 1 Installation
固定孔
A处放大
固定孔
A处放大
进线通道
进线通道
Power module
Fixing hole
Amplification of A
Cable entrance
Cable entrance
1. Each module shall be installed from bottom to top, the default setting of the system is module No. 1,
2, 3, 4, 5, 6, 7, 8, 9, and 10.
2. Insert the module into installation position, and push in the cabinet. The wiring terminals in between
shall be tight, and excessive force shall be prevented against the damage to inserted pins of the
terminals.
3. Fix the module to the cabinet though the mounting holes on two sides of the front plate of the
module.
Fig 1-8 Power Module Installation Diagram
1.4.8 Cable Entry
Cables can enter the UPS from top and below as shown in fig 1-9. Both the top and bottom of the
UPS have cable entrance.
The recommended installation practice is to install power cables in the entrance channel
at both sides of the cabinet back door, so as not to affect the ventilation.
Fig 1-9 Cable Entry Diagram
11
Chapter 1 Installation
警告
危险
Note
For IT power network system, 4-pole protective device must be installed on the external input
distribution of the UPS.
20 batteries connected in series
1.5 Protective Devices
For safety concerns, it is recommended to install external circuit breakers or other protective devices
for the input AC supply of the UPS system. This section provides generic practical information for
qualified installation engineers. The installation engineers should have the knowledge of the regulatory
wiring standards, and of the equipment to be installed.
1.5.1 Rectifier and Bypass Input Supply of the UPS
Install suitable protective devices in the distribution unit of the incoming mains supply, considering
the power cable current-carrying capacity and overload capacity of the system. Generally, the magnetic
circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the current listed in table 1-2 is
recommended.
If protection against earth faults (RCD devices) is required for the upstream of the input supply, the
installed device should:
Sensitive to DC unidirectional pulses (class A) in the network
Insensitive to transient current pulses
Have an average sensitivity that is adjustable between 0.3A~1A
The RCCB must be sensitive to DC unidirectional pulses (class A) in the network, while insensitive
to transient current pulses, as shown in fig 1-10 respectively.
Fig 1-10 RCCB sign
1.5.2 Battery
A battery unit is composed of 40 batteries connected in series, a centreline is drawn from in
between (the joint part between the 20th and 21st battery), plus the line drawn from the front and back,
there are altogether 3 lines connected with UPS line contact bank. The battery line must push through a
DC circuit breaker before connecting to corresponding UPS line contact bank. The detailed wiring please
refer to fig 1-11 below:
12
Chapter 1 Installation
警告
危险
Warning
Prior to cabling the UPS, confirm the status and positions of the switches of the UPS rectifier input
power supply / bypass power supply and mains power distribution board.
Ensure that these switches are opened and attached with WARNING label so as to prevent
unauthorized operation to these switches.
System Name
MD36/6
MD72/12
MD60/6
MD120/12
Capacity
System
capacity
36kVA
72kVA
60Kva
120kVA
Module
capacity
6kVA
12kVA
6kVA
12kVA
Cabinet
dimension
600*900*1600(W*D*H mm)
600*900*2000(W*D*H mm)
Main
Input
Rated
current A
90
180
150
300
Cable mm2
25
50
50
90
Output
Rated
current A
90
180
150
300
Cable mm2
25
50
50
90
Battery
Rated
current A
133
267
223
445
Cable mm2
35
75
75
120
PE
Cable mm2
16
50
50
50
警告
危险
Warning
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC
SHOCK HAZARD OR RISK OF FIRE.
Fig 1-11 Diagram of batteries connected in series
1.5.3 UPS Output
A main output switch has been installed in UPS, the user shall install the over current protective
device on the bypass of each output of the external distribution cabinet.
1.6 Power Cables
Design the cables according to the descriptions in this section and local regulatory wiring standards,
and the environmental conditions should be taken into consideration. Refer to IEC60950-1 Table 3B.
1.6.1 Maximum stable state current and configuration of cable system
Maximum stable state current and configuration of cable system, please refer to table 1-2.
