Optex FTN-AM, FTN-ST Installation

Page 1
N219
CONTENTS
1 INTRODUCTION
1-1 BEFORE INSTALLATION ................2
1-2 PARTS IDENTIFICATION ................3
1-3 DETECTION AREA..........................3
2 INSTALLATION
2-1 INSTALLATION ................................4
3 WALK TEST
3-1 WALK TEST .....................................7
4-1 LED ..................................................8
4-2 ALARM OUTPUT .............................8
4-3 PIR SENSITIVITY ............................8
4-4 ANTI-MASKING ...............................8
5 OTHERS
5-1 WALL TAMPER (OPTION)
CONNECTION.................................9
5-2 EXAMPLE OF EOL WIRING .........10
5-3 LED LIGHT PATTERN ...................11
6 SPECIFICATIONS
6-1 SPECIFICATIONS .........................11
6-2 DIMENSIONS ................................12
FTN-ST Standard model with 2 PIRs FTN-AM FTN-ST with anti-masking
Compact design
190° adjustable bracket
Intelligent AND logic
Digital anti-masking (AM model)
Wall tamper (option)
NO.59-1645-0 091201
INSTALLATION INSTRUCTIONS
Compact outdoor detector
Compact outdoor detector
fit series
fit series
- 1 -
Page 2
1
INTRODUCTION
1-1
BEFORE INSTALLATION
Warning
Failure to follow the instructions provided with this indication and improper handling may cause death or serious injury.
Caution
Failure to follow the instructions provided with this indication and improper handling may cause injury and/or property damage.
The check mark indicates recommendation.
The nix sign indicates prohibition.
Warning
Caution
Do not remove the PCB. Do not touch the PCB except for the DIP switch.
ON
2 3 4
1
Mounting height. Keep the detector parallel to the
ground.
Consider the direction a person is approaching from, as well as the detection area.
Install the detector in a place where it is free from false alarm factors. For example:
Sunlight and reflection
Heat source
Objects moving in the wind
0.8 – 1.2 m (2'7" – 3'11")
Parallel
Tilt
- 2 -
Page 3
0
10
0'0'5'
5'
5'
10'
10'
10'
15'
15'
15'
2 3 4 5
1
1
1
2
3
4
5
(m)
(ft.)
(ft.)
(m)
2
4
5
3
1-2
PARTS IDENTIFICATION
-Optional accessories
Wall tamper (WRS-02)
Bracket
Sponge
Fixture
Main unit
Main unit cover
Lens
Screw kit
Screw (3 × 20 mm)
0' 5' 10' 15'
0.8
0
(m)
1.0
1.2
2'7"
0'
(ft.)
3'3" 3'11"
10 2 3 4 5
(m)
(ft.)
0' 5' 10' 15'
0.8
0
(m)
1.0
1.2 10 2 3 4 5
(m)
2'7"
0'
(ft.)
3'3" 3'11"
(ft.)
1-3
DETECTION AREA
Top view Side view
2 m detection length
5 m detection length
Adjustable range: 95° (by 5° pitch)
Adjustable range: 95° (by 5° pitch)
Sponge
- 3 -
Page 4
2
INSTALLATION
2-1
INSTALLATION
1
Open the main unit cover.
2
Remove the fixture.
FixtureFixture
3
Hold the top of the bracket lifted and
remove the main unit.
Bracket
Main unit
2
1
Bracket
Main unit
2
1
4
Put the wire extending from the wall
through the wiring hole in the bottom of the bracket, and mount the bracket on the wall.
Note>>
For wall tamper wiring (option), refer to page 9.
Screw (3 × 20 mm)
Screw (3 × 20 mm)
Mounting height:
0.8 – 1.2 m (2'7" – 3'11")
Sponge
Screw (3 × 20 mm)
Screw (3 × 20 mm)
Mounting height:
0.8 – 1.2 m (2'7" – 3'11")
Sponge
5
Pull the wire through the main unit. Lift the top of the bracket slightly and mount
the main unit to the bracket.
1
3
2
83.5 mm (3.29")
- 4 -
Page 5
6
Wire terminal connections.
Notes>>
Anti-masking output is recognized as TROUBLE. For EOL, refer to page 10.
-Power cable length
The power cable should be limited to the following length.
Unit: m (ft.)
Cable diameter
FTN-ST FTN-AM
12 V 14 V 12 V 14 V
AWG22 (0.33 mm2)
340
(1,120')
730
(2,400')
290
(950')
620
(2,030')
AWG20 (0.52 mm2)
530
(1,740')
1,160
(3,810')
450
(1,480')
980
(3,220')
AWG18 (0.83 mm2)
850
(2,790')
1,850
(6,070')
720
(2,360')
1,570
(5,150')
Power input (+)
Power input (-)
Alarm output
COM
Spare
Tamper
Power input (+)
Power input (-)
Alarm output
COM
Trouble output
Tamper
FTN-ST FTN-AM
Power input (+)
Power input (-)
Alarm output
COM
Spare
Tamper
Power input (+)
Power input (-)
Alarm output
COM
Trouble output
Tamper
FTN-ST FTN-AM
7
Determine the horizontal detection angle and attach the fixture.
