OptiPure OP175 Maintenance Manual

OP175
Advanced Membrane
Separation System
Installation, Operation
& Maintenance Manual
Rev. 1
OP175_manual_v1.indd ©2010 Procam Controls, Inc. All Rights Reserved
Manufactured By:
OptiPure Div. of
2605 Technology Drive, Bldg. 300
Plano, TX 75074
P: 972.881.9797 F: 972.422.6262
OP175 System Installation, Operation & Maintenance 2
General Information
Safety Warning
Electrical work should be performed by a qualied
electrician in accordance with all applicable codes and regulations.
Service Contact
For local maintenance and service information please contact your nearest Authorized Service Representative. Service inquiries may be directed to technical support at:
OptiPure div. of Procam Controls, Inc. 2605 Technology Dr. Bldg. 300 Plano, TX 75074 USA
Phone #: 972.881.9797 Fax #: 972.422.6262
E-mail correspondence to: techsupport@optipure.net
Safety Instructions
1. Please read and follow these instructions when connecting and using the system.
2. Never use the system if the power cord has been damaged. Do not allow anything to rest on the power cord, and keep the cord away from any place where people may trip over it.
3. When disconnecting from the electric socket hold the plug, not the cord.
4. Unplug the RP pump from the AC outlet prior to any service.
5. Locate the RP Assembly as close as possible to an AC outlet.
6. Securely bolt processor to wall before operating.
7. Avoid cross-connections and install on cold water supply only.
Environmental Conditions
The OP175 is certied to operate under the
following conditions:
1. Altitude up to 2000 m.
2. Ambient temperature of 40-105°F (5 - 40°C).
3. Max relative humidity 80% at 88°F (31°C).
4. Main supply voltage not to exceed +/- 10%.
5. Installation category II.
6. Pollution degree II.
7. Indoor use only, protect from elements.
Explanation of Symbols
The following symbols are used on the water processor. The symbols and their explanation is given below:
Earth ground:
8. Use approved Air-Gaps when connecting to drain lines.
9. Do not exceed system pressure rating and use water hammer arrestors when water hammer is evident.
10. Turn off Feed-Water supply before lter or
membrane cartridge replacement.
WARNING: Hazardous Voltage:
OP175 System Installation, Operation & Maintenance 3
Getting To Know Your System
The OP175 is an Advanced Membrane Separation System designed to purify water by removing dissolved minerals and then add back a consistent amount of a balanced blend of TDS (Total Dissolved Solids), or mineral content, in the treated water.
Tank Repressurization
Water Quality Indicator -
Operates momentarily, push purple button to turn on. Push “IN” button for the TDS of the water going into your equipment. Push “OUT” button
for the TDS of the puried water
from the membrane.
Return-
1/2” gray hose - Connect to Repressurization Assembly Outlet
Operating Pressure Gauge
Emergency Bypass Valve -
User can switch from Optimized Water to Untreated Water if needed.
Feed water Inlet 3/8” Push-To-
Connect ­Connect to Water Supply Valve.
Reject Water Outlet
- 1/4” Push-to-Connect ­Connect to drain per local regulations.
1
2@ CTO-Q10 Pre-Filters PN: 300-05828
2
Membrane Reject Water Tubing Connection
Optimized Water To Storage Tank -
3/8” Push-To-Connect
- Connect to Optimized Water Storage Tank Inlet
Buffer Tank - Pre-charged air bladder - 20 psi
3
AMS-QT15 Membrane Cartridge
Buffer Tank Valve
Normally open, shown closed.
Pressurized Optimized Water Outlet -
4
1@Mineral Addition Cartridge PN: 300-05850
1/2” gray hose
-Connect to End User Equipment
Sample Port -
3/8” Push-to-Connect - Used to
ush replacement lters, gather
water sample, measure production or to drain water from storage tank.
Repressurization Pump 120VAC - Plug in to standard
wall outlet.
Absolute 0.2 micron Hydrophobic Air­Breather/Filter
Repressurization Assembly Outlet
- 1/2” Hose Barb ­Connect to Pressurized Water Inlet on Processor
Optimized Water to Storage Tank Inlet
- 3/8” Push-to-Connect
- Connect to Optimized Water Outlet on OP175 processor.
Tank Inlet Divert Valve
- Normally in Down position. Turn handle to Up position to divert Opti­mized water to sample port.
