opti-solar GT 3000, GT, GT4000, GT1500, GT2000 Installation And Operation Manual

Solar On-Grid Inverter
GT Series
Installation and Operation Manual
English
Only an electro-skilled person or trained assembly staff can install or open the Inverter.
Before you start…
Thanks for purchasing OPTI-Solar. GT Series Inverter is a highly reliable product due to innovative design and perfect quality control. This manual contains important information of installation, operation and safety reminding of this unit. Be sure to read this manual carefully before enjoying this product. If you encounter any problem during installing or running this unit, please check this manual first before contacting with your local dealer or representative. Most of the problems you encountered will be solved according to the instruction inside.
Thank you for purchasing our product again. Please keep this manual in safe place for later use.
Safety instructions
z Risk of Electric Shock
1. Do not remove the covers. No user serviceable parts inside. Refer service to qualified service personnel.
2. Both AC and DC voltage sources are terminated inside this equipment. Each circuit must be individually disconnected before servicing.
3. When a photovoltaic array is exposed to light, it supplies a DC voltage to this equipment.
4. Risk of electric shock from energy stored in capacitors. Do not remove cover until 3 hours after disconnecting all power sources.
5. This unit is designed to feed power to grid (utility) only, do not connect this unit to AC power supplier. If connecting to those facilities, AC power supplier will be damaged.
6. Please take out the unit from packaging box carefully. Check if there is any outside damage. If you find any damage, please contact with your local dealer.
WARNING: HIGH LEAKAGE CURRENT EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY.
2. Installation
Before starting installation please check the following items:
This unit is designed for indoor and outdoor usage. But it is suggested
that the unit can’t be exposed under rain or water directly and use a shelter to protect the unit would be better.
Do not expose this unit to the sun directly. This may reduce the output
power due to high temperature.
Check the ambient temperature of installation is within specification
(-25~+55°C).
The grid to be connected is 230V system. The connection to grid is approved by utility company .
The installation must be done by qualified personnel . Though GT can be installed where temperature up to 50°C, we still strongly recommend that it should be installed where ambient temperature in the range of 0~40°C.
Mount GT to the wall
1. Select a wall or solid place can support the inverter.
2. Convection cooling space required. To dissipate the heat generated by
inverter, 25cm space at least on the top and bottom is necessary.
3. Mark the hole position according to following table or mounting template
attached.
W (mm)
GT1500 GT2000 GT3000 GT4000
347.6 347.6 347.6 546
H (mm)
4. Drill the holes with screw.
257 257 257 257
5. Hang the inverter on the 4 screws.
6. Drive “fix screw” on bottom leg to fix the inverter.
Be sure to check the mounting of inverter. Try to lift up the inverter on the bottom, make sure it is firmly attached.
Select the installation location carefully. The height of inverter is recommended to be seeable, so that user can check the inverter status easily; the wall must be firmly enough, this can prevent slight vibration during inverter
wwoorrkkiinngg..
Connect to grid (AC utility)
1. Check the grid (utility) voltage and frequency, 230VAC (or 220VAC),
50/60Hz, single phase.
2. Open the AC breaker or fuse between AC wire and utility.
3. For GT4000 GT3000 GT2000 GT1500, connect AC wires as follows:
Disassemble female socket. Connect AC wires to connection socket as indication:
Female insert
with coupling ring
Shell
Pinch ring
Pressing screw
AC wire inserting direction
Insert Line wire to L, Neutral wire to N and Ground wire to pin Assembly the socket again. Insert the whole socket set to inverter.
Twist the coupling ring to receptacle on inverter. Make sure it is
perfectly matched.
4. Suggested wire size for AC cable:
Model
φ (mm)
AWG no.
GT1500
1.29 16
GT2000
1.29 16
GT3000
1.72 14
GT4000
2.05 12
Connect to PV array (DC)
1. Turn off the DC switch.
2. Make sure the maximum open circuit voltage (V
oc
) of each PV string is
less than 500V UNDER ANY CONDITION. We recommend use PV array which V
oc
is less than 430VDC under 25°C ambient.
3. Use MC (Multi-contact or Tyco) connectors as PV array terminals.
4. Connect positive from array to (+) terminals and negative to (-) terminals. Each DC terminal on GT can withstand 20A DC current at most.
5. Turn on the DC switch.
Note:
Before connecting to DC terminals, please make sure the polarity is correct. Incorrect connection will damage the unit forever!
Checking
1. After connecting DC
1
, the message on the LCD display should be in the
sequence of “INV Waiting” “No Utility” and the RED fault LED keeps on.
1
The AC is not connected yet!
2. Close the AC breaker or fuse in previous section, check whether the inverter starts to work.
3. If inverter works normally, the LCD will show “Working mode”. That is the power feed to grid.
4. The checking is completed.
3. System diagram
1. The connection of whole PV system is indicated as figure.
2. PV array: Provide DC power to GT inverter.
utility
Connection
system
PV array
3. GT inverter: Convert DC power from PV array to AC (Alternative Current) power. Because GT is a grid-connected inverter, it works to control its current amplitude according to power provided from PV array. GT always try to get maximum power from PV array.