Note>>
To make adjustments, remove the fixture.
Note>>
Check that the fixture and bracket engage correctly.
Note>>
Check that the fixture and bracket engage correctly.
Angle pitch: 5°
95°
95°
Angle pitch: 5°
95°
95°
+ -
AL C SP TP TP
+ -
AL C TR TP TP
- 5 -
Page 6
8
Determine the detection length. (2 m or 5 m)
If 2 m is required, rotate the lower lens 180 degrees.
Note>>
Do not remove the upper lens.
If 2 m is required, rotate the lower lens 180 degrees.
Note>>
Do not remove the upper lens.
5 m detection length (Factory default)
2 m detection length
Side view
0' 5' 10' 15'
0.8
0
(m)
1.0
1.2
2'7"
0'
(ft.)
3'3" 3'11"
10 2 3 4 5
(m)
(ft.)
0' 5' 10' 15'
2'7"
0'
(ft.)
3'3" 3'11"
0.8
0
(m)
1.0
1.2
(ft.)
10 2 3 4 5
(m)
Side view
5 m detection length (Factory default)
2 m detection length
Side view
0' 5' 10' 15'
0.8
0
(m)
1.0
1.2
2'7"
0'
(ft.)
3'3" 3'11"
10 2 3 4 5
(m)
(ft.)
0' 5' 10' 15'
2'7"
0'
(ft.)
3'3" 3'11"
0.8
0
(m)
1.0
1.2
(ft.)
10 2 3 4 5
(m)
Side view
9
Attach the main unit cover.
Note>>
To prepare for walk test, check that DIP switch 1 (LED) is set to “ON” before attaching the main unit cover.
10
Perform walk test.
For details, refer to page 7.
- 6 -
Page 7
3
If the LED does not need to be turned
on at all times, set the DIP switch 1 (LED) to “OFF”.
ON
1 2 3 4
ON
1 2 3 4
DIP switch
ON
1 2 3 4
ON
1 2 3 4
DIP switch
2
Check that LED lights for 2 seconds
when the intended object is detected.
1
Set DIP switch 1 (LED) to “ON”.
Note>>
The switch is set to “ON” by factory default.
ON
1 2 3 4
ON
1 2 3 4
DIP switch
ON
1 2 3 4
ON
1 2 3 4
DIP switch
3
WALK TEST
3-1
WALK TEST
Detected
Not detected
- 7 -
Page 8
4-1
LED
DIP switch 1
FTN-ST
FTN-AM
ON
1 2 3 4
ON
OFF
Position Function
ON
(Factory default)
LED ON
OFF LED OFF
4-2
ALARM OUTPUT
DIP switch 2
FTN-ST
FTN-AM
ON
1 2 3 4
N.O.
N.C.
Position Function
N.O. N.O. output
N.C.
(Factory default)
N.C. output
4-3
PIR SENSITIVITY
DIP switch 3
FTN-ST
FTN-AM
ON
1 2 3 4
STD
LOW
Position Function
STD
(Factory default)
Normal sensitivity
LOW Low sensitivity
4-4
ANTI-MASKING
DIP switch 4
FTN-ST
FTN-AM
ON
1 2 3 4
Position Function
ON
(Factory default)
ANTI-MASKING ON
OFF ANTI-MASKING OFF
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
●: Factory default
DIP switch
1 LED
2 ALARM OUTPUT
3 PIR SENSITIVITY
4 ANTI-MASKING
4
DIP SWITCH SETTING
ON
2 3 4
1
Do not touch the PCB except for the DIP switch and the terminal.
ON
OFF
- 8 -
Page 9
5-1
WALL TAMPER (OPTION) CONNECTION
Connect the tamper lead as shown below when connecting a wall tamper (option).
CAL+SP TP TP
Wall tamper (option) WRS-02
Twist and swage the wires.
Control panel
-ANTI-MASKING function
When masking condition continues more than 3 minutes, TROUBLE will be generated. TROUBLE is generated after 20 seconds under the anti-masking test mode.
Note>>
If a trouble is output (mal-detection of anti-masking) immediately after the operation has started, set the DIP switch 4 (ANTI-MASKING) to “OFF” and then to “ON”, and close the cover.
Teaching mode starts when the main unit cover are attached. Please be careful not to leave any object within 1 m from the unit.
ANTI-MASKING test mode
The trouble is output after 20 seconds.
Normal mode
The trouble is output after 3 minutes.
10 minutes
Teaching
1 minute
-Mounting position
Note>>
Pull the wire through the bracket before installing the wall tamper (option).