Optimized Water Storage Tank
- 16 gal. Atmospheric
OP175 System Installation, Operation & Maintenance 4
Installation Requirements
This section and the next provide the water, electrical and space requirements for the OP175. Pay
special attention to the feed-water chemistry requirements. Operating a system on water supplies
outside of these parameters may lead to premature membrane failure. This product is for commercial use only and must be installed and maintained in accordance with manufacturer’s guidelines and local regulatory plumbing and electrical codes.
Operating parameters
Typical Membrane TDS* rejection: 97+% Feed Temperature: 40 - 100° F (4 - 38° C) Feed pressure: 50 - 80 psi
(3.4 - 5.9 bar) at 1 gpm Production** (at 77°F, 60 psi) 184 gals/day,
7.7 gals/hr, 0.13 gpm Recovery: up to 33%.
IMPORTANT NOTE: The nominal production rate
is strictly dependent on feed water temperature and pressure. Reduced temperature or pressure will reduce production. For example: Operating
pressure of 30 psi will cut production by 50%. 48˚F
feedwater will cut production by 50%.
Location
The system should be installed indoors, in the proximity of the equipment (within 25 feet) and protected from the elements. Do not let the processor or storage tank freeze or be exposed to rain or direct sunlight.
Post-treatment
Treated water stored in a tank may absorb organic compounds from the tank, which can affect water taste and odor. If product water is for consumption, an
optional post-treatment lter, such as an OptiPure FX or QT carbon lter, should be installed after the
tank. If used, it is best installed as close to the point of use as possible. Other specialized post-treatment is also available.
Feed water connection
An adequate ow and pressure of water to the unit is
essential for successful operation. Provide a dedicated 1/2” water line to the vicinity of the installation. Install
a full-ow ball valve and pressure gauge with 1/2”
female pipe thread (user supplied) for connection to installation hardware provided with the system. A 1/2”
*TDS (total dissolved solids) create conductivity in water and are expressed in ppm or mg/l (parts per million or milligram per liter).
**Nominal production @ 77°F (25°C) @ 500 ppm based on a 24 hr day. Actual production will vary based on variations in water temperature, pressure, and TDS.
male pipe thread x 3/8” push-to-connect adapter is included in the installation kit.
Drain
A drain should be located within 5 feet of the location
of the unit. Drain must allow a minimum ow of 2
gallons per minute. Compliance with most local plumbing codes requires installation of an approved air gap in the drain line. The drain connection should be accessible for system set-up and service.
Electrical requirements
A power source should be located within 5 feet of the location of the unit.
RP Pump 120V 60Hz 2 Amps
Feed-water chemistry
Feed TDS Up to 1200 ppm Feed pH 6 - 10 Hardness 28 grains or less Free chlorine <2 mg/l Iron (Fe) 0.1 mg/l max. Turbidity <0.05 NTU Manganese 0.05 mg/l max.
Hydrogen sulde 0.0 mg/l
A water analysis must be conducted before installing the system or the information requested above can be obtained from your local water utility. If your water analysis shows that any of these parameters are not within range, additional pretreatment and/or higher frequency of maintenance may be required. Contact your OptiPure distributor for assistance. The presence
of silica or occulants such as alum or cationic
polymers in the feedwater may cause membrane fouling and may require special chemical pretreatment or periodic membrane cleaning. Please note that membrane failure due to fouling is not covered by the warranty.
Storage Tank
The tank must be located within 10 feet of the water
processor unit. The oor beneath the storage tank
should be smooth, clean and free of sharp objects that could puncture the bottom of the tank. Note: The tank
is atmospheric, with a sub-micron, hydrophobic air
breather lter.
Optimized Water Lines to Equipment
Tubing, piping and associated ttings connecting
Optimized water lines to equipment shoud be food grade material that meets NSF Std 51 or 61 with a minimum pressure rating of 75 PSI. Optimized water may react with most metal piping imparting a bad taste. Plastic pipe or reinforced opaque beverage tubing are acceptable choices for Optimized water distribution. The larger inside diameter tubing or hose, the better to minimize pressure drop.
OP175 System Installation, Operation & Maintenance 5
Typical Installation with Atmospheric Tank
Important: Plumbing should be performed by a qualied plumber in accordance with local codes.
Power
120VAC, 2A
Feed
Water
User-Supplied
Water Supply Valve &
Pressure Gauge
Feed Water Line -
Green - from Water Supply Valve to Feed Water Inlet
When installing keep lines from the Repressurization Assembly to the equipment as short as possible to minimize pressure loss.
