1st row area
sensitivity potentiometer
2nd & 3rd row area
sensitivity potentiometer
1
Area depth angle adjustment
5
Mode setting switch
(Left bank)
4
Area width setting switch
(Right bank)
5-1. Setting the Presence timer
2
ADJUSTMENTS for OA-613 T
Adjusting the Sensitivity
1 2 1 2 1 2 1 2
15 Sec.
30 Sec.
60 Sec. 120 Sec.
33
Setting2Setting1
1st row area
angle screw
2nd &3rd row area
angle screw
Set the dipswitch as necessary.
Active
Inactive
1,2
3
4
5
6
7,8
: Presence timer
: Frequency
: Rain mode
: Snow mode
: Area depth
: Extend Lockout timer
1
Timer adjustment
ADJUSTMENTS for OC-913C T
3
Initial setup
NOTE
InactiveActive
5-2. Setting the Frequency
44
RainNormal
5-3. Setting the Rain mode
55
SnowNormal
5-4. Setting the Snow mode
66
SHALLOWDEEP
5-5. Setting the Area depth 5-6. Setting the Extend Lockout timer
NOTE
Safety output
hold time
(0.5 to 10sec.)
Lockout
timer
(0 to 24sec.)
MaxMinMaxMin
1. Always keep the detection window clean. If dirty, wipe the window with a damp cloth.(Do not use any cleaner / solvent.)
2. Do not wash the sensor with water.
3. Do not disassemble, rebuild or repair the sensor yourself, otherwise electric shock may occur.
4. When the operation indicator blinks Green, contact your installer or service engineer.
5. Always contact your installer or service engineer when changing the settings.
6. Do not paint the detection window.
WARNING
1. After applying power, wait 10 seconds then walk test detection area to ensure proper operation.
2. Do not place any objects that move or emit light in the detection area. (e.g. Plant, illumination, etc.)
NOTE
INFORM BUILDING OWNER / OPERATOR OF THE FOLLOWING ITEMS
NOTE
When set to "Rain", the actual
detection area may become
smaller.
NOTE
7 8 7 8 7 8 7 8
+0 Sec.
+1Sec.
+2 Sec. -1 Sec.
MaxMin
Knowing Act
timer
(0 to 24sec.)
Knowing Act Function
Set the Lockout time to the time for the
door to reach full closed position from
full open position. Lockout timer is
effective only when dipswitch 3 is set to
"Manual" and dipswitch 5 is set to "OFF".
Set the time required for door to close from fully open position to
within 10 degrees when uses for Knowing Act application(dipswitch 4:ON).
See ADJUSTMENTS for OC-913C T
NOTE
Set the Safety output duration time.
OA-613 T
OPERATION INDICATOR
Min Max
Min Max
1st row area
sensitivity
potentiometer
2nd & 3rd row
area sensitivity
potentiometer
Start with 2nd & 3rd row area depth angle
at +5 degrees(deep).
If after walk test the pattern is too deep,
adjust towards shallow as necessary.
For standard
application.
For bi-fold or
smaller door.
: Enable area
: Disable area
Use this function when Primary Activation is Knowing Act (i.e. Push Plate, Card reader, etc.) and
a secondary activation sensor(door mount or header mount) is desired.
See WIRING in the installation manual when Knowing Act Function is required.
Secondary activation sensor status in Knowing Act Function:
- Full Closed position
Secondary activation sensor is inactive until the Knowing Act device is initiated.
Door can be used manually without activation or reactivation from sensor.
- Door opening & Full open
When door is activated by Knowing Act, the secondary activation sensor is active
and the door will remain open when the sensor is in detection.
- Door closing
Secondary activation sensor is active and will reactivate the door upon detection
until the Knowing Act timer expires. Set the Knowing Act timer on OC-913C T control
to stay active to within 10 degrees from full closed.
When using the Knowing Act Function, Push/Pull activation MUST be disabled at the door controller.
Start with 1st row area depth angle
at -5 degrees(shallow).
If after walk test the pattern is too shallow,
adjust towards deep as necessary.
2
Setting the dipswitches
Set the dipswitches as shown below.
Safety relay contact
Door open signal switch
Auto Lockout
Knowing Act
ON
Manual
OFF
Auto
1
2
3
4
5
6
7
8
Dipswitch setting ONOFF
Data input
Test input
Test input High
OFF
Low
ON
Act
NO NC
Saf
PWM
OFF ON
See PREMIER T installation manual step 6
(PREMIER Learn process).
Enable Disable
OPTEX Co.,LTD.
Manufacturer
5-8-12 Ogoto Otsu 520-0101, Japan
TEL.: +81(0)77-579-8700
FAX.: +81(0)77-579-7030
WEBSITE:
www.optex.co.jp/as/eng/index.html
East coast office
8510 McAlpines Park Drive, Suite 108
Charlotte, NC 28211 U.S.A.
TEL.: +1-800-877-6656
FAX.: +1(704)365-0818
WEBSITE: www.optextechnologies.com
OPTEX INCORPORATED
North and South America Subsidiary
18730 S. Wilmington Avenue, Suite 100
Rancho Dominguez CA 90220 U.S.A
TEL.: +1-800-877-6656
FAX.: +1(310)898-1098
WEBSITE: www.optextechnologies.com
1. Safety relay contact
: Choose the Relay contact.
