Opop H 418, H 430, H 440, H 460, Comfort User Manual

Content list: Site 2: INSTALLATION GUIDE FOR OPOP BOILER Site 3: INSTALLATION GUIDE FOR OPOP / NBE BOILER Site 4: BOILER INSTALLATION GUIDE Site 5: SETTING BY WEIGHT Site 6-11: USER GUIDE Site 12: EXTENDED SET-UP GUIDE Site 13: CLEANING GUIDE Site 14: MAINTAIN GUIDE Site 15: TROUBLESHOOTING Site 16-17: ELECTRICAL WIRING DIAGRAMS Site 18: ACCESSORIES Site 19: WARANTY Site 20: MOUNTING THE PELLET HOPPER Site 21: EXCEPTION FOR PRESSURE EXPANSION Side 22: EC DECLARATION OF CONFORMITY
EN 303-5 approved by DTI (Danish Technological Institute) Approved for pressure expansion Energy class AA
Wood Pellets Burner
Version 6
Installing the burner into the boiler:
1. Install the burner on the side of the boiler (there should be no shield on the burner, when using the comfort boiler ).
2. Fit the controls either on the cabinet or on the wall.
3. Install the overheating safety cut off into the pocket on the side of the boiler, and connect the
controls so that the overheating safety cut off will cut the power if the boiler overheats.
4. Install the heat sensor on the output flow, either in the pocket or by the sensor on the output flow. (The sensor must be insulated to the output flow.)
5. Fit the pipe on the drop shaft.
6. Fit the hopper and auger so that the pipe slopes.
(PELLETS MUST NOT GET STUCK IN THE PIPE.)
General guidelines:
The boiler should be installed by an authorized fitter and must be installed in accordance with work supervision publication 42 ( Danish ) covering equipment working with water. The outlet duct should be no longer than 1m, and should be fitted with a cleaning door. The chimney draught should be at least 5 PA and should be stable, a draught stabilizer should always be installed. If combustion gases condense in the chimney (wet ash) install a draught stabilizer in the chimney, or open the flue (the flap inside at the back of the boiler) as wide as possible to increase the temperature of the smoke. The boiler must be spanned with a bypass to ensure the back flow is always kept above 45 degrees.
Manual
NBE pellet system
INSTALLATION GUIDE FOR OPOP BOILER
Diag. Example of installation
OPOP H 418 H 430 H 440 H 460 Comfort
A Height 865 1005 1025 1105 1145 B Depth 670 670 830 910 730 C Width without burner 386 490 550 850
700
D Height smoke pipes 635 755 890 860 770 E Height Returns 99 99 215 200 230 F Height Output 781 921 1150 1045 930 G Boiler feet deep 470 470 710 640 620 H Boiler feet Wide 316 420 510 750 670 Hole to burner H x B 120x120 195x175 150x150 235x240 120x120 Smoke tube outer D 130 130 158 158 130 Pipe connections 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4
Installing the burner into the boiler:
1. Install the burner on the side of the boiler
(there should be no shield on the burner, when using the comfort boiler ).
2. Fit the controls either on the cabinet or on the wall.
3. Install the overheating safety cut off into the pocket on the side of the boiler, and connect the
controls so that the overheating safety cut off will cut the power if the boiler overheats.
4. Install the heat sensor on the output flow, either in the pocket or by the sensor on the output flow. (The sensor must be insulated to the output flow.)
5. Fit the pipe on the drop shaft.
6. Fit the hopper and auger so that the pipe slopes.
(PELLETS MUST NOT GET STUCK IN THE PIPE.)
General guidelines:
The boiler should be installed by an authorized fitter and must be installed in accordance with work supervision publication 42 ( Danish ) covering equipment working with water. The outlet duct should be no longer than 1m, and should be fitted with a cleaning door. The chimney draught should be at least 5 PA and should be stable, a draught stabilizer should always be installed. If combustion gases condense in the chimney (wet ash) install a draught stabilizer in the chimney, or open the flue (the flap inside at the back of the boiler) as wide as possible to increase the temperature of the smoke. The boiler must be spanned with a bypass to ensure the back flow is always kept above 45 degrees.
Manual
NBE pellet system
INSTALLATION GUIDE FOR OPOP / NBE BOILER
Diag. Example of installation
NBE / OPOP 30 S 60 M 80 L
A Height 1142 1272 1272
B Depth 750 896 1003
C Width without burner 513 643 743
D Height smoke pipes 885 997 997
E Height Returns 276 276 283
F Height Output 1030 1161 1154
Smoke tube outer D 130 150 180
Pipe connections 3/4” 1” 1 ¼”
Pipe connections ½” ½” ½”
Weight 250 300 350
Water content 75 105 125
Hole to burner H x B 152x132 180x180 248x248
Manual
NBE pellet system
BOILER INSTALLATION GUIDE
Installing into boiler:
1. Check that the burner is undamaged.
2. Fit the burner and tighten it firmly using the two wing nuts supplied.
3. Ensure that the burner is in a horizontal position and all connections are tight.
4. Fit the cover and the plug.
5. Wire up the overheating safety fuse following the electrical wiring diagram.
Outer auger:
6. Install the auger through the opening over the burner.
7. Ensure that the pipe slopes enough to allow the pellets to fall into the burner.
When using for the first time:
8. Make sure there are enough pellets by the entrance to the outer auger.
9. Force-start the auger by holding down the UP button by the power input point.
10. If the pellets fall into the combustion chamber, turn off again by pressing DOWN. Then restart the burner using electrical ignition.