4. Connection system: The “interface” between Utility and inverter. It may consist of electrical breaker, fuse and terminals for connection. To make sure safety, this part must be designed by qualified technician.
5. Utility: It is also call “grid” in this manual. The way your power company provides power to your place. Please note that, GT can connect to low-voltage system (namely, 220, 230VAC) system only.
4. Inverter status
GT is designed to be friendly, therefore, the status of inverter can be easily understood by panel display. All the possible information is shown in the following table.
Display information LED
There are 2 LED’s on GT, one is blue and the other is red.
1. Power on (Blue LED): It lights when GT is working. It will be dark when fault mode or shutdown mode.
2. Fault (red LED): Once the LED light, it means inverter meets “fault” or
“failure” conditions. The detail conditions can be found in the table below.
LCD
(A) In generally, LCD will show “Working Mode” as GT is working.
(B) When LCD shows “Working Mode”, press button over 3 sec., LCD will
show “Setting” then enter setting function mode: LCD Contrast setting > press button over 3 sec. to enter Press button to select: Contrast 1 to Contrast 5
Then press button over 3 sec.
LCD will show “Setting”, Contrast setting is OK.
LCD Language setting > press button over 3 sec. to enter Press button to select: English or German.
Then press button over 3 sec.
LCD will show “Setting”, Language setting is OK.
If user doesn’t touch button over 5 sec.,
LCD will escape setting function mode.
(C) In “Working Mode”, you can toggle button to enter meter value mode,
LCD will show general meter value by turns:
O/P Watt = PV Volt = Grid Volt = Grid Freq = O/P Cur =
xxx KWH (O/P energy) Rating= xx KW (PV Inverter Rating) M CPU Ver xxx (Firmware version of Mater CPU ) S CPU Ver xxx (Firmware version of Slave CPU)
1). If user doesn’t touch button over 5 sec., LCD will escape meter value mode then LCD shows “Working Mode”.
2). During meter value mode, if user press button over 5 sec., the current screen will “Freeze” (Lock).
3). If screen is freezing (Lock), user press button over 5 sec., the current screen will “Unfreeze” (Unlock).
(D) Error Message: No Utility No AC Line PV Over Voltage PV Voltage is too high DC Bus High DC bus voltage is too high DC Bus Low DC bus voltage is too low Over Temperature Temperature is too high Grid Fault Grid Voltage or Grid Frequency is wrong Device Fault Hole sensor, GFCI Device
or AD Reference Voltage Fault Isolation Fault PV Panel isolation problem Impedance Fault Grid Impedance Fault Ground I Fault Output ground leakage current too high Relay Failure Output Relay Fail DC INJ High Output DC injection too high Ref 2.5V Fault 2.5V reference voltage inside problem DC Sensor Fault Output DC sensor abnormal GFCI Fault GFCI detection problem Sci Fault Communication between Master and Slave problem Consistent Fault The value of Master and Slave are mismatch CPU Ver Mismatch Firmware Version of Master and Slave are not
the same EEPROM Fault EEprom problem Grid V Mismatch The Grid V of Master and Slave are mismatch Grid F Mismatch The Grid F of Master and Slave are mismatch Grid Z Mismatch The Grid Impedance of Master and Slave are
mismatch GFCI Mismatch The GFCI value of Master and Slave are mismatch DC Curr Mismatch The Output DC current of Master and Slave are mismatch
Message table in English
Operating conditions
Normal working status
Power off No display Standby INV Standby 90V< Input voltage < =100V.
Initialization & waiting INV Waiting
Check grid Testing Feeding grid, MPPT Working Mode Inverter is feeding power.
Updating Master CPU firmware Master Flash
Updating Slave CPU firmware Slave Flash
Monitoring parameters
Instantaneous Output power
Accumulated energy information xxxxx KWh
Grid voltage
Grid frequency
AC feeding current
PV panel voltage
Isolation failure Isolation Fault GFCI
(Ground Fault Current Interrupter) active
Display
message
O/P
Watt=xxxxW
GRID
VOLT=xxx.xV
GRID
FREQ=xx.xHz
O/P
CUR=xx.xA
PV
VOLT=xxx.xV
System fault
Ground I Fault
Description
PV inverter is totally shutdown, IPV <=90V.
Input voltage range 100~150V during start-up. After PV voltage is higher than 100V, inverter is waiting for feeding to grid. When PV voltage> 150V, inverter is checking feeding conditions.
The internal program is updating Master CPU through RS232 interface. The internal program is updating Slave CPU through RS232 interface.
The real time output power in xxxx W. Total energy which has been feed to grid since inverter was installed.
Grid voltage in xxx.x VAC.