Optimized Water Line - Blue
- from Optimized Water Outlet to Tank Inlet
Pressurized Water Line - 1/2" Gray Hose with hose barb inserts at
both ends - from Repressurization Assy Outlet to Pressurized Water Inlet.
Feed Water Inlet
Connection
(behind valve)
Emergency
Bypass Valve
Membrane Reject Water
Tubing Connection
Processor
Reject
Water
Outlet
CTO-Q
Pre-Filter
1
Water Quality Monitor
Tank
Repressurizaton
CTO-Q
Pre-Filter
2
Return
Storage Tank
AMS-QT15
3
Operating
Pressure
Gauge
Optimized
Water To
Membrane Cartridge
Mineral Addition
Cartridge
4
Sample Port
Optimized Water Outlet to Equipmt
Buffer Tank Valve
(Normally Open,
shown closed)
Optimized
Water to
Storage Tank Inlet
(on Valve)
Repressurization
Assembly Outlet
(Hose Barb)
Tank Inlet
Divert Valve
(Valve handle
normally in Down
position. Turn to
Up position to
divert Optimized
water to the
sample port.)
Repressurization Assembly
Buffer Tank
Bypass
Optimized Water
Storage Tank
- 16 gal. Atmospheric
Repressur­ization Pump 120VAC
Tank Full Shutoff Valve
(inside tank)
Air Breather
Reject Water (to Drain)
Drain Line - Black -
from Reject Outlet to Drain
Optimized Water Line - 1/2" Gray Hose
with hose barb insert - Make connection to
distribution and (optional) post-treatment.
Optional Carbon Post­Treatment
Optimized (Treated) Water to Equipment
IMPORTANT - THE SYTEM MUST BE IN­STALLED INDOORS. DO NOT INSTALL IN DIRECT SUNLIGHT OR WHERE EXPOSED TO FREEZING TEMPERATURES OR RAIN. IDEAL­LY USE NON-METAL PIPING FOR OPTIMIZED WATER CONDUIT.
Plywood anchored
to wall
OP175 System Installation, Operation & Maintenance 6
Outside edge of processor bracket
9.1”
10.7”
15.2”
17.2”
Wall Mounting
The processor unit should always be mounted where it is well-supported, either using anchors in a cement wall, or using the support of studs in a wall-board wall. Never mount it directly to sheet-rock alone. Instead, mount it on a sheet of plywood which is anchored to the wall studs, as shown above.
Four user-supplied bolts or screws with a head
diameter of approximately 1/2” (which will t into the
keyholes in the system bracket, but will not slip out when tightened) should be used to hang the system.
This will allow the unit to be lifted off the bolts, if necessary for maintenance, without removing all the bolts from the wall. Hold the processor in place (without the cartridges) to mark the locations for the screws. BE SURE TO ALLOW 3” BELOW THE CARTRIDGES TO ALLOW FOR REMOVAL. Screw the four bolts or screws in place, leaving approximately 1/4” clearance between the bottom of each bolt head and the wall. Position the system over the mounting bolts, and let the bracket slip down into the keyholes.
Tighten all screws.
System Installation
Note: Do not install the cartridges in the processor until completing this section. Do not plug in the power cord from the RP pump until completing the following section, “System Start-Up”.
Refer to “Typical Installation” diagram on page 5 and “How to Use Our Quick-Connect Fittings” on page 16 when making the following connections.
A feed water ball valve and pressure gauge (user supplied) should be installed to provide water to the system FEED WATER INLET with the green tubing
(supplied). Hose, tubing and ttings for making
connections between the processor, storage tank and drain are supplied in the installation kit with the system.
1. Remove the tank lid. Inside the tank, the oat
valve may be secured for shipping. Remove any
wrapping on the oat to allow it to hang and move
freely.
2. DRAIN: Connect the 1/4” black tubing from the installation kit to the REJECT WATER OUTLET on the processor. Run the line to an appropriate drain. Observe local plumbing codes and supply an
appropriate air gap. (Any ttings for connecting to
the drain will need to be supplied by the customer.) Fix tubing in place at the drain.