Table 1-2 Maximum stable state current and configuration of cable system
13
Chapter 1 Installation
警告
危险
Note
The operations described in this section must be performed by authorized electricians or qualified
technical personnel. If you have any difficulties, do not hesitate to contact our Customer Service &
Support department .
警告
危险
Warning-Hazardous battery terminal voltage of 400Vdc
Ensure the correct polarity connection between the battery terminals and the UPS terminals: Positive
terminal to positive terminal, negative terminal to negative terminal, and disconnect one or more than
one cable between every two layers of batteries. Do not connect the cables and close the battery
circuit breakers before getting the approval from the commissioning engineer.
干接点接口
SNMP卡接口
RS485接口
RS232接口
LBS接口
Dry contact
interface
SNMP card port
LBS port
RS232 port
RS485 port
1.6.2 Cable Connection
After the equipment has been finally positioned and secured, connect the power cables as
described in the following procedures:
1. Verify that all the external input distribution switches of the UPS are completely opened and the
UPS internal maintenance bypass switch is opened. Attach necessary warning signs to these
switches to prevent unauthorized operation.
2. Open the back door of the cabinet, remove the cover and then the input and output terminal,
battery terminal and earth terminal are visible.
3. Connect the input earth wire to input earth terminal. Please note: the earth wire shall be connected
in accordance with related local or state regulation
4. For common bypass and rectifier inputs, connect the AC input supply cables to the UPS input
terminals (Main input A-B-C-N), and connect the output loaded cable to the UPS output terminals
(Output A-B-C-N) and tighten the connections to 13 Nm (M8 Bolt). ENSURE CORRECT PHASE
ROTATION.
5. Connect the battery cables between the UPS battery terminals and battery switch. ENSURE
CORRECT PHASE ROTATION.
6. Re-install all the protective covers.
1.7 Control and Communication Cabling
As shown in fig 1-12, the front panel of the bypass module will provide dry contact interface
(J2~J10), communication interface (RS232, 485 and SNMP card interface), as well as LBS interface.
Fig 1-12 Dry contact interface and communication interface
14
Chapter 1 Installation
J2J3
TEMP_BAT
TEMP_ENV
Position
Name
Purpose
J2.1
TEMP_BAT
Battery temperature detection
J2.2
GND
Power ground
J3.1
TEMP_ENV
Environment temperature detection
J3.2
GND
Power ground
Note: Specified temperature sensor is required for temperature detection (R25=5Ohm,
B25/50=3275), please confirm with the manufacturer, or contact local maintenance engineers when
placing an order.
The UPS accepts external signal from zero-voltage (dry) contacts connected through external dry
contact terminals produced and phoenix terminals that are in bypass module. Through software
programming, these signals become active when these contacts connect to +24V to ground).The cables
connected to DRY terminal must be separated from power cables. Moreover, these cables should be
double insulated with a typical 0.5 to 1.5 mm
between 25 and 50 meters.
2
cross-section area for a maximum connection length
1.7.1 Dry Contact Interface of Battery and Environmental Temperature Detection
The input dry contact J2 and J3 can detect the temperature of batteries and environment
respectively, which can be used in environment monitoring and battery temperature compensation 1.
J2 and J3 interfaces diagram are shown in fig 1-13, the description of interface is in table 1-3.
Fig 1-13 Diagram of J2 and J3 dry contact for temperature detecting
Table 1-3 Description of input dry contact interface J2 and J3
1.7.2 Remote EPO Input Port
The UPS has an Emergency Power OFF (EPO) function. This function can be activated by pressing
a button on the control panel of the UPS or through a remote contact provided by the user. The EPO
pushbutton is protected by a hinged plastic cover.
J4 is the input port for remote EPO. It requires shorting NC and +24v during normal operation, and
the EPO is triggered when opening NC and +24v, or shorting NO and +24v. The port diagram is shown in
fig 1-14, and port description is shown in table 1-4.