Turning off the alarm:
11. If the alarm goes off or the burner will not start, Press down button to reset alarm
Manual
NBE pellet system
SETTING BY WEIGHT
Unplug the burner and force-run the auger until pellets start to come out of it, continue for 15 minutes.
Then weigh the amount of pellets after 360 seconds and enter the result into the controls as the capacity of the auger.
Once again plug in the burner and start it.
There can be 3 run mode to see in the display You change by pressing up / down
RUN MODE 1:
Boiler temp./ Smoke temp. / Hot water temp. Return temp./ Tank content / Light sensor / Kwh / Clock mode. Circulation Pump / 3 way valve. / Ignition. When making ignition, you can see time counting down.
RUN MODE 2:
Boiler temp. / Return temp. / Smoke temp. / O2 %. Flow system. / Kwh / light sensor. / Burner temp. Circulation Pump / Ignition When making ignition, you can see time counting down.
RUN MODE 3:
Watt pr m2. / Outside temp. / Tank content /Total hour / Total use of pellets. / Time
Press SET and the display will show SETUP for standard settings. The UP button is used to increase the setting and for force-running the auger ( hold for longer than 5 seconds ). To force run the auger for an long time , hold UP button while switching power to control box The DOWN button is used to decrease the setting and switch the controls on/off ( hold for 10 seconds ). Resets alarms.
.
Manual
NBE pellet system
USER GUIDE
BOILER TEMP.
Setting the required boiler temperature. The burner sets the performance higher or lower depending on the figure entered ( set point ).
DIFFERENCE TEMP.
The setting defining how far the boiler temperature, can go over set point before pause or stop.
HOT WATER TEMP.
Setting the required hot water temperature. Only to be adjusted if hot water temp. sensor and 3 way valve is fitted. and activated in accessories in the Tech Setup. ( 3 way valve on L5 or L6 )
DIF. HOTWATER
The setting defining how far the temperature can drop, before starting making hot water again.
PUMP STOP TEMP.
The setting defining what temperature the pump stops, pump will always run, when the pellets burner is burning. Must be activated in accessories in the Tech Setup ( pump on L5 or L6 )
SUMMER STOP .
The setting defining what outside temperature the burner stops, . An outside temperature sensor must be fitted in T5
SUN STOP .
The setting defining how power full the sun must be before the burner stops, . An W/m2 sensor must be fitted in T6
CALIBRETING SUN STOP .
The sensor calibrating it self to 1000w/m2 If it is out of range it can be done manual.
Temperature
Magazine
Auto combustion
Man. combustion
Timer
Cleaning / power
O2 Control
Manual
NBE pellet system
USER GUIDE
ACTUAL CONTENT
Adjusting the content of the magazine.
RESET CONSUMPT.
Putting the pellets kg counter to zero.
SCREW CAPACITY
After setting the auger performance in 360 seconds the control will automatically calculate the amount of pellets in low power and high power, pellets in pause , and pellets for ignition Under normal conditions these numbers will be correct. To increase combustion, set the value DOWN. To reduce combustion, set the value UP.
CHIMNEY DRAUGHT
With a strong chimney draught the ventilator performance will be higher, At low steam and during pause. If the amount of chimney draught is increased, the automatic calculation sets more pellets in low steam and during pause. The smaller the chimney draught and the greater the back pressure of the boiler, the lower the value must be. The greater the chimney draught and the lower the back pressure of the boiler, the higher the value must be
YES/NO
Switching automatic calculations on/off. If automatic calculation is on, only the auger performance can be set.
PELLETS LOW
Setting the amount of pellets for low performance. Should be set so there is a flame when running 10% power. NOTE: can only be adjusted if auto combustion is on NO
PELLETS HIGH
Setting the amount of pellets for full performance. Should be set so that combustion is powerful when running at 100% power. NOTE: can only be adjusted if auto combustion is on NO
PAUSE PELLETS
Setting the amount of pellets for during lag. If in doubts about the settings, use the automatic calculation program. NOTE: can only be adjusted if auto combustion is on NO
STARTS / MINUTE
Setting how many time auger is running / minute.
Temperature
Magazine
Auto combustion
Man. combustion
Timer
Cleaning / power
O2 Control
Temperature
Magazine
Auto combustion
Man. combustion
Timer
Cleaning / power
O2 Control
Temperature
Magazine
Auto combustion
Man. combustion
Timer
Cleaning / power
O2 Control