Oppermann Regelgeräte KRM-1, KRM-2, KRM-2-MOD Technical Data Manual

Duct Smoke Sensor KRM®
Technical Data
Sensor: Scattering RM 3.3 (ALK-E) Supply voltage KRM-1: 230 V AC ± 10 %, 50/60 Hz Supply voltage KRM-2/KRM-2-MOD: 24 V AC/DC +15 % / -10 % Rated current: KRM-1: 30 mA
KRM-2/KRM-2-MOD: 120 mA
Relay outputs: oating Alarm relay locked: 1 changeover contact, 8 A,
250 V AC or 24 V DC
1 NC, 8 A, 250 V AC or 24 V DC
Contamination relay: Operating temperature: Permissible humidity: Protection class:
(water resistant housing)
Approvals: Sensing chamber and air duct frames: VdS approval G210059 Tested:
according to FprEN54-27
LED display:
at > 70 %
LED in housing:
blue lack of air ow yellow failure, electronics, smoke detector defective, low voltage red smoke alarm, including contamination > 99 %, ashes at attempts to release when the sensing chamber is not empty
Adaptergehäuse: ABS Air measuring tube:
shortest length 160 mm standard length 600 mm
Dimensions: Screw connection:
% contamination level ashes
257 x 166 x 77 mm (L x W x H)
1 NC contact, 6 A, 250 V AC or 24 V DC
-10 °C - +50 °C
10 - 95 % non-condensing
IP 54, IP 65 with WDG
green operating
Aluminium / plastic
3 x M16
VdS certication (G210059)
Patented single tube air sampling system
Contamination display in %
and signalling at 100 %
Electronic air ow control
Externally operable reset button in the
housing
Remote reset option via terminals
Long service life, low contamination
Accessories
Mounting bracket: KS (for insulated / circular ducts) Housing: waterresistant housing for outdoor
installation and increasing protection class to IP 65
Function
The KRM duct smoke detector is designed for smoke detection in ventilation ducts. It constitutes a combination of a smoke detector with an adapter system, whose measuring tube and housing have been specially adapted for optimal air ow through the smoke detector. The multi-chamber measuring tube in the air duct transports the air within the air duct along the entire length of the tube, through the sensing chamber and back into the air duct. Upon detection of smoke, the sensor reacts immediately and triggers an alarm. Over time, the sensor becomes contaminated. Because of alarm threshold tracking, the sensitivity up to total pollution remains the same. From 70 % contamination upwards, the sensor is trig­gered and indicates this by ashing. If the sensor is not replaced the smoke alarm is triggered at 99 % contamination. The contamination level is indicated in a two-line LED display; at > 70 % it ashes. To verify operability, the device is equipped with electronic air ow monitoring, which lights a blue LED at < 1 m/s. The failure LED illuminates when the smoke sensor or the electronics are defective, in the absence of a smoke sensor, and with short­circuits or cable breakage. The smoke alarm must be released with the reset button. A functionality test is also possible with the same button. The operation functions like a smoke alarm. Furthermore, the same function takes place on restart or when the bridge circuit between terminals 9 and 10 is opened (remote release).
