Oppermann Regelgeräte KRM-1, KRM-2, KRM-2-MOD Technical Data Manual

Duct Smoke Sensor KRM®
Technical Data
Sensor: Scattering RM 3.3 (ALK-E) Supply voltage KRM-1: 230 V AC ± 10 %, 50/60 Hz Supply voltage KRM-2/KRM-2-MOD: 24 V AC/DC +15 % / -10 % Rated current: KRM-1: 30 mA
KRM-2/KRM-2-MOD: 120 mA
Relay outputs: oating Alarm relay locked: 1 changeover contact, 8 A,
250 V AC or 24 V DC
1 NC, 8 A, 250 V AC or 24 V DC
Contamination relay: Operating temperature: Permissible humidity: Protection class:
(water resistant housing)
Approvals: Sensing chamber and air duct frames: VdS approval G210059 Tested:
according to FprEN54-27
LED display:
at > 70 %
LED in housing:
blue lack of air ow yellow failure, electronics, smoke detector defective, low voltage red smoke alarm, including contamination > 99 %, ashes at attempts to release when the sensing chamber is not empty
Adaptergehäuse: ABS Air measuring tube:
shortest length 160 mm standard length 600 mm
Dimensions: Screw connection:
% contamination level ashes
257 x 166 x 77 mm (L x W x H)
1 NC contact, 6 A, 250 V AC or 24 V DC
-10 °C - +50 °C
10 - 95 % non-condensing
IP 54, IP 65 with WDG
green operating
Aluminium / plastic
3 x M16
VdS certication (G210059)
Patented single tube air sampling system
Contamination display in %
and signalling at 100 %
Electronic air ow control
Externally operable reset button in the
housing
Remote reset option via terminals
Long service life, low contamination
Accessories
Mounting bracket: KS (for insulated / circular ducts) Housing: waterresistant housing for outdoor
installation and increasing protection class to IP 65
Function
The KRM duct smoke detector is designed for smoke detection in ventilation ducts. It constitutes a combination of a smoke detector with an adapter system, whose measuring tube and housing have been specially adapted for optimal air ow through the smoke detector. The multi-chamber measuring tube in the air duct transports the air within the air duct along the entire length of the tube, through the sensing chamber and back into the air duct. Upon detection of smoke, the sensor reacts immediately and triggers an alarm. Over time, the sensor becomes contaminated. Because of alarm threshold tracking, the sensitivity up to total pollution remains the same. From 70 % contamination upwards, the sensor is trig­gered and indicates this by ashing. If the sensor is not replaced the smoke alarm is triggered at 99 % contamination. The contamination level is indicated in a two-line LED display; at > 70 % it ashes. To verify operability, the device is equipped with electronic air ow monitoring, which lights a blue LED at < 1 m/s. The failure LED illuminates when the smoke sensor or the electronics are defective, in the absence of a smoke sensor, and with short­circuits or cable breakage. The smoke alarm must be released with the reset button. A functionality test is also possible with the same button. The operation functions like a smoke alarm. Furthermore, the same function takes place on restart or when the bridge circuit between terminals 9 and 10 is opened (remote release).