5
OTHERS
Bracket
Sponge
- 9 -
Page 10
1 2 3 4 5 6 7
Alarm relay Trouble relay Tamper
Tamper-EOL-ResistanceAlarm-EOL-Resistance
Control panel Control panel
Positive (+)
terminal
Negative (-)
terminal
Alarm
(N.C./N.O.)
COM Trouble (N.C.) Tamper (N.C.) Tamper (N.C.)
5-2
EXAMPLE OF EOL WIRING
Since the alarm and trouble outputs share the COM terminal, the wire connection should be made for the fit series detector according to the following diagram.
-Double EOL
-Triple EOL
1 2 3 4 5 6 7
Alarm relay Trouble relay Tamper
Tamper-EOL-ResistanceAlarm-EOL-Resistance
Control panel Control panel
Positive (+)
terminal
Negative (-)
terminal
Alarm
(N.C./N.O.)
COM Trouble (N.C.) Tamper (N.C.) Tamper (N.C.)
1 2 3 4 5 6 7
Alarm relay Trouble relay Tamper
Tamper-EOL­Resistance
Alarm-EOL­Resistance
Control panel Control panel
Positive (+)
terminal
Negative (-)
terminal
Alarm
(N.C./N.O.)
COM Trouble (N.C.) Tamper (N.C.) Tamper (N.C.)
Trouble-EOL­Resistance
- 10 -
Page 11
5-3
LED LIGHT PATTERN
The following explains the LED light pattern.
Detector condition LED indicator
Warm-up
Note>>
The LED blinks even if the DIP switch 4 (LED) is set to “OFF”.
• Blinks for approx. 60 seconds.
Alarm
Lights for 2 seconds.
Masking detection (FTN-RAM only)
Note>>
The LED blinks even if the DIP switch 4 (LED) is set to “OFF”.
Blinks 3 times and then repeats.
LED
Blink Light OFF
6
SPECIFICATIONS
6-1
SPECIFICATIONS
Model FTN-ST FTN-AM Detection method Passive infrared PIR coverage 5 × 1 m (16'5" × 3'3") Detection length limit 2 m, 5 m (6'7", 16'5") Detectable speed 0.3 – 1.5 m/s (1' – 4'11"/s) Sensitivity 2.0°C (at 0.6 m/s) (3.6°F (at 2'/s)) Operating voltage 9.5 – 18 V DC Current draw 17 mA (max.) (at 12 V DC)
20 mA (max.) (at 12 V DC) Alarm period 2.0 ±1.0 sec. Warm-up period Approx. 60 sec. (LED blinks) Alarm output N.C./N.O. Selectable 28 V DC 0.1 A (max.) Trouble output N.C. 28 V DC 0.1 A (max.), open when the cover is removed. LED indicator Light/Blink: Warm-up, alarm, masking detection (FTN-AM only) Operation temperature -20 – +60°C (-4 – +140°F) Environment humidity 95% max. Weatherproof IP55 Mounting Wall (Outdoor, Indoor) Mounting height 0.8 – 1.2 m (2'7" – 3'11") Weight 100 g (3.5 oz.) Accessories Screw (3 × 20 mm) × 2
*Specifications and design are subject to change without prior notice.
- 11 -
Page 12
6-2
DIMENSIONS
Unit: mm (inch)
35 (1.38") 42.5 (1.67")
155 (6.10")
Unit: mm (inch)
35 (1.38") 42.5 (1.67")
155 (6.10")
OPTEX INCORPORATED (USA)
TEL:+1-909-993-5770 Tech:(800)966-7839 URL:http://www.optexamerica.com/
OPTEX KOREA CO., LTD. (KOREA)
TEL:+82-2-719-5971 URL:http://www.optexkorea.com/
OPTEX SECURITY Sp. z o. o. (POLAND)
TEL:+48-22-598-06-55 URL:http://www.optex.com.pl/
OPTEX (DONGGUAN) CO., LTD. SHENZHEN OFFICE (CHINA)
TEL:+86-755-33302950 URL:http://www.optexchina.com/
OPTEX CO., LTD. (JAPAN)
(ISO 9001 Certified) (ISO 14001 Certified)
5-8-12 Ogoto Otsu Shiga 520-0101 JAPAN TEL:+81-77-579-8670 FAX:+81-77-579-8190 URL:http://www.optex.co.jp/e/
OPTEX (EUROPE) LTD. (UK)
TEL:+44-1628-631000 URL:http://www.optexeurope.com/
OPTEX SECURITY SAS (FRANCE)
TEL:+33-437-55-50-50 URL:http://www.optex-security.com/
Note>>
These units are designed to detect an intruder and activate an alarm control panel. Being only a part of a complete system, we cannot accept responsibility for any damages or other consequences resulting from an intrusion. These products confirm to the EMC Directive 2004/108/EC.
- 12 -