15
Chapter 1 Installation
J4
EPO_NC
+24V
EPO_NO
+24V
Position
Name
Purpose
J4.1
EPO_NC
EPO is activated when disconnecting fromJ4.2
J4.2
+
24V
+24V, connect the common terminal of NC and NO
J4.3
EPO_NO
EPO is activated when shorting with J4.2
警告
危险
Note
1. The emergency stop action within the UPS will shut down the rectifier, inverter and static bypass.
However, it does not internally disconnect the mains input power supply. To disconnect ALL power to
the UPS, open the upstream input circuit breaker(s) when the EPO is activated.
2. Pin 1 and 2 of J4 have been shorted before the UPS is delivered.
Fig 1-14 Diagram of input port for remote EPO
Table 1-4 Description of input port for remote EPO
The EPO is triggered when shorting pin 2 and 3 or opening pin 2 and 1 of J4.
If an external emergency stop facility is required, it is connected via the reserved terminals of J4.
The external emergency stop facility needs to use shielded cables to connect to the normally
open/closed remote stop switch between these two pins. If this facility is not used, then pin 3 and pin 4 of
J4 must be open, or pin 1 and pin 2 of J4 must be shorted.
1.7.3 Generator Input Dry Contact
J5 is status interface for generator connection. Connect pin 2 of J5 with + 24V power supply, it
indicates that the generator has been connected with the system. The interface diagram is shown in fig
1-15, and interface description is shown in table 1-5.
16
Chapter 1 Installation
J5
GEN
+24V
AUX-N.O.
AUX-N.O.
发电机
Position
Name
Purpose
J5.1
+24V
+24V power supply
J5.2
GEN
Connection status of generator
J5.3
GND
Power ground
BCB_DRV
BCB_CONT
J6
J7
BCB_ONL
+24V
+24V
+24V
Position
Name
Description
J6.1
BCB_DRV
BCB actuating signal, provide the actuating signal of +18V, 20mA
J6.2
BCB_CONT
BCB contact status, connect with the normally open signal of BCB
J7.1
GND
Power ground
J7.2
BCB_ONL
BCB on-line–input (normally open) , BCB is on-line when the signal
is connecting with GND
Generator
Fig 1-15 Diagram of status interface and connection of generator
Table 1-5 Description of maintenance bypass switch and output switch status interface
1.7.4 BCB Input Port
J6 and J7 are the ports of BCB. The port diagram is shown in fig 1-16, and description is shown in
J8 is the output dry contact interface, which outputs the battery warnings of low or excessive
voltage, when the battery voltage is lower than set value, an auxiliary dry contact signal will be
provided via the isolation of a relay. The interface diagram is shown in fig 1-17, and description is
shown in table 1-7.
17
Chapter 1 Installation
J8
BAT_LOW_NC
BAT_LOW_NO
GND
Position
Name
Purpose
J8.1
BAT_LOW_NC
Battery warning relay (normally closed) will be open during warning
J8.2
BAT_LOW_NO
Battery warning relay (normally open) will be closed during warning
J8.3
GND
Center of battery warning relay
J9
ALARM_NC
ALARM_NO
GND
Position
Name
Purpose
J9.1
ALARM_NC
Integrated warning relay (normally closed) will be open during warning
J9.2
ALARM_NO
Integrated warning relay (normally open) will be closed during warning
J9 is the integrated warning output dry contact interface, when one or more than one present
warning is triggered, the system will send an integrated warning information, and provide an auxiliary
dry contact signal via the isolation of a relay. The interface diagram is shown in fig 1-18, and description
is shown in table 1-8.
J10 is the output dry contact interface for mains failure warning, when the mains fails, the system
will send a mains failure warning information, and provide an auxiliary dry contact signal via the isolation
of a relay. The interface diagram is shown in fig 1-19, and description is shown in table 1-9.
18
Chapter 1 Installation
J10
UTI_FAIL_NC
UTI_FAIL_NO
GND
Position
Name
Purpose
J9.1
UTI_FAIL_NC
Mains failure warning relay(normally closed) will be open during
warning
J9.2
UTI_FAIL_NO
Mains failure warning relay (normally open) will be closed during
warning
RS232 and RS485 Port: provide serial data which can be used for commissioning and maintenance
by authorized engineers or maintainers, or can be used for networking or integrated monitoring system in
the service room.