Fire Protection | Data sheet No. 41300 | Version 01-2011 | 1 | 8
Duct Smoke Sensor KRM
10
9
11
12
13
8
6
5
7
1
14
Electrical connection
Power supply 230 V AC
Test/Reset
1 2
3 4
9 10 11 12 13 14
15 16 17
4
2
3
Power supply 230 V AC
Smoke alarm
Service signal Contamination
14
11
9
10
Smoke alarm
Test/Reset
green
red
yellow
13
12
1 Adapter plate with gasket 2 Patented measuring tube (max. length 3 m) 3 End cap 4 Rubber bushing (only for insulated or circular ducts) 5 Lower housing with seal 6 Electronics 7 Optical smoke sensor 8 Upper casing with seal 9 Red LED: alarm / reset button 10 Yellow LED: interference 11 LED display: % of sensor contamination 12 LED green: in operation 13 LED blue: air ow under 1 m / s 14 Opening for test gas 15 Air duct
10 11 12 13 14
15 16 17
1 2
3 4
9
Power supply 230 V AC
Smoke alarm
Smoke alarm
Service signal Contamination
Power supply 24 V AC/DC
Test/Reset
green
Test/Reset
red
yellow
blue
Power supply 24 V AC/DC
Test/Reset
KRM-2-MOD, 24 V
10 11 12 13 14
15 16 17
1
2
3
4
5
6
7
8
9
KRM-1
Bus B
Bus B Bus A
Bus A
Power supply 24 V AC/DC
Smoke alarm
Smoke alarm
Service signal Contamination
Test/Reset
blue
green
red
yellow
KRM-2, 24 VKRM-1, 230 V
KRM-2
Programming the Bus address for the KRM-2-Mod:
Press buttons T3+T4 on the circuit board (to the right, next to the display) at the same time, so that the display changes from con­tamination level to show the bus address (the display will ash). Press button T3 or T4 to adjust the desired address (1-99). The last set bus address is automatically saved. The display resets automa­tically after 3 seconds or by simultaneously pressing T3+T4.
Contact depictions are with the power o (alarm)
KRM-2-MOD
Notes: The oating switching contacts (terminals 11-17) are uniformly assigned to an installation category according to EN 60730-1.
blue
These switching contacts are only to be used for 230 V AC or 24 V AC/DC, a combination is not permitted. A mixed connection of safety extra-low voltage (SELV) and low voltage must not occur. The assembly may only be operated on one mains phase.
2 | 8 | Fire Protection | Data sheet No. 41300 | Version 01-2011
Duct Smoke Sensor KRM
Installation Instructions
Install the detector where ow meters, etc. are normally xed, so that the air ow can run in a laminar manner with the measu­ring tube. Follow the installation instructions. All work must be carried out by suciently qualied craftsman.
Current local rules and regulations (e.g. building regulations, elecrical/VDE guidelines, etc.) are to be observed. Installers and operators are required to be adequately informed before operation. We assume no liability for misprints and changes after printing. Compliance with operating and installation instructions is also included within the regulations of intended use. We assume no liability for damages caused by improper use. Operating licenses and guarantees and all warranty claims will be voided in the event of unauthorized modications or any tampering with the device.
Maintenance
Targeted maintenance can be carried out since the smoke detector is equipped with a contamination indicator. From a 70 % contamination level or higher the smoke sensor must be changed. There is a contact available for this signal, and it should be connected to the automation station.
Accessories
Splash-proof housing (type WDG) for outdoor installation to prevent condensation. The housing is lined with insula­ting foam.
Mounting bracket
Type KS is required if the duct smoke sensor must be moun­ted on round air ducts. The bracket can also be used with insulated rectangular ducts. For this the adapter is moun­ted with the air measuring tube before insulation.
Installation and positioning
1.
We recommend that the duct smoke detector be installed at the same distance to heating, cooling and humidity equipment and be mounted similarly to ow sensors. The distance of the smoke sensor to ttings, valves, lters, etc., should be 3 times the diago­nal length of the cross-section of the duct when going against the air ow, and 5 times the diagonal length with the ow.
2.
Drill a hole of 43-44 mm in diameter at the intended mounting location.
Note: Installation of the TurboTube measuring tube is possible either from the top, bottom or side of the channel for all duct cross-sections (for round ducts as well).
Fire Protection | Data sheet No. 41300 | Version 01-2011 | 3 | 8
3.
Determine how long the measuring tube must be.
The TurboTube measuring tube must be inserted into the duct at least to the middle of the duct‘s cross-section.
If necessary, shorten the tube. Minimum length 160 mm.
Deburr the cutting face and put the end plug back on up
to the stop collar.