Fire Protection | Data sheet No. 41300 | Version 01-2011 | 1 | 8
Duct Smoke Sensor KRM
10
9
11
12
13
8
6
5
7
1
14
Electrical connection
Power supply 230 V AC
Test/Reset
1 2
3 4
9 10 11 12 13 14
15 16 17
4
2
3
Power supply 230 V AC
Smoke alarm
Service signal Contamination
14
11
9
10
Smoke alarm
Test/Reset
green
red
yellow
13
12
1 Adapter plate with gasket 2 Patented measuring tube (max. length 3 m) 3 End cap 4 Rubber bushing (only for insulated or circular ducts) 5 Lower housing with seal 6 Electronics 7 Optical smoke sensor 8 Upper casing with seal 9 Red LED: alarm / reset button 10 Yellow LED: interference 11 LED display: % of sensor contamination 12 LED green: in operation 13 LED blue: air ow under 1 m / s 14 Opening for test gas 15 Air duct
10 11 12 13 14
15 16 17
1 2
3 4
9
Power supply 230 V AC
Smoke alarm
Smoke alarm
Service signal Contamination
Power supply 24 V AC/DC
Test/Reset
green
Test/Reset
red
yellow
blue
Power supply 24 V AC/DC
Test/Reset
KRM-2-MOD, 24 V
10 11 12 13 14
15 16 17
1
2
3
4
5
6
7
8
9
KRM-1
Bus B
Bus B Bus A
Bus A
Power supply 24 V AC/DC
Smoke alarm
Smoke alarm
Service signal Contamination
Test/Reset
blue
green
red
yellow
KRM-2, 24 VKRM-1, 230 V
KRM-2
Programming the Bus address for the KRM-2-Mod:
Press buttons T3+T4 on the circuit board (to the right, next to the display) at the same time, so that the display changes from con­tamination level to show the bus address (the display will ash). Press button T3 or T4 to adjust the desired address (1-99). The last set bus address is automatically saved. The display resets automa­tically after 3 seconds or by simultaneously pressing T3+T4.
Contact depictions are with the power o (alarm)
KRM-2-MOD
Notes: The oating switching contacts (terminals 11-17) are uniformly assigned to an installation category according to EN 60730-1.
blue
These switching contacts are only to be used for 230 V AC or 24 V AC/DC, a combination is not permitted. A mixed connection of safety extra-low voltage (SELV) and low voltage must not occur. The assembly may only be operated on one mains phase.
2 | 8 | Fire Protection | Data sheet No. 41300 | Version 01-2011
Duct Smoke Sensor KRM
Installation Instructions
Install the detector where ow meters, etc. are normally xed, so that the air ow can run in a laminar manner with the measu­ring tube. Follow the installation instructions. All work must be carried out by suciently qualied craftsman.
Current local rules and regulations (e.g. building regulations, elecrical/VDE guidelines, etc.) are to be observed. Installers and operators are required to be adequately informed before operation. We assume no liability for misprints and changes after printing. Compliance with operating and installation instructions is also included within the regulations of intended use. We assume no liability for damages caused by improper use. Operating licenses and guarantees and all warranty claims will be voided in the event of unauthorized modications or any tampering with the device.
Maintenance
Targeted maintenance can be carried out since the smoke detector is equipped with a contamination indicator. From a 70 % contamination level or higher the smoke sensor must be changed. There is a contact available for this signal, and it should be connected to the automation station.
Accessories
Splash-proof housing (type WDG) for outdoor installation to prevent condensation. The housing is lined with insula­ting foam.
Mounting bracket
Type KS is required if the duct smoke sensor must be moun­ted on round air ducts. The bracket can also be used with insulated rectangular ducts. For this the adapter is moun­ted with the air measuring tube before insulation.
Installation and positioning
1.
We recommend that the duct smoke detector be installed at the same distance to heating, cooling and humidity equipment and be mounted similarly to ow sensors. The distance of the smoke sensor to ttings, valves, lters, etc., should be 3 times the diago­nal length of the cross-section of the duct when going against the air ow, and 5 times the diagonal length with the ow.
2.
Drill a hole of 43-44 mm in diameter at the intended mounting location.
Note: Installation of the TurboTube measuring tube is possible either from the top, bottom or side of the channel for all duct cross-sections (for round ducts as well).
Fire Protection | Data sheet No. 41300 | Version 01-2011 | 3 | 8
3.
Determine how long the measuring tube must be.
The TurboTube measuring tube must be inserted into the duct at least to the middle of the duct‘s cross-section.
If necessary, shorten the tube. Minimum length 160 mm.
Deburr the cutting face and put the end plug back on up
to the stop collar.
Min. 160 mm Attention:
Operation without end plug not permitted.
Loading...
+ 5 hidden pages