3. FEED WATER: Apply 3 ‘wraps’ of Teon tape to the 1/2” FPT x 3/8” push-connect tting (supplied). Screw the tting into the Feed Water Supply Ball
Valve and tighten (DO NOT OVERTIGHTEN). Connect one end of the 3/8” GREEN TUBING to
this tting. Connect the other end of the tubing to
the FEED WATER INLET located on the left side of the Processor. Cut the tubing to the required
OP175 System Installation, Operation & Maintenance 7
Equipment Dimensions
IMPORTANT - ALLOW A MINIMUM OF 24” IN FRONT OF THE PROCESSOR FOR MAINTENANCE AND SERVICE. DO NOT MOUNT SYSTEM ABOVE THE CEILING OR IN A LOCATION THAT IS NOT EASILY ACCESSIBLE. WHEN THE 16 GAL. TANK ASSEMBLY IS FULL OF OPTIMIZED WATER IT WILL WEIGH 140 LBS. ALWAYS LOCATE THE STORAGE TANK WHERE IT CAN BE ACCESSED (OR IS ACCESSIBLE) DURING SERVICE.
Processor
Left Side
View
Processor Front View
Tank Assembly (16 gal.)
Allow 3” to remove cartridges
Front View Right Side View
OP175 System Installation, Operation & Maintenance 8
Inlet
Repressurization Assy Outlet
Optimized Water Inlet
Tank Inlet Divert Valve- Shown in the normal positon
length if necessary.
NOTE: When cutting the tubing use a sharp tubing cutter or blade and make a clean, straight cut
before inserting into a push-connect tting. When
routing tubing, do not make sharp bends or crimp the tubing.
4. PROCESSOR TO TANK: Connect a piece of the 3/8” blue tubing to the OPTIMIZED WATER
TO STORAGE TANK tting on the processing
unit. Connect the other end of this tubing to the OPTIMIZED WATER TO STORAGE TANK INLET on the storage tank INLET DIVERT VALVE.
5. REPRESSURIZATION ASSEMBLY TO PROCESSOR: Using two of the 1/2” hose barb inserts (supplied), a piece of 1/2” gray hose, and two hose clamps, connect hose from the REPRESSURIZATION ASSEMBLY OUTLET on the Repressurization Assembly to the TANK REPRESSURIZATION RETURN on the Processor. The ridged end of a hose barb insert goes into each end of the hose with a hose clamp tightened onto it. The smooth ends of the hose
barb inserts go into the push-to-connect ttings on
the Processor and Repressurization Assembly.
Water Outlet
1 2
Reject tubing connected to stem connector on bottom of AMS-QT15 Cartridge
3
4
Install QT Cartridges
NOTE: Before installing the QT Cartridges make sure to remove the four plugs in the QT heads.
1. Insert the CTO-Q10 cartridges into QT heads 1 & 2 (starting from the left or inlet side of the processor) and turn to align arrows.
2. Insert the AMS-QT15 membrane cartridge into the QT head #3 and turn to align arrows.
3. Insert the MA-QT mineral addition cartridge into the QT head #4 (far right) and turn to align arrows.
4. Connect the Push-to-Connect elbow (remove plug in elbow) on the end of the black Reject tubing to the stem connector on the bottom of the AMS­QT15 cartridge.
Optimized
6. OPTIMIZED WATER TO EQUIPMENT: Connect a piece of 1/2” i.d. gray hose the the OPTIMIZED WATER OUTLET on the processor with a 1/2” hose barb insert and clamp (supplied). The other end of this line will be connected to the distribution line that will deliver Optimized Water to the equipment at a later time. Prepare any necessary plumbing to make the connection between the 1/2” hose and distribution line, but for now leave the line loose and route the loose end of the gray hose into a drain or bucket (make certain the hose length will reach the storage tank - this will be required for the Start-Up procedures). The equipment connection will be completed in “Connect to Equipment.”
Optional RP Assembly Location
The Repressurization Pump and Buffer Tank assembly is on a stand that can be remote from the storage tank. Simply remove the four bolts on the feet of the bracket and lengthen the gray hose from the tank to the pump and the red bypass tubing from the Tank Inlet Divert Valve to the required length. Four rubber feet and mounting screws are available to put on the bottom of the Tank Stand. Kit Part number 164-89116.
OP175 System Installation, Operation & Maintenance 9
System Start-Up
Refer to the illustration in “Typical Installation” (page
5).
from the Optimized Water Outlet on the Processor
to the distribution line feeding the equipment that will be using the Optimized Water.