Min. 160 mm Attention:
Operation without end plug not permitted.
4.
Determine the direction of ow and t the adapter plate
so that the line on the adapter plate under the text „Strömungsrichtung“ is parallel to the ow direction.
Four self-tapping screws serve for attaching it to the sheet
metal duct (not included in delivery).
5. Installation on a rectangular air duct
Installation on a circular air duct
6.
For mounting on a circular air duct use mounting bracket
type KS and the rubber bushing rations they can be adapted to a round duct.
. Thanks to the bend perfo-
Duct Smoke Sensor KRM
Mounting bracket
The type KS mounting bracket is supplied at.
7. Installation on air ducts with insulation
Use the rubber bushing and insert it into the Ø 43-44mm
opening in the air duct.
Install the mounting bracket.
Insert the assembled adapter plate into the measuring tube
by sliding the measuring tube through the grommet, and screw the adapter plate onto the mounting bracket using the 4 self-tapping screws. Then the insulation can be installed.
8. Installation outdoors or in a cold environment
As protection for smoke detectors, which are exposed to the
open air or in a cold environment, there is a special WDG type housing. This enclosure prevents the warm air in the smoke detector duct from condensing.
inner
Rubber bushing
Mounting bracket Insulation
outer
4 | 8 | Fire Protection | Data sheet No. 41300 | Version 01-2011
9. Installing the housing with the sensor
Attach the housing bottom part with the electronics and sensor
to the adapter plate. The housing can be attached at incre­ments of 90 °. The direction of the housing has no eect on the measurement result. You can align the housing with the sensor optimally.
Check that the seals in the housing upper part are correctly
positioned.
By snapping on and tightening the upper housing and then
rmly pressing down on the arrow marked on the central cable area (to ensure that the catch at the lower end of the housing snaps in correctly) the mounting is complete.
10. Testing the duct smoke sensor
After completing the installation work, doing proper wiring
and applying power, the duct smoke sensor is operational.
The green LED (12) illuminates.
By pressing the alarm/reset button (9), an initial simple
functional test can be made. All LEDs must light up and all the relays drop out. The units connected to the relays are activa­ted! The display (11) indicates the current degree of sensor contamination. If the button is released, all LEDs will go out except for LED (12) which shows the supply voltage, and the relays activate.
For testing the smoke sensor the housing must not be
opened. It has a self-closing test opening (14) in the center of the transparent cover. Use Oppermann test gas spray. Insert the test spray‘s tube fully into the test opening (appx.1.5mm deep) and release as much test gas as needed until the smoke sensor activates. The alarm/reset button lights up, the relays drop out. The electronics are on alert and locked. To release, the alarm/reset button must be pressed. At the time of the reset, the sensor must be free of smoke and test gas. Should there still be test gas in the chamber a higher degree of con­tamination will appear. In this case, after some time perform a reset by disconnecting from the power or by an external reset.
Duct Smoke Sensor KRM
11. Final review
Are all screws tight?
Is the adapter plate properly mounted for the ow direction?
Are all seals in the correct position?
In operation, when air ow > 1 m/s the blue LED may not
light up.
Fire Protection | Data sheet No. 41300 | Version 01-2011 | 5 | 8
Duct Smoke Sensor KRM
Display and operation for Duct Smoke Sensor KRM
LED Smoke alarm (red) LED Smoke alarm (red)
LED Failure (yellow) LED Power supply
(green)
LED Alarm (red) and Alarm / reset button
Failure reset: Briey press button and release
Alarm reset: Press button for at least 2 seconds until the red LED goes out
Display Meaning Comments
Shortly after starting the software version is displayed (4 digits),
Start / calibration
Contamination
in %
00 – 99
e.g. 00 then 17 = Software 0017. Thereafter, the rotating segment display follows at startup or after a power failure.
Flashes starting at 70 %; at 99 % with display LED alarm.
