Onset WNB-3D Operating Manual

WattNode® Pulse Output kWh Transducer Connection Instructions
For use with HOBO® H21, H22, U30, UX90, UX120, and RX3000 series data loggers, and HOBO data nodes
Applies to these WattNode Pulse Output kWh Transducers:
Onset Part No. Configuration / VAC Output Maximum Pulse Output WattNode Part No.
T-WNB-3Y-208 Single-phase 120 or
Wye 208-240
T-WNB-3Y-208-P Single-phase 120 or
Wye 208-240
T-WNB-3D-240 Delta 208-240 Pulses representing kWh 4 Hz WNB-3D-240-P
T-WNB-3D-480 Delta (or Wye) 480 Pulses representing kWh 4 Hz WNB-3D-480-P
Pulses representing kWh 4 Hz WNB-3Y-208-P
Pulses representing kWh 4 Hz WNB-3Y-208-P
option P3
DANGER!—HIGH VOLTAGE HAZARD
Installing transducers in an energized electrical enclosure or on any energized conductor can result in severe injury or death. These transducers are for installation by qualified personnel only. To avoid electrical shock, do not perform any installation or servicing of these transducers unless you are qualified to do so. Disconnect and lock-out all power sources during installation and servicing. Please read transducer user manuals for instructions and use.
This document provides instructions on connecting the WattNode Pulse Output kWh Transducers listed above to HOBO H21, H22, U30, UX90, UX120, and RX3000 series data loggers and to ZW series data nodes. Note: For information on connecting the kWh transducer to the power source and other transducer details, refer to the WattNode documentation provided by Continental Control Systems.
Required
Selected WattNode Pulse Output kWh Transducer
Appropriately rated Current Transducer(s)
Smart Sensor-compatible HOBO data logger (H21, H22, U30, or RX3000 series) with:
o Pulse Input Adapter(s), Onset Part No: S-UCC-M00x*
®
o HOBOware
software (version 2.2 or higher for H21 or H22, 2.4 or higher for U30), or HOBOlink for
RX3000
22 AWG twisted pair wire (customer supplied) for UX120 series with HOBOware software, version 3.2.0 or higher
Pulse input-compatible HOBO data node (ZW series) and HOBO data logger (UX90 series) with:
o Onset Part No: CABLE-2.5-STEREO* o HOBOware Pro software, version 3.0 or higher for ZW series and HOBOware version 3.3 or higher for UX90
series
* For monitoring power demand as well as generated power, a second S-UCC-M00x pulse input adapter (for H21, H22, U30
or RX3000 series) or CABLE-2.5-STEREO (for pulse input-compatible ZW series) is required (at output terminal P2).
WattNode Pulse Output kWh Transducer
(Onset Part No. T-WNB-3Y-208-P shown)
WattNode Pulse Output kWh Transducer Features
The WattNode transducer includes three LEDs—one per phase—for diagnostics and indication of power direction and
correctly installed CTs.
The WattNode transducer provides bidirectional kWh energy pulses. Positive energy pulses (energy consumed from the
utility) are output on the P1 and COM terminals and negative energy pulses (energy produced and supplied to the utility) are output on the P2 and COM terminals. It can be used for conventional power and energy measurement as well as for net metering and PV applications. For monitoring power demand as well as generated power, a second S-
© 2005–2015 Onset Computer Corporation. All rights reserved. Onset, HOBO, HOBOware, and HOBOlink are registered trademarks of Onset Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners.
WattNode Pulse Output kWh Transducer Connection Instructions
UCC-M00x pulse input adapter (for H21, H22, U30, or RX3000 series) or CABLE-2.5-STEREO (for pulse input­compatible ZW series) is required (at output terminal P2).
The T-WNB-3Y-208-P can measure two or three separate branch circuits simultaneously. Note that an S-UCC-M00x
pulse input adapter (for H21, H22, U30, or RX3000 series) or a CABLE-2.5-STEREO (for pulse input-compatible ZW series) is required for each circuit monitored.
Note: Refer to the WattNode WNB Series Installation and Operation Manual for details of these features.
Configuring the System
To configure the system, refer to the applicable connection diagram that corresponds to your electrical power configuration. Also refer to the WattNode manual for additional configurations.
HOBO H21, H22, or U30 Series Data Logger
HOBO H21, H22, U30, or RX3000 Series
Data Logger (H22-001 shown)
(H22-001 shown)
P3
S-UCC-M00x
Pulse Input Adapter
White
Black
P2 P1
COM
Output
Connect to
Smart Sensor port
Customer-supplied
22 AWG twisted pair
HOBO UX120 Series Data Logger
Connect (+) terminal from
UX120 terminal block to P1
P3 P2 P1
COM
Connect ground ( ) terminal from
UX120 terminal block to COM
HOBO UX90-001/M Data Logger
Output
CABLE-2.5-STEREO
HOBO ZW Series Wireless Data Node
Connect to
pulse port
CABLE-2.5-STEREO
Red wire not used
White
Black
Red wire not used
P3 P2 P1
COM
Output
White
Black
Figure 1: Connecting HOBO Data Logger or Data Node to WattNode
Electrical Service Types
Below is a list of service types, with connections and recommended WattNode models. Note: the WattNode ground connection improves measurement accuracy, but is not required for safety.
Model Type
Phase to
Neutral
WNB-3Y-208-P Wye 120 VAC
Phase to
Phase
208–240
VAC
Electrical
Service Types*
1 Phase 2 Wire 120V with neutral 1 Phase 3 Wire 120V/240V with neutral 3 Phase 4 Wire Wye 120V/208V with neutral
P3 P2 P1
COM
Output
1 Phase 2 Wire 208V (No neutral) 1 Phase 2 Wire 240V (No neutral)
WNB-3D-240-P
Delta
or Wye
120–140
VAC
208–240
VAC
1 Phase 3 Wire 120V/240V with neutral 3 Phase 3 Wire Delta 208V (No neutral) 3 Phase 4 Wire Wye 120V/208V with neutral 3 Phase 4 Wire Delta 120/208/240V with neutral
3 Phase 3 Wire Delta 480V (No neutral) 3 Phase 4 Wire Wye 277V/480V with neutral 3 Phase 4 Wire Delta 240/415/480V with neutral
WNB-3D-480-P
Delta
or Wye
277 VAC 480 VAC
*The wire count does NOT include ground. It only includes neutral (if present) and phase wires.
Page 2 of 7
WattNode Pulse Output kWh Transducer Connection Instructions
Single-Phase Two-Wire with Neutral
This configuration is most often seen in homes and offices. The two wires are neutral and line. For these models, the WattNode is powered from the N and ØA terminals.
Figure 2: Single-Phase Two-Wire Connection
Recommended WattNode Model
The following table shows the WattNode model that should be used, depending on the line to neutral voltage.
Line to Neutral Voltage WattNode Model
120 VAC WNB-3Y-208-P
Single-Phase Three-Wire
This configuration is seen in North American residential and commercial service with 240 VAC for large appliances. The three wires are neutral and two line voltage wires with AC waveforms 180° out of phase; this results in 120 VAC between either line wire (phase) and neutral, and 240 VAC (or sometimes 208 VAC) between the two line wires (phases).
Figure 3: Single-Phase Three-Wire Connection
Page 3 of 7