IMPORTANT: Before proceeding, position the
Processor EMERGENCY BYPASS VALVE in the “SERVICE” position, assure that the Buffer Tank Valve is closed, and position the TANK INLET DIVERT VALVE to bypass the tank (Blue Valve Handle pointing up).
1. Slowly open the user-supplied WATER SUPPLY
VALVE and allow the lter housings to ll. Water will begin to ow from the end of the 1/4” black
tubing routed to the drain. After some time, water
will begin to ow from the gray hose which is
temporarily routed to a bucket or the drain. Allow
several minutes to ush the system until water ows smoothly from the gray hose and drain line.
Check all of the plumbing connections and correct any leaks if necessary.
2. The tank must be ll to start-up and purge the Repressurization Assembly. You can quickly ll the
storage tank using the “System Bypass” on the processor. To do this use the following:
• Route the 1/2” gray hose from the OPTIMIZED WATER
OUTLET directly into the storage tank.
• Turn the EMERGENCY BYPASS VALVE on the processor
to “BYPASS.” This will allow feed water to bypass the
processor and quickly ll the storage tank.
When the tank lls to approximately 14 gallons return
the processor EMERGENCY BYPASS VALVE to the “SERVICE” position. When the tank is full, the shutoff
valve will close, stopping all ow.
• With the tank full, ensure the valve at the top of the BUFFER
TANK is in the OPEN position and that the 1/2” gray hose is still directed into the storage tank.
3. Plug the power cord from the RP pump into the
outlet. Water should begin to ow rapidly from the
storage tank, through the RP assembly and back into the storage tank through the gray hose. Allow the pump to run for several minutes until all of the air is purged from the Repressurization Assembly. As the air is purged, the pump will run more
smoothly and the water ow from the gray hose
will become steady.
4. Unplug the RP Pump cord.
Connect to Equipment
You are almost ready to enjoy the benets of
Optimized Water. All that remains is to make the connection for distribution to your equipment.
3. Ensure that any valves or solenoid valves on the connected equipment are closed. Plug the RP
pump back in. The pump will run and will ll the
Buffer Tank until the pressure in the Buffer TAnk reaches 70 psi, and then the RP Pump will shut off.
4. Open downstream valves at the equipment to allow air to purge from the distribution lines. When purging distribution lines do not allow the water level in the storage tank to drop below 1/4 full.
Once purged and ushed, close the equipment
valves. When there is no demand for water the pump will shut off automatically.
5. Turn the TANK INLET DIVERT VALVE to the “TANK” position (blue valve handle pointing down).
Complete the Installation
Transition to Owner/Operator
The nal step is to meet with the owner/operator,
familarize them with the system and complete the post installation check list.
The system is now in “normal operating” mode and
the storage tank will ll with Optimized Water from the processor. Complete the “Check List” to “Conrm
Normal Operation and System Settings” (page 4 of the “Quick Installation Guide”) with the Owner/Operator.
Allow the tank to ll before beginning operation of the
connected equipment.
Reading the TDS
1. Push the purple “POWER” button on the Water Quality Monitor located on the upper left corner. It will immediately display the “IN” or Optimized Water TDS (Total Dissolved Solids) in PPM (parts per million). Document this number as the Optimized Water TDS.
2. Within 30 seconds, push the “OUT” button to display the Membrane Permeate TDS and record this number as the Permeate TDS.
1. Remove the 1/2” gray hose from the storage tank and replace and tighten the lid to the storage tank.
2. Complete the connection of the 1/2” gray hose
OP175 System Installation, Operation & Maintenance 10
What are all those parts and what do they do?
3
FEED
9
1
1
4.
4
8
6
PG
7
13
5
10
2
Sample Port
To User
Equipment
20
To Drain
18
15
16
This section will give you an overview of how the system works.
Incoming water is ltered by the prelters
(1), which remove sediment, chlorine and organics.
When the Emergency Bypass Valve (3) is in the normal SERVICE mode, water ows
through the Processor. When the Bypass Valve (3) is in System Bypass mode, the water is diverted directly out to the equipment, bypassing both the Processor and the Repressurization Assembly.
When water in the storage tank is at a low storage level, the oat valve at the tank
(12) opens, lowering the pressure in the Optimized Water line from the Processor to the Repressurization Assembly, causing the Automatic Shutoff Valve (4) in the Processor
to open, allowing feed water to ow through to
the AMS-QT15 membrane (7).