2. Door open signal switch
: Determines safety output when door is open.
3. Auto Lockout
: Set the Lockout method
ON : Manual (by volume setting on OC-913C T)
OFF : Auto (by motor voltage)
4. Knowing Act
: If uses Knowing Act Function, set to "ON".
5. Data input
: If using data output from door control for Lockout, set to "ON".
When Data input is "ON", setting of Auto Lockout(dipswitch 3) is ignored.
6. PWM
: If using PWM from door control for Lockout, set to "ON”.
When using PWM, dipswtich 5 also needs to be set to "ON" and setting of Auto Lockout(dipswitch 3) is ignored.
7. Test input
: If not using Test input from door control for Lockout, set to "ON". When not using Test input, dipswitch 7 also needs
to be set to "ON", and setting of Test input(dipswitch 8) is ignored.
8. Test input
: If using Test input of "Active Low" for Lockout, set to "ON".
Whenever a dipswitch is moved a PREMIER Learn process is enabled, ensure proper completion of process
(See step 3).
This sensor has the function to fit floor condition
changes automatically.
Therefore, even if objects are put in the detection
area, sensor will learn the changes gradually and
set back to normal operations automatically after
presence timer has expired.
To enable a Learn process only, flip any dipswitch
on OA-613 T sensor head and wait 1 second,
then flip it back to the original position.
Check the wiring cable.
Check the connector.
Replace as necessary.
Check the dipswitch settings.
Verify proper settings.
See installation manual step 5.
Possible countermeasures
Set to the stated voltage.
Wrong wiring cable (Brown &Orangewires)
of OC-913C T.
Connection failure from OA-613 T to
OC-913C T.
Twice
Orange
blinking
Defective communication cable.
Blinking
Yellow
Blinking
Green
OC-913C T dipswitches set wrong.
Solid
Green
or
Solid
Red
or
Blinking
Red
Proper
Set dipswitch 6 on left bank dipswitch of
OA-613 T on/up (shallow).
Remove the objects.
Verify proper settings.
See installation manual step 5.
Adjust the sensitivity lower.
Set the snow mode to "Snow".
Set the rain mode to "Rain".
Use the rain-cover
(Separately available). Or install in a
place keeping the water drops off.
Check the installation condition referring
to MANUFACTURER'S STATEMENT.
Remove the objects.
Stalling caused by traffic just outside of
swing path.
Moving objects near guide rails.
Area width dipswitches set wrong.
(Right bank dipswitches on OA-613 T)
Sensitivity is too high.
Snow drifting.
Other than above.
Water drops on the detection window.
Wet floor.
The exhaust emission or fog penetrate
into the detection area.
Reflecting objects in the detection area.
Objects that move or emit light
(Ex.Plant, illumination, etc.)
Red or
Blinking
Red
Verify proper settings.
See installation manual step 5.
Area width dipswitches set wrong.
(Right bank dipswitches on OA-613 T)
Slow
Orange
blinking
When all the area are inactive.
(Right bank dipswitches on OA-613 T)
Twice
Orange
blinking
or
None
Proper
Symptom
OA-613 T
None
Operation indicator
OC-913C T
Adjust the sensitivity higher.Sensitivity is too low.
Solid
Green
Proper
Possible cause
Power supply voltage.None
Slow
Green
blinking
Proper
Signal saturation.
Sensor failure.
Fast
Green
blinking
Proper
Remove highly reflecting objects from
the detection area. Or lower the
sensitivity.
Set 1st row area angle at -5 degrees
(shallow) or 2nd & 3rd row area angle
at +5 degrees (deep).
Improper 1st row or 2nd & 3rd row area
angle adjustment.
Wipe the detection window with a damp
cloth.
(Do not use any cleaner or solvent.)
Dirty detection window.
Contact your installer or service
engineer.
TROUBLESHOOTING
OC-913C T dipswitches set wrong. Check the dipswitch settings.
See installation manual step 2.
Initial setup
can not start.
Incomplete
initial setup
Sensor detects
when no one
is in the
detection area.
(Ghosting)
Set 1st row area angle at -5 degrees
(shallow) or 2nd & 3rd row area angle
at +5 degrees (deep).
Improper 1st row or 2nd & 3rd row area
angle adjustment.
Door does not
operate properly
when a person
enters the
detection area.
(Sensor does
not detect.)
OA-613 T
detects but door
operate.
Solid
Green
Proper
Improper wiring of door equipment on /
off / hold switch.
Verify proper wiring of on / off /
hold switch.
Door remains
open.
When using more than one sensor close to each
other, set the different frequency for each sensor by
dipswitch 3.
To comply with ANSI standard, set to "30sec." or
longer.
Set dipswitch 4 to "Rain" if the sensor is used in a
region with a lot of rain.
Set dipswitch 5 to "Snow" if the sensor is used in
a region with snow or a lot of insects.
Fine-tune the Lockout time after setting the Lockout
timer on OC-913C T by volume (0-24 sec.)
Only effective when dipswitch 3 is set to "Manual"
and dipswitch 5 is set to "OFF" on OC-913C T.