LED Air ow (blue)
e.g. Missing smoke detector, disrupted communication with the smoke detector,
Failure
88
00 – 99
ashing
6 | 8 | Fire Protection | Data sheet No. 41300 | Version 01-2011
Conrmation
reset / new start
BUS adresse
processor failure. Failure LED & alarm LED light up at the same time (not on the DIBT version). Troubleshooting: Change the detector and conrm by pressing the alarm / reset button.
If alarm / reset button is pressed for more than 8 seconds, or if terminal 9 / 10 is open (missing bridge circuit or remote reset). Display goes out after releasing the alarm / reset button
Display only with MOD versions after pressing the address buttons T3 / T4 directly on the circuit board.
LEDs Meaning Comments
Reset after failure:
Briey press alarm / reset button. KRM immediately restarts.
Alarm / reset
(red)
Smoke alarm or
failure (not on
the DIBT version)
Reset after alarm:
Press and hold the alarm / reset button for at least 2 seconds until the red alarm LED in the button goes out. Do not release it until then. KRM will start again only after release. As long as the alarm / reset LED ashes when the button is pressed, the smoke sensor is still lled with test gas / test spray / smoke, and can not be reset. In that case blow the sensor out or wait.
Duct Smoke Sensor KRM
Failure
(yellow)
Smoke alarm
(2 x red)
Power
(green)
Air ow
(blue)
Defective circuit
board or missing
smoke alarm
Smoke alarm
or contamination
99 %
Supply voltage
is on
Air ow is too
low
Check / replace circuit board or smoke detector RM 3.3 (ALK-E)
Red LEDs directly on the smoke detector RM 3.3 (ALK-E). Red LEDs directly on the smoke detector RM 3.3 (ALK-E). LEDs permanently on until reset has taken place.
Green LED lights up if supply voltage is on
Blue LED lights up when air ow is too low. Check smoke detector position in the duct, check sampling tube (TurboTube) for contamination / clean if necessary.
Behavior of the alarm relay and fault relay and displays, plus reset options
Smoke alarm Device failure / missing detector…
DIBT versions
KRM-1-DZ / KRM-2-DZ
Alarm relay
11 / 12 / 13
Relais Alarm
14 / 15
LED
Alarm / Reset
Relay failure
18 / 19
LED failure Does not light up Does not light up Lights up Lights up
Alarm reset or
failure reset
Drops out Drops out Does not drop out Drops out
Drops out Drops out Does not drop out Drops out
Lights up Lights up Does not light up Lights up
Does not drop out
Not with power
interruption!
It is mandatory to use
the alarm button or ter-
minal 9 / 10 provided that
sensing chamber is free.
KRM-1 / KRM-2
KRM-2-MOD
---------
Not equipped
With power interruption,
alarm button or with
terminal 9 / 10 provided
that sensing chamber
is free.
DIBT versions
KRM-1-DZ / KRM-2-DZ
Drops out
Not with power
interruption!
It is mandatory to use
the alarm button or ter­minal 9 / 10 provided that sensing chamber is free +
disturbance has ceased.
KRM-1 / KRM-2
KRM-2-MOD
---------
Not equipped
With power interruption,
alarm button or with
terminal 9 / 10 provided
that sensing chamber
is free + disturbance has
ceased.
Fire Protection | Data sheet No. 41300 | Version 01-2011 | 7 | 8
Dimensions
Duct Smoke Sensor KRM
166
233
77
40
24
70
37.3
L= 160 - 3000 mm
50
Dimensions in mm
Oppermann Regelgeräte GmbH | Im Spitzhau 1 | 70771 Leinfelden-Echterdingen, Germany
Phone +49 711 72 72 35 60 | Fax +49 711 72 80 52 7 | info@oppermann-regelgeraete.de | www.oppermann-regelgeraete.de
8 | 8 | Fire Protection | Data sheet No. 41300 | Version 01-2011 Specications subject to change.