The membrane feed water pressure is
indicated by the pressure gauge (6).
The water ows to the inlet of the membrane
(7). The water is split by the membrane into a pure water stream and a reject water stream.
The reject water ows to the Reject Flow
Control (10) and then on to drain.
17
14
19
Storage
Tank
11
12
The pure water stream continues through the
Permeate Check Valve (8), and through the Mineral Addition cartridge (2), then on to the tank through the Tank Inlet Divert Valve (11) on top of the Storage Tank (14). Air in the tank is displaced by the incoming water and vented out of the Sub-Micron Air Breather (16).
When the tank completely lls, the tank oat valve (12) closes, causing pressure
in the Optimized Water Line to rise, which then causes the Automatic Shutoff Valve
(4) to close, stopping the ow through the
Processor.
When the “IN” button is actuated on the
Water Quality Monitor (9), it measures the average TDS of the Optimized Water in the Pressurized Water Line coming from the storage tank. When the “OUT” button is actuated, the Water Quality Monitor (9) indicates the TDS of the Permeate water exiting the Membrane (7). If the Bypass Valve (3) is in System Bypass mode, the Water Quality Monitor (9) will measure the TDS of the untreated Feed Water when the “OUT” button is actuated. The Water Quality Monitor (9) is battery powered with two AA batteries. It will automatically shut-off after 30 seconds.
OP175 System Installation, Operation & Maintenance 11
The Repressurization Pump (15) is designed
to draw water from the Atmospheric Storage Tank (14) and dispense the Optimized water to the Processor and through the One-Way Check Valve (5) and out to the equipment. A Buffer Tank (18) between the pump and the downstream equipment to prevent short cycling of the pump for low volume demands. The Repressurization Pump is equipped with a pressure switch so that when the pressure in the Buffer Tank drops, the Pump runs to repressurize the Buffer Tank, and when the pressure reaches 70 psi, the Pump shuts off.
Water demand for downstream equipment is
directly supplied from the Buffer Tank (18), and demand can go on and off as necessary. The RP Pump is not directly affected by downstream demand, but only activates in
response to a sufcient drop in Buffer Tank
pressure. Downstream equipment is also not affected by the automatic starting or stopping of the RP Pump.
The Optional Post-Treatment Filter (20) is
designed to provide additional treatment
based upon specic application requirements.
For beverage applications an activated
carbon lter is recommended.
As Optimized Water is dispensed from the
storage tank by the Repressurization Pump (15), air is replaced in the tank through the Sub-Micron (0.2 micron) Air Breather (16).
If the Repressurization Pump (15) fails, water ow and can be restored to the equipment by
turning the Emergency Bypass Valve (3) to the position to “SYSTEM BYPASS” position. This allows tap water to bypass the processor and RP assembly.
Repressurization Pump
The Repressurization Pump Assembly that comes standard with the OP175 System includes a diaphragm pump controlled by a built-in Pressure Switch, and a Buffer Tank between the Pump and the downstream equipment maintains pressure downstream. When a valve or solenoid valve is opened down-stream of the Buffer Tank, the de­mand is supplied from the Buffer Tank. When the
pressure drops sufciently in the Buffer Tank, the pump starts automatically and rells the Buffer
Tank. The operating pressure for the Buffer Tank
is preset (to 70 psi) and is NOT eld adjustable.
The pump also incorporates check valves to keep the Buffer Tank and downstream line pressurized. The pump is equipped with auto-reset, thermal overload protection and is designed for intermit­tent duty.
If the pump runs erratically, allow the pump to run to open drain with valve fully open to purge air from the pump head. Disconnect the power and reconnect several times to facili­tate air purging.
Pump will prime only if all the pressure is relieved from the outlet port. The pump is self-priming up to 11 ft. The pump can run dry but will overheat and the pump overload will shut the pump off.
A Sample Port (13) provides the ability to
measure membrane production by closing the Buffer Tank Valve (17) and turning the Tank Inlet Divert Valve (11) to the bypass or UP position. This diverts the permeate (pure water produced by membrane) from the Storage Tank (14) through the Bypass Check Valve (19) and back to the processor where opening the Sample Port (13) will allow you to
directly measure the permeate ow rate.
Additionally the Sample Port (13) provides
the ability to drain water from the Storage Tank (14) by closing the user-supplied Water Supply Valve, opening the Buffer Tank Valve (17) and opening the Sample Port (13).
