Optex MX-40QZ, MX-50QZ, MX-40PI, MX-40PT Owner's Manual

nEASY INSTALLATION
•Easy Wiring Knockout
•Wiring Guide
•·Spare Terminal [MX-40QZ/50QZ/40PT Only]
•Tamper Terminal [MX-40QZ/50QZ/40PT Only]
•·D.L. Terminal [MX-40QZ(BE)/50QZ(BE) Only]
•Wide Wiring Space
•40ft.×40ft.(12m×12m)Wide Angle [MX-40 Series]
•50ft.×50ft.(15m×15m)Wide Angle [MX-50 Series]
•QUAD Zone Logic
•Patented Multi-focus Lens
•Improved Sealed Optics
•Temperature Compensation Logic
•Pet Immunity [MX-40PI/PT Only] (See Section 5 for Pet Immunity)
nFUNCTION
•Selectable Pulse Count(2 or 4)
•LED ON/OFF
•Tamper Switch [MX-40QZ/50QZ/40PT Only]
•Microwave Range Selector(LONG or SHORT)
nOPTION
•FA-3 Wall & Ceiling Mount Bracket (Horizontally ±45°& Vertically 0°to-15°)
2. DESCRIPTION,OPERATION and DIMENSIONS
TAMPERSP
DL
ALARM
Corner mount
knockout
Wiring knockout
P.C.B. unit
Tamper switch
Terminals
2.44(62)
Cover
LED Indicator
Lens
Base
Wiring guide
Mounting knockout (Pitch=3.29"/83.5mm) (Pitch=3.58"/91.0mm)
Fastening screw
inch(mm)
3. DETECTION AREA
WIDE ANGLE
n


TOP VIEW
n




SIDE VIEW
1. INSTALLATION HINTS
Use the pin switch for Pulse Count Selection ( 2 or 4 ).
Use the pin switch for LED ON/OFF .
n LED ON/OFF
n PULSE COUNT
With PET IMMUNITY&TAMPER
MX-40PT
With PET IMMUNITY
MX-40PIMX-40QZ MX-50QZ
PASSIVE INFRARED and MICROWAVE COMBINATION DETECTOR
P.C.B. hook
MX-40 AREA MX-50 AREA
30
35
25
50 ft
35
30
0
10
9 12
8 ft
15m
50 ft
25
9
4
S
2
0
2
5
10
2015
20
6
2.2m
0
1510
5
0
3
3
4
S
15m
40 45
12
40
45
5
15
20
S
5
10
15
20
25 ft
8m
25 ft
8m
1.5m
3.0m
2.4m
5 f
t
7.5 ft 10 ft
No.59-0967-0 0009-25
N219
4
2
OFF
ON
n
D.L. TERMINAL D.L. TERMINAL
D.L. TERMINAL D.L. TERMINAL
D.L. TERMINAL
(MX-40QZ(BE),MX-50QZ(BE) Only)
LED can be enabled or disabled remotely from control panel by D.L. terminal. Place jumper pin switch in OFF position.
n
MICR
OO
OO
OWAVE RANGE
LONG
SHORT
n
EASY WIRING KNOCKOUTS
Press firmly with a screwdriver to open.Enlarge the hole according to size of wire.
LED Enabled Connect D.L. terminal to common ground(with detector). LED Disabled No ground to D.L. terminal (open circuit).
Avoid Curtain,Screen,etc. blocking detection area.
Avoid vapor or high humidity that can cause condensation.
Avoid direct sunlight.
Do not install outdoors.
Do not aim towards outside areas where there is frequent movement.
Do not mount in unstable location where vibration or shock may affect the detector.
Do not install unit near fluorescent lights.
Avoid mounting detector where movement of Fans or Air Conditioning can be detected.
Do not aim detection area towards equipment which continually moves in the detection area (i.e.curtain, blinds).
P.I.R. Sensor
Do not touchDo not touch
Do not touchDo not touch
Do not touch!
Do not touchDo not touch
Do not touchDo not touch
Do not touch!
Microwave Sensor
Select RANGE SELECTOR according to the room size. (SHORT or LONG)
MX-40 Series Select RANGE SELECTOR "SHORT" when it's used with 24ft (7 m)square and Smaller room.
MX-50 Series Select RANGE SELECTOR "SHORT" when it's used with 34ft (10m)square and Smaller room.
18mA (max.) at 12VDC 20mA (max.) at 12VDC
1. Pet Immunity is most effective on the following sized animals:Rodents = 0 to 4 inches high Cats and small to medium sized dogs = 0 to 16 inches high at normal room temperature.
2. Installation Instructions a. Mount between 7 and 8 ft. (For better immunity,
especially for medium sized dogs, mount as close to8ft. as possible.) b. Do not angle detector towards the ground or use the angle bracket. Mount flat on the wall or in the corner. c. For best pet immunity, limit the detectors field of view to30 ft. maximum in any direction. d. For rodents If any shelves within 15 ft.of the detector have a height that comes wihtin 2.5 ft.below the mounting height of the detector and rodents can access these areas, pet immunity will be reduced. Please select mounting location of detectors carefully to avoid this situation. e. For cats and dogs (16 inches in height or less at normalroom temperature) When a dog jumps up on desks, the detector may detect it. Adjust detection area to avoid such places. f. For cats If there are cats, any shelves in the detection area will reduce pet immunity. g. Pulse Count 4 is not required for Pet Immunity applications.Use 4 pulse only in harsh environment.
Power wires should not exceed the following lengths.
When using two or more units on one wire, the maximum length is obtained by dividing the maximum wire length listed above by the number of units used.
PROBLEM
REMEDYPROBABLE CAUSE
Correct the voltage supply to 9.5-16VDC .
LED does not light.
See Section 3. Turn on the Switch. (See Section 2 )
Incorrect power supply voltage.(disconnection, low voltage) Incorrect detection area. LED switch is OFF.
Moving object within area. (curtain,wall hanging, etc.)
LED lights even though no person is within area.
Remove the source from area, or change location of detector.
Remove object from detection area, or change location of detector.
Rapid temperature changes within area.(heater,air-conditioner, etc.)
7. TROUBLE SHOOTING AND MAINTENANCE
8. SPECIFICATIONS
Faulty wiring.
Wire correctly.
Check load of output. The unit needs repair or replacement.
LED lights but signal is not sent.
Relay contact is stuck or damaged due to overloading.
6. WIRING
*UL requires MX-40QZ,50QZ,40PI,40PT to be connected to a UL listed power supply capable of providing a nominal input of 12VDC , 20mA(max.) (at 12VDC )and battery standby time of 4 hours. *The equipment shall be installed in accordance with the National Electrical Code, NFPA 70.
*These features have been tested by Underwriters Laboratories.
5. PET IMMUNITY (MX-40PI/40PT Only)
*Specifications and design are subject to change without prior notice.
2140' (650m) 3400' (1020m) 5300' (1S00m)
WIRE GAUGE 12VDC
1070' (320m) 1 700' (510m)
27 00' (820m)
14VDC
AWG 22( 0.33mm )
2
2
AWG 20( 0.52mm )
2
AWG 18( 0.83mm )
4.INSTALLATION
a.Loosen fastening screw and remove cover. b.Release hook at bottom of P.C.B.unit. Remove P.C.B. unit from base. c.Route wires through knockouts along the wiring guide on the rear side of base. Mount base with supplied screws. When small animal immunity is required, refer to Section 5.When using a bracket,check matching knockout positionbefore opening mounting hole. d.Wire according to Section 6.
e.Fix P.C.B.unit into base. Supply power. Allow 1 min. to warm up. f.Conduct walktest and make adjustments. (Section 2) Fit cover using fastening screw.
FCC Notice : This equipment has been tested and found to comply with the limits for a field disturbance sensor, pursuant to Part 15 of the FCC Rules. The user is cautioned that changes or modifications not expressly approved by OPTEX could void the user's authority to operate this equipment.
TAMPERSP
DLALARM
DL TERMINAL
[MX-40QZ(BE)/
50QZ(BE) Only]
TAMPER( N.C. )
[MX-40QZ/50QZ/
40PT Only]
SPARE
[MX-40QZ/50QZ/
40PT Only]
ALARM OUTPUT ( N.C. )
POWER INPUT (9.5-16VDC )
Pulse Count Warm up period Power input Current draw Weight Operating temperature Environmental humidity Microwave Frequency RF interference D.L. Terminal
Approx. 20 sec 2 or 4
Approx. 1 min
9.5-16VDC
3.9 oz (110g)
-14°F - +131°F (-10 - +55°C) 95% max.
2.45GHz
No Alarm 20V/m
See Section 2
