Grid frequency in xx.x Hz.
AC grid current amount in xx.x A. Input voltage from PV panel, xxx.x
VDC.
Earth fault of the PV-panels or failure of surge voltage protection.
Current on ground conductor is too high.
Grid failure Grid Fault
Abnormal Grid Impedance
No grid utility voltage No Utility
DC-Input voltage too high
Consistent failure
Bus failure
Device failure Device Fault
Temperature too high
Impedance
Fault
PV Over
Voltage
Inverter failure
Consistent
Fault
DC Bus High DC Bus Low
Over
Temperature
Grid measured data is beyond the specification (voltage & frequency).
1. Grid impedance higher than the permissible value.
2. Grid impedance change is higher than limit.
1. Inverter is not connected to grid
2. Grid is absent.
DC-Input voltage higher than the permissible 500V.
The readings of 2 microprocessors are not consistent. It is probably caused of CPU and/or other circuit do not function well.
DC-Bus voltage too high or too low. The device is unable to return to
normal status. The internal temperature is higher than specified normal value.
5. Communication
GT is equipped with power communication interface and options. User can use “Solar Control” software to monitor the status of inverter with PC. Also, qualified personnel can upgrade the f/w inside through RS232 port.
1. RS232: To use RS232 port, you have to remove the RS232 cover on bottom side of GT. It is a DB9 socket, the pin definition is :
Pin Assignment Description
1 N.C. 2 TxD 3 RxD 4 N.C. 5 Common 6 N.C. 7 N.C. 8 N.C. 9 N.C.
NN..CC.. mmeeaannss ““NNoo CCoonnnneeccttiioonn””
2. Optional communication slot: This slot is a very powerful extension slot now and future. GT can accept card special design for the slot only. There are 2 kinds of cards can be applied now. One is RS485 card and the other is SNMP (Simple Network Management Protocol) card. In the future, extension card such as data logger or others may be developed. For card detail information, please refer to use manual of individual card.
3. F/W upgrade: To keep the firmware newest, one can use RS232 port and special program to upgrade inside F/W. To do this, please contact with your local representative.
We do not suggest end-user to upgrade the f/w himself. There is risk to do that without proper operations!
6. Trouble shooting
In this section, the trouble-shooting techniques are stated. This can help the technician to understand the problem and decide a proper action.
Tools to be prepared:
1. Digital Multi-Meter: For checking DCV, ACV, ACF (AC frequency) and
open-short circuit.
2. Screwdriver: For removing unit form bracket and disconnect wiring
3. This manual.
4. Laptop computer with the installation of PCM solar control and Firmware
upgrade program.
5. Standard RS232 cable.
6. Oscillate Scope (Not necessary).
Fault condition message in English
Fault Display Possible actions
1. Check the impedance between PV (+) & PV (-) and earth ground.
System
fault
Isolation
Fault
Ground I
Fault
Grid Fault
Impedance
Fault
No Utility
The impedance must be larger than 8MΩ.
2. If above action is useless, the isolation detection circuit fails, replace one unit.
1. This is caused by too high ground current.
2. Unplug PV generator from the input, check AC peripheral system.
3. After the cause is cleared, plug PV input again. Check the status of the inverter.
4. If above actions are useless, the GFCI circuit fails, replace one unit.
1. Wait for 20 seconds, if the grid come back to normal, inverter will start again automatically.
2. Make sure grid voltage and frequency meet the specifications.
3. Use PCM solar control to adjust operation range.
4. If above actions are useless, replace one unit.
1. Grid impedance higher than the permissible value.
2.Wait for 20 seconds, see if it works again.
3.Check the wires between inverter and grid. Change larger wires if
necessary.
4.Adjust impedance parameter by PCM solar control program.
5. If useless, the impedance circuit inside fails, please replace another.
1. Grid is not connected; check the AC connection by multi-meter.
2. Check grid connection, such as wire and connector to the inverter.
3. Check breaker between inverter and grid; if it is tripped, DO NOT CLOSE again, replace another unit.
Fault Display Possible actions
1. Check the PV open voltage, see if it is more than or too close to 500VDC.
2. If PV voltage is much less than 500VDC (e.g. <430V), measure the DCV by multi-meter, compare the readings on meter and LCD, if >5%, replace another unit.
1. It is caused by the reading between main and redundant controllers are different.
2. Disconnect PV (+) or PV (-) from the input, start the unit again.
3. If this does not work, replace another one.
1. Caused by improper operation of the circuit.
2. Disconnect PV (+) or PV (-) from the input, start the unit again.
3. If it does not work, replace another one.
1. The internal temperature is higher than specified normal value.
2. Reduce the ambient temperature by some other ways.
3. Or move inverter to cooler place.
4. If it is not effective, the temperature sensors fails, replace another one.
Inverter
failure
PV Over
Voltage
Consistent
Fault
Device Fault
Over
Temperature
Loading...
+ 40 hidden pages