OP175 System Installation, Operation & Maintenance 12
OP175 Processor Components
Automatic Shutoff Valve -
PN: 524-20010
“IN” Optimized Water Conductivity Probe -
Pressure Gauge -
PN: 530-20018
Green Tubing -
Filtered Water Line
Blue Tubing -
Optimized Water Line
Red Tubing -
Bypass Water Line
Reject Flow Control -
PN: 564-02105
Water Quality Monitor -
PN: 530-40112
Bypass Valve -
PN: 520-12230
Sample Port Valve -
PN: 520-12223
“OUT” Permeate Conductivity Probe
Mineral Addition Cartridge -
PN: 300-05850
AMS-QT15 Cartridge -
PN: 204-52820
Stem Connector -
PN: 551-65210
Union Elbow -
PN: 551-63021
Pressurized Water Check Valve -
PN: 524-01035
Permeate Check Valve -
PN: 524-01030
Black Tubing -
Reject Water Line
CTO-Q10 PreFilters (x2) -
PN: 300-05828
OP175 System Installation, Operation & Maintenance 13
Tank/RP Components
Buffer Tank Valve -
PN: 520-14501
Bypass Check Valve-
PN: 524-01030
Buffer Tank -
PN: 340-50001
RP Pump -
PN: 704-35513
Tank Bracket -
PN: 594-80516
RP Assy Outlet -
1/2” Hose Barb Insert, PN: 550-08730 Connect to equipment inlet.
Optimized Water Inlet -
Connect line from Optimized Water To Storage Tank Outlet on OP175 processor.
Tank Inlet Divert Valve -
PN: 520-12235
Air Breather -
PN: 300-40005
Float Valve -
(inside tank) PN: 520-01203
16 Gal Storage Tank -
PN: 570-00016
OP175 System Installation, Operation & Maintenance 14
Routine Maintenance: Filter Change Procedure
The only routine maintenance required on the system is periodic replacement of the carbon/
sediment pre-lters and the mineral addition
cartridge. The CTO-Q10 cartridges should be changed every 3-6 months depending on water usage. In areas with high levels of sediment and other contaminants the CTO-Q10 cartridges may require more frequent changes. The mineral addition cartridge should be changed when the Optimized Water TDS drops.
Pre-Filter change procedure
1. Either close the Water Supply Valve (shutting
off all water ow), or put the Emergency
Bypass Valve (on the Processor) in the System Bypass position (allowing untreated
water to continue to ow to the equipment).
2. Wait a moment for system pressure to drain off.
3. Once the system pressure has been relieved, remove the two CTO-Q10 cartridges by turning a quarter-turn to the left and pulling down on the cartridge.
9. Check for leaks.
Optional Post-treatment cartridge change procedure
(if applicable)
1. Close the ball valve at the inlet to the Post­Treatment assembly.
2. Remove the existing cartridge and discard.
3. Install the new cartridge.
4. Open the ball valve and the RP pump should
actuate lling the housing with water.
4. Install the new CTO-Q10 cartridges into the QT heads by aligning the notches and pushing up, then turn a quarter-turn to the right.
5. If it is necessary to replace the Mineral Addition Cartridge, repeat steps 4 - 5 for the Mineral Addition Cartridge.
6. Install a piece of 3/8” tubing in the Processor Sample Port valve, open the Sample Port, and direct to a bucket or drain.
7. Turn the Tank Inlet Divert Valve to the Bypass Mode (Handle Pointing UP).
8. Open the Water Supply Valve and put the Emergency Bypass Valve in the “SERVICE” position, allowing water to run into the new Pre-Filter cartridges and purge air through the system and out the Sample/Flush Port to drain.
9. Once the air has been purged and lters ushed, close the Sample Port valve and
return the Tank Inlet Divert Valve to the Normal position (handle horizontal or down).
CTO-Q10 Pre­Filters PN: 300-05828 Change Every 3 to 6 months
MA-Q10 Mineral Addition Cartridge PN: 300-05850
OP175 System Installation, Operation & Maintenance 15
Routine Maintenance: AMS-QT15Change Procedure
The AMS-QT15 membrane is a high-efciency, low-
fouling reverse osmosis membrane that will provide product water with 95+% rejection of the Feed Water. The life of the membrane will vary depending on Feed Water quality, usage, and Pre-Filter maintenance. Typical membrane life is 12 to 18 months, but with rou­tine scheduled Pre-Filter replacement, and no adverse Feed Water conditions, the AMS-QT15 membrane may last 2-5 years.