MODEL
Detection method Coverage Detection zones Mounting Height Sensitivity Detection speed LED Alarm Ind i cat er Alarm period Alarm output Tamper switch
Passive Infrared and Microwave
40ft×40ft(12m×12m) 85°wide 50ft×50ft(15m×15m) 85°wide
78 zones(PIR)
5-8ft (1.5-2.4m) 7.5-10ft (2.2-3.0m)
3.6°F ( 2°C) at 2ft/sec (0.6m/sec) 1-5ft/sec (0.3-1.5m/sec)
Switch-able ON/OFF
Approx. 2.5 sec
N.C. , 28VDC 0.2A max.
N.C. , Open when cover is removed. (N.C. , 28VDC 0.1A max.)
MX-50QZ
MX-40QZ/PI/PT
This unit is designed to detect movement of an intruder and activate an alarm control panel. Being only a part of a conplete system,we cannot accept responsibility for any damages or other consequences resulting from an intrusion.The following statement will be provided with the equipment as required by Article 6.3 of the R&TTE Directive , 1999/5/EC. The Optex MX-40 and MX-50 are in conformity with all essential requirements of the R&TTE Directive (1999/5/EC). This equipment has been assessed to the following standardsW I-ETS 300 440:December 1995 ETS 300 683:June 1997 EN 60950: 1992, Incl Amdt 1-4, 11 This product is marked with which signifies conformity with Class II product requirements specified in the R&TTE Directive. The following table indicates the areas of intended use of the equipment and any known restrictions. For countries not included in this list, please consult the responsible Spectrum Management Agency.
NOTE
Country of intended use Restrictions Austria Belgium Denmark Finland France Germany Greece Ireland Italy Luxembourg The Netherlands Spain Sweden United Kingdom Other non EU : Iceland Norway Switzerland
2.450GHz
Loading...