Onset VER-PXU Operating Manual

Page 1
Veris Differential Pressure Transducer Connection Instructions
For use with HOBO® H22, U12, U30, UX120-006M, and RX3000 data loggers and HOBO ZW data nodes
Applies to these Veris Differential Pressure Transducers:
T-VER-PXU-L 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXULX05S (LCD display)
T-VER-PXU-X 0-10” WC 4-20mA (or 0-5V/0-10V) representing 0 to 10” WC PXUXX05S (no display)
This document provides instructions on connecting the Veris Differential Pressure Transducers listed above to each of the following:
FlexSmart
Analog Sensor Port/Module used with HOBO U30 and RX3000 series data
loggers
Voltage adapter used with the U12 and UX120-006M data loggers and ZW series
data nodes
It also lists configuration values used by HOBOware each transducer. Note: For information on connecting the differential pressure transducer to the pressure source, and other transducer details, refer to the documentation provided by Veris.
Required
Selected Veris Differential Pressure Transducer
HOBO H22, U12, U30, UX120-006M, or RX3000 data logger, or HOBO ZW data node
FlexSmart Analog Module, Onset Part No: S-FS-CVIA (for H22 series); Analog Sensor Port/Module option (for U30 and
RX3000 series); voltage adapter, Onset Part No. CABLE-ADAP5 or CABLE-ADAP10 (for U12, UX120-006M, or ZW series)
HOBOware software, version 2.2.1 or higher (2.4.0 or higher for U30 series; 3.6 or higher for UX120-006M);
HOBOware Pro 3.0 or higher for ZW series
HOBOlink (for RX3000 series data loggers)
Customer-supplied length of 18 AWG, shielded, multi-conductor cable
Analog Module used with HOBO H22 series data loggers
®
software to configure the logger for
Veris Differential Pressure Transducer
(Onset Part No. T-VER-PXU-L shown)
Connecting the Differential Pressure Transducer to the Analog Module or Port
H22 Connection
HOBO H22 Series D ata Logger
S-FS-CVIA
FlexSmart Analog Mo dule
FlexSmart Analog Mo dule
S2+
S1-
S1+
Shld
© 2009–2015 Onset Computer Corporation. All rights reserved. Onset, HOBO, HOBOware, and HOBOlink are registered trademarks and FlexSmart is a trademark of Onset Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners.
13038-D MAN-VERIS-PXL
S2-
Exc+
Exc-
Conductor
Conductor
for 4-20mA Output
Terminal Block
inside transducer housing
POWER/4-20mA
N/C
N/C N/C
OUT (0-10V) COM
ZERO
FlexSmart Analog Module
Shld
Differential Pressure Transducer
Customer-supplied 18 AWG
shielded multi-conductor cable
S2+
S1-
S1+
for 0-5V/0-10V Output
S2-
Exc+
Exc-
Conductor Conductor Conductor
Terminal Block
inside transducer housing
POWER/4-20mA OUT (0-10V)
COM N/C N/C
ZERO
Page 2
Veris Differential Pressure Transducer Connection Instructions
U30 or RX3000 Connection (U30 Shown)
HOBO U30 Series Data Logger
Analog Sensor Port
Ch2 Signal
Shield
Conductor
Conductor
Ext Return
Ch2 Return
Terminal Block
inside transducer housing
POWER/4-20mA
N/C
N/C N/C
OUT (0-10V) COM
ZERO
Ch1 Return
Ch1 Signal
Shield
Exc Out
for 4-20mA Output
ZW, U12, and UX120-006M Connection
HOBO ZW Series Wireless Data Node; U12 or UX120-006M Logger
HOBO ZW Series Wireless Data Node or U12 Series Data Logger
(ZW shown)
Analog Sensor Port
Differential Pressure Transducer
Customer-supplied 18 AWG
shielded multi-conductor cable
Analog Sensor Port
Ch1 Return
Ch1 Signal
Shield
for 0-5V/0-10V Output
Ext Return
Ch2 Return
Ch2 Signal
Shield
Exc Out
Conductor Conductor Conductor
Differential Pressure Transducer
Terminal Block
inside transducer housing
POWER/4-20mA OUT (0-10V)
COM N/C N/C
ZERO
*CAUTION: Polarity is very important! Before plugging AC-SENS-1 into AC power, make sure the correct polarity lead connections to device are made as shown!
AC-SENS-1*
Blue (-)
Yellow (+)
CABLE-4-20MA
Connect to analog port
CABLE-4-20MA (for 4-20mA output) or
CABLE-ADAP5 (for 0-5VDC output) or CABLE-ADAP10 (for 0-10VDC output)
inside transducer housing
(+)
(-)
N/C
N/C N/C
Use appropriate termination for
connection (denoted with )
for 4-20mA Output
Terminal Block
POWER/4-20mA OUT (0-10V) COM
ZERO
Page 2 of 3
AC-SENS-1*
(+)
(-)
White (+)
Black (-)
(Red wire not used)
CABLE-ADAP5 or CABLE-ADAP10
for 0-5V/0-10V Output
AC-SENS-1*
Terminal Block
inside transducer housing
POWER/4-20mA OUT (0-10V) COM
N/C
ZERO
N/C
Page 3
Veris Differential Pressure Transducer Connection Instructions
Configuring the Data Logger for the Differential Pressure Transducer using HOBOware Software
HOBOware software provides configuration files for the transducers. The table below lists the recommended configuration values that these files contain. For information on loading configuration files, refer to the software documentation.
Onset Part Nos. Channel
T-VER-PXU-L and T-VER-PXU-X
Name
Diff Pressure 20 sec Current 4 20 mA 0 0.1 (or 0.25,
Warm-Up Measurement
Type
Voltage 0 5 (or 10) V
Raw Value 1
Raw Value 2
Raw Units
Scaled Value 1
Scaled Value 2
0.5, 1, 2.5, 5, or 10)
Notes:
Excitation power provided by the FlexSmart Analog Module (Onset Part No. S-FS-CVIA) with H22; by the Analog
Sensor Port/Module with U30 and RX3000; and by power adapter (Onset Part No. AC-SENS-1) with ZW, U12, or UX120-006M.
Both differential pressure transducer models have switch-selectable ranges and scales, as listed.
Scaled Units
in WC
Page 3 of 3