AMS-QT15 Replacement
1. Either close the Water Supply Valve (shutting off
all water ow), or put the Emergency Bypass Valve
(on the Processor) in the System Bypass position
(allowing untreated water to continue to ow to the
equipment).
2. Place a bucket or other similar catch basin under the AMS-QT15. Remove the black reject line from the push-to-connect elbow on the bottom of the membrane. (Refer to “Push-to-Connect Fittings” on page 16.) Allow the membrane and reject line to drain into the bucket.
3. Remove the AMS-QT15 cartridge from the head by turning the cartridge a quarter-turn to the left and pulling down on the cartridge.
4. With a wrench, remove the push-to-connect elbow and stem adapter attached to the bottom of the
AMS-QT15 cartridge. Remove the residual Teon
tape from the male 1/8” threads on the stem adapter.
5. Wrap the 1/8” male thread on the stem adapter
with 2 wraps of Teon tape and re-install in the
bottom of the new AMS-QT15 cartridge.
6. Align the taps on the AMS-QT15 cartridge with the QT head and insert into the head and turn a quarter-turn to the right.
7. Insert the black reject line into the push-to-connect elbow on the bottom of the AMS-QT15 cartridge.
8. Install a piece of 3/8” tubing in the Processor Sample Port valve, open the Sample Port, and direct to a bucket or drain. Turn the Tank Inlet Divert Valve to the Bypass or UP position. Open the Water Supply Valve and put the Emergency Bypass Valve in the “SERVICE” position. Allow
water to ush through the membrane displacing air and preservative to ow out the Sample/Flush port
to drain for 5-10 minutes.
9. Actuate the Water Quality Monitor and check the “OUT” or Permeate Water TDS.
10. After the AMS-QT15 cartridge is purged of air, close the Sample Port.
11. Check for leaks.
Trouble-Shooting
Problem Possible Cause Resolution
Running out of water. Operating Pressure reduced
Very cold Feed Water temperature
Low Feed Water Pressure Demand exceeds system capacity
Poor water quality. Membrane failure Replace AMS-QT15 membrane
Short AMS-QT15 mem­brane life.
Short Pre-Filter life Heavy sediment loading Add FXAF01-12 or -12B for added Pre-Filter protection
Processor Does Not Shut Off or Turn On
Water Quality Monitor will not turn on
RP Pump runs intermit­tently or rough.
RP Pump cycles on-off frequently
Poor Feed Water quality, presence of iron, silica or non-calcium carbonate hardness
Automatic Shutoff Valve not function­ing
Dead batteries Replace batteries by sliding Water Quality Monitor up and removing the six
Air trapped in pump head. Downstream water leak.
Low air pre-charge in Buffer Tank Empty Buffer Tank and re-charge air pressure to 20 psi.
Pre-Filters need to be replaced Raise water temp to increase production or determine if higher capacity
system is required Install optional Feed Water Pressure Booster Pump Determine if the demand is unusual or consistent or resize system
Determine Feed Water quality by obtaining a water quality report from city water supply utility or contact your OptiPure dealer
Replace Automatic Shutoff Valve
screws on the back cover. Remove cover to access battteries.
Unplug pump and open downstream valve to empty Buffer Tank. Repair or eliminate downstream water leak.
OP175 System Installation, Operation & Maintenance 16
How to Use Our Push-to-Connect Fittings
Fitting Overview
Fitting Body
Collet/Gripper (Dark Gray)
To Attach Tubing:
To ease insertion, moisten end of tubing with fresh water or 3% hydrogen peroxide solution.
Push tubing straight in.
2
Resistance will be felt when the tubing meets the O ring.
Tubing Preparation
The outside of the tubing must be free of knicks and gouges.
Cutaway view of tting and tubing
1
Keep pushing until the resistance is overcome and the tubing rests against the stop.
Cut tubing with a plastic tubing cutter or a razor knife. Make a clean, square cut.
After cutting, make sure the end of the tube is round. Correct any out of roundness that may have occured in cutting the tubing.
Tube Stop O-Ring
3
To Remove Tubing:
Press collet in to release grippers. While holding the collet in, pull out on the tubing.
It may be necessary to use a partially open crescent wrench or similar device to hold both sides of the collet in while pulling the tubing out.
Loading...