SNMP Card Port: used for field installation of the communication option card(SNMP card).
1.7.9 LBS (Load Bus Synchronizer) Port
The dual bus system (DBS) consists of two independent UPS rack module systems, as shown in fig
1-20. The dual bus system is configured for high availability and is suitable for powering the load with
dual inputs. If the load is single-input load, the static transfer switch and LBS control is recommended to
maintain both UPS outputs synchronized for uninterrupted transfers. Please install the system according
to the installation descriptions for different system configurations.
The dual bus system is supported by UPS, it requires connecting the LBS signal cables of two UPS
when constructing the dual bus system; please refer to relevant chapter for detailed configuration and
installation, and the system software shall be configured as required.
1.8 Installation Drawing
Please refer to fig 1-21, fig 1-22, fig 1-23 and fig 1-24:
Fig 1-20 LBS Connection Diagram
19
Chapter 1 Installation
Fig 1-21 Installation Diagram
20
Chapter 1 Installation
顶视图
Top view
2m cabinet front view
1.6 m cabinet (front view)
Fig 1-22 UPS front view (Unit: mm)
21
Chapter 1 Installation
A
A
2m cabinet
1.6m cabinet
Fig 1-23 UPS back view
22
Chapter 1 Installation
A
A处放大
Amplification of A
Fig 1-24 UPS front view
23
24 Chapter 2 Operations
警告
危险
Warning: Hazardous mains voltage and/or battery voltage present(s)behind the protective cover
The components that can only be accessed by opening the protective cover with tools can not be
operated by user.
Only qualified service personnel are authorized to remove such covers.
Chapter 2 Operations
This chapter introduces the basic knowledge of UPS operations, including working principle,
operation mode, battery management and protection.
2.1 Introduction
UPS provides the critical load (such as communication and data processing equipment) with high
quality uninterruptible AC power. The power from UPS is free from voltage and frequency variations and
disturbances (interruption and spike) experienced at the Mains AC input supply.
This is achieved through high frequency double conversion power pulse width modulation (PWM)
associated with full digital signal processing control (DSP), which features high reliability and
convenience for use.
2.1.1 Principle
As shown in fig 2-1, the AC input mains source is supplied at UPS input and converted into a DC
source. This DC source feeds the inverter that converts the DC source into a clean and input
independent AC source. The battery powers the load through the inverter in case of an AC input mains
power failure. The utility source can also power the load through the static bypass.
When the UPS needs maintenance or repair, the load can be transferred to maintenance bypass
without interruption and the power module and bypass module can be removed for maintenance.
24
Chapter 2 Operations 25
警告
危险
Note
When the UPS is operating in bypass mode or on maintenance bypass, the connected equipment is
not protected from power failures or surges and sags.
Fig 2-1 System principle framework
2.1.2 Bypass Module
The circuit blocks labeled “bypass module” in fig 2-1 contain electronically controlled switching
circuits that enable the critical load to be connected to either the inverter output or to a bypass power
source via the static bypass line. During normal system operation the load is connected to the inverter;
but in the event of a UPS overload or inverter failure, the load is automatically transferred to the static
bypass line.
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the
inverter output and bypass supply must be fully synchronized during normal operating conditions. This is
achieved through the inverter control electronics, which makes the inverter frequency track that of the
static bypass supply, provided that the bypass remains within an acceptable frequency window.
A manually controlled maintenance bypass supply is incorporated into the UPS design. It enables
the critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine
maintenance.
2.2 Operation Mode
The MD UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these
modes:
Normal mode
25
26 Chapter 2 Operations
警告
危险
Warning: Hazard may occur after transferring to maintenance bypass
After UPS being transferred to maintenance bypass, power module and bypass module do not work,
no display on LCD, and input and output terminals as well as N bus are electrically connected.
Battery mode
Auto-Restart mode
Bypass mode
Maintenance mode (manual bypass)
ECO mode
Frequency converters mode
2.2.1 Normal Mode
The UPS inverter power modules continuously supply the critical AC load. The rectifier/charger
derives power from the AC mains input source and supplies DC power to the inverter while
simultaneously FLOAT or BOOST charging its associated backup battery.
2.2.2 Battery Mode
Upon failure of the AC mains input power; the inverter power modules, which obtains power from the
battery, supplies the critical AC load. There is no interruption in power to the critical load upon failure.
After restoration of the AC mains input power, the “Normal Mode” operation will continue automatically
without the necessity of user intervention.
Note: UPS can also be started through battery (charged) mode via battery cold start function upon
failure of the AC mains. Therefore, the battery power can be used independently to improve the
utilization rate of UPS.
2.2.3 Auto-Restart Mode
The battery may become exhausted following an extended AC mains failure. The inverter shuts
down when the battery reaches the End of Discharge voltage (EOD). The UPS may be programmed to
“Auto Recovery after EOD” after a delay time if the AC mains recovers. This mode and any delay time
are programmed by the commissioning engineer.
During the process of delay time, the battery will be charged by UPS to prevent any risks to load
equipment from future mains failure.
2.2.4 Bypass Mode
If the inverter overload capacity is exceeded under normal mode, or if the inverter becomes
unavailable for any reason, the static transfer switch will perform a transfer of the load from the inverter
to the bypass source, with no interruption in power to the critical AC load.
2.2.5 Maintenance Mode
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS
becomes unavailable e.g. during a maintenance procedure.
Note: This manual bypass switch is fitted in all UPS modules. Transfer UPS system to bypass mode
for power supply first, then close maintenance bypass switch Q2, followed by Q1 and Q3.
26
Chapter 2 Operations 27
2.2.6 ECO Mode
If economical (ECO) mode is selected, the double-conversion UPS will stop to work so as to save
energy. During the operation of ECO mode, the load power will be supplied by bypass preferentially.
When bypass power is within the range of normal frequency and voltage, load power will be supplied by
bypass, or the system will transfer to inverter output, followed by load power interruption which extends
within 3/4 of the utility period. E.g. when the frequency is 50Hz, the interruption time will be less than
15ms; when the frequency is 60Hz, the time will be less than 12.5ms.
2.2.7 Frequency Converters Mode
If the frequency converter configuration is used by UPS, it will provide 50Hz or 60Hz stable output
frequency. The range of output frequency is 40Hz~70Hz. Under this mode, static bypass is unavailable,
but battery can be selected according to the actual requirements of battery mode.
2.3 Battery Management
2.3.1 Normal Function
The following functions should be fitted by commissioning engineers with specified software.
1. Constant current boost charging
Current can be set up.
2. Constant voltage boost charging
Voltage of boost charging can be set as required by the type of battery.
For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not
exceed 2.4V / cell.
3. Float charge
Voltage of float charging can be set as required by the type of battery.
For VRLA, float charge voltage should be between 2.2V to 2.3V.
4. Float charge temperature compensation (optional)
A coefficient of temperature compensation can be set as required by the type of battery.
5. End of discharge (EOD) protection
If the battery voltage is lower than the EOD, the battery converter will shut down and the battery is
isolated to avoid further battery discharge. EOD is adjustable from 1.6V to 1.75V per cell (VRLA) or 0.9
to 1.1 V per cell
6. Battery low warning time
It is adjustable between 3 and 60 minutes. The default is 5 minutes.
2.3.2 Advanced Functions (Battery Self-checking and Maintenance)
At periodic intervals, 20% of the rated capacity of the battery will be discharged automatically, and
the actual load must exceed 20% of the rated UPS (KVA) capacity. If the load is less than 20%,
auto-discharge cannot be executed. The periodic interval can be set from 30 to 360 days. The battery
self-test can be disabled.
Conditions—Battery at float charge for at least 5 hours, load equal to 20~100% of rated UPS capacity
Trigger—Manually through the command of “Battery Maintenance Test” in LCD panel or automatically
Battery Self-Test Interval—30-360 days (default setting is battery self-test disabled).
27
Loading...